515 BF03 Om
515 BF03 Om
515 BF03 Om
Operation Manual
Application BF03
Batch/Flow Controller
for
Mass Frequency Flowmeters
15 August 2021
Model 515 Flow Computer - Operation Manual
Part of the software embedded in this product is eCos - Embedded Configurable Operating System, a trademark of
Red Hat. Portions created by Red Hat are Copyright © 1998, 1999, 2000 Red Hat, Inc.
(http://www.redhat.com). All rights reserved
The software in this product was in part provided by Red Hat and any express or implied warranties, including, but
not limited to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. In no
event shall the author be liable for any direct, indirect, incidental, special, exemplary, or consequential damages
(including, but not limited to, procurement of substitute goods or services; loss of use, data, or profits; or business
interruption) however caused and on any theory of liability, whether in contract, strict liability, or tort (including
negligence or otherwise) arising in any way out of the use of this software, even if advised of the possibility of such
damage.
Contrec Ltd
Riverside, Canal Road, Sowerby Bridge,
West Yorkshire HX6 2AY UNITED KINGDOM
Tel: +44 1422 829944
Email: sales@contrec.co.uk
Website: www.contrec.co.uk
The manufacturer assumes no liability for injury or damage caused by misuse of the
instrument or for modifications made to the instrument.
This document must be consulted in all cases where the following “Caution” safety symbol is
used :
Qualified Personnel
The instrument must be installed, operated and serviced by persons who have been properly
trained and authorised. Personnel must read and understand this manual prior to installation and
operation of the instrument. Refer to section 3 for further information regarding permitted
maintenance operations. The safety of any system incorporating the equipment is the
responsibility of the assembler of the system.
Static Hazard
The 500 series flow computer uses high speed CMOS circuitry which is sensitive to static
damage. The user should observe accepted safety practices for handling electronic devices,
especially during servicing. Once the unit is installed, grounded and interconnected, the chances
of static damage are greatly reduced.
Voltage Hazard
Before connecting power to the instrument, ensure that the supply voltage for the AC or DC
input is suitable. The AC voltage rating is as stated on the instrument rating plate. Personnel
should take all due care to avoid electric shock. For safe operation it is essential to connect a
mains safety earth to the A.C. power inlet. Do not operate at altitudes above 2000m.
Welding Hazard
Do not perform electric welding in close proximity to the instrument or its interconnecting
cables. If welding in these areas must be performed, disconnect all cables from the instrument.
Failure to do so may result in damage to the unit.
Moisture Hazard
To avoid electrical faults and corrosion of the instrument, do not allow moisture to remain in
contact with the instrument. Operate only in a clean, dry and pollutant-free environment.
Instrument Disposal
Contrec instrumentation should not be thrown into the general waste system.
If within EU member states, this instrument should be disposed of according to
the guidelines set by the WEEE (Waste Electrical and Electronic Equipment)
directive 2012/19/EU. If outside of the EU, this equipment should be
responsibly disposed of according to local and national regulations for EEE
(Electrical and Electronic Equipment).
By not discarding of this product along with other house hold waste you are
preserving natural resources and reducing waste sent to landfill and incinerators.
Remove batteries and dispose of separately (see Disposal of Batteries) before disposal of
Contrec instrumentation.
Disposal of Batteries
Batteries have an environmental impact. Safe and responsible disposal should
be undertaken.
In all EU member states, as per Directive 2006/66/EC, batteries must not be
thrown away with general waste. Contact your local environmental authority
for information regarding disposal or recycling of used batteries, alternatively
they can be returned directly to Contrec Ltd. for disposal.
Please Contact Contrec Ltd before returning batteries for disposal.
2 Specifications
Specification Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Operation
Front Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Default Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Front Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Main Menu Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Detail and Basic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Setting the Batch Preset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Setting the Flow Control Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Data Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Model Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Flow Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Local Flow Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Loop Flow Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Loop Tuning Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Tuning the Control Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Batch Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Preset Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
On-Off Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Release Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Batch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operation Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Safety and Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Starting a Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Stopping a Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Resetting a Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Printing a Delivery Docket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Logic Input Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Batch Flow Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Batch Control Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5 Instrument Calibration
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Calibration View Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Calibration Set Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Changing the Instrument Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Program Backup & Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Backup via 500 Series Program Manager . . . . . . . . . . . . . . . . . . . . . . 41
Printing Configuration Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Upload and Clone of Application Software . . . . . . . . . . . . . . . . . . . . . 41
Calibration Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Instrument Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6 Communications
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Hardware Interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Simple ASCII Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Requests Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Instrument Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Corrupted or Invalid Requests . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Modbus RTU Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
List of Data Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Printer Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Types of Printouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Printer Data Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Appendix A Glossary
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Features
• Tailored for mass frequency flow inputs
• Single or Dual stage control
• Preset or manual On-Off modes
• Easy access to batch and flow rate presets
• No-flow, leakage and overflow error detection
• Remote RUN/STOP/RESET functions
• Allows for permissive with prompt
• Uses PI Loop Control
• Allows for non-linear correction
• Storage of 1000 transactions with time and date stamp
• Selection of Detail or Basic main menu to suit operator and application
• Selection of second language and user tags
• Pulse width and scaling of pulse output
• 4-20 mA retransmission
• Available protocols on communication ports including Printers, Modbus
RTU and TCP/IP
• Front panel adjustment of 8-24 V DC output voltage
• Backlit display with LCD backup
Overview
The 515 BF03 application is a batching flow controller for delivery of preset
quantities at preset flowrates using a mass frequency input. Batch control
can operate in preset or on-off modes, while flow control can be set to local
(manual) or PI loop mode.
This application provides the operator with clear local readout including
flowrate deviation and can be controlled via communications in more
automated systems. There is quick access to commonly used preset values
directly from the front panel if access has been authorized.
The overrun compensation value is valid for a new preset value provided the
stored overrun is less than 20% of the new preset.
Displayed Information
The front panel display shows the current values of the input variables and
the results of the calculations.
* These variables are logged and can be printed but are not shown in main menu.
Units of Measurement
Communications
There are two communication ports available as follows:
• COM-1 RS-232 port
• COM-2 RS-485 port (optional) or Ethernet (optional)
The ports are available for remote data reading, printouts and for initial
application loading of the instrument.
Isolated Outputs
The opto-isolated outputs can retransmit any main menu variable. The type
of output is determined by the nature of the assigned variable. Totals are
output as pulses and rates are output as 4-20 mA signals. One output is
standard, a second output is available as an option.
Relay Outputs
The relay outputs 1 and 2 are used to control the flow of product for each
delivery. These contacts are normally open and can be used to drive external
relays, valves, pump circuits etc. The advanced option provides another two
relays that can be used as fully programmable alarms for any rate type
variable.
Software Configuration
The instrument can be programmed to suit the particular application needs
and the flexible I/O can be assigned as required. Program settings can be
changed either via the front panel (depending on assigned access levels) or
via the 500 Series Program Manager (500-PM software).
The software is a Windows based program that is freely available from the
download section of the Contrec website. The program can be used to create
a custom version of an existing application to be saved for backup purposes
and/or to generate a PDF of configuration report for record keeping.
The instrument stores all set-up parameters, totals and logged data in non-
volatile memory with at least 30 years retention.
Example
Batch/Flow
Configuration
Approvals
This instrument conforms to the EMC-Directive of the Council of
European Communities 2014/30/EU, the LVD safety directive 2014/35/EU
and the following standards:
• EN61326:2013 Electrical equipment for measurement, control and
laboratory use – EMC requirements: Industrial Environment.
• EN61010:2010 Safety requirements for electrical equipment for
measurement, control, and laboratory use.
FCC Declaration
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, might
cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in
which case the user will be required to correct the interference at his own
expense.
Properly shielded and grounded cables and connectors must be used in order
to meet FCC emission limits. Contrec Ltd is not responsible for any radio or
television interference caused by using other than recommended cables and
connectors or by unauthorized changes or modifications to this equipment.
Unauthorized changes or modifications could void the user's authority to
operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) this device might not cause harmful
interference, and (2) this device must accept any interference received,
including interference that might cause undesired operation.
Transducer Supply
Voltage 8 to 24 volts DC, programmable
Current 70 mA @ 24 V, 120 mA @ 12 V maximum
Protection Power limited output
Isolated Output
No. of Outputs 2 configurable outputs
Configuration Pulse/Digital or 4-20 mA output
Pulse/Digital Output
Signal Type Open collector
Switching 200 mA, 30 volts DC maximum
Saturation 0.8 volts maximum
Pulse Width Programmable: 10 , 20, 50, 100, 200 or
500ms
4-20 mA Output
Supply 9 to 30 volts DC external
Resolution 0.05% full scale
Accuracy 0.05% full scale (20C)
0.1% (full temperature range, typical)
Installation Instructions
The safety of any system incorporating the equipment is the responsibility
of the assembler of the system and should be installed such that there is no
risk of impact damage.
This instrument is intended for fixed installation only, e.g. within a panel or
cabinet, and is not intended for desktop use. It is not suitable for outdoor use
unless fitted into an appropriate outdoor enclosure with a minimum type 3,
IP54, rating. The instrument has a ‘Pollution degree II’ rating.
Panel Mounting
The instrument should be located in an area with a clean, dry atmosphere
that is also relatively free of shock and vibration.
Figure 2 shows the panel mounting requirements for the 515 instrument.
Side View Top View RS232
Rear Connectors
22 mm 25 mm Port
145 mm 138 mm
Front
74 mm
66 mm
Panel
Mounting Clip
Min. 189 mm
67 mm
70 mm
139 mm
147 mm
Panel Cut-out
Electrical Connection
Rear Panel Connections
Figure 3 shows the connections on the original rear panel of the instrument
where relays 1 to 4 (terminals 32-35) share a single Relay Common
(terminal 31). Note: The 5 way relay terminal block is GREEN.
On the newer rear panel option cards the instrument relays 1 and 2
(terminals 32-33) share Relay Common 1-2 (terminal 31) and relays 3 and
4 (terminals 34-35) share Relay Common 3-4 (terminal 36).
Note: On these option cards the 6 way relay terminal block is ORANGE.
Figure 4 shows the new option card with the RS-485 port (terminals 19-21).
Figure 5 shows the new option card with the optional Ethernet port in place
of RS-485 port (terminals 19-21).
Terminal Designations
Terminals 1-30 are all rated at <35Vdc and wiring with basic insulation is
adequate.
Relay Wiring
Relay terminals are 31-35 or 31-36 depending on the version of option card
fitted. When controlling circuits powered by mains, or voltages >35Vdc, it
is necessary to use UL/CSA approved cabling with supplementary
insulation and a current capacity suitable for the connected circuit.
(0.75mm², 6A current capacity is sufficient).
Use copper conductors only. The maximum current must be <5A as stated
in the Specifications.
The terminal designations (L/N/E) are clearly indicated just above the mains
input connector on the rear panel of the instrument.
Inputs
Frequency Input Connection
Connect pulse or frequency input signals from devices such as: TTL,
CMOS, open collector, reed relay switch, coil and Namur proximity switch,
as shown below. For better signal integrity, it is recommended to use
shielded cable. Refer to Terminal Designations on page 11 for specific
terminal numbers for this application.
3 Signal Ground
18 Shield
Open Collector
+V
NPN PNP
Frequency Frequency
+ Input + Input
(FINPn) (FINPn)
3 Signal Ground
18 Shield
Frequency
+ Input
(FINPn)
18 Shield
It is possible to read the status of all the logic inputs via a Modbus register
even if they are not used for a control purpose in the application.
23 2+
24 3+
25 4+
26 C-
Signal Ground
Outputs
The advanced option for the instrument provides two opto-isolated output
ports. Either or both can be used for 4-20 mA or pulse outputs.
CAUTION
Due to the dual-purpose nature of the outputs, take care not to
set the output as an open collector pulse type signal when
connected to a 4-20 mA loop circuit.
515
+
4-20 mA
Output DC supply
(OUTn) 9-24V
-
Load
18
Shield
500
Vo +8...24V DC 15
External Load
Resistor 10K
Logic Input
+
DC Ground 16
18
Shield
The advanced option has two extra relays that can be freely assigned as
alarm relays. The operation of alarm relay(s) can be set to various modes as
described in Alarms on page 55. On the newer option card the separate
common terminal for relays 1 and 2 and another common terminal for relays
3 and 4 allow for different signal or supply types to be connected to the
control or alarm devices, as shown in Figure 9.
There is also an equipment failure alarm option. This alarm can have
normally closed (open) contacts which open (close) when the instrument
displays any error message as listed in Error Messages on page 64, or if
there is a loss of power to the instrument.
Relay 1 500
RC Relay 1-2 Common
1-2
MOV Control Supply
R1
Relay 2
MOV Control
R2
Relay 3
MOV Alarm/Load
R3
Relay 4
MOV Alarm/Load
R4
Supply
RC
3-4 Relay 3-4 Common
The basic principle of the operation is that the capacitor prevents a series of
sparks arcing across the contact as the contact breaks. The series resistor
limits the current through the contact when the contact first makes.
Communications
The communication protocols are described in Communications on
page 67.
6 7 8 9
1 2 3 4 5
Note: The instrument does not require a null-modem cable for connection
to a personal computer. Refer to Hardware Interconnection on
page 67 for cable termination requirements.
Gnd Gnd
+ - + -
19 20 21 19 20 21
Instrument Instrument
Mains Connection
Earthing and Shielding
A case earthing point is provided via the mains inlet. Note that this earthing
point is for the case only and there is electrical isolation between this point
and all electronic circuits. For EMC purposes, or when the instrument is
connected to mains, this point must be connected to a good earth.
It is a good practice to use shielded cable for all signal connections to the
instrument. Care must be taken to separate signal cables from power cables
to minimize interference.
Disconnection Device
When powered from a mains supply this unit requires the provision of a
suitable mains isolation device, capable of interrupting both poles of the
supply and meeting your local wiring regulations, to be suitably located and
easily accessible near to the installed instrument. It must be marked as the
disconnecting device for the equipment. It must be suitably rated with
respect to the cross sectional area of the supply conductors.
Maintenance Instructions
Occasionally it may be necessary to open the unit in order to change the Real
Time Clock battery. No other service operations are permitted. In order to
perform these operations and maintain safety it is essential to follow the
instructions below. If mounted in an ExD enclosure, before proceeding,
refer to the ExD manual for further information. This work may need to be
scheduled and carried out in accordance with the local electrical Code of
Practice.
Battery Replacement
1. Remove the top row of terminal blocks (19-36) and any communication
cables if applicable.
2. Remove the two pan head machine screws on each side of the rear panel.
4. Firmly press the battery holder tab to release the coin cell battery.
5. Identify the part number of the coin cell which is clearly marked on one
side of the cell.
Battery Type
*Issue 7 option card can be identified with 6 way (31-36) ORANGE relay
connector.
In normal operation, press the buttons on the front panel to control the
operation of the batch controller or to display the values recorded and
calculated by the instrument.
There are several categories of information that the instrument can display:
• Totals
• Rates
• Batch preset values
• Flow control values
• Instrument settings
Total Rate
Mass Mass Flowrate
Default Variable
Status LEDs
The instrument makes three beeps when it resets the totals and two beeps
when a printout is started.
DISPLAY Press the DISPLAY key to step or scroll through the main menu items.
BATCH Hold the BATCH key to display the current batch preset value. Continue to
hold for two seconds to enter edit mode for the preset if access is authorised.
Pressing the BATCH key briefly displays the accumulated total.
The main menu in this instrument consists of the following items. The
DISPLAY key is used to step or scroll through the list. The full menu can only
DISPLAY
Description Options
MASS Mass Hold the SET key to display (or edit) the batch
preset or briefly press to view the accum total
P-FLOW Process flowrate Hold the SET key to display (or edit) the
controlling setpoint
P-CTRL Process control output Hold the SET key to display (or edit) the
controlling setpoint
DEVIAT Process flowrate Hold the SET key to display (or edit) the
deviation controlling setpoint
TO RESET Reset delivery total Hold the SET key to manually reset the current
delivery (batch) total.
TO PRINT Only shown if a printer Hold the SET key to manually print a delivery
protocol is used. docket.
REPORT PRINT Only shown in Detail Hold the SET key to print log report as defined in
Menu if a printer the TM/LOG section of calibration.
protocol is used
LOGGED DATA Only shown in Detail Hold the SET key to display data logs as
Menu if real-time clock described in Data Logs on page 25.
option is installed
MODEL INFO Only shown in Detail Hold the SET key to display the Model
Menu information as described in Model Information
on page 26.
CAL MENU Only shown in Detail Hold the SET key to enter Calibration View
Menu mode as described in Calibration View Mode on
page 38.
The 515 instrument has the option to switch the main menu from the full
Detail menu to a Basic menu. The Detail menu includes all of the main
menu variables and the HOLD SET sub menu items as listed above. In the
Basic menu only the application or operator essential main menu variables
are shown. The main menu variables to be shown in the basic menu need to
be selected in the 500 Series Program Manager prior to the application
software being downloaded to the instrument. The 500 Series Program
Manager (500-PM) is Windows based configuration and resource tool for
the 500 Series and is freely available from the www.contrec.co.uk website.
To switch between the Detail and Basic menu, while in the main menu,
press and hold the DISPLAY and SET keys together for 5 seconds. When
switching to the Detail menu the display will briefly show:
display DETAIL MENU.
When switching to the Basic menu the display will briefly show:
display BASIC MENU.
When the application software is first installed, the default is the Detail
menu. From that point, the menu type is saved and restored on power cycle.
The menu type will need to be Detail to access the CAL MENU
These can then be accessed whilst in batch edit mode (described above) by
pressing the DISPLAY key. The pre-programmed values will appear in the
order they were entered in calibration. The display will step through the
presets back to the currently entered value which can still be manually
edited. While displaying the desired preset value, press the SET key to
accept the value and exit edit mode.
Data Logs
The instrument will log up to 1000 deliveries (batches) if the real-time clock
option is installed. The logs are taken at the end of each batch or upon reset
if a batch has been aborted before the preset total has been reached. Each
entry has a log number, a delivery number and a time and date stamp.
When the number of log entries exceeds 999 the oldest log entry is
overwritten by the newest one.
Use the following procedure to view the data that has been logged by the
instrument:
1. Press the DISPLAY key to scroll through the menu to the LOGGED DATA
prompt.
2. Hold the SET key.
The instrument displays the most recent log record first. The log record
number and corresponding delivery number are shown, for example LR-001
and DEL 1236.
1236
LR-001 DEL
4. Press the DISPLAY key to show the information stored in the selected log
record. Each log record consists of:
• time and date stamp,
• error code
• totals for the delivery.
5. While holding the DISPLAY key use the key to step through the stored
information.
6. While holding the DISPLAY key use the RESET key to print the data for the
displayed log if the printer option has been selected.
The following example shows the format of the time and date stamp at 15:25
(3:25 pm) on 16 January 2019. The day and month alternate with the year in
the bottom right hand corner.
15-25 15-25
LOG-TM 16/01 LOG-TM 2019
Model Information
DISPLAY
Description
DISPLAY
Description
The Process Controller has a special control mode, within the Parameters
section of calibration, to assist in tuning the control loop. This mode
provides a concise list of key parameters and allows for immediate
feedback. The basic principle in tuning the loop is to gradually adjust the
Proportional Band (P-BAND) and the Integral Time (I-TIME) and observe
the response to a step change in the setpoint.
The tune menu provides for this by allowing the P-BAND and I-TIME to be
programmed and then a Process Flow (P-FLOW) setpoint value to be
entered. The next items in the menu are the actual live process variable and
the deviation from the target value, so that the response of the system to a
setpoint change can be observed. Unless the menu is quit the program will
step back to start of the tuning menu so that new values of P-BAND and
I-TIME can be entered and the effect of a step change in the setpoint be
monitored.
As the idle position for any On-Off control valve in a batching system is
“closed”, a special option in the Batch Mode parameter, RELEASE, allows
the valve to be opened from within calibration. For more information, refer
to Release Mode on page 30.
This sequence is used for Loop mode. The tuning procedure is as follows:
1. Before tuning the control loop it is essential to program in the correct
parameters for the flowmeters, including filtering.
2. The actual Process Flow Range (P-FLOW RANGE) should be measured
and entered. It is determined by setting the Control Mode to LOCAL,
Batch Mode to RELEASE, setting the Flow Setpoint (control output) to
100% (20mA) and then observing the steady state flowrate.
3. With the correct Process Flow Range entered and Batch Mode still set to
RELEASE the Control Mode should now be set to LOOP to continue the
tuning procedure.
4. With the Loop Error Deadband (D-BAND) and the Output Ramp Time
(R-TIME) set at zero, the I-TIME should be set to zero (disabled) and the
P-BAND set at 150%.
The system should be tuned around the flowrate at which the eventual
system will operate. The stability of the loop should then be checked at
various flowrates and setpoints.
Preset Mode
If the batch mode is PRESET the prestop and shut-off points are
determined by the instrument.
The instrument can be set to count up from zero or down from the preset
value. A slow flow start feature and reduction of flowrate when approaching
the desired quantity is available for smoother batching. The automatic
overrun compensation feature can be used to improve accuracy and
repeatability. An auto-restart feature for automated repeat batches is also
available in preset mode.
On-Off Mode
The instrument will operate in a count up direction. The slow flow start
feature can still be used, but in this mode starting and stopping is determined
by the operator and in this mode there is no End of batch output signal.
Release Mode
The RELEASE prompt in batch mode is used to open the On-Off control
valve from within calibration, primarily for tuning and commissioning
purposes.
The RUN led is illuminated while the On-Off valve is “open”. The type of
flow control while the valve is open is dependent on the control mode at the
time. If in LOOP mode PI Loop flow control is activated.
For PI Loop tuning procedures that may need the flow to be “released” for
a considerable time it is important that the flow is directed to an
appropriately sized vessel.
If calibration is exited while in RELEASE mode the On-Off valve will close
and the batch mode will default to PRESET mode.
Batch Operation
Operation Configurations
For batch control this instrument can be used in three main configurations:
• Config 1. Using flow control output plus 1 control relay
• Config 2. Using flow control output only (no relays)
• Config 3. Using 2 control relays (no flow control)
Configuration 1
Flow Control & 1 Relay The Hold Output feature can be used in this
configuration to provide a faster return to
the desired flowrate when the next batch is
started.
Frequency
The analog flow control output can be used
Analog Relay
Output 1 Input 1 Output 1 to operate either a proportional control valve
or a variable speed drive.
Configuration 2
Flow Control Only (no relays) The Hold Output feature must be disabled in
this configuration as the system relies on the
proportional control valve to completely
stop the flow.
Frequency
While this system uses less hardware it is
Analog
Input 1 Output 1 not recommended when high accuracy
batching is required.
Process Flow
Flowmeter Proportional
Control Valve
Configuration 3
2-Stage Relay Control (no flow control) The batch controller can also be used in a
conventional dual stage configuration. The
Control Mode should be set to Local and the
analog flow control output remains unused.
Connecting a Permissive
If this feature has been enabled, the Permissive Input on logic input 3
ensures that a closed circuit to the common terminal (0 volts) must exist
before a delivery can be started. A batch will not continue if the permissive
input is removed and can not be resumed until the permissive input is
restored. A prompt to ‘Connect Permissive’ is scrolled on the display if the
permissive circuit is not closed.
Starting a Batch
The delivery (batch) will start when the RUN key is pressed. The RUN led
will illuminate and the instrument will begin to totalise from zero or, if
programmed for PRESET and count down mode, the display will decrement
from the preset quantity.
The batch controller’s analog output and two relays can be used to control
the delivery of product. These are energised and de-energised as described
below.
Stopping a Batch
The delivery (batch) can be stopped at any time by pressing the STOP key.
Once the process has been interrupted in this way it can be continued by
pressing the RUN key or the batch can be stopped completely by holding
the STOP key until the run led turns off.
When the process is in pause mode, the RUN led will flash to prompt the
operator to continue or abort the batch.
Resetting a Batch
If the print option has been enabled, a delivery docket can be printed by
different means. The print prompt can only be accessed or a printout
initiated if there is no delivery (batch) in progress.
• If the AUTO PRINT feature has been Enabled in the TM/LOG menu, a
delivery docket will automatically be printed at the end of each batch at
the same time that the delivery is logged. End of batch occurs when a
batch ends normally or if a batch is manually ended.
• The HOLD.SET - TO PRINT prompt in the main menu can be used to
initiate the printing of a delivery docket. The DISPLAY key can be used to
scroll through the main menu items or the RESET / PRINT key can be
used to step directly to the HOLD.SET - TO RESET prompt and then a
single press of the DISPLAY key will step onto the print prompt. If an
original printout has already been printed, a subsequent delivery docket
will include the text “(DUPLICATE DOCKET)”.
• Previous (logged) delivery transactions can be reprinted from within the
LOGGED DATA menu by scrolling to the desired DEL number, then
while holding the DISPLAY key, press RESET ( PRINT ) key to initiate a
reprint.
This instrument allows for remote operation via the logic inputs on the rear
terminals. The logic input have the following functions:
• Logic Input 1 - Remote Run
• Logic Input 2 - Remote Stop/Reset
• Logic Input 3 - Permissive Input
• Logic Input 4 - CAL Switch - In field access protection
The Remote Stop input can also be used to reset the batch total by holding
the logic input low for 2 seconds if the batch is already complete.
The instrument has the ability to raise an alarm when it detects a loss of
flow, a quadrature input error, an unexpected/overflow or a leakage in the
system.
• No Flow Error - The no flow condition is detected when the flow
timeout expires during a delivery. There must not be a period of no flow
greater than the timeout value during the delivery.
• Unexpected/Over Flow Error - The overflow condition is detected
when the flow continues longer than the timeout period after the
controller has attempted to stop (or pause) the flow.
• Leakage Error - The leakage condition is detected when an amount
greater than the acceptable total is received without flow being initiated
by the batch controller.
The point at which these errors are detected is dependent on the values
programmed into the calibration parameters such as Batch Flow Timeout
and Acceptable Total. The open collector outputs can be assigned to activate
whenever one of the flow errors occur. Refer to Instrument Settings on
page 44 for more details.
If Manual Reset the RESET key must be pressed at the end of the batch to
clear the batch total. This must be done before another batch can be started.
If Automatic Reset is programmed, a new batch is commenced each time the
RUN key is pressed.
PAUSE
Preset Qty
Run Stop Run Reached Reset Run
Count Down
Batch
Total
Count Up
Relay 1
Relay 2
Slow Start Time Prestop Qty
End of
Batch
End of Batch
Pump
Control
Analog
Prestop “Hold Output”
Control Disabled
Output Flowrate
Prestop Qty
Analog
“Hold Output”
Control
Prestop Enabled
Output
Flowrate
Hold Output Time
Prestop Qty
Automatic Restart
Count Down
Batch
Total
Count Up
Relay 1
Relay 2
Slow Start Time Prestop Qty
Analog
Prestop “Hold Output”
Control Disabled
Output Flowrate
Prestop Qty
Analog
“Hold Output”
Control
Prestop Enabled
Output
Flowrate
Hold Output Time
Prestop Qty
Introduction
The 500 Series instrument calibration settings can be programmed via the
front panel, according to program access levels explained below, or via the
500 Series Program Manager - a freely available Windows based
configuration and resource tool.
You can view or change the settings of the instrument according to the
access level for each parameter, as set by the 500 Series Program Manager.
There are different types of access to the parameters as follows:
Note: When you enter Calibration Set mode, the instrument prompts to
enter a password only if the password setup via the 500 Series
Program Manager is non-zero (000000 is the factory default value).
Entering any value at the password prompt will allow to change the
settings of the “programmable” parameters, but the correct password
must be entered to change the password-protected parameters.
Likewise, the CAL switch (Logic Input 4) must be used to enter
Calibration Set mode to change the CAL switch protected
parameters.
Run The instrument beeps once, illuminates the Cal indicator and shows CAL
Set on the display panel.
Alarm
Cal
3. Press to select any flashing menu heading except END.
4. Hold the SET key for two seconds, or if “Cal switch protected” items
exist the CAL switch can be closed for two seconds.
The instrument prompts for a password to be entered if the password is
non-zero, otherwise the password prompt is skipped.
5. If the password prompt is shown, press or to change the value
of the current digit. To select the next digit, press .
6. Press SET or use the CAL switch on Logic Input 4 (if “Cal switch
protected” items exist) to accept the password and proceed.
7. Proceed and observe the access confirmations.
• If the CAL switch is used and the password is correct, the instrument
makes two beeps and displays message:
-EDIT- CS_PW MODE
and enables you to change “programmable”, “password protected” and
“CAL switch protected” parameters.
• If the CAL switch is used but the password has been skipped or is
incorrect, the instrument makes one beep and displays message:
-EDIT- CAL_SW MODE
and enables you to change “programmable” and “CAL switch
protected” parameters.
• If the SET key is pressed and the password is correct the instrument
makes two beeps and displays the message:
-EDIT- PASSW MODE
and enables you to change the “programmable” and “password-
protected” parameters.
• If the SET key is pressed but the password has been skipped or is
incorrect, the instrument makes one beep and displays the message:
-EDIT- PROG MODE
and enables you to change only the “programmable” parameters.
Run The instrument illuminates both the Cal and Set indicators.
Set
Alarm
Cal
8. Edit the instrument parameters as required. The programmable values
are indicated by the flashing display.
• To change a numerical value, press to increase a value, or press
to decrease a value. Press a key momentarily to change the value
one number at a time. Hold a key to scroll through the numbers. To
proceed to next digit, press .
• To change an option setting, press or to scroll through the
options.
9. Press SET to accept the currently displayed value and proceed to the next
parameter. You can press DISPLAY to briefly view the current edit mode:
-EDIT- XXXXXX MODE, as described in step 6 above.
Continue to hold the DISPLAY key to return to the main calibration menu.
10.To exit from Calibrate Set mode, press to scroll through the main
calibration menu to END, then press SET . Otherwise, to quick exit from
any menu, you can press and hold SET for two seconds or, if “Cal switch
Run protected” items exist, the CAL switch can be closed for two seconds.
Set
Alarm The instrument makes two beeps and cancels the Cal and Set indicators.
Cal
In Calibration Set mode, the display flashes the item that can be changed.
For option settings, the display flashes the complete option. For a numeric
parameter, the display flashes one digit at a time, you can change the value
of the flashing digit as required, then move the flashing cursor to change
another digit.
Note: When you change the setting of a parameter, the instrument records
the result as soon as you move to another parameter, or exit from the
Calibration Set mode.
When you display an option that can be changed, the entire option flashes
on the display, such as the choices of ODD, EVEN or NONE for the
communications parity bit checking. Press or to change the
option. You can “scroll” through the options in either direction to make a
selection as shown below.
ODD EVEN NONE
6789.123
Press to select the digit that you wish to change.
To change the position of the decimal point, press to move the flashing
selection until the decimal point flashes. Press or to move the
decimal point to the right or left as required.
Units of Measurement
The calibration of some parameters is based on the units that are defined for
the relevant variables. These units of measurement can been viewed in the
UNITS menu in the Instrument Settings section below.
As well as programming the 500 Series instruments via the front panel
(according to program access levels), the 500 Series Program Manager
(500-PM) can be used to create a custom version of the application software
and program parameters preset prior to downloading the application
software. Backups of customised applications can be saved as download-
able APX or APL files and the full configuration reports printed or saved as
PDF. The 500-PM is a Windows based programming tool and resource
centre and is freely available from the Contrec www.contrec.co.uk website.
Instruments are often supplied from the factory with the default application
software, but it is by using 500-PM software that program access levels are
set, USER text and messages customised and print headers and footers
entered.
To assist in keeping an audit trail of the program settings and changes made
via the front panel, the 515 instrument provides the ability to print the
configuration to a local printer if one has been connected and assigned to
one of the 515 communication ports.
The prompt to hold the Reset key to print the configuration report
HOLD.RST CONFIG PRINT
is found at the end of the Model Info menu, described in Model
Information on page 26. The report can be lengthy and adequate printer
paper must be available (Note: this feature is available starting from version
3.0.377).
Once uploaded to the 500-LT, the report can be viewed or printed. The
Upload Application is automatically saved as an APL file. The file can be
used then or reopened later to download to another 515 instrument (of the
same or higher class) to create a clone of the original instrument.
