SV-iS7 Series
[ RAPIEnet, EtherNet/IP, Modbus TCP Protocol ]
iS7 RAPIEnet+ Option Manual
SAFETY PRECAUTIONS
Always follow safety instructions to prevent accidents and potentially hazardous situations.
Safety precautions are classified into “WARNING” and “CAUTION,” and their meanings are as follows:
Symbols used in this document and on the product indicate the following.
Presence of "dangerous voltage" inside the product that may cause harm or electric shock.
Read the operating instructions carefully to fully understand the functions of the SV-iS7 series inverters
and use them properly.
CAUTION
Correctly align the communication board to the installation connector for installation and
ensure that it is firmly connected to the inverter.
Otherwise, the module may be damaged or a communication error may result.
1
iS7 RAPIEnet+ Option Manual
Table of Contents
1. Overview ............................................................................................................................................... 5
2
iS7 RAPIEnet+ Option Manual
11.2 Smart scaling (LS ELECTRIC master module: XGL-EFMxB V8.0 or later)............................................ 21
3
iS7 RAPIEnet+ Option Manual
4
iS7 RAPIEnet+ Option Manual
1. Overview
The RAPIEnet+ communication board allows the SV-iS7 inverter to connect to an Ethernet or RAPIEnet
network that is compliant with international standards, Type 21 of IEC 61158 and RRP of IEC 62439. The
RAPIEnet+ communication board supports three protocols: RAPIEnet, EtherNet/IP, and Modbus TCP.
By utilizing the 100 Mbps auto negotiation feature, the RAPIEnet+ communication board provides real-
time network communication without collisions and allows for controlling and monitoring of the inverter via
PLC sequence programs or a Profibus master module.
With simple network cable wiring, installation times can be reduced and maintenance becomes easier.
(When accessing a RAPIEnet v2.0 network with XG5000, LS ELECTRIC network master module XGL-
EFMxB V8.0 or later is required.)
RAPIEnet+ is a hybrid networking solution that incorporates RAPIEnet, LS ELECTRIC’s real-time industrial
Ethernet based on international standards, with highly compatible Modbus TCP and EtherNet/IP network
technologies. This highly efficient industrial Ethernet by LS ELECTRIC allows for integration of various future
technologies required for factory automation, such as the IoT.
Items Description
* The iS7 RAPIEnet+ communication board supports all the features of the iS7 Ethernet communication board.
5
iS7 RAPIEnet+ Option Manual
3. Package components
The product package contains: RAPIEnet+ communication board (1 ea), fix screws (2 ea), and
RAPIEnet+ communication board User Manual.
6
iS7 RAPIEnet+ Option Manual
② Install the RAPIEnet+ communication board to the installation connector on the iS7 inverter, then install the
fixing screws (2 ea).
③ The RAPIEnet+ communication board has been installed on the iS7 Inverter.
Do not install or remove the RAPIEnet+ communication board to or from the iS7 inverter while the inverter is
turned on.
Ensure that the electric charge in the capacitors inside the inverter is completely discharged before installing
or uninstalling the RAPIEnet+ communication board.
Correctly align the communication board to the installation connector for installation and ensure that it is
firmly connected to the inverter.
7
iS7 RAPIEnet+ Option Manual
6. Network connection
8 8
7
6
5
4
3
2
1 1
8
iS7 RAPIEnet+ Option Manual
Category 5 network cables support a frequency band up to 100 MHz, with up to 60 MHz channel
performance and up to 100 Mbps data transmission speed.
9
iS7 RAPIEnet+ Option Manual
10
iS7 RAPIEnet+ Option Manual
Set DRV-06 (Cmd Source) to “4 (Fieldbus)” using the keypad to operate the iS7 inverter via the
RAPIEnet+ communication board.
Set DRV-07 (Frq Ref Src) to “8 (Fieldbus)” using the keypad to provide frequency reference via the
RAPIEnet+ communication board.
11
iS7 RAPIEnet+ Option Manual
13
iS7 RAPIEnet+ Option Manual
14 opt para-5 Enter the 1st decimal number of the subnet address.
15 opt para-6 Enter the 2nd decimal number of the subnet address.
16 opt para-7 Enter the 3rd decimal number of the subnet address.
17 opt para-8 Enter the 4th decimal number of the subnet address.
COM 18 opt para-9 Enter the 1st decimal number of the gateway address.
19 opt para-10 Enter the 2nd decimal number of the gateway address.
20 opt para-11 Enter the 3rd decimal number of the gateway address.
21 opt para-12 Enter the 4th decimal number of the gateway address.
Network communication speed
22 opt para-13
(0 fixed, automatically set to 100 Mbps)
RAPIEnet: Set the Input Parameter Size
23 opt para-14
EtherNet/IP: Set the Input Instance
RAPIEnet: Set Output Parameter Size
24 opt para-15
EtherNet/IP: Set Output Instance
Enable or disable RAPIEnet
25 opt para-16 2: Enable RAPIEnet
0: RAPIEnet Disable
30 ParaStatus Num Displays the number of transmitted data
14
iS7 RAPIEnet+ Option Manual
PRT 13 Lost Cmd Time Set the decision time for a lost command.
15
iS7 RAPIEnet+ Option Manual
Select the command source for the iS7 inverter. Set to “4 (Field Bus)" to set the RAPIEnet+
communication board as the command source and provide commands via network.
Select the frequency command source for the iS7 inverter. Set to “8 (Field Bus)" to set the
RAPIEnet+ communication board as the frequency command source and provide frequency
commands via network.
Automatically indicates the version of the communication board installed to the iS7 inverter.
② [COM-07] FBus ID: Station ID of the communication board (communication board ID)
R: Set the station ID for the iS7 RAPIEnet+ communication board. A total of 64 station IDs are
available from 0 to 63. (The station ID must be set before you can configure network communication
using the RAPIEnet protocol.)
When setting the station ID, be careful not to use a station ID that is not already occupied by the
PLC system or other network devices.
After making setting changes, you must set COM-94 (Comm Update) to “1 (Yes)” before the
changes can take effect.
③ [COM-09] FBus Led: Information about LED indicators on the communication board
Displays on the Keypad the status of the LED indicators on the iS7 RAPIEnet+ communication
board. Refer to sections "11.3/12.4 LED indications and troubleshooting."
16
iS7 RAPIEnet+ Option Manual
09 FBus LED
④ [COM-22] opt para-13: Set the network communication speed. (100 Mbps, Auto Negotiation)
The Ethernet speed parameter is fixed at "0" by default for 100 Mbps communication speed.
Used to monitor one of the smart scaling transmission data of the iS7 RAPIEnet+ communication
board. You can select one of the data transmission addresses from COM31 to COM38 for
monitoring.
You can set “opt para-14 (smart scaling transmission data index)” to between “0” and “11.” Refer to
the following table for the description of the “opt para-14” settings.
The “opt para-14 (smart scaling transmission data index)” setting cannot be written while the
inverter is operating. Stop inverter operation before making changes to the setting.
This parameter setting is also required for a service via EtherNet/IP protocol. It specifies the data
format of the inverter status to be transmitted to the client (originator) during an I/O communication
via a CIP (Common Industrial Protocol). Refer to the Assembly Object section of the EtherNet/IP.
Set value Input instance value (E) Data size (R/E) Number of parameters (R/E)
0 70 4 X
1 71 4 X
2 110 4 X
3 111 4 X
17
iS7 RAPIEnet+ Option Manual
4 141 2 1
5 142 4 2
6 143 6 3
7 144 8 4
8 145 10 5
9 146 12 6
10 147 14 7
11 148 16 8
Used to monitor one of the smart scaling reception data of the iS7 RAPIEnet+ communication board.
You can select one of the data reception addresses from COM51 to COM58 for monitoring.
You can set “opt para-15 (smart scaling reception data index)” to between “0” and “11.” The
description of the “opt para-15” settings are as follows.
