Differential Pressure Transmitter PAD Manual
Differential Pressure Transmitter PAD Manual
Differential Pressure Transmitter PAD Manual
for
Smart Pressure Transmitter
Model: PAD
PAD
1. Contents
1. Contents ........................................................................................................ 2
2. Introduction ................................................................................................... 4
2.1 Using This Manual ............................................................................... 4
2.2 Overview of Transmitter ....................................................................... 5
2.3 Software Compatibility ......................................................................... 5
2.4 Transmitter Components ..................................................................... 6
3. Handling Cautions ....................................................................................... 10
3.1 Unpacking .......................................................................................... 11
3.2 Models and Specifications Check ...................................................... 11
3.3 Storage .............................................................................................. 11
3.4 Selecting the Installation Locations .................................................... 12
3.5 Performing Sensor Zero Trim after Installation .................................. 12
3.6 Pressure Connections........................................................................ 13
3.7 Waterproofing of Cable Conduit Connections .................................... 13
3.8 Restrictions on Use of Radio Transceivers ........................................ 13
3.9 Insulation Resistance Test and Dielectric Strength Test .................... 14
3.10 Installation of Explosion Protected Type Transmitters ....................... 15
3.11 Notes on the machine and pressure equipment directive .................. 20
4. Transmitter Functions ................................................................................. 20
4.1 Overview ............................................................................................ 20
4.2 Safety Message ................................................................................. 20
4.3 Warning ............................................................................................. 21
4.4 Fail Mode Alarm ................................................................................. 21
4.5 EEProm-Write Enable / Disable Mode Switch ................................... 23
4.6 Configuration of Alarm and Security Jumper Procedures .................. 24
4.7 Configuration Using Zero and Span Push Buttons ............................ 24
4.8 Additional Functions (valid for PAD-F only) ....................................... 35
4.9 Wiring Connections for External HHT/ Ammeter ................................ 42
5. Installation ................................................................................................... 43
5.1 Overview ............................................................................................ 43
5.2 Safety Message ................................................................................. 43
5.3 Warning ............................................................................................. 44
5.4 Commissioning on the bench with Hand-Held Terminal .................... 45
5.5 General Considerations ..................................................................... 46
5.6 Electrical Considerations ................................................................... 46
5.7 Wiring................................................................................................. 47
5.8 Mechanical Considerations ................................................................ 54
5.9 Environmental Considerations ........................................................... 56
6. On-line Operation ........................................................................................ 57
6.1 Overview ............................................................................................ 57
6.2 Safety Message ................................................................................. 57
6.3 Configuration Data Review ................................................................ 57
6.4 Check Output ..................................................................................... 58
6.5 Basic Setup........................................................................................ 58
6.6 Detailed Setup ................................................................................... 59
6.7 Tag Information set up ....................................................................... 59
6.8 Diagnostics and Services................................................................... 60
Version: 01/0918
2. Introduction
The PAD Smart Pressure Transmitter is correctly calibrated at the factory before
shipment. To ensure correct and efficient use of the instrument, please read this
manual thoroughly and fully understand how to operate the instrument before
operating it
(1) The contents of this manual are subject to change without prior notice.
(2) All rights reserved. No part of this manual may be reproduced in any form
without Kobold Messring’s written permission.
(3) If any question arises or errors are found, or if any information is missing from
this manual, please inform the nearest sales office.
(4) The specifications covered by this manual are limited to those for the
standard type under the specified model number break-down and do not
cover custom-made instrument.
(5) Please note that changes in the specifications, construction, or component
parts of the instrument may not immediately be reflected in this manual at the
time of change, provided that postponement of revisions will not cause
difficulty to the user from a functional of performance standpoint.
Chapter 3 Handling
Chapter 3 provides instructions on software functions, configuration parameters,
and online variables.
Chapter 5 Installation
Chapter 5 contains mechanical, environment and electrical installation
instructions for Model PAD Smart Pressure Transmitters.
Chapter 7 Maintenance
Chapter 7 contains hardware diagnostics, troubleshooting and maintenance
tasks.
● : Supported.
∆ : Supported but update required
3. Handling Cautions
This chapter consists of cautions for transmitter handling and storage, selection of
installation locations, insulation structure, etc.
3.1 Unpacking
When moving the transmitter to the installation site, transfer it in its original
packaging. Only unpack the transmitter on site of installation to avoid damage
during transit.
3.3 Storage
The following precautions must be observed when storing the instrument,
especially for a long period.
However, it can also be stored under ambient temperature and relative humidity
within the following published ranges.
(2) When storing the transmitter, repack with original (or similar) packaging that
was shipped from the factory.
(3) If storing a transmitter that has already been used, thoroughly clean all wetted
parts including diaphragm seals (if installed), process connections/manifolds
in contact with process fluid. In addition, make sure before storing the
transmitter that remote seal (if supplied) assemblies are securely mounted.
(2) For Sensor Zero Trim, make input pressure of transmitter zero prior to
initiating zero trim calibration. Any Sensor Trim done in field must be carried
out after installation is finalized and with transmitter position fixed. Also if
applying external pressure ensure the display is sufficiently stabilized (after
approximately 10 to 15 seconds) before initiating any Trim function.
(3) There are two recommendations for making input pressure “zero”. One is to
apply a “zero” pressure source (mandatory for absolute pressure models).
The second option is to open equalizing valve of manifolds and venting to
atmospheric pressure (allowed only for Gauge type models).
(4) Sensor Zero Trim can be performed using an external HHC (Hand held
calibrator), PC or PDA configurator, and/ or using Zero/Span local push
buttons provided on the transmitter.
(5) When using local push buttons please refer to Chapter 4.7 of this manuals for
detailed instructions. If using an external HHT or HART® PC configurator
please refer to the user manuals supplied by the third party supplier.
▲ Warning
Instrument installed in the process is under pressure. Never loosen or tighten the
flange bolts as it may cause dangerous spouting of process fluid.
If the accumulated process fluid may be toxic or otherwise harmful, take
appropriate care to avoid contact with the body or inhalation of vapors even after
dismounting the instrument from process line for maintenance.
(1) Do not perform such tests more frequently than is absolutely necessary. Even
test voltages that do not cause visible damage to the insulation may degrade
the insulation and reduce safety margins.
(2) Never apply a voltage exceeding 500 VDC (100 VDC with an internal lightening
protector) for the insulation resistance test, nor a voltage exceeding 500 VAC
(100 VAC with an internal lighting protector) for the dielectric strength test.
(3) Before conducting these tests, disconnect all signal lines from the transmitter
terminals. Perform the tests in the following procedure.
Note 5. Installation
All wiring shall comply with local installation requirement.
The cable glands and blanking elements shall be of a certified flameproof type,
suitable for the condition of use and correctly installed. Also those devices
should be endured at the 130C.
Housing Ground must be followed to “local electrical codes”. The most efficient
ground procedure is to connect directly to the earth as least impedance.
Note 6. Operation
WARNING-DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE
PRESENT
Take care not to generate mechanical spark when access to the instrument
and peripheral devices in hazardous location.
INSTALLATION
◈ Wiring is to be carried out only by qualified staff.
◈ The power supply voltage limits shall not be exceeded.
◈ Maintenance and repair should be isolated by power supply and any pressure.
◈ Wiring methods and length of cable of power supply cable and ground cable
should be considered by proper Ex condition.
◈ Transmitter has the ‘reverse polarity protection diode’ in order to prevent failure
in the field while wiring +, - power supply voltage. However if the wiring is not
performed correctly or wrong terminals on rear terminal board are used for
power supply, the transmitter may malfunction.
◈ Housing Grounding
● Internal Ground Connection: Open rear cover on transmitter, the ground bolt
is located inside with grounding mark
● External Ground Assembly: On the left side of transmitter, there is a bolt for
ground with grounding mark (for grounding use a cable lug).
● Housing Rotation hexa screw bolt shall be screwed tightly in order to hold
the position of transmitter.
◇ Compliance for intrinsically safety is ensured only if the intrinsically safe safety
barrier complies with safety parameters as provided in the relevant ATEX
certification
◇ To comply with intrinsic safe system concept, the transmitter is connected with
the safety barrier in a loop (see chapter 5.7. Wiring).
◇ To assure an Intrinsic Safety System, the transmitter and barrier must be
wired in accordance with the barrier manufacturer’s field wiring instructions
and the applicable circuit diagram.
Warning
The entity concept allows interconnection of intrinsic safe apparatus to
associated apparatus not specifically examined in combination as a
system.
◇ The approved value of open circuit max. voltage Uo, max. short circuit current
Io and max. power Po in associated equipments are should be less than or
equal for max. safe input voltage Uo, max. input current Ii and max. safe
power Pi of the transmitter with Ex ia.
◇ The approved value of max. capacitance Co in associated equipments should
be bigger than total value of capacitance Ci in transmitter with Ex ia + cable
capacitance in associated equipment.
◇ The approved value of max. inductance Lo should be bigger than total value
of inductance Li in transmitter with Ex ia + cable inductance in associated
equipment.
Equip with Ex ia Comparison Associated Equipment
Ui = 30 VDC ≥ Uo
Ii = 200 mA ≥ Io
Pi = 0.9 W ≥ Po
Ci = 27 nF < Co
Li = 104 uH < Lo
Caution
External load resistance includes the safety barrier resistance for intrinsic
safety device.
Diagram 2
Vessels referred to in Article 4(1)(a)(i), second indent
4. Transmitter Functions
4.1 Overview
This Chapter contains information on operating Model PAD. Tasks that should be
performed on the bench prior to installation are explained in this chapter.
4.3 Warning
▲ Warning
Electrical can result in death serious injury:
Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
▲ Warning
Electrical can result in death serious injury:
Only qualified & trained personnel should be allowed to operate these
transmitters.
Fail Mode Selection (Fail High/UP or Low/DOWN) can be configured using the
appropriate jumper switch provided on the LCD Module or DIP switches included
on the Main CPU Module. For units provided with a LCD module one can select
desired fail safe mode directly from the jumper switch included in the front display
and this setting overrides the DIP settings on the back-end Main CPU module,
provided the DIP switch “2” on CPU module is DOWN. If DIP switch “2” on CPU
module is UP, this setting overrides the jumper setting on LCD module. Default
setting from the factory is “Fail Down” (DIP Switch “2” on CPU Module is DOWN).
However in case of blind units please select your required DIP switch settings
from the DIP switch labelled (2) marked on the Main CPU board. Recommended
jumper & DIP settings are listed in the table below for ready reference.
UP
DOWN
Note: DIP Switch (1) shown on Left in Fig 4-1 is for Write Enable/ Disable
selection. DIP switch (2) shown on right in Fig 4-1 is for Fail Mode.
U O O O U O O O D O O O D
(FAIL MODE DOWN, FAIL MODE SELECT (FAIL MODE UP,
place jumper to right) place jumper to left)
Figure 4-3. CPU Module Fail Mode, EEPROM-Write Selection Jumper Switch
Note: DIP Switch (1) shown on Left in Fig 4-1 is for Write Enable/ Disable
selection.
DIP switch (2) shown on right in Fig 4-1 is for Fail Mode.
4.5.1 Security
To quickly summarize there are three options available to implement
configuration security
lock out within the PAD. These include:
(1) DIP settings on CPU Board
(2) Software enable/ disable on Write function using HHT or HART® PC.
(3) Physically removing Zero and Span Magnetic Buttons from Transmitter
thereby restricting local access to push button menus. This option will still
allow changes via a remote HHT or HART® enabled configurator.
Caution: Do not fully unscrew all screws in order not to lose them.
Caution: After 30 seconds inactivity the automatic time out feature will
default user back to normal measurement mode with a “BT-Err”
message on display. Please refer to Appendix 1 for LCD display
messages and the button errors.
First time users should familiarize themselves with numeric value input sequence
prior to accessing above sub menus. Due to limited flexibility with only 2 push
buttons
available for configuration, it is not possible to directly input numeric values within
these sub-menus. Instead, the correct sequence requires user to first set an
increment (10x) rate e.g. 0.01, 0.1, 1.0, 10. 100, 1000 etc and then proceed with
changing numeric value by the set rate increment.
For example, to input a numeric value as “3810” from existing displayed value of
“0000”:
->First Set increment rate as “1000”
->Increase display “0000” value 3 times in steps of 1000 till it reads “3000”
->Then set increment rate again as “100”
->Increase 8 times in steps of 100 till display reads “3800”
->Set increment rate again as 10
->Increase 1 time for a step change of 10 till display reads 3810.
This section outlines the push button sequence for facilitating direct
numeric value input from following sub-menus :
When activating these sub-menus (by pushing down & releasing (span) button
from within its active menu) the display will automatically prompt for “SEL INC”
message.
Note: When setting URV/ LRV numeric data please ensure values being
inputted fall within the allowed minimum/maximum specifications
published for the installed sensor range code. Only if display shows –
DONE- will the transmitter update its stored configuration & accept the new
values. If out of limits the transmitter will reject values entered and default
to previous saved values after displaying a “RNGOVR” error message.
- To save the settings, press SPAN button. And indicating “DONE” message.
Important Note: Always select only one of NOR (normal) modes. Though it
is possible to set ENG (engineering) modes also from this menu it is not
recommended unless specific Engineering mode parameters such as
engineering units, High/Low values, Linear/Sq-Root functions etc have
been pre-configured either from factory ( if specified on your order) or
using an external HHC based configuration when available. With
engineering mode enabled users have the added flexibility of configuring
LCD display to emulate custom preferences separate from the transmitter
current output functions. As such with engineering mode enabled users
can program custom units, engineering units for flow, volume totals and
level, scale different URV/LRV, linear mode etc independent of those
explained in previous sections.
*3-2 format will be displayed for mA and % regardless of any other setting.
- The set value will be applicable for displaying PV value and Engineering
value.
- The LCD will display “LCD_OV” and current setting unit when the pressure
exceeds the limit of the setting value.
Please refer to Appendix 1 for LCD display message and the button errors.
4.8.1 Summary
The functioning of Flow Meter “Totaliser”:
The measured differential pressure corresponds to a specific flow range (programmed
as “Flow rate LRV” and “Flow rate URV” in the programming menu). Example: 0...1200
mmH2O = 4...20 mA = 0...+100% = -30...+50 l/h (to be confirmed by the user while
ordering))
The percentage of delta P thus determines the actual flow rate as the relationship
between percentage delta P and flow rate is linear, e.g. +50%=+10 l/h.
By integrating the flow rate function with respect to time over a specific time span, flow
totalisation value is determined.
By knowing the flow rate URV and choosing a pre-defined pulse scale (unit volume per
pulse e.g. m3/pulse), the pulse duty cycle (pulses/sec) is calculated (see section
4.8.2.3 for an example).
Note: PAD-F measures the flow rate by using differential pressure. It cannot
compensate the changes in operating temperature and static pressure.
Relay or
Impulse Counter
DC Power Supply
Terminal Block
Port "1"
Terminal Block
Port "2"
4.8.2.3 Spec.
Scaled Pulse : A Single pulse is output for a specified flow amount.
Pulse Width : 10 ms, 50 ms, 100 ms selectable (Negative going pulse)
Duty Cycle : 49 Pulse/sec. Max.
Output Type : Open Collector, 30 V, 500 mA Max.
When pulse output is used, the most important thing is to check the above
Duty_cycle, Flow_rate and Pulse_scale. The specification check of the system in
which PAD-F pulse output will be input is also important. For examples, if the
system to which PAD-F will be applied is used to measure the flow rate
0~20,000l/h and the Pulse_Scale is set to 0.1, Pulse Duty Cycle will be shown as
follows.
If the pulse is beyond maximum Duty Cycle like the above case, the output pulse will
be set to 49 Pulse/sec and “PLS-OV” mark will be shown on the LCD.
