PACKAGED ELECTRIC/electric: Raider Rooftop Units
PACKAGED ELECTRIC/electric: Raider Rooftop Units
PACKAGED ELECTRIC/electric: Raider Rooftop Units
ZCA
Raider Rooftop Units
®
60 HZ
Bulletin No. 210748
P R O D U C T S P E C I F I C AT I O N S November 2017
Supersedes June 2017
ASHRAE 90.1
COMPLIANT
3 to 6 Tons
Net Cooling Capacity − 34,600 to 68,000 Btuh
Optional Electric Heat - 5 to 30 kW
MODEL NUMBER IDENTIFICATION
Z C A 060 S 4 B N 1 Y
Brand/Family Voltage
Z = Raider® Product Line Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Unit Type
C = Packaged Electric Cooling w/ optional Electric Heat
I
D G
B
C
H
Raider® rooftop units from Lennox are the new standard for cost efficient, reliable rooftop
units built for long-lasting performance that can significantly improve indoor environments.
Raider rooftop units feature:
• Quick and Easy Retrofit - Fast installation for replacement of many existing rooftop
units - fits high volume competitor’s roof curbs
• R-410A Refrigerant - Environmentally friendly
• Single Speed Scroll Compressor - Furnished on all models
• Lennox’ Environ™ Coil System - Smaller, lighter condenser coil
• High Pressure Switch - Protects compressor
• Belt Drive Blower Motor - Maximizes air performance
• Downflow or Horizontal Airflow - Easy field conversion
• Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost
any angle
• Corrosion-Resistant Drain Pan - Provides application flexibility, durability, improved
serviceability and meets ASHRAE 62.1 requirements for drain pan slope
CONTENTS Filter/Drier
Blower Data - Belt Drive . . . . . . . . . . . . . . . . . . . . . . . . . . 13 High capacity filter/drier protects
the system from dirt and moisture.
Dimensions - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dimensions - Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 C Lennox Environ™ Coil System
Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . 20 Condenser
coil features
Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . 24
lightweight,
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 all aluminum
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . .1 brazed fin
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 construction.
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Constructed
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 of three
components:
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
a flat extrusion tube, fins in-
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 between the flat extrusion tube and
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 two refrigerant manifolds.
Environ™ Coil System Features:
• I mproved heat transfer
APPROVALS R-410A Refrigerant performance due to high
AHRI Certified to AHRI Standard Non-chlorine, primary surface area (flat
210/240-2008 (3 - 5 ton models) ozone friendly, tubes) versus secondary
and AHRI Standard 340/360-2007 R-410A. surface (fins).
(6 ton models). Unit is factory pre-charged with • S maller internal volume
CSA listed. refrigerant. See Specifications (reduced refrigerant charge).
Table. • High durability (all aluminum
Units are Certified by CSA.
Components bonded for grounding B Single Speed Scroll Compressor construction).
to meet safety standards for Resiliently mounted on rubber • Fewer brazed joints.
servicing required by UL, ULC and grommets for quiet operation. • Compact design (reduces unit
National and Canadian Electrical Scroll compressors for high weight).
Codes. performance, reliability and quiet
• Easy maintenance/cleaning.
All models are ASHRAE 90.1 operation.
Mounting brackets with rubber
compliant. Compressor Crankcase Heater inserts secure coil to unit providing
ISO 9001 Registered Protects against refrigerant vibration dampening and corrosion
Manufacturing Quality System. migration that can occur during low protection
WARRANTY ambient operation.
Evaporator Coil
Limited five years on compressors. Refrigerant Metering Orifice Copper tube construction,
Limited three years on the Accurately meters refrigerant in enhanced rippled-edge aluminum
Lennox’ Environ™ Coil System. system. fins, flared shoulder tubing
Refrigerant control is accomplished connections, silver soldered
Limited five years optional High construction for improved heat
by exact sizing of refrigerant
Performance Economizers. transfer. Factory leak tested. Cross
metering orifice.
Limited one year all other covered row circuiting with rifled tubing
components. High Pressure Switch optimizes both sensible and latent
Protects the compressor from cooling capacity.
COOLING SYSTEM
overload conditions such as
Designed to maximize sensible dirty condenser coils, blocked Condensate Drain Pan
and latent cooling performance at refrigerant flow, or loss of outdoor Plastic pan, sloped to meet
design conditions. fan operation. drainage requirements of ASHRAE
System can operate from 35°F 62.1.
Automatic reset.
to 125°F without any additional End drain connection.
controls.
Access Panels
Access panels are provided for
the compressor, heating, controls,
blower and air filter/economizer
section.
