Product datasheet RMCL55BD

Characteristics Isoled Analog Converter - 0..20 mA - for Zelio Analog

Main
Range of product Zelio Analog
Product or component type Voltage/current converter
Analogue input type Current 0...20 mA
Current 4...20 mA
Voltage +/- 10 V DC
Voltage 0...10 V DC
Analogue output type Current 0...20 mA <= 500 Ohm switchable
Current 4...20 mA <= 500 Ohm switchable
Voltage +/- 10 V >= 100 kOhm switchable
Voltage 0...10 V >= 100 kOhm switchable

Complementary
Protection type Overvoltage protection on output (+/- 30 V)
Reverse polarity protection on output

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Short-circuit protection on output
Analogue output voltage 0 V, range: 0...10 V when no input wired or wire broken
-10 V, range: +/- 10 V when no input wired or wire broken
Analogue output current 0 A, range: 0...20 mA when no input wired or wire broken
0.004 A, range: 4...20 mA when no input wired or wire broken
[Us] rated supply voltage 24 V DC +/- 20 %, isolated
Current consumption <= 70 mA for voltage output
<= 90 mA for current output

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Local signalling LED green (power ON)

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Measurement error +/- 1 % of full scale at 20 °C
+/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)
Repeat accuracy +/- 0.2 % full scale at 20 °C
+/- 0.6 % full scale at 60 °C
Temperature coefficient 200 ppm/°C
Clamping connection capacity 1 x 2.5 mm²
2 x 1.5 mm²
Tightening torque 0.6...1.1 N.m
Marking CE
Surge withstand 0.5 kV for 1.2/50 µs conforming to IEC 61000-4-5
[Ui] rated insulation voltage 2 kV
Fixing mode By screws, mounting plate
Clip-on, 35 mm symmetrical DIN rail
Product weight 0.12 kg

Environment
Standards IEC 60584-1
IEC 60947-1
Product certifications CSA
GL
UL
IP degree of protection IP20 terminal block
IP50 housing
Fire resistance 850 °C conforming to IEC 60695-2-1
850 °C conforming to UL
Shock resistance 50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance 5 gn (f = 10...100 Hz) conforming to IEC 60068-2-6
Resistance to electrostatic discharge 6 kV (in contact) conforming to IEC 61000-4-2 level 3
8 kV (in air) conforming to IEC 61000-4-2 level 3
Resistance to fast transients 1 kV on input-output conforming to IEC 61000-4-4
2 kV on power supply conforming to IEC 61000-4-4

1/3
Disturbance radiated/conducted CISPR 11
CISPR 22 group 1 - class B
Ambient air temperature for storage -40...85 °C
Ambient air temperature for operation 0...50 °C (mounting side by side)
0...60 °C (2 cm spacing)
Pollution degree 2 conforming to IEC 60664-1

Contractual warranty
Period 18 months

Analog Interface (Converter)

Dimensions

(1) Terminal block AB1TP435U or AB1RRNTP435U2

Mounting

Mounting on Rails AM1•••••

Panel Mounting

Analog Interface: Voltage/Current Converter

Wiring Diagram

(1) Use 1 input only.

2/3
The input, output and power supply lines must be kept away from the power cables to avoid effects due to induced interference.
The input and output cables must be shielded as indicated in the schemes and must be kept away from each other.

3/3

You might also like