515 BF03 - 15 August 2021 41
Instrument Calibration
CTRL MODE
View/Edit LOCAL FINP1
units of LOOP P-FLOW OUT1 ALRM3
measurement TUNE
OR
SIGNAL PULSE FUNC selection
RETRANS
TUNE LOOP NPS TYPE
DBNCE OP-ERR
COIL
OP-CTRL POINT
Press P-BAND P-FLOW RANGE CUTOFF OP-RST
SET I-TIME P-BAND selection OP-END HYST
FILTER
P-FLOW SP I-TIME 4-20 mA PULSE DELAY
CORR
P-FLOW value D-BAND LINEAR NON-LIN PT-MIN WIDTH ALRM4
DEVIAT value R-TIME PT-MAX PULSE
KFACT NO-PTS selection
HOLD CTRL
OR FREQ01 FREQn TYPE
OUT2
HOLD SEC
LOCAL FACT01 FACTn POINT
FUNC
R-TIME RETRANS HYST
OP-ERR
OP-CTRL DELAY
OP-RST
BATCH MODE selection OP-END
PRESET
ON-OFF 4-20 mA PULSE
RELEASE
OR
PT-MIN WIDTH
PRESET ON-OFF
PT-MAX PULSE
PERMIS INPUT PERMIS INPUT
COUNT DIR
OR
AUTO RESET
P-FLOW value
PRESET BATCH
O-RUN COMP
S-BITS
RTU DATA
RTU ADDR
ASCII ADDR
FLASH PORT
Instrument Settings
Units of Measurement
The Units menu allows the units to be viewed and edited if necessary
without the reloading of new application software. Any change in units will
result in a full reset to initially downloaded settings. Therefore, any required
changes to units of measurement should be made before changing any other
settings.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
ITEM n unit The units for main menu or calibration items can be viewed by pressing
the SET key.
Press or to select YES, then press the SET key. The instrument
makes three beeps to confirm the reset command.
Parameters
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
CTRL MODE Select the required loop control mode.
• LOCAL - Manual control operating mode
• LOOP - PI loop control operating mode
• TUNE - PI loop control tuning mode
Note: The flow control items actually shown in the PARAMS menu are dependent on the
CONTROL MODE chosen above. Items that are not relevant for that mode will not appear.
Use the Calibration Menu Tree as a guide to the relevant items.
P-FLOW RANGE The process or loop flow range is the maximum flowrate that the system
will achieve on the process flow line. This value is used by the loop
control algorithm and is entered in the same units as the main menu
Process Flowrate variable. It can be determined by setting the process
control setpoint to 100% whilst in LOCAL mode and observing the
flowrate.
P-BAND % The proportional band of PI control algorithm.
Enter the value in percentage. For means of determining this value see
Tuning the Control Loop on page 28.
I-TIME SEC The loop integral time of PI control algorithm. This parameter must be set
to a non-zero value to enable the integral term in the control algorithm.
Enter the value in seconds. For means of determining this value see
Tuning the Control Loop on page 28.
D-BAND % The loop error deadband can be programmed to prevent the output
continuously changing and thereby reducing wear on valves and
actuators. Enter the value as a percentage.
While the main menu Deviation (error) is within the deadband, the
process control signal will remain steady (i.e. the error is treated as zero
in the algorithm).
R-TIME SEC The ramp time limits the rate of change of the loop output signal and
assists in bumpless loop operation when changing operation mode or loop
parameters. It represents the minimum time required for the output signal
to traverse between saturation points (i.e. from 0 to 100% or vice versa).
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
HOLD CTRL The hold control output feature leaves the output signal at its last value at
the end of a batch (flow should be stopped by the on-off valve).
This allows the control actuator to start a new batch without ramping up
from a fully closed position.
Note: The batch control items actually shown in the PARAMS menu are dependent on the
BATCH MODE chosen above. Items that are not relevant for that mode will not appear. Use
the Calibration Menu Tree as a guide to the relevant items.
PERMIS INPUT The permissive input feature ensures that a batch will not be allowed until
a permissive contact is closed. A prompt to connect permissive is
displayed. The requirement for the permissive can be enabled or disabled.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
P-STOP %FLOW The batch prestop flowrate is programmed as a percentage of the
loop/process flowrate setpoint and is used to slow the flow the flow
during the prestop stage of batching.
ACCEPT TOTAL The batch acceptable total is the minimum total for the system leakage to
be logged (a value of zero disables logging of leakages). It also allows
small totals due to “meter skips” and vibration to be discarded without
being considered as a valid delivery.
The automatic reset feature allows the previous batch total to be reset
automatically when a new batch is started with the RUN key.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
AUTO COMP The batch automatic overrun compensation allows the instrument to
automatically compensate for any consistent overrun at the end of the
batch. Overrun is typically due to the slowness of a valve to close or a
pump to stop on receiving a signal from the batch controller and results
in the delivered quantity being greater than the entered preset.
The following PARAMS menu item(s) are also accessible via Modbus communications. For
a complete Modbus parameter listing, refer to Instrument Configuration Parameters on
page 81.
P-CTRL SP Preset process control signal setpoint. This setpoint is only available for
LOCAL control mode.
If LOCAL control mode the live P-FLOW value is now shown to give immediate feedback
without leaving calibration set mode.
P-FLOW SP Preset Loop/Process flowrate setpoint. This setpoint is only available for
LOOP control and TUNE modes. The value of the setpoint must not be
greater than the process flow range (P-FLOW RANGE).
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
If LOOP control or TUNE mode the live P-FLOW and DEVIATION values are now shown
to give immediate feedback without leaving calibration set mode.
PRESET BATCH Enter the batch preset quantity. This setpoint is only available for
PRESET batch mode.
This value is only used for batch overrun compensation when auto
overrun compensation is disabled.
Inputs
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
Frequency Input 1
INPUT For this application, the Frequency Input Channel 1 is assigned to mass
P-FLOW FINP1 flowrate.
SIGNAL FINP1 Frequency input 1 signal type.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
CUTOFF FINP1 The Cut-off is the lowest frequency for which the instrument continues
to calculate a rate from the flowmeter.
The value for the cut-off is specified as the frequency of the flowmeter in
Hertz.
Be careful when setting low cut-off values because the display update
time for the flow rate becomes very long. For example if the cut-off is set
to 0.01 Hz, and the measured flow stops, the instrument continues to
display the flow rate for 100 seconds before it can determine that the flow
has actually stopped.
FILTER FINP1 Input fluctuations caused by pulsating flow tend to create distortion in the
input readings of the rate. The instrument has a digital filter that averages
out these fluctuations.
As a guide to the degree of filtering to use, the following table shows the
response time (in seconds) to reach 90% and 99% of a step change in
input.
The value A is the filter constant that the user can set.
Filter setting A Seconds to reach 90% Seconds to reach 99%
of full swing of full swing
0 0 0
2 2 4
4 4 8
6 5 10
10 8 15
15 12 23
20 14 27
25 18 34
35 25 48
45 32 62
60 42 82
75 52 102
90 62 122
99 68 134
The input filter range is from 0 to 99. A setting of 0 (zero) means that
there is no filtering.
CORR FINP1 If the input sensor has non-linear characteristics, select NON-LINEAR
to apply correction factors to the input signal.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
KFACT1 unit This parameter is available for viewing and editing only when the
correction type is set to Linear.
The K-factor of the flowmeter is the number of pulses from the flowmeter
per unit of volume (or mass). The K-factor cannot be 0 (zero).
NO-PTS FINP1 This parameter is available for viewing and editing only when the
correction type is set to Non-linear.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
FREQ01 FINP1 This parameter is available for viewing and editing only when the
to correction type is set to Non-linear.
FREQn
Enter the frequency for this correction point.
FACT02
FACT03
FACT01 FACT05
FACT04
Frequency
FREQ01 FREQ02 FREQ03 FREQ04 FREQ05
Outputs
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
Note: In the factory default version of this application output channel 1 (OUT1) is dedicated
as the 4-20mA Process Control signal. Output channel 2 can be freely configured.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
FUNC OUTn The isolated output can function as either a passive 4-20 mA output, or a
pulse/logic open collector output:
• RETRANS - Retransmit totals as a pulse output or rates type
variables as a 4-20mA signal.