The “opt para-15 (smart scaling reception data index)” setting cannot be written while the inverter is
operating. Stop inverter operation before making changes to the setting.
This parameter is also required for EtherNet/IP protocol service. It configures the format of the
command data transmitted to the inverter by the client (originator) during the I/O communication via
the CIP (Common Industrial Protocol). Refer to the Assembly Object section of the EtherNet/IP.
Set value Output instance value (E) Data size (R/E) Number of parameters (R/E)
0 20 4 X
1 21 4 X
2 100 4 X
3 101 4 X
4 121 2 1
5 122 4 2
6 123 6 3
7 124 8 4
8 125 10 5
9 126 12 6
10 127 14 7
11 128 16 8
18
iS7 RAPIEnet+ Option Manual
This feature is compatible with LS ELECTRIC products (XGL-EFMxB V8.0 or later) for the
RAPIEnet v2 smart scaling service.
If you have installed the iS7 RAPIEnet+ communication board to an inverter made by another
manufacturer (to utilize it as an iS7 Ethernet communication board), set the parameter to “0,” then
run “Comm Update” to operate the inverter with the RAPIEnet feature disabled.
You can set COM-23 (opt para-14) to change the number of transmission data to between “0” and
“8.” The RAPIEnet+ communication board can transmit up to 8 pieces of data. You can configure
the address of the transmission data with parameters COM-31 through COM-38.
⑨ [COM-31] Para Status1 – [COM38] Para Status8: Transmission data address settings
After setting the number of transmission data with COM-30, enter the matching number of data
addresses for the data to transmit to the client (originator) with parameters COM-31 through COM-
38.
This parameter setting is not required for Modbus TCP network communications.
You can set COM-50 (opt para-15) to change the number of reception data to between “0” and “8.”
The RAPIEnet+ communication board can receive up to 8 pieces of data. You can configure the
address for the received data with parameters COM-51 through COM-58.
⑪ [COM-51] Para Control1 – [COM58] Para Control8: Reception data address settings
After setting the number of reception data with COM-50, enter the matching number of data
addresses for receiving command data from the client (originator) with parameters COM-51 through
COM-58.
This parameter setting is not required for Modbus TCP network communications.
19
iS7 RAPIEnet+ Option Manual
⑫ [COM-94] Comm Update: Update setting changes via the communication board
The COM group parameters display the settings stored on the inverter connected to the RAPIEnet+
communication board and the changes made on the keypad are not directly reflected on the
RAPIEnet+ communication board.
The changed settings will be reflected on the RAPIEnet+ communication board when you set COM-
94 (Comm Update) to “1 (Yes).” (Parameters that require communication updates include COM-7
and COM 10 through COM-25.)
You can select the operation mode for when a network failure or connection failure between the
inverter and the communication occurs while the inverter is operated via network communication.
Set the time duration until the operation mode set with PRT-12 will be reflected following a
command loss. You can set a value between "0.1" and "120" seconds.
When a lost command occurs, a protective function is activated and the inverter continues to
operate using the frequency set with PRT-14. The setting value is from the start frequency to the
max frequency [Hz].
- RAPIEnet
When the RAPIEnet master (XGL-EFMxB V8.0 or later) fails to receive data for the watchdog time,
the communication board enters lost command mode, and the inverter will operate according to the
settings at PRT-12 after the time set with PRT-13 has elapsed.
Refer to item (2) of section 11 for how to set the watchdog timer for the master module.
- EtherNet/IP
If the implicit message connection (Class 1 Connection) between the originator (a PLC or client)
and the target (inverter) breaks for longer than one second, the Ethernet communication board
enters lost command mode, and the inverter will operate according to the settings at PRT-12 after
the time set with PRT-13 has elapsed.
- Modbus TCP
If the Modbus TCP receives no data from the client for five seconds, the Ethernet communication
board enters lost command mode, and the inverter will operate according to the settings at PRT-12
after the time set with PRT-13 has elapsed.
20
iS7 RAPIEnet+ Option Manual
RAPIEnet+
communication board RAPIEnet v2 EtherNet/IP Modbus TCP
PAR -> COM-25 Availability Availability Availability
[Opt Parameter-16]
Setting: ‘2’
O O O
RAPIEnet v2 Enable
Setting: ‘0’
X O O
RAPIEnet v2 Disable
11.2 Smart scaling (LS ELECTRIC master module: XGL-EFMxB V8.0 or later)
The smart scaling service is a communication service between automation products that allows for the
extension of multiple PLCs and inverters utilizing simple configurations, without the need for complicated
parameters settings or programming. The smart scaling service also has the EtherNet/IP service
integrated within.
The iS7 RAPIEnet+ communication board enables 8-word data input/out transmissions via an LS
ELECTRIC master module, simply by configuring the number of transmission/reception data (COM-
30/COM-50) and the addresses for transmission/reception data (COM-31 – COM-38 / COM-51 – COM-
58). Besides, it provides various features, such as, monitoring of diagnostic parameters, RAPIEnet auto
scan, and system diagnosis.
The following figure shows an example of the XG5000 settings screen for an LS ELECTRIC network
master module (XGL-EFMxB V8.0 or later).
21
iS7 RAPIEnet+ Option Manual
Note) “Smart scaling memory area settings”: The iS7 RAPIEnet+ communication board has a 64-byte (32 Word)
memory area assigned for it (fixed). When configuring the addresses, be careful not to use addresses already
occupied by other programs to avoid collisions. Separate warnings are not provided, nor are duplicated addresses
prohibited because users may configure a certain area of the addresses to be superimposed for special purposes.
22
iS7 RAPIEnet+ Option Manual
Also, to configure a network communication utilizing a PLC system, installation of the XG5000
program is required. You can download XG5000 program from the LS ELECTRIC website.
In the Connection tap of the Add Network Device window, you can configure the properties and click “OK” to add a network
device [CENT] (RAPIEnet+ communication board) for a smart scaling service.
23
iS7 RAPIEnet+ Option Manual
Watchdog timer: The time for the network device (iS7 RAPIEnet+ communication board) to monitor the
uninterrupted network connection with the master module.
24
iS7 RAPIEnet+ Option Manual
25
iS7 RAPIEnet+ Option Manual
① Click [Online] -> [Network module settings and diagnosis] -> [System diagnosis].
26
iS7 RAPIEnet+ Option Manual
② In the [System diagnosis] window, right-click the master module (XGL-EFMxB) on the figure, then
click Service status.
③ Click [Service status] -> [Smart scaling] tap to view the scaling service status.
27
iS7 RAPIEnet+ Option Manual
④ In step ②, you can click the [Auto scan] tap to view the RAPIEnet connection status.
28
iS7 RAPIEnet+ Option Manual
29
iS7 RAPIEnet+ Option Manual
*1: For a RAPIEnet network communication, check keypad parameter settings for COM-7, COM-13, COM-30, and COM-50, and the
PLC settings. (When the RAPIEnet+ communication board is communicating with an LS ELECTRIC master module and the RAPIEnet
network feature is enabled, the COM-7 [station ID] and COM-13 [IP address] parameters must be set to avoid collisions with other
RAPIEnet+ communication boards on the same network.)
Flashing
Communication between the
Synchronous flashing with
RAPIEnet+ communication board and
LED0
the inverter is abnormal.
(1 second interval)
30
iS7 RAPIEnet+ Option Manual
RAPIEnet+
communication board RAPIEnet v2 EtherNet/IP Modbus TCP
PAR -> COM-25 Availability Availability Availability
[Opt Parameter-16]
Setting: ‘2’
O O O
RAPIEnet v2 Enable
Setting: ‘0’
X O O
RAPIEnet v2 Disable
12.2 EtherNet/IP
31
iS7 RAPIEnet+ Option Manual
The EtherNet/IP is a protocol which implements the CIP (Common Industrial Protocol,
specified by the ODVA) using the TCP and UDP protocols.
Originator: Devices that make connection requests, which are also called clients.
Target: Devices that respond to connection requests, which are also called servers.
① Scope of support
Transport type
Target->Originator: Multicast
Configuration connection: 1
Priority
Originator->Target: Scheduled
Target->Originator: Scheduled
32
iS7 RAPIEnet+ Option Manual
② Input instances
Input instances refer to the status data periodically sent from the inverter to PLC or other
client devices.
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Running1
0 Faulted
(Fwd)
70 1
2 Speed Actual (Low Byte) – RPM unit (note 1)
3 Speed Actual (High Byte) – RPM unit
At Ref From Ctrl From Running 2 Running1
0 Ready Warning Faulted
Reference Net Net (Rev) (Fwd)
71 1 Drive State
2 Speed Actual (Low Byte) – RPM unit
3 Speed Actual (High Byte) – RPM unit
Running1
0 Faulted
(Fwd)
110 1
2 Speed Actual (Low Byte) – Hz unit (note 1)
3 Speed Actual (High Byte) – Hz unit
At Ref From Ctrl From Running 2 Running1
0 Ready Warning Faulted
Reference Net Net (Rev) (Fwd)
111 1 Drive State
2 Speed Actual (Low Byte) – Hz unit
3 Speed Actual (High Byte) – Hz unit
0 Status Parameter - 1 data (Low Byte)
141
1 Status Parameter - 1 data (High Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
142
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (High Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
2 Status Parameter - 2 data (Low Byte)
143
3 Status Parameter - 2 data (High Byte)
4 Status Parameter - 3 data (Low Byte)
5 Status Parameter - 3 data (High Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (High Byte)
144
4 Status Parameter - 3 data (Low Byte)
5 Status Parameter - 3 data (High Byte)
6 Status Parameter - 4 data (Low Byte)
7 Status Parameter - 4 data (High Byte)
33
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (High Byte)
4 Status Parameter - 3 data (Low Byte)
145
5 Status Parameter - 3 data (High Byte)
6 Status Parameter - 4 data (Low Byte)
7 Status Parameter - 4 data (High Byte)
8 Status Parameter - 5 data (Low Byte)
9 Status Parameter - 5 data (High Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (High Byte)
4 Status Parameter - 3 data (Low Byte)
5 Status Parameter - 3 data (High Byte)
146
6 Status Parameter - 4 data (Low Byte)
7 Status Parameter - 4 data (High Byte)
8 Status Parameter - 5 data (Low Byte)
9 Status Parameter - 5 data (High Byte)
10 Status Parameter - 6 data (Low Byte)
11 Status Parameter - 6 data (High Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (High Byte)
4 Status Parameter - 3 data (Low Byte)
5 Status Parameter - 3 data (High Byte)
6 Status Parameter - 4 data (Low Byte)
147
7 Status Parameter - 4 data (High Byte)
8 Status Parameter - 5 data (Low Byte)
9 Status Parameter - 5 data (High Byte)
10 Status Parameter - 6 data (Low Byte)
11 Status Parameter - 6 data (High Byte)
12 Status Parameter - 7 data (Low Byte)
13 Status Parameter - 7 data (High Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (High Byte)
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (High Byte)
4 Status Parameter - 3 data (Low Byte)
148
5 Status Parameter - 3 data (High Byte)
6 Status Parameter - 4 data (Low Byte)
7 Status Parameter - 4 data (High Byte)
8 Status Parameter - 5 data (Low Byte)
9 Status Parameter - 5 data (High Byte)
34
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
10 Status Parameter - 6 data (Low Byte)
11 Status Parameter - 6 data (High Byte)
12 Status Parameter - 7 data (Low Byte)
13 Status Parameter - 7 data (High Byte)
14 Status Parameter - 8 data (Low Byte)
15 Status Parameter - 8 data (High Byte)
The following table explains the data (bytes 0 and 1) for instances 70, 71, 110, and
111.
Related attribute
Name Description
Class Attr. ID
Faulted Inverter Error 0x29 10
Warning Not supported 0x29 11
Running1 Motor is running Forward 0x29 7
Running2 Motor is running Reverse 0x29 8
Ready Motor is ready for operation 0x29 9
Ctrl From Net Run/Stop control 0x29 15
Ref From Net Speed control 0x2A 29
At Reference Reached reference Speed 0x2A 3
Drive State Current motor status 0x29 6
Actual speed Reference speed 0x2A 7
③ Output instances
Out instance refers to the status data periodically sent from the PLC or other client devices
to the inverter.
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault Run
0
reset Fwd
20 1 0
2 Speed Reference (Low Byte) – RPM unit
3 Speed Reference (High Byte) – RPM unit
NetRef NetCtrl Fault Run Run
0
(note 2) (note2) reset Rev Fwd
21 1 0
2 Speed Reference (Low Byte) – RPM unit
3 Speed Reference (High Byte) – RPM unit
35
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault Run
0
reset Fwd
100 1 0
2 Speed Reference (Low Byte) – Hz unit
3 Speed Reference (High Byte) – Hz unit
Fault Run Run
0 NetRef NetCtrl
reset Rev Fwd
101 1 0
2 Speed Reference (Low Byte) – Hz unit
3 Speed Reference (High Byte) – Hz unit
0 Control Parameter - 1 data (Low Byte)
121
1 Control Parameter - 1 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
122
2 Control Parameter - 2 data (Low Byte)
3 Control Parameter - 2 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
2 Control Parameter - 2 data (Low Byte)
123
3 Control Parameter - 2 data (High Byte)
4 Control Parameter - 3 data (Low Byte)
5 Control Parameter - 3 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
2 Control Parameter - 2 data (Low Byte)
3 Control Parameter - 2 data (High Byte)
124
4 Control Parameter - 3 data (Low Byte)
5 Control Parameter - 3 data (High Byte)
6 Control Parameter - 4 data (Low Byte)
7 Control Parameter - 4 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
2 Control Parameter - 2 data (Low Byte)
3 Control Parameter - 2 data (High Byte)
4 Control Parameter - 3 data (Low Byte)
125
5 Control Parameter - 3 data (High Byte)
6 Control Parameter - 4 data (Low Byte)
7 Control Parameter - 4 data (High Byte)
8 Control Parameter - 5 data (Low Byte)
9 Control Parameter - 5 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
126 2 Control Parameter - 2 data (Low Byte)
3 Control Parameter - 2 data (High Byte)
4 Control Parameter - 3 data (Low Byte)
36
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
5 Control Parameter - 3 data (High Byte)
6 Control Parameter - 4 data (Low Byte)
7 Control Parameter - 4 data (High Byte)
8 Control Parameter - 5 data (Low Byte)
9 Control Parameter - 5 data (High Byte)
10 Control Parameter - 6 data (Low Byte)
11 Control Parameter - 6 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
2 Control Parameter - 2 data (Low Byte)
3 Control Parameter - 2 data (High Byte)
4 Control Parameter - 3 data (Low Byte)
5 Control Parameter - 3 data (High Byte)
6 Control Parameter - 4 data (Low Byte)
127
7 Control Parameter - 4 data (High Byte)
8 Control Parameter - 5 data (Low Byte)
9 Control Parameter - 5 data (High Byte)
10 Control Parameter - 6 data (Low Byte)
11 Control Parameter - 6 data (High Byte)
12 Control Parameter - 7 data (Low Byte)
13 Control Parameter - 7 data (High Byte)
0 Control Parameter - 1 data (Low Byte)
1 Control Parameter - 1 data (High Byte)
2 Control Parameter - 2 data (Low Byte)
3 Control Parameter - 2 data (High Byte)
4 Control Parameter - 3 data (Low Byte)
5 Control Parameter - 3 data (High Byte)
6 Control Parameter - 4 data (Low Byte)
7 Control Parameter - 4 data (High Byte)
128
8 Control Parameter - 5 data (Low Byte)
9 Control Parameter - 5 data (High Byte)
10 Control Parameter - 6 data (Low Byte)
11 Control Parameter - 6 data (High Byte)
12 Control Parameter - 7 data (Low Byte)
13 Control Parameter - 7 data (High Byte)
14 Control Parameter - 8 data (Low Byte)
15 Control Parameter - 8 data (High Byte)
37
iS7 RAPIEnet+ Option Manual
The following table explains the data (bits for byte 0) for instances 20, 21, 100, and 101.
Related attribute
Name Description
Class Attr. ID
Run Fwd (Note1) Forward Run Command 0x29 3
Run Rev (Note1) Reverse Run Command 0x29 4
Fault reset (Note1) Fault Reset Command 0x29 12
NetRef (Note2) Not used 0x2A 4
NetCtrl (Note2) Not used 0x29 5
Speed Reference Reference speed 0x2A 8
(Note1) Refer to the Drive Run and Fault sections in the "Control Supervisor Object
(Class 0x29)".
(Note2) Reference speed and Run/Strop control can be set only on the LCD control panel.
Network control instances 21 and 101 (NetRef, NetCtrl) are not available.
Using the UCMM communication, data exchange is made without connecting the
originator and the target, and periodic data exchange is available as well using the Class
3 connection.
Attribute
Attribute
Access Attribute Name Data Length Attribute Value
ID
1 Get Vendor ID (LS ELECTRIC) Word 259
2 Get Device Type (inverter) Word 2
3 Get Product Code Word 100 (Note1)
Revision
4 Get High Byte - Major Revision Word (Note2) 0x0101
Low Byte - Minor Revision
38
iS7 RAPIEnet+ Option Manual
(Note2) The revision number is identical to the version of the Ethernet communication
board. The high byte stands for a major revision number, and the low byte stands for a
minor revision number. For example, “0x0102” stands for "version 1.02."
The version of the Ethernet communication board can be displayed on the Keypad using
the COM-6 (FBus S/W Ver) parameter.
Bit Description
0: Device is not connected to the master
0
1: Device is connected to the master
1 Reserved
Configured (fixed as ‘0’ because LS ELECTRIC EtherNet/IP is not
2
supported)
3 Reserved
4 0: Unknown
5 2: Faulty IO connection
6 3: IO connection has not been made
5: Major fault
7 6: IO connection has been made
8 Minor recoverable fault (Inverter is in warning status)
9 Minor unrecoverable fault (N/A)
10 Major recoverable fault (inverter H/W trip occurred)
11 Major recoverable fault (inverter non-H/W trip occurred)
(Note4) Serial number uses the last 4 digits of the MAC ID.
Service
39
iS7 RAPIEnet+ Option Manual
Attribute
0: Non-standard motor
1: PM DC Motor
2: FC DC Motor
3: PM Synchronous Motor
4: FC Synchronous Motor
3 Get Motor Type 0 – 10 5: Switched Reluctance Motor
6: Wound Rotor Induction Motor
7: Squirrel Cage Induction Motor
8: Stepper Motor
9: Sinusoidal PM BL Motor
10: Trapezoidal PM BL Motor
[Get]
Reads the value at BAS-13 Rated Curr.
0.0 –
6 Get/Set Motor Rated Curr [Set]
1000.0
Set value is reflected to BAS-13 Rated Curr.
Scale 0.1
[Get]
Reads the value of the BAS-15 Rated Voltage.
0– [Set]
7 Get/Set Motor Rated Volt
690 Set value is reflected in the BAS-15 Rated
Voltage.
Scale 1
Service
40
iS7 RAPIEnet+ Option Manual
Attribute
Attribute
Access Attribute Name Range Definition
ID
0 Stopped
3 Get/Set Forward Run Cmd.
1 Forward run (Note1)
0 Stopped
4 Get/Set Reverse Run Cmd.
1 Reverse run (Note1)
Configurable only with the inverter
5 N/A Net Control -
parameter.
0 Vendor Specific
1 Startup
2 Not Ready (resetting in progress)
3 Ready (stopping in progress)
6 Get Drive State Enabled (running, not applicable to
4
deceleration stop)
5 Stopping (decelerating)
6 Fault Stop
7 Faulted (trip occurred)
0 Drive stopped.
7 Get Running Forward
1 Running Forward
0 Drive stopped.
8 Get Running Reverse
1 Running Reverse
0 Resetting in progress or trip occurred
9 Get Drive Ready
1 Inverter is ready for operation
0 Trip has not occurred
10 Get Drive Fault
1 Trip has occurred
Trip reset to release the trip. Resetting will
0
12 Get/Set Drive Fault Reset begin only when the value changes from
1 FALSE to TRUE. (Note2)
Refer to the following Drive Fault Code
13 Get Drive Fault Codes
table (Note2)
Commands are made using sources other
0
than the DeviceNet communication.
14 Get Control From Net.
Commands are made using the DeviceNet
1
communication as the source.
41
iS7 RAPIEnet+ Option Manual
Inverter operation using Forward Run Cmd. and Reverse Run Cmd.
In the table above, Run1 indicates Forward Run Cmd. and Run 2 indicates Reverse Run
Cmd. Commands are made by the Ethernet communication board when the value
changes from 0 (FALSE) to 1 (TRUE). The Forward Run Cmd. value does not indicate
the present operation status of the inverter; it indicates the operation command value on
the Ethernet communication board.
Fault Code
Description
Number
0x0000 None
Ethermal Out Phase Open InverterOLT
InPhaseOpen ThermalTrip UnderLoad
0x1000 ParaWriteTrip IOBoardTrip PrePIDFail
OptionTrip1 OptionTrip2 OptionTrip3
LostCommand UNDEFINED LostKeypad
0x2200 OverLoad
0x2310 OverCurrent1
0x2330 GFT
0x2340 OverCurrent2
0x3210 OverVoltage
0x3220 LowVoltage
0x2330 GroundTrip
42
iS7 RAPIEnet+ Option Manual
Fault Code
Description
Number
0x4000 NTCOpen
0x4200 OverHeat
0x5000 FuseOpen HWDiag
0x7000 FanTrip
0x7120 No Motor Trip
0x7300 EncorderTrip
0x8401 SpeedDevTrip
0x8402 OverSpeed
0x9000 ExternalTrip BX
The Drive Fault Reset gives TRIP RESET reference to the inverter when the setting value
changes from 0 to 1 (FALSE to TRUE). Overwriting 1 (TRUE) over 1 (TRUE) does not
generate RESET reference for a trip. To allow the Ethernet communication board to send
a RESET command to the inverter when the value is 1 (TRUE), write 0 (FAULT) first,
then write 1 (TRUE) again.
Service
43
iS7 RAPIEnet+ Option Manual
Attribute
Attribute
Access Attribute Name Range Definition
ID
Service
Attribute
Attribute Attribute
Instance Access Attribute Number
Name Value
1 (DRV Group) Identical to the iS7 Manual Code number.
2 (BAS Group) Identical to the iS7 Manual Code number.
3 (ADV Group) Identical to the iS7 Manual Code number.
4 (CON Group) Identical to the iS7 Manual Code number. Parameter
setting range
5 (IN Group) Identical to the iS7 Manual Code number. iS7 Keypad
for the iS7
Title
6 (OUT Group) Get/Set Identical to the iS7 Manual Code number. inverter
(Refer to the
7 (COM Group) Identical to the iS7 Manual Code number. (Refer to the
iS7 inverter
8 (APP Group) Identical to the iS7 Manual Code number. iS7 inverter
user manual)
user
9 (AUT Group) Identical to the iS7 Manual Code number. manual)
10 (APO Group) Identical to the iS7 Manual Code number.
11 (PRT Group) Identical to the iS7 Manual Code number.
12 (M2 Group) Identical to the iS7 Manual Code number.
Service
45
iS7 RAPIEnet+ Option Manual
PDU is the actual data in the Modbus TCP communication, which is composed of a
function code and data.
