SEL-PSM Power Supply Module Instruction Manual: General Features
SEL-PSM Power Supply Module Instruction Manual: General Features
SEL-PSM Power Supply Module Instruction Manual: General Features
Instruction Manual
General Features
The SEL-PSM provides the following features:
➤ Converts station battery control power to electronic power levels.
➤ Powers up to four SEL-DTA Display/Transducer Adaptors located remotely from SEL protective
relays.
➤ Use wherever a reliable, industrial source of low-voltage dc is required.
➤ Triple outputs: +5 V, +12 V, –12 V or +5 V, +15 V, –15 V models available.
➤ Four output ports ease connection to multiple loads.
➤ Two wide input voltage ranges available: 30–60 Vdc; 85–280 Vdc/85–265 Vac.
➤ Alarm contact closes for loss of +5 V output.
➤ Power input and alarm connections are standard 10-32 screw terminals.
➤ Power fail detect signals at each output port indicate loss of dc to loads.
➤ Red LED indicates power-on condition.
➤ Designed for mounting inside switchboards; does not require panel space.
Installation Instructions
Refer to Figure 3 for dimensions, mounting hole locations, terminals, and
connectors. Refer to Figu for more details on the output port connections.
Step 1. Mount the SEL-PSM Power Supply Module to a flat surface.
Step 2. Connect Terminal 3 of the terminal block to frame ground.
Step 3. Connect Terminals 4 and 5 to the input power. Observe polarity
for the 48 V rated supplies. Polarity is unimportant for the
125 V rated supplies.
Step 4. If desired, connect Terminals 1 and 2 to an annunciator to
signal loss of power. The alarm contacