IntelliSlot® Relay Card

User Manual
Contents
1.0 Introduction 3
1.1 Inspecting Shipment on Receipt. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2.0 Installation 4
2.1 Required Parts & Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Installation Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3.0 PIN Configuration 5


Table 1: IntelliSlot Relay Card PIN Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4.0 Jumper Setup 6


Table 2: Jumper Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5.0 Technical Support 7


5.1 Contact Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

While every precaution has been taken to ensure accuracy and completeness in this manual, EGS Electrical Group, LLC. assumes no responsibility, and disclaims all
liability for damages resulting from use of this information or for any errors or omissions.
The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Office. All other product or service names are the property of their registered owners.
©2011 EGS Electrical Group, LLC. All rights reserved. Specifications are subject to change without notice.
1.0 Introduction
The IntelliSlot relay card (IS-RELAY) provides contact closure for remote monitoring of alarm conditions in your SolaHD UPS.
The IntelliSlot relay card is easy to install and integrates with other relay contact monitoring systems.
This advanced power management device is designed to function in units with a IntelliSlot port, such as:
• S4KC Series
• S5K Series
Please visit our Web site at www.solahd.com for the current list of supported products.
On supported units, the inverter shut-off command can be controlled from the computer directly connected to the UPS (via
the factory-installed DB9 connector) and will conserve battery power after the workstation shutdown is complete.
The IntelliSlot relay card is rated for 24 V ac/V dc at 1 A.

1.1 Inspecting Shipment on Receipt


Upon accepting shipment, inspect the packaging and product for any damaged or missing parts. If any damage is observed,
report it to the shipping company and your local SolaHD representative immediately. If any components are missing, contact
your local SolaHD representative for replacement.
Items included with the shipment are:
• IntelliSlot relay card protected by an anti-static bag
• User manual

intellislot relay card User Manual  |  3


2.0 Installation
2.1 Required Parts & Tools
NOTE: Make sure you have the following parts and tools before you begin the installation.
• IntelliSlot relay card (provided)
• #2 (medium) Phillips or small flathead screwdriver

2.2 Installation Instructions


1. Turning off the UPS prior to installation is suggested, although not required.
2. Locate the IntelliSlot port. (See examples in Figure 1.) Refer to the UPS user manual for port location and orientation.
3. Remove the two retaining screws from the IntelliSlot port cover plate (see Figure 1). Save the screws for reassembly in
Step 5.
4. Insert the IntelliSlot relay card. Make sure the holes are aligned with those on the UPS. Initially, the card should slide in
freely as you carefully align the screw holes. As you feel it click into place, press firmly to ensure solid seating in the slot.
5. Use the screwdriver to secure the IntelliSlot relay card to the UPS chassis with the two retaining screws removed in Step 3.
Make sure the screws are snug, not tight, to avoid damage to the device.

IntelliSlot
Relay Card

Remove screws

Figure 1: Installation

6. Use these guidelines for terminal block specifications:


Acceptable wire size: 24–16 AWG
Wire strip length: 0.24–0.28 in. (6–7 mm)

Please proceed to Sections “3.0 Pin Configuration” and “4.0 Jumper Setup” to configure the terminal blocks and jumpers.

intellislot relay card User Manual  |  4


3.0 PIN Configuration
The IntelliSolt relay card has two terminals blocks, TB1 (green, numbered 1–9) and TB2 (black, numbered 10–18), as shown in
Figure 2.

1 10

TB1 TB2
green black

9 18

Figure 2: PIN location & numbering

Please refer to the UPS User manual for the UPS terminal block configuration. The PIN functions in Table 1 apply only to the
SolaHD units listed in Section “1.0 Introduction”.

Table 1: IntelliSlot Relay Card PIN Configuration


PIN Function Operation
1 Common — Low Battery
2 Low Battery Closed if Low Battery point occurs
3 Low Battery Closed if battery is OK
4 Common — UPS Fault
5 UPS Fault Closed if UPS Fault occurs
6 UPS Fault Closed if no UPS failure
7 Common — On Battery
8 On Battery Closed if On Battery power (utility failure)
9 On Battery Closed if not On Battery power (utility OK)
10 Signal Ground Use for UPS Any-Mode Shutdown
11 Signal Ground Use for UPS Any-Mode Shutdown
12 UPS Any-Mode Shutdown Turn UPS output off when shorted to PIN 10 or 11
13 Summary Alarm Closed if no alarm conditions are present
14 Summary Alarm Closed if Summary Alarm occurs
15 Common — Summary Alarm
16 On UPS Closed if ON UPS (inverter) power
17 On Bypass Closed if On Bypass
18 Common — On Bypass

intellislot relay card User Manual  |  5


4.0 Jumper Setup
The IntelliSlot relay card has five jumpers, P3 through P7, as shown in Figure 2. Each jumper connects two PINs.

Front of card Jumper


P6

Jumper
P5

Jumper
P4

Jumper
P3

Jumper
P7

Figure 3: Jumper location & numbering

By default, all five jumpers have shunts installed. The two PINs are shunted together to provide the functions shown in Table 2,
allowing relay commons to be tied together.
NOTE: The jumpers should be removed if there are any external voltage sources that may intentionally or inadvertently be
connected to the relay. Removing the shunt from any two PINs breaks the connection between the relay commons so they
are not tied together.

Table 2: Jumper Connections


Jumper Relay
P6 On Battery
P5 UPS Fault
P4 Low Battery
P3 On Bypass
P7 Summary Alarm

intellislot relay card User Manual  |  6


5.0 Technical Support
5.1 Contact Information
To contact SolaHD technical support, please use one of the following methods:
• Phone: 1.800.377.4384 (US) or 1.847.268.6651 (International)
• E-mail: solahd.technicalservices@emerson.com
• Web site: www.solahd.com

intellislot relay card User Manual  |  7


SolaHD • 1.800. 377.4384 (US) • 1.847.268.6651 (International) • www.solahd.com

P/N: A272-240 Rev 0