46
iS7 RAPIEnet+ Option Manual
Read Input registers are functions used to read the server (inverter) data.
The following table explains the components of a request data frame from a client to a
server.
The following table explains the components of a response data frame from a server to a
master.
Read Input registers are functions used to read the server (inverter) data.
The following table explains the components of a request data frame from a client to a
server.
47
iS7 RAPIEnet+ Option Manual
The following table explains the components of a response data frame from a server to a
master.
Write Single registers are functions used to write a single server (inverter) data.
The following table explains the components of a request data frame from a client to a
server.
The following table explains the components of a response data frame from a server to a
master.
48
iS7 RAPIEnet+ Option Manual
Write Multiple registers are functions used to write 1 to 16 consecutive data items on the
server (inverter).
The following table explains the components of a request data frame from a client to a
server.
The following table explains the components of a response data frame from a server to a
master.
49
iS7 RAPIEnet+ Option Manual
Exception code
50
iS7 RAPIEnet+ Option Manual
connected LINK 1
Network
Orange ON Check Ethernet settings*1
LED1 LINK2 fault
connected LINK 2
51
iS7 RAPIEnet+ Option Manual
*1: For Ethernet network settings, check keypad parameters COM-10, COM-11, COM-14, COM-15, COM-23, and COM-24, and the
settings for the client devices, such as the PLC.
*2: To synchronize the Ethernet communication board settings with the keypad parameter settings, check the
COM Group parameter settings and set COM-94 (Comm. Update) to "1 (yes)."
52
iS7 RAPIEnet+ Option Manual
제품을 사용하기 전에
먼저 저희 iS7 RAPIEnet+ 옵션 보드를 사용하여 주셔서 감사합니다.
안전상의 주의사항
안전상의 주의사항은 사고나 위험을 사전에 예방하여 제품을 안전하고 올바르게 사용하기 위한 것
이므로 반드시 지켜주십시오.
주의사항은 ‘경고’와 ‘주의’의 두 가지로 구분되어 있으며 ‘경고’와 ‘주의’의 의미는 다음과 같습니다.
주 의
1
iS7 RAPIEnet+ Option Manual
목 차
1. 소개 ................................................................................................................................................................................................... 5
3. 제품 구성물................................................................................................................................................................................... 6
(1) 외관 ........................................................................................................................................................................................... 6
6. Network 연결 .............................................................................................................................................................................. 8
8. 인버터 통신 주소...................................................................................................................................................................... 10
2
iS7 RAPIEnet+ Option Manual
11.1 개요 ......................................................................................................................................................................................... 21
(5) 진단 변수 할당................................................................................................................................................................... 25
3
iS7 RAPIEnet+ Option Manual
12.1 개요 ......................................................................................................................................................................................... 31
4
iS7 RAPIEnet+ Option Manual
1. 소개
RAPIEnet+ 통신 옵션 보드는 SV-iS7 인버터를 산업통신망 국제규격인 IEC 61158의 Type 21과 IEC
62439의 RRP에 해당하는 RAPIEnet 그리고 Ethernet 네트워크에 연결되도록 합니다. RAPIEnet+ 통신
옵션 보드는 RAPIEnet, EtherNet/IP 그리고 Modbus TCP 3가지의 Protocol 을 지원합니다.
100Mbps Auto Negotiation 방식을 이용하여 충돌 없는 통신으로 통신 상의 실시간성을 확보하며,
iS7 인버터의 제어 및 모니터링이 PLC의 시퀀스 프로그램 또는 임의의 Master Module에 의해
제어가 가능해 집니다.
배선이 간단하여 설치 시간을 절감할 수 있고 유지 보수가 쉬워 집니다.
(단, XG5000에서 RAPIEnet v2.0을 사용시에는 당사 통신 마스터 XGL-EFMxB V8.0 이상에서
호환됩니다.)
** 당사 홈페이지 http://www.lselectric.co.kr/ 에 접속하여 “사용설명서_XGT_FEnet”을 다운로드 받으실 수 있습니다.
참고) ‘RAPIEnet+’ 란?
실시간성(Real-time)과 링제어 국제표준 기반의 LS ELECTRIC 산업용 이더넷 RAPIEnet 통신에 범용성이 장점인
Modbus TCP, EtherNet/IP 통신 기술을 하나로 통합한 하이브리드 통신 솔루션이며, 자동화 산업에 필요한 IoT
및 미래 기술도 융합할 수 있는 고성능, 고효율의 LS ELECTRIC 산업용 이더넷 입니다.
항목 설명
통신 속도 100Mbps
통신 방식 Auto Negotiation
최대접속국수 64국
5
iS7 RAPIEnet+ Option Manual
3. 제품 구성물
4. iS7 RAPIEnet+ 통신 옵션 보드 형명
형명: CENT
5. iS7 RAPIEnet+ 통신 옵션 보드 외관 및 설치
(1) 외관
6
iS7 RAPIEnet+ Option Manual
7
iS7 RAPIEnet+ Option Manual
6. Network 연결
(1) 통신선 연결 단자 관련 정보
Pin No. 신호 설명 선 색
4 NONE 사용 안 함 청색
5 NONE 사용 안 함 흰/청색
7 NONE 사용 안 함 흰/갈색
8 NONE 사용 안 함 갈색
(2) 통신선 연결 단자 부
8 8
7
6
5
4
3
2
1 1
8
iS7 RAPIEnet+ Option Manual
7. Network 케이블 규격
(1) 사용 주파수 대역
분류 상세 용도
최대 200MHz
UTP (U.UTP) 비차폐 고속신호용 케이블
음성+정보(Data)+저급영상 신호
9
iS7 RAPIEnet+ Option Manual
8. 인버터 통신 주소
10
iS7 RAPIEnet+ Option Manual
11
iS7 RAPIEnet+ Option Manual
참고) COM-07, COM-10~25 파라미터 값 변경을 원하는 경우, 반드시 COM-94 Comm-Update 를 통해
업데이트를 해주어야 설정 값이 저장 됩니다. (만약, 파라미터를 변경 시도를 한 상태에서 COM-94 Comm-
Update 실행을 하지 않은 경우, Error LED를 통해 RED 2초 간격 점멸을 통해 사용자가 인지 하실 수 있도록
동작 합니다.)
12
iS7 RAPIEnet+ Option Manual
0: None
1: Free-Run
2: Dec Lost Command가 발생하였을 경우 인버터
PRT-12 Lost Cmd Mode None R/E/M
3: Hold Input 동작 설정합니다. (주1)
4: Hold Output
5: Lost Preset
PRT-14 Lost Preset F 0.00 0.05 ~ 60.00 Lost Preset의 속도를 설정 R/E/M
13
iS7 RAPIEnet+ Option Manual
Code 파라미터 이름 기능 설명
06 Cmd Source 운전 지령 방법
DRV
07 Freq Ref Src 주파수 설정
14
iS7 RAPIEnet+ Option Manual
Code 파라미터 이름 기능 설명
0: RAPIEnet Disable
15
iS7 RAPIEnet+ Option Manual
(2) CNF 그룹
(3) DRV 그룹
(4) COM 그룹
16
iS7 RAPIEnet+ Option Manual
17
iS7 RAPIEnet+ Option Manual
6 143 6 3
7 144 8 4
8 145 10 5
9 146 12 6
10 147 14 7
11 148 16 8
⑥ [COM-24] opt para-15: 수신 Data 설정
iS7 RAPIEnet+ 통신 옵션의 스마트 증설 수신 데이터 중 하나를 모니터링 하는 목적으로
사용하며, 수신 데이터 주소 [COM51]~[COM58]의 주소 중 모니터링을 원하는 값을 설정합니다.
“opt para-15”(스마트 증설 수신 Data Index)의 설정 값은 0~11 입니다. “opt para-15”의 설정에
따른 의미는 다음과 같습니다.