First time users should familiarize themselves with numeric value input sequence
prior to accessing above sub menus. For an example to demonstrate push button
sequence for facilitating direct numeric value input, refer to section 4.7.3.3.
Message
Definition Description Remark
on LCD
Shows Flow Rate/ Totaliser/ PV
FL_RO Flow Rotation Mode
values in rotation on LCD
F_RATE Flow Rate Shows Flow Rate value on LCD
FTOTAL Flow Totaliser Shows Flow Totaliser value on LCD
5. Installation
5.1 Overview
The information in this chapter 5 covers installation considerations. Dimensional
drawings for Model PAD variation and mounting configuration are included in this
chapter.
5.3 Warning
▲ Warning
Explosion can result in death or serious injury:
Do not remove the transmitter covers in hazardous locations when the circuit is
live.
Transmitter covers must be fully engaged to meet explosion proof approval
requirements.
▲ Warning
Electrical shock can result in death or serious injury. If you install transmitter around
a high voltage environment e.g. power lines there may be a very high likelihood of
high voltages induced on to the signal lines.
Avoid direct contact with the signal leads and terminals to avoid potential
electrocution.
▲ Warning
Process leaks can cause death or serious injury:
Install and tighten before applying pressure. Inspect regularly for process leaks.
▲ Warning
Electrical can result in death serious injury:
Only qualified & trained personnel should be allowed to operate these
transmitters.
▲ Warning
Instrument installed in the process is under pressure. Never loosen or tighten
the flange bolts as it may cause leakage of process fluid.
If the process fluid may be toxic or otherwise harmful, take appropriate care to
avoid contact and/ or exposure to direct vapours even after dismounting the
instrument from process line for maintenance.
Start
No
Basic Set up
Yes
a) Unit Setup
b) Range Setup
c) Damping Setup
d) Transmitter
advanced functions
e) Set Jumpers (fail safe!)
Field Install
a) select correct location
b) connect signal leads
c) check grounding
d) connect power supply
e) Verify values
End
Here, loop resistance of minimum 250 ~ 550Ω (@24 VDC) is recommended for
HART® communication.
5.7 Wiring
CO M M TEST
Local Indicator
or
Ampere Meter
+ -
DCS or
Power Supply
5.7.4 Wiring
A. Loop Configuration
Kobold Series Transmitters use a two-wire system for power supply, 4~20mA
analogue signal transmission and HART digital transmission.
DC Power Supply is required for the transmitter loop. The Transmitter and
distributor are connected as shown below.
Apply a non-hardening
sealant to the terminal
box connection port
and the threads on the
flexible metal conduit
for the waterproofing.
[Figure 5-4a
Typical Wiring using
Flexible Metal Conduit]
[Figure 5-4b
Typical Wiring using Flameproof Metal Conduit]
5.7.5 Grounding
(a) Grounding should satisfy typical requirements (grounding resistance 10 Ohm
or less). Grounding is required below 10 Ohm for explosion proof
requirements.
(b) There are ground terminal provided on the inside and outside of the terminal
box. Either one of these terminals may be used for grounding the
transmitters.
(c) Use PVC insulated wire (600V min rated) for grounding.
5.8.1 Mounting
During installation provide transmitters with adequate support. In the case of
severe vibration, we recommend mounting to a 2” pipe using appropriate
mounting bracket available as option. Kobold offers two styles of mounting
brackets in SS. These include an “Angle type” and a “Flat type”.
6. On-line Operation
6.1 Overview
This chapter describes configuration functions of PAD smart pressure
Transmitter. Transmitter can be configured in either On-Line or Off-Line mode. In
On-Line configuration mode, you must connect through an external HHT (Hand
Held Terminal) supporting HART® DDL technologies. When connecting in Multi-
drop mode ensure each device on the HART® bus is provided with a unique
HART® device ID for identification.
6.2.1 Warning
▲ Warning
Explosion can result in death or serious injury:
- Do not remove the transmitter covers in hazardous areas when
the circuit is live.