• OP-ERR - An error signal that will become active for the no flow,
overflow or leakage error conditions.
• OP-CTRL - A control signal that is active during a batch, can be
used as a pump control or indicator.
• OP-RST - A control signal that produces a 300ms pulse that can
be used to reset remote counters etc. Activates when the controller’s
total(s) are reset.
• OP-END - A control signal that reflects the End of Batch
condition (Note: not applicable if Batch mode is ON-OFF).
CAUTION
Due to the dual-purpose nature of the outputs, take care not to
set the output as an open collector pulse type signal when
connected to a 4-20 mA loop circuit.
WIDTH OUTn The Output Pulse Width is available for viewing and editing only when
the assigned variable is a total (pulse output) type.
Pulse output is usually used to drive remote counters. Set the pulse width
(in milliseconds) as required by the remote counter.
Press or to set to: 10, 20, 50, 100, 200 or 500 ms.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
PULSE OUTn The Output Pulse Factor is available for viewing and editing only when
the assigned variable is a total (pulse output) type.
The Output Pulse Factor is the scaling factor for the retransmission of the
measured total quantity.
The output minimum value corresponds to the 4 mA point and the output
maximum value corresponds to the 20 mA point.
Setting the output range differently from the input range enables the
instrument to amplify the input signal. You can drive a chart recorder that
“zooms in” on a specified range of values instead of displaying the full
operating range of the transducer.
Increasing the output pulse width reduces the maximum frequency at which
a total variable can be retransmitted. Pulses will be missed if the output
cannot “keep up” with the rate of total counts. You can use the output pulse
factor to ensure that this maximum is not reached.
For example: To calculate the required pulse factor to avoid losing counts
in retransmission if a total counts at a maximum rate of 75 units/sec (Hz) and
the required pulse width of a remote counter is at least 50 ms:
1000
The maximum pulse output frequency is: --------------- = 10Hz
2 50
75
The minimum pulse factor for that frequency is: ------ = 7.5
10
Alarms
The alarm relay(s), in the advanced option, can be assigned to rate variables
such as flowrate, or set as an equipment failure alarm.
The alarm switches “on” whenever an alarm condition exists. The alarm
switches “off” when the alarm condition no longer exists. However, you
may need to configure external alarm devices that require acknowledgement
for cancelling an alarm.
Any alarm relay can be assigned as an equipment failure alarm. This alarm
setting can have normally closed (open) contacts that open (close) when the
instrument displays any error message as listed in Error Messages on page
64.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
RELAY ALRMn Select a rate variable to assign to the alarm relay.
Note: If the alarm type is set to “equipment alarm”, this relay assignment
setting is ignored.
SET UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
TYPE ALRMn The options available for alarm types are as follows:
• HI-NO — High Alarm, Normally Open contacts
• HI-NC — High Alarm, Normally Closed contacts
• LO-NO — Low Alarm, Normally Open contacts
• LO-NC — Low Alarm, Normally Closed contacts
• BD-NO — Band Alarm, Normally Open contacts
• BD-NC — Band Alarm, Normally Closed contacts
• AL-NO — Equipment Alarm, Normally Open contacts
• AL-NC — Equipment Alarm, Normally Closed contacts
Each alarm is completely independent, e.g. a High alarm does NOT need
to have a higher setpoint than the a Low alarm.
HYST ALRMn The Alarm Hysteresis is available for viewing and editing for any alarm
type except ‘equipment alarms’.
Alarm hysteresis loops occur when the alarm toggles continuously on and
off when the process variable is close to the setpoint.
For a high alarm, the alarm activates when the value of the variable rises
above the alarm setpoint and deactivates when the value falls below the
alarm setpoint minus the amount of the hysteresis setting (if any).
For a low alarm, the alarm activates when the value of the variable falls
below the alarm setpoint and deactivates when the value rises above the
alarm setpoint plus the amount of the hysteresis setting (if any).
For a band alarm, the alarm activates whenever the value of the variable
is outside the setpoint plus or minus the amount of the hysteresis.
For example, with a high alarm setpoint of 200, and a hysteresis setting
of zero, a value oscillating between 197 and 202 will cause the alarm to
toggle on at 200 and toggle off below 200. However, if the hysteresis is
set to 5, the value of the variable must fall below 195 to cancel the alarm.
The alarm will reactivate only when the value again rises above 200.
DELAY ALRMn The Alarm Delay is programmed in seconds and can be used to eliminate
undesired alarm activation during start-up or shutdown operation.
Communications
The baud rate of the instrument must match the baud rate of the
communication device that the instrument is connected to.
The parity bit setting of the instrument must match the parity bit setting
of the communication device that the instrument is connected to.
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
RTU DATA The Modbus RTU data format for the 2-register (4-byte) values can be
set as either floating point or long integer values.
Note: The master device uses the RTU address 0 (zero) for broadcasting
to all connected slave units.
ASCII ADDR The ASCII protocol address identifies each communicating device.
The default setting of this assignment is the RS-232 port. The Ethernet
port, if fitted, can not be used as the Flash port.
Instrument Clock
The instrument has a real-time clock for recording logged events. The clock
displays the time and the date. The date format can be set to European
format (day/month/year) or American format (month/day/year). The time
clock uses the 24-hour format.
Note: If there is an interruption to the power supply and the battery has
failed, the instrument displays an error message when the power
supply is restored. In this case, you should set the current time and
date so that the instrument continues to log data at the correct times.
Data Logging
The instrument will log a total of 1000 deliveries (batches) if the real-time
clock option is installed. The logs are taken at the end of each batch or upon
reset if a batch has been aborted before the preset total has been reached.
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
DATE FORM Clock Date Format
CLOCK M-DAY The Clock M-DAY setting defines the current month and date for the
real-time clock. This parameter is programmed in Month-Day format for
both European and American date formats.
CLOCK H-MIN The Clock H-MIN setting is the current time in hours and minutes for the
real-time clock.
RESET LOGS Reset the logged data. You may need to reset (clear) the logged data if
you change the time/log settings.
Press or to select YES, then press the SET key. The instrument
makes three beeps to confirm the reset command.
REPORT LOGS The Printer Protocol Report Logs defines the number of latest logs to be
included into a printable report.
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
PRN TYPE The Printer Protocol Printer Type allows the nature of the printer being
used to be specified. The following printer types available in this
instrument are:
• PRN-01 Generic computer printer
• PRN-02 Generic roll printer (prints first line first)
• PRN-03 Slip printer TM295
• PRN-04 Label (roll) printer - Citizen CMP30L
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
T-OUT MODE If the Display Timeout mode is enabled, and there is no user activity for
the defined timeout period, the display panel returns to the default
display.
Press or to select YES, then press the SET key. The instrument
makes three beeps to confirm the reset command.
DISPL TAGS The Display Tags option determines whether the instrument displays the
default display tags or the user-defined tags. The display tag setting also
defines whether the instrument displays the default error and warning
messages, or the user-defined messages.
Note: The user-defined tags can be entered into the instrument only by
the manufacturer or the distributor.
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
BACK-L T-OUT If the backlight timeout is enabled, and there is no user activity (any keys
pressed) for a period of 10 seconds, the display backlight switches off to
save power. The backlight switches on when a key is pressed. Select the
backlight timeout mode as required.
Test Menu
The Test menu enables you to view the inputs and outputs to and from the
instrument.
In Calibration Set mode (by entering the system password), you can control
the outputs and the alarms as described in the table below.
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
FINPn Hz The frequency of the input to FINPn is displayed in Hertz.
AINPn units The units are displayed according to the calibration setup for the analog
input. If unused or set to Default the input is 4-20mA and displayed in
mA.
LINPn STATE You can view the state of the logic inputs. If the input is an open contact
or inactive it will display HI. If the input is a closed contact or active it
will display LO.
SET UNITS PARAMS INPUTS OUPUTS ALARMS COMMS TM/LOG SETUP TEST END
OUTn STATE You can control the state of the outputs. Press the or keys to set
the output state as follows:
• PROCESS - the output depends on the current values of the inputs
and the calculations that the instrument performs.
For a pulse output, such as a total, the output produces a pulse train as
follows:
• ON - a pulse train with a pulse width as set for the particular output
in the Outputs menu.
• OFF - no output.
For a 4-20 mA output, such as a rate, the output is as follows:
• HI - the output is set to 20 mA.
• LO - the output is set to 4 mA.
ALRMn STATE You can control the state of the relays (alarms). Press the or
or keys to set the selected relay as follows:
REL-n
• PROCESS - the relay operates according to the current values of the
inputs and the relay settings as programmed.
• OPEN - the relay output contacts are set to “open”.
• CLOSED - the relay output contacts are set to “closed”.
SUPPLY V You can display the actual DC output supply voltage, which may help
with troubleshooting.
If the actual supply voltage is lower than the preset value (refer to
General Setup Parameters on page 60) it may indicate that the output is
overloaded.
System Messages
The instrument displays messages for defined events and fault conditions.
Error Messages
The system displays error messages, and records the associated exception
status code, in the order of highest to lowest priority as listed in the
following table:
Warning Messages
Prompt Messages
Overview
This chapter describes the communications between the instrument and
another communicating device such as a computer or a printer. You should
have relevant information about the devices to which the instrument will be
connected. Some connection examples are included in this manual,
however, the operation and connection of other devices is outside the scope
of this manual.
Hardware Interconnection
The instrument has two communication ports:
• COM-1 RS-232 port on the rear panel (DB9 female connector)
• COM-2 RS-485 port on the rear panel (optional) or Ethernet (optional)
The appropriate interface and protocols are selected during calibration.
Instrument Computer/Printer
TxD 2 2 RxD 3
RxD 3 3 TxD 2
Common
GND 5 5 GND 7
Optional
CTS 7 7 RTS 4
Optional
RTS 8 8 CTS 5
Gnd Gnd
+ - + -
19 20 21 19 20 21
Instrument Instrument
For further advice and example of Ethernet port usage and setup, refer to
Ethernet Port & Setup on page 92 in the Appendix.
Protocols
The communications protocols can be assigned to the communication ports
on the instrument as follows:
• ASCII - Simple ASCII
• RTU - Modbus RTU
• PRN - Printer Protocol
• NONE - If a port is not being used, set the protocol to NONE.
Note: The Printer Protocol is only available if the option with Real Time
Clock is installed. Also a protocol cannot be assigned to more than
one port at a time as described in Communications on page 57.
This simple ASCII protocol requires that all requests are initiated with a
colon ( : ) and terminated with a carriage return (CR). The message
termination can include a linefeed before the carriage-return ( LFCR), but it
is the carriage-return that acts as the message termination.
Requests Format
The format of a request to the instrument is as follows:
:A001:LR001:XXX? LFCR
Each request must include the address and command portions. The
underlined section is an optional part of the request string.
Address
Note: The instrument always responds with its address in the header
regardless of the type of request.
The log type and number enables a communicating device to retrieve data
from the instrument. The data can be from the event-based logs or from the
current process variables with the either accumulated or non-accumulated
(resettable) totals.
The log request is optional. If the log request is not included, or the log
number is set to 000, the instrument returns the current process variables. If
the log request is included, the log number defines the specific log entry by
counting backwards. The most recent log entry for a timebase is 001.
The “last edit” log records the process variables at the time of the last exit
from the calibration edit mode. There is only one “last edit” log, therefore,
if a number is included in the request, the instrument ignores the number and
returns the data at the time of the last edit. Likewise, there is only one set of
current process variables with “non-accumulated totals”, therefore it also
ignores any log number included in that request.
Log Type
LE - last edit log
LR - logged records (non-timebased logging)
LN - current totals displayed as Non-accumulated
The number of the log entry is the same as shown on the front panel of the
instrument. For example, a request for LR003 would return the data for the
log entry two batches prior to the most recent batch log entry.
Instrument Responses
The instrument response time to any enquiry is not more than 300 ms. The
responses from the instrument are in the following format:
HEADER LFCR
DATA LFCR
DATA LFCR
.
.
.
DATA LFCR
L C
F R
Header
The instrument Exception Status codes that the instrument returns for the
ASCII protocol are the same as those described for the Modbus RTU
protocol in Instrument Exception Status on page 79.
Data
8 9 1 2 3 . 4 5 6 M 3 V O L U M E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 24 25 26 27
space
space
Value (aligned right) Unit (aligned left) Item (aligned left)
Variables Request
The variables request asks the instrument to return the value of one or more
requested variables. All totals are transmitted as accumulated totals.
Command Description
:RVA? Return all variables
:RVD? Return the default Total and Rate
:RV0? … Return the specific variable. The numbers relate to the
:RV9? position in the variables menu. For example, V0 is Energy,
V1 is Power and so on.
The following request is for the only instrument that is connected to the
communication port to return the values of all main menu variables.
: A 0 0 1 : R V A ? LF C
R
L C
6 . 1 1 6 M W h E N E R G Y F R
L C
1 6 . 5 7 3 M W P O W E R F R
L C
1 3 2 0 . 5 3 0 m 3 V O L U M E F R
L C
5 8 . 3 0 0 m 3 / M V - F L O W F R
L C
7 6 2 7 . 1 1 7 K G M A S S F R
L C
3 4 4 . 4 6 0 K G / M M - F L O W F R
L C
2 3 0 . 0 0 0 D E G C T E M P F R
L C
1 . 2 6 0 M P A P R E S S F R
L C
0 . 1 7 4 m 3 / K G S P - V O L F R
L C
2 8 8 6 . 7 6 0 K J / K G S P - E N T F R
L C
F R
The following message to an instrument, requests the current values for the
default rate and total:
L C
: A 0 0 1 : R V D ? F R
L C
1 2 6 . 4 5 5 m 3 V O L U M E F R
L C
2 0 . 4 3 7 m 3 / M V - F L O W F R
L C
F R
Log Request
The log request asks the instrument how many logs will be included in a
printed log report. These are the values described in Time Settings and
Data Logging on page 58.
Command Description
:RLR? Return the number of log records (non- timebased logging)
The following message asks the instrument with address 001 to return the
number of logs that the instrument stores:
L C
: A 0 0 1 : R L R ? F R
L C
2 4 F R
L C
F R
The clear data request asks the instrument to clear the data in the selected
registers.
Command Description
:RCN? Clear the non-accumulated (resettable) totals
:RCA? Clear the accumulated totals
:RCL? Clear the logs except for the “last edited” log
The following message asks the instrument with address 001 to clear the
logged data that the instrument stores:
L C
: A 0 0 1 : R C L ? F R
L C
F R
The Instrument Information request asks the instrument to return the general
information about the model and version codes. The instrument exception
status is returned as a part of the header as it is with the header for all
command responses.
Command Description
:RIG? Return the general information about the instrument such as
Model number, Application number, Version and Serial
numbers etc. These items are returned as a block in the same
format as shown on the display in the “Model Info” menu.
The following message asks the instrument with address 001 to return the
general information about the instrument:
L C
: A 0 0 1 : R I G ? F R
L C
5 1 5 M O D E L - 1 1 - F - F R
L C
S C 0 1 I N P U T F - T P - - F R
L C
S C 0 1 V E R S 0 1 0 1 . 0 0 1 F R
L C
C U S T O M V E R S 0 0 0 0 0 1 F R
L C
U N I T S / N 1 2 3 4 5 6 F R
L C
F R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
If the instrument receives a request message in the correct format, but for a
non-existent option, it returns only the message header. For example, if the
instrument received the following request variables message :A001:RVT?
it will return only the header because there is no T option for the ‘Variables
Request’ message.
Message Format
In RTU mode, messages start with a silent interval of at least 3.5 character
times. The first field transmitted is the device address. Following the last
transmitted character, a similar interval of at least 3.5 character times marks
the end of the message. A new message can begin after this interval. The
entire message frame must be transmitted as a continuous stream. A typical
message frame is shown below:
Instrument Address
Function Codes
Exception Response
The data registers represent different data types as specified in the tables:
• I - Integer, 2 bytes (Holding Register)
• L - Long Integer, 4 bytes (2 registers)
• P - Programmable Format, 4 bytes (2 registers)
The “Programmable Format” data type for 4-byte (2 registers) data values
can be set as either Floating Point or Long Integer via the “Data Type”
program item as described in Communications on page 57.