CABINET
Z1GARD52AT1 12X20 X
ELECTRICAL
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
Unit Fuse Block (required) - See Electrical/Electric Heat Tables for Selection X X X X
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
pressure.
3
Sound Rating Number (SRN) rated in accordance with test conditions included in ANSI/AHRI Standard 270-2008.
3
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors
furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp output. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
4
1.5 hp motor is required with the ZA05 and ZA06 drive kits.
5
2 hp blower motor is required with the ZAA04 drive kit.
ZCA036 66 70 73 72 70 67 60 78
ZCA048 68 71 75 74 71 68 63 80
ZCA060 73 74 78 77 73 69 63 83
ZCA072 73 76 80 78 73 68 66 84
1
Sound Rating Number according to ANSI/AHRI Standard 270-2008. “SRN” is the overall A-Weighted Sound Power Level, (LWA), dB (100 Hz to 10,000 Hz).
OUTDOOR AIR
HOOD
C
D B
HORIZONTAL
OUTDOOR AIR
C HOOD
D B
C C
A B D Top
1
Unit Clearance Downflow Horizontal
Clearance
in. mm in. mm in. mm in. mm in. mm
Service Clearance 36 914 36 914 36 914 60 1524 36 914
Unobstructed
Minimum Operation Clearance 36 914 36 914 36 914 60 1524 36 914
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
Service Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.
Optional Accessories
Outdoor temperature sensor C0SNSR04AE1- X2658
Optional wall mounting plate C0MISC17AE1- X2659
OPTIONS / ACCESSORIES
Shipping Weights
lbs. kg
ECONOMIZER
Economizer, Includes Outdoor Air Hood and Downflow 75 34
Barometric Relief Dampers with Hood
Horizontal 102 46
OUTDOOR AIR
Outdoor Air Dampers
Motorized 39 18
Manual 29 13
POWER EXHAUST
Standard Static Downflow 54 24
Horizontal 41 19
ELECTRIC HEAT
5 kW 25 11
7.5 kW 26 12
10 kW 27 12
15 kW 27 12
22.5 kW 29 13
30 kW 30 14
ROOF CURBS
Hybrid Roof Curbs, Downflow
8 in. height Z1CURB70A-1 63 29
14 in. height Z1CURB71A-1 83 38
18 in. height Z1CURB72A-1 93 42
24 in. height Z1CURB73A-1 113 51
CEILING DIFFUSERS
Step-Down RTD9-65S 80 36
RTD11-95S 118 54
Flush FD9-65S 80 36
FD11-95S 118 54
25-5/8 5-1/8
(651) (130)
AA BB
29
BOTTOM (737)
A SUPPLY 17-3/4
B FF AIR (451)
16-1/8 C
(410) 13-5/8 OPENING
11-1/8
(346) (283) 5-3/4
(146)
DD BOTTOM CC
24-9/16 POWER 12-1/8 5-1/8
(624) ENTRY (308) (130)
(See Table)
EE
75-7/8
(1927)
TOP VIEW (Base)
HORIZONTAL
44-7/8 (1140) 072
CONDENSATE
RETURN
11-7/8
1 (302) OUTLET 25-3/4
(25) (654)
Either side 6-1/4
(159)
HORIZONTAL 8-3/8
SUPPLY (213)
5-3/4 5-3/4
3-1/2 (89) (146) (146)
18-1/4
18-1/4 (464) 31
(464) (787)
3/4
(19)
SIDE VIEW
10-5/8
(270)
OUTDOOR AIR
DAMPER HOOD
(Furnished)
SIDE VIEW
MANUAL OUTDOOR AIR HOOD MOTORIZED OUTDOOR AIR HOOD
OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)
OUTDOOR AIR/
BAROMETRIC
RELIEF HOOD
(Furnished with
Economizer)
31 TOP VIEW
(787)
15
(381) 42-5/16
32-1/16 (1075)
(814)
14
71 (356)
(1803) RETURN 20-1/4
OPENING (514)
SUPPLY
8 (203)
OPENING 14 (356)
18 (457)
3-5/8 24 (610)
(92)
17-3/16
(437)
1/2 (13)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
NAILER STRIP PERIMETER WOOD
(Furnished) NAILER STRIP
CANT STRIP 8 (203)
ROOF CURB
(Field Supplied) 14 (356)
(Extends around entire
perimeter of unit) 18 (457)
ROOFING 24 (610)
MATERIAL
RIGID INSULATION
(Field Supplied)
1-3/4
(44)
G H D G H D
E E
F H F H
G C G C
2 (51) 2 (51)
L A A
B
B
J
K
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2017 Lennox Industries, Inc.