Intellislot Relay Card: User Manual
Intellislot Relay Card: User Manual
Intellislot Relay Card: User Manual
User Manual
Contents
1.0 Introduction 3
1.1 Inspecting Shipment on Receipt. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 Installation 4
2.1 Required Parts & Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Installation Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
While every precaution has been taken to ensure accuracy and completeness in this manual, EGS Electrical Group, LLC. assumes no responsibility, and disclaims all
liability for damages resulting from use of this information or for any errors or omissions.
The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Office. All other product or service names are the property of their registered owners.
©2011 EGS Electrical Group, LLC. All rights reserved. Specifications are subject to change without notice.
1.0 Introduction
The IntelliSlot relay card (IS-RELAY) provides contact closure for remote monitoring of alarm conditions in your SolaHD UPS.
The IntelliSlot relay card is easy to install and integrates with other relay contact monitoring systems.
This advanced power management device is designed to function in units with a IntelliSlot port, such as:
• S4KC Series
• S5K Series
Please visit our Web site at www.solahd.com for the current list of supported products.
On supported units, the inverter shut-off command can be controlled from the computer directly connected to the UPS (via
the factory-installed DB9 connector) and will conserve battery power after the workstation shutdown is complete.
The IntelliSlot relay card is rated for 24 V ac/V dc at 1 A.
IntelliSlot
Relay Card
Remove screws
Figure 1: Installation
Please proceed to Sections “3.0 Pin Configuration” and “4.0 Jumper Setup” to configure the terminal blocks and jumpers.
1 10
TB1 TB2
green black
9 18
Please refer to the UPS User manual for the UPS terminal block configuration. The PIN functions in Table 1 apply only to the
SolaHD units listed in Section “1.0 Introduction”.
Jumper
P5
Jumper
P4
Jumper
P3
Jumper
P7
By default, all five jumpers have shunts installed. The two PINs are shunted together to provide the functions shown in Table 2,
allowing relay commons to be tied together.
NOTE: The jumpers should be removed if there are any external voltage sources that may intentionally or inadvertently be
connected to the relay. Removing the shunt from any two PINs breaks the connection between the relay commons so they
are not tied together.