This means that two data registers must be read or written to obtain, or
preset, one data value.
Use the log timebase and log number to retrieve the logged information
from the appropriate register. If a particular log number does not exist, or
the instrument does not have the optional real-time clock, the time and date
stamp and associated variables are set to zero.
0 = Reset
1 = Maintenance
2 = Completed
3 = Waiting to restart
4 = Paused
5 = Waiting for timeout
6 = Running (Slow Start)
7 = Running (Prestop)
8 = Running (Full Flow)
B0 = relay 1 (LSB)
B1 = relay 2
B2 = relay 3
B3 = relay 4
46 Relay Control 0 to 15 Binary representation of relay control. R/W I
0 = open; 1 = close.
B0 = relay 1 (LSB)
B1 = relay 2
B2 = relay 3
B3 = relay 4
47 Relay Control 0 to 15 Binary representation of relay control source. R/W I
Source 0 = Local (controlled by instrument operation) 1 = RTU
(controlled by Modbus register 46).
B0 = relay 1 (LSB)
B1 = relay 2
B2 = relay 3
B3 = relay 4
48 Delivery Provides the delivery number (batch record) for a stored R L
Number transaction (determined by Modbus register 38).
50 Control Mode 0 = Idle/Local Control from logic inputs R/W I
1 = Stop Suspend current batch
2 = Run Resume/start batch
3 = Reset Clear current batch totals
Printer Protocol
A printer protocol is available in the 500 Series. It provides the ability to
print out live data, individual logged data and to do some report-style
printing of logged data. The method of printing these and the format of the
printouts are described below. If chosen, a printer protocol also enables
application/configuration uploading and printing a configuration report, as
shown in Printing Configuration Report on page 41.
Note: Printer output is only available if the Real Time Clock option is fitted.
Report Types
The number of logs printed in each report are determined by the values
programmed for Report Logs in the TM-LOG menu.
Printer Types
Customizing a Printout
Types of Printouts
Live Data
(Note that blank header and footer lines are not printed).
The instrument serial number and unit tag is the same as the information
shown in the Model Info menu. For more details refer to Model
Information on page 26
Delivery Number
The delivery number that appears on the live data printout shows the
assigned delivery number that is stored with the logged data. This number
is cleared when the Logs are cleared in the TM/LOG menu. If a second print
or docket of the same delivery is generated, the words “(DUPLICATE
DOCKET)” are included at the top of the printout. i.e.
(DUPLICATE DOCKET)
####
When in the Log Menu and while holding the DISPLAY key to view the
data of the log of interest, the RESET key can be pressed to initiate a
printout of that log entry. The printout will have the time and date stamp
corresponding to when the log was taken. After the print has been initiated
there will be the opportunity to scroll to view another log entry and print
again.
Since each log entry stores the delivery totals only, the printout will not have
any accumulated totals. The format of the printout with this exception is the
same as the LIVE DATA printout:
There is a HOLD.SET REPORT PRINT prompt under the main menu with
the ability to print the pre-selected type of report. Pressing and holding the
SET key for two seconds will initiate the printout. Any of the Log Reports
will have the following format:
Delivery No.
Date & Time & Status
Variable unit value
Variable unit value
etc.
-------------------------------------------- <separation line>
Delivery No.
Date & Time & Status
Variable unit value
Variable unit value
etc.
-------------------------------------------- <separation line>
Delivery No.
Date & Time & Status
Variable unit value
Variable unit value
etc.
Reports such as “Latest Logs” will print in the historical order, and for those
logs that have no data (e.g. unit was powered off at the time) the print will
show “Data not available”, i.e.
-------------------------------------------- <separation line>
Del No. Data Not Available
-------------------------------------------- <separation line>
Delivery No.
Date & Time & Status
Variable unit value
Variable unit value
etc.
If the unit is programmed for 0 logs for the latest log reports then the report
will only consist of the header and ID information and a “Data Not
Available” message.
Title of Report
Error Messages
PAPER OUT
This message is related to the Printer Type PRN-03 TM295 Slip printer. It
is standard procedure with this printer to check for paper status before
printing. If a print is attempted but there is no paper the PAPER OUT
message will be scrolled. The instrument will continue to poll the printer for
paper and if paper is detected before a communications timeout expires the
print will commence.
COMMS TIMEOUT
This message is relevant for all printer types and will be activated for the
following conditions.
2. If Printer Type is PRN-03 Slip printer and a paper status is requested but
no response is received within the timeout period.
3. Paper Out has been detected for Printer Type PRN-03 but no paper is
inserted within the timeout period.
500-PM The 500 Series Program Manager (500-PM software) is a Windows based
Software program that is freely available from the download section of the Contrec
website. The program is a comprehensive configuration tool and resource
centre that can be used to tailor an instrument to suit specific application
needs including program settings, units of measurement, custom tags/text,
access levels and more. Custom versions can be saved and configuration
reports generated as a PDF.
ASCII American Standard Code for Information Interchange. For the ASCII
protocol, the instrument receives and transmits messages in ASCII, with all
command strings to the instrument terminated by a carriage return. Replies
from the instrument are terminated with a line-feed and a carriage-return.
K-factor The K-factor is a constant value associated with frequency type flowmeters.
It is a scaling factor used in calculations to determine flow rate.
Linear A scaling of the input signal to represent the actual flow parameter.
Correction
Modbus RTU The Modbus protocol is a message structure for communications between
controllers and devices regardless of the type of network. In RTU (remote
terminal unit) mode, each 8-bit byte in a message contains two 4-bit
hexadecimal characters. This mode has greater character density than
ASCII and allows better data throughput than ASCII for the same baud rate.
Normalised A normalised input ranges from 0 to 1.000. For 4-20 mA input, the signal is
Input set to 0 at 4 mA and the signal is set to 1.000 at 20 mA.
Watchdog The WDT is used to monitor the activity of the micro processor and will
Timer (WTD) force a reboot if the micro processor stops, while power is applied, due to
any internal or external influences.
Product Codes
Model Supplementary Code Description
515 . - BF03
1 Panel mount enclosure
2 Field mount enclosure (NEMA 4X / IP66)
Note: Example full product part number is 515.111USC-BF03 (this is the number used for
placing orders).
06
etc.
0 English (Default)
1 German
2 Dutch
User Language 3 French
4 Spanish
5
etc.
000
Distributor’s own choice. Possibly a code that identifies the
Distributor’s Code … customer and the application.
999
F-tP--
BT01 INPUT
Application number
The Application Information code is returned as part of a General Instrument request (as
described in Instrument Information Request on page 73).
For example, F-tP-- is an instrument with FINP1 (frequency input 1) assigned to a flow
input, AINP1 assigned to a temperature input and AINP2 assigned as a pressure input. The other
inputs are not used.
Ethernet Port
The optional Ethernet port simplifies the communication network and avoids the need for an
external 3rd party Serial to Ethernet converter. It allows communications via an existing
Ethernet network. In some installations you will need to speak with your network (IT)
administrator in order to correctly set up your network. Applications, such as DataMod
(available via Contrec), can communicate over the Ethernet network to perform remote
monitoring and Data Logging operations.
Within the instrument’s calibration menus the Ethernet port uses the settings for the RS-485 port
that need to match a supplied Ethernet unit as follows:
• Protocol: RTU
• Baud Rate: 19200
• Data Bits: 8
• Parity: Even
• Stop Bits: 1
Contrec Limited will not be held responsible for any changes made to customer router and
network settings. Further guides on how to access the module settings and discovering IP
address’ can be supplied upon request.
Ensure all other settings are correct as per the Datamod User Guide and the 515 Ethernet
Guide - Establishing a Connection to Datamod. Both of these documents are available from
Contrec on request.
S W
safety & security 32 warnings 64
serial number 26 watchdog timer (WDT) 27
SET key 24 wiring
setpoint, alarm 56 insulation 12
settings mains power 12
instrument 44 relays 12
setup menu 60
shielding 19
snubber 17
software configuration tool 4
specifications 7
standards 4
starting a batch 32
status LEDs 22
stop bits 57
STOP key 22
stopping a batch 33
suppression, interference 17