-Before connecting HHT in a classified zone, check that the
configuration device connecting to transmitter also complies to
required safety regulations.
-Both transmitter covers must be fully engaged to meet explosion
proof certification requirements
6.5.3 Rerange
Set the Zero and Span for the 4~20mA analogue output.
The Meaning of
Damping time is to
reach 63.2% of target
value
63.2 % of Total
6.9 Calibration
Re-Ranging scales the upper and lower ranges of transmitter outputs and does
not affect the stored calibration data of the transmitter. On the other hand a
Sensor Trim function can be used to tune/modify the stored calibration.
It is important to keep in mind that Smart transmitters operate differently from
conventional analogue transmitters. A Smart transmitter uses a microprocessor
that contains information about the sensor's specific characteristics in response
to pressure and temperature inputs which is what is used for calculating final PV
(Process Variable). These calibration curves are performed under traceable
laboratory standards and stringent quality control parameters. Changing factory
calibration data is advisable only if it is necessary to correct transmitter offsets
and only when checking against a traceable calibration source which is at least
five time more accurate than the transmitter under test.
As such a Sensor trim and Output Re-range function differ. Re-ranging sets the
transmitter analogue output to the selected upper and lower range points and can
be done with or without an applied pressure. Re-ranging does not change the
factory characterization curve stored in the microprocessor. Sensor trimming
requires an accurate pressure input and adds additional compensation that
adjusts the position of the factory characterization curve to optimize transmitter
performance over a specific pressure range.
Two point trim is a full sensor trim, in which two accurate pressures with
difference within the published sensor span specifications for the specific range
codes are applied (equal to or greater than the range values), and the output is
set to linear. You should always adjust the low trim value first to establish the
correct offset.
Zero adjustment allows user to add a pre-defined offset (other than zero) to
measured PV that may be required on certain applications such as Level
measurements to compensate for nozzle placements.
7. Maintenance
7.1 Overview
This chapter describes breakdown diagnostic and maintenance.
7.2.1 Warning
▲ Warning
Explosion can result in death or serious injury:
Do not remove the transmitter covers in hazardous locations when the circuit is
live.
Transmitter covers must be fully engaged to meet explosion proof approval
requirements.
▲ Warning
Electrical shock can result in death or serious injury. If you install transmitter around
a high voltage environment e.g. power lines there may be a very high likelihood of
high voltages induced on to the signal lines.
Avoid direct contact with the signal leads and terminals to avoid potential
electrocution.
▲ Warning
Process leaks can cause death or serious injury:
Install and tighten before applying pressure. Inspect regularly for process leaks.
▲ Warning
Electrical can result in death serious injury:
Only qualified and trained personnel should be allowed to operate these
transmitters.
▲ Warning
Instrument installed in the process is under pressure. Never loosen or tighten
the flange bolts as it may cause leakage of process fluid.
If the process fluid may be toxic or otherwise harmful, take appropriate care
to avoid contact and/ or exposure to direct vapors even after dismounting the
instrument from process line for maintenance.
+
Galvanometer
_
_
Wiring
Electronic Terminal
Module
1. Disconnect the power to the transmitter. Remove the cover from the
electronics side of the transmitter housing (Figure 7.2).
2. Do not remove the instrument cover in explosive atmospheres when the
circuit is alive.
3. Remove the LCD meter by first disconnecting the screws and then pulling
out the LCD module from the plug in connector located behind the
module.
4. Remove the two screws that anchor the electronics module to the
transmitter housing.
5. Remove the analogue sensor cable & power cables from their plug in
connectors.
6. Firmly grasp the electronics module and pull it straight out of the housing,
taking care not to damage the interconnecting pins.
8. Appendix I
PAD SMART PRESSURE TRANSMITTER
LCD DISPLAY CODE
9. EU Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole
responsibility that the product:
to which this declaration relates is in conformity with the standards noted below:
Kobold Messring GmbH recommends customer to apply the Metal Conduit Wiring
or to upset the twisted pair Shield Cable for signal wiring to conform the
requirement of EMC Regulation, when customer installs Kobold Series
Transmitters to the plant.