18
iS7 RAPIEnet+ Option Manual
19
iS7 RAPIEnet+ Option Manual
- EtherNet/IP
Originator(PLC 혹은 Client)와 Target(Inverter)사이에 Implicit Message Connection (Class1
Connection)이 1초 동안 맺어 있지 않으면 통신 옵션 모듈은 Lost Command 상태가 되고 PRT-
13에 설정된 시간이 지나면 PRT-12 설정에 따라 인버터는 동작하게 됩니다.
- Modbus TCP
Modbus TCP는 5초 동안 Client로부터 Data가 오지 않을 경우 통신 옵션 모듈은 Lost
Command 상태가 되고 PRT-13에 설정된 시간이 지나면 PRT-12 설정에 따라 인버터는
동작하게 됩니다.
20
iS7 RAPIEnet+ Option Manual
11.1 개요
RAPIEnet+ 옵션보드
RAPIEnet v2 EtherNet/IP Modbus TCP
PAR -> COM 25
[Opt Parameter-16]
사용 가능 여부 사용 가능 여부 사용 가능 여부
설정 값: ‘2’ O O O
RAPIEnet v2 Enable
설정 값: ‘0’ X O O
RAPIEnet v2 Disable
21
iS7 RAPIEnet+ Option Manual
22
iS7 RAPIEnet+ Option Manual
참고) ‘스마트 증설 메모리 영역 설정’: iS7 RAPIEnet+ 옵션 보드는 64Byte (32Word) 영역이 고정 할당됩니다.
프로그램에서 사용하는 주소와 충돌이 나지 않도록 설정합니다. 단, 사용자가 특정 목적으로 메모리 영역을
겹치도록 설정하는 경우가 있으므로 별도의 경고를 띄우거나 설정을 막지 않습니다.
RAPIEnet+ 옵션의 경우, iS7 RAPIEnet+ 통신 옵션을 사용하여 PLC System과 통신하기 위해서는
XGL-EFMxB(RAPIEnet I/F 모듈)을 사용하여야 합니다. 스마트 증설 서비스를 사용하기 위해서는
스마트 증설 디바이스의 국번(EB)과 IP주소(ex> [PAR->COM] 07 FBUS ID: ‘05’, [PAR->COM] 13 Opt
Parameter4: ‘100+ FBUS ID = 105’)를 먼저 설정해야 합니다. 인버터 옵션 보드 간의 IP 주소
충돌을 막기 위함입니다.) XGL-EFMxB 제품에 대한 사용설명서를 참고하여 사용법을 숙지하여
주시기 바랍니다.
또한, PLC 시스템을 사용하여 통신 설정을 하기 위해서는 XG5000 프로그램을 설치하여야
합니다. XG5000 프로그램은 당사 홈페이지를 통해 다운받으실 수 있습니다.
** 당사 홈페이지 http://www.lselectric.co.kr/ 에 접속하여 다운로드 받으실 수 있습니다.
23
iS7 RAPIEnet+ Option Manual
(2) 마스터 설정
XGL-EFMxB (V8.0 이상) 마스터의 경우, ‘워치독 타이머’ 설정이 가능합니다. 인버터 키패드 PAR-PRT 12 Lost
Cmd Mode 를 활성화 하는 경우, PAR-PRT 13의 Lost Cmd Time 을 설정할 때, 마스터의 워치독 타이머 설정
값이 더해지므로, 해당 사항을 고려하여 인버터의 PAR-PRT 13의 Lost Cmd Time 값을 설정합니다.
워치독 타이머: 통신 디바이스(iS7 RAPIEnet+ 옵션 보드)가 마스터와 연결 유지를 감시하는 시간.
(3) 통신 디바이스 동작 설정
핫스왑 설정을 선택합니다. 선택하지 않으면 통신에 참여 중인 EB 중 1개만 탈락되어도 전체가 스톱하게 됩
니다
24
iS7 RAPIEnet+ Option Manual
(4) 입력/출력 변수 할당
아래와 같이 자동으로 입/출력 변수 8word/8word 통신이 가능합니다.
(5) 진단 변수 할당
25
iS7 RAPIEnet+ Option Manual
(6) 통신 디바이스 연결 구성
(7) 서비스별 상태
26
iS7 RAPIEnet+ Option Manual
③ [서비스별 상태] -> [스마트 증설] 탭을 선택하면 스마트 증설 서비스의 상태를 확인할 수
있습니다.
27
iS7 RAPIEnet+ Option Manual
28
iS7 RAPIEnet+ Option Manual
11.3 LED 정보 및 고장 처리
LED 의미 Color 동작 의미 동작 의미
Network RAPIEnet 통신 설정 확인 *1
LED0 LINK1 Orange ON
설정 확인 주기 통신이 1초 이상 없는 경우
Network RAPIEnet 통신 설정 확인 *1
LED1 LINK2 Orange ON
통신 불량 주기 통신이 1초 이상 없는 경우
*1: RAPIEnet 통신 설정 확인의 경우 [COM-7], [COM-13] 그리고 [COM-30], [COM-50] Keypad 설정 값과 PLC의 설정을 확인하여
주십시오.(RAPIEnet+ 옵션 보드가 RAPIEnet Enable 상태에서 당사 마스터와 통신 시에, COM-7 국번, COM-13 IP 주소가 통신에
29
iS7 RAPIEnet+ Option Manual
LED 의미 Color 동작 의미 동작 의미
Flashing
RAPIEnet+ 통신 옵션 보드와 인버터
LED0과 동기 점멸
사이에 통신 불량
(1초 주기)
EEPROM 파손 시
ON 2개의 링크 모두 연결이 없는 경우
국번 또는 IP address 충돌하는 경우
*2: Keypad 설정 파라미터와 통신 모듈 설정을 동일하게 하기 위해서는 COM그룹의 설정을 확인한 후 [COM-94] Comm Update를 1 yes
로 설정하여 주시면 설정 값이 통신 모듈에 적용됩니다.
30
iS7 RAPIEnet+ Option Manual
12.1 개요
RAPIEnet+ 옵션보드
RAPIEnet v2 EtherNet/IP Modbus TCP
PAR -> COM 25
[Opt Parameter-16]
사용 가능 여부 사용 가능 여부 사용 가능 여부
설정 값: ‘2’ O O O
RAPIEnet v2 Enable
설정 값: ‘0’ X O O
RAPIEnet v2 Disable
12.2 EtherNet/IP
(1) 프로토콜에 대한 기본 구성
31
iS7 RAPIEnet+ Option Manual
① 지원 범위
Transport Type
Originator->Target: Point to Point
Target->Originator: Multicast
Transport Trigger: Cyclic
Configuration Connection: 1
Connection Tag: 지원 하지 않음
Priority
Originator->Target: Scheduled
Target->Originator: Scheduled
Configuration Data: 지원 하지 않음
② Input Instance
인버터에서 PLC혹은 Client기기에 인버터 상태를 주기적으로 보내는 Data입니다.
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Running
0 1 Faulted
(Fwd)
70
1
2 Speed Actual (Low Byte) – RPM unit (note 1)
3 Speed Actual (High Byte) – RPM unit
At Ref From Ctrl From Running 2 Running Warnin
71 0 Ready Faulted
Reference Net Net (Rev) 1 (Fwd) g
32
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 Drive State
2 Speed Actual (Low Byte) – RPM unit
3 Speed Actual (High Byte) – RPM unit
Running
0 1 Faulted
(Fwd)
110
1
2 Speed Actual (Low Byte) – Hz unit (note 1)
3 Speed Actual (High Byte) – Hz unit
At Ref From Ctrl From Running 2 Running Warnin
0 Ready Faulted
Reference Net Net (Rev) 1 (Fwd) g
111 1 Drive State
2 Speed Actual (Low Byte) – Hz unit
3 Speed Actual (High Byte) – Hz unit
0 Status Parameter - 1 data (Low Byte)
141
1 Status Parameter - 1 data (Hi Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (Hi Byte)
142
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (Hi Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (Hi Byte)
2 Status Parameter - 2 data (Low Byte)
143
3 Status Parameter - 2 data (Hi Byte)
4 Status Parameter - 3 data (Low Byte)
5 Status Parameter - 3 data (Hi Byte)
0 Status Parameter - 1 data (Low Byte)
1 Status Parameter - 1 data (Hi Byte)
2 Status Parameter - 2 data (Low Byte)
3 Status Parameter - 2 data (Hi Byte)
144
4 Status Parameter - 3 data (Low Byte)
5 Status Parameter - 3 data (Hi Byte)
6 Status Parameter - 4 data (Low Byte)
7 Status Parameter - 4 data (Hi Byte)
145 0 Status Parameter - 1 data (Low Byte)
33
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
34
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
35
iS7 RAPIEnet+ Option Manual
③ Output Instance
PLC혹은 Client기기가 인버터에 지령을 주기적으로 보내는 Data입니다.
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault Run
0
Reset Fwd
1 0
20
2 Speed Reference (Low Byte) – RPM unit
1 0
21
2 Speed Reference (Low Byte) – RPM unit
Fault Run
0
Reset Fwd
1 0
100
2 Speed Reference (Low Byte) – Hz unit
1 0
101
2 Speed Reference (Low Byte) – Hz unit
36
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
37
iS7 RAPIEnet+ Option Manual
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
38
iS7 RAPIEnet+ Option Manual
Related Attribute
Name Description
Class Attr. ID
Fault reset(주1) Fault Reset Command 0x29 12
NetRef(주2) Not used 0x2A 4
NetCtrl(주2) Not used 0x29 5
Speed Reference Speed Command 0x2A 8
(주1) Control Supervisor Object (Class 0x29)의 Drive Run부분과 Fault부분을 참
조하기 바랍니다.
(주2) Reference Control 과 Run/Strop Control 의 설정은 LCD Control Pannel을
통해서만 가능하게 되어 있습니다. 따라서 Instance 21 과 101에서 (NetRef,
NetCtrl)은 사용되지 않습니다.
(4) 지원 Object
Attribute
Attribute
Access Attribute Name Data Length Attribute Value
ID
1 Get Vendor ID (LS Industrial System) Word 259
2 Get Device Type (AC Drive) Word 2
3 Get Product Code Word 100 (주1)
Revision
4 Get High Byte - Major Revision Word (주2)0x0101
Low Byte - Minor Revision
39
iS7 RAPIEnet+ Option Manual
Service
Service Support for Support for
Definition
Code Class Instance
0x0E Get Attribute Single No Yes
0x05 Reset No Yes
0x01 Get Attribute All No Yes
40
iS7 RAPIEnet+ Option Manual
Attribute
Attribute
Access Attribute Name Range Definition
ID
0 : Non-standard motor
1 : PM DC Motor
2 : FC DC Motor
3 : PM Synchronous Motor
4 : FC Synchronous Motor
3 Get Motor Type 0~10 5 : Switched Reluctance Motor
6 : Wound Rotor Induction Motor
7 : Squirrel Cage Induction Motor
8 : Stepper Motor
9 : Sinusoidal PM BL Motor
10 : Trapezoidal PM BL Motor
[Get]
BAS-13 Rated Curr값을 읽어 옵니다.
0.0~1 [Set]
6 Get/Set Motor Rated Curr
000.0 Set 한 값이 BAS-13 Rated Curr에 반영
됩니다.
Scale 0.1
[Get]
BAS-15 Rated Voltage값을 읽어 옵니다.
0~ [Set]
7 Get/Set Motor Rated Volt
690 Set 한 값이 BAS-15 Rated Voltage에
반영 됩니다.
Scale 1
Service
Service Support for Support for
Definition
Code Class Instance
0x0E Get Attribute Single No Yes
0x10 Set Attribute Single No Yes
41
iS7 RAPIEnet+ Option Manual
Attribute
Attribute
Access Attribute Name Range Definition
ID
0 정지
3 Get / Set Forward Run Cmd.
1 정 방향 운전 (주1)
0 정지
4 Get / Set Reverse Run Cmd.
1 역 방향 운전 (주1)
5 지원 안함 Net Control - Inverter 파라미터로만 설정 가능합니다.
0 Vendor Specific
1 Startup
2 Not Ready (reset 중)
3 Ready (정지 중)
6 Get Drive State
4 Enabled (Run 중 단 감속 정지 중 제외)
5 Stopping (정지 감속 중)
6 Fault Stop
7 Faulted (Trip 발생)
0 정지 중
7 Get Running Forward
1 정 방향 운전 중
0 정지 중
8 Get Running Reverse
1 역 방향 운전 중
0 Reset 중이거나 Trip이 발생한 경우
9 Get Drive Ready
1 인버터가 운전할 수 있는 정상 상태
0 현재 Trip 발생이 발생 하지 않음
10 Get Drive Fault
1 현재 Trip 발생한 상황임.
42
iS7 RAPIEnet+ Option Manual
위에 표에서 Run1은 Forward Run Cmd.를 나타내는 것이며 Run 2는 Reverse Run
Cmd.를 나타냅니다. 즉 0(FALSE)->1(TRUE)로 변하는 순간에 옵션이 인버터에 운
전 지령을 내리게 됩니다. Forward Run Cmd.의 값을 읽었을 때 에는 현재 인버터의
운전 상태를 나타내는 것이 아니라 옵션의 운전 명령 값에 대한 것을 나타냅니다.
(주2) Drive Fault
인버터에 Trip이 발생하였을 때 Drive Fault 은 TRUE가 된다.
이때 Drive Fault Code는 아래와 같다.
Drive Fault Code
Fault
Code Description
Number
0x0000 None
Ethermal Out Phase Open InverterOLT
InPhaseOpen ThermalTrip UnderLoad
0x1000 ParaWriteTrip IOBoardTrip PrePIDFail
OptionTrip1 OptionTrip2 OptionTrip3
LostCommand UNDEFINED LostKeypad
0x2200 OverLoad
0x2310 OverCurrent1
0x2330 GFT
0x2340 OverCurrent2
0x3210 OverVoltage
0x3220 LowVoltage
0x2330 GroundTrip
0x4000 NTCOpen
0x4200 OverHeat
0x5000 FuseOpen HWDiag
0x7000 FanTrip
0x7120 No Motor Trip
0x7300 EncorderTrip
43
iS7 RAPIEnet+ Option Manual
Fault
Code Description
Number
0x8401 SpeedDevTrip
0x8402 OverSpeed
0x9000 ExternalTrip BX
Drive Fault Reset
Drive Fault Reset은 0->1 즉 FALSE->TRUE로 갈 때 인버터에 TRIP RESET 지령
을 내리게 됩니다. 1(TRUE)인 상태에서 한번 더 1(TRUE)을 쓴다고 해서 인버터의
TRIP에 RESET지령을 내리지는 않습니다. 1(TRUE)인 상태에서는 다시 0(FAULT)으
로 쓰고 다시 한번 더 1(TRUE)을 쓰셔야 RESET지령이 옵션에서 인버터로 지령이
내리게 됩니다.
Service
Service Support for Support for
Definition
Code Class Instance
0x0E Get Attribute Single No Yes
0x10 Set Attribute Single No Yes
Attribute
Attribute Attribute
Access Range Definition
ID Name
출력 주파수가 설정 주파수에 도달 하지
0
않음을 나타냅니다.
3 Get At Reference
출력 주파수가 설정 주파수에 도달 했음을
1
나타냅니다.
Net
4 지원 안함 -
Reference
0 Vendor Specific Mode
1 Open Loop Speed(Frequency)
Drive Mode
6 Get 2 Closed Loop Speed Control
(주1)
3 Torque Control
4 Process Control(e.g.PI)
0~ 현재 출력 주파수를 [rpm]으로 환산해서
7 Get SpeedActual
24000 표시해줍니다.
44
iS7 RAPIEnet+ Option Manual
Attribute Attribute
Access Range Definition
ID Name
목표 주파수를 [rpm]으로 환산해서 지령
0~
8 Get / Set SpeedRef 을 줍니다. DRV-07 Freq Ref Src가
24000
FieldBus로 설정이 되어야 반영이 됩니다.
Actual 0~111.0 0.1 A 단위로 현재 전류를 모니터링 합니
9 Get
Current A 다.
주파수 지령 Source가 DeviceNet 통신이
0
Ref.From 아닙니다.
29 Get
Network 주파수 지령 Source가 DeviceNet 통신입
1
니다.
0~400.00 현재 운전중인 주파수(Hz단위)를 모니터링
100 Get Actual Hz
Hz 합니다.
DRV-07 Freq Ref Src가 8.FieldBus로 설
0~400.00
101 Get / Set Reference Hz 정 시 지령 주파수를 통신으로 설정 가능
Hz
합니다.
Acceleration 0~6000.0
102 Get / Set 인버터 가속 시간을 설정/모니터링 합니다.
Time (주2) sec
Deceleration 0~6000.0
103 Get /Set 인버터 감속 시간을 설정/모니터링 합니다.
Time (주3) sec
(주1) DRV-10 Torque Control, APP-01 App Mode와 관련 있습니다. DRV-10
Torque Control을 Yes로 설정하면 Drive Mode가 “Torque Control”가 되고
APP-01 App Mode를 Proc PID, MMC로 설정을 하면 Drive Mode가 “Process
Control(e.g.PI)”가 됩니다.
(주2) DRV-03 Acc Time 값입니다.
(주3) DRV-04 Dec Time 값입니다.
Service
Service Support for Support for
Definition
Code Class Instance
0x0E Get Attribute Single No Yes
0x10 Set Attribute Single No Yes
45
iS7 RAPIEnet+ Option Manual
Attribute
Acc Attribute Attribute
Instance Attribute Number
ess Name Value
1 (DRV Group) iS7 Manual Code 번호와 동일
2 (BAS Group) iS7 Manual Code 번호와 동일
3 (ADV Group) iS7 Manual Code 번호와 동일
iS7
4 (CON Group) iS7 Manual Code 번호와 동일
Parameter
5 (IN Group) iS7 Manual Code 번호와 동일 iS7 Keypad
Get/ 의 설정 범
6 (OUT Group) iS7 Manual Code 번호와 동일 Title
Set 위
7 (COM Group) iS7 Manual Code 번호와 동일 (iS7 Manual
(iS7
8 (APP Group) iS7 Manual Code 번호와 동일 참조)
Manual 참
9 (AUT Group) iS7 Manual Code 번호와 동일
조)
10 (APO Group) iS7 Manual Code 번호와 동일
11 (PRT Group) iS7 Manual Code 번호와 동일
12 (M2 Group) iS7 Manual Code 번호와 동일
Service
Service Support for Support for
Definition
Code Class Instance
0x0E Get Attribute Single No Yes
0x10 Set Attribute Single No Yes
46
iS7 RAPIEnet+ Option Manual
47
iS7 RAPIEnet+ Option Manual
요구 Frame 길이 값
Function Code 1 Bytes 0x03
통신주소 2 Bytes 0x0000 ~ 0xFFFF
Data 요구 개수 2 Bytes 1~16 (LS ELECTRIC 인버터
기준)
응답 Frame 길이 값
Function Code 1 Bytes 0x03
통신주소 1 Bytes 2 x Data 요구 개수
Data 요구 개수 Data 요구 개 통신 주소로부터 개수 만큼의
수 x 2 Bytes Data 값
요구 Frame 길이 값
Function Code 1 Bytes 0x04
통신주소 2 Bytes 0x0000 ~ 0xFFFF
Data 요구 개수 2 Bytes 1~16 (LS ELECTRIC 인버터
기준)
48
iS7 RAPIEnet+ Option Manual
응답 Frame 길이 값
Function Code 1 Bytes 0x03
통신주소 1 Bytes 2 x Data 요구 개수
Data 요구 개수 Data 요구 개 통신 주소로부터 개수 만큼의
수 x 2 Bytes Data 값
응답 Frame 길이 값
Function Code 1 Bytes 0x06
통신주소 2 Bytes 0x0000 ~ 0xFFFF
Data 값 2 Bytes 0x0000 ~ 0xFFFF
요구 Frame 길이 값
Function Code 1bytes 0x10
통신주소 2bytes 0x0000 ~ 0xFFFF
수정하는 Data 개 2byte 1~16 (LS ELECTRIC 인버터
수 기준)
Byte Count 1byte 2 X Data 개수
수정할 Data 값 Data 개수 수정할 Data들
x 2 bytes
49
iS7 RAPIEnet+ Option Manual
응답 Frame 길이 값
Function Code 1 Bytes 0x10
통신주소 2 Bytes 0x0000 ~ 0xFFFF
수정하는 Data 개 2 Bytes 1~16 (LS ELECTRIC 인버터
수 기준)
Exception Frame 구성
Error Frame 길이 값
Error Code 1bytes 0x80 + Client가 요구한
Function Code
Exception Code 1bytes 0x0000 ~ 0xFFFF
Exception Code 종류
종류 Code 설명
지원하지 않는 Function에 대해서
ILLEGAL FUNCTION 0x01
요구가 있을 경우
사용하지 않는 어드레스의 Data를
ILLEGAL DATA ADDRESS 0x02
요구하거나 수정하려는 경우
Data 수정을 할 때 Data 허용 범위
ILLEGAL DATA VALUE 0x03
를 밖에 값으로 수정하려는 경우
Server에 오류가 있을 경우
(인버터와 CAN 통신 ERROR, 옵션
SLAVE DEVICE FAILURE 0x04
초기화 ERROR 경우, 인버터와의
DATA통신을 실패한 경우)
Server가 다른 처리 중이라 응답을
할 수 없을 때
SLAVE DEVICE BUSY 0x06
(인버터 파라미터 초기화, 옵션의 초
기 설정 중일 경우)
LS 인버터에만 존재하는 Code로
WRITE PERMITION ERROR 0x20 수정 금지 파라미터에 값을 수정하려
고 할 때
50
iS7 RAPIEnet+ Option Manual
12.4 LED 정보 및 고장 처리
LED 의미 Color 동작 의미 동작 의미
Network Ethernet 통신 설정 확인 *1
LED0 LINK1 Orange ON
설정 확인 주기 통신이 1초 이상 없는 경우
Network
LED1 LINK2 Orange ON Ethernet 통신 설정 확인 *1
통신 불량
*1: Ethernet 통신 설정 확인의 경우 [COM-10], [COM-11], [COM-14], [COM-15] 그리고 [COM-23], [COM-24] Keypad 설정 값
과 클라이언트 (PLC 등)의 설정을 확인하여 주십시오.
51
iS7 RAPIEnet+ Option Manual
LED 의미 Color 동작 의미 동작 의미
Flashing
RAPIEnet+ 통신 옵션 보드와 인버
LED0과 동기 점멸
터 사이에 통신 불량
(1초 주기)
EEPROM 파손 시
ON 2개의 링크 모두 연결이 없는 경우
IP 충돌 시
*2: Keypad 설정 파라미터와 통신 모듈 설정을 동일하게 하기 위해서는 COM그룹의 설정을 확인한 후 [COM-94] Comm Update를 1 yes
로 설정하여주시면 설정 값이 통신 모듈에 적용됩니다.
52
■ Headquarter
■ Overseas Branches
■ Seoul Office
Tel: 81-3-6268-8241 E-Mail: jschuna@lselectric.biz
E-mail: automation@lselectric.co.kr
• LS ELECTRIC Shanghai Office (China)
■ Overseas Subsidiaries
• LS ELECTRIC Guangzhou Office (China)
www.lselectric.co.kr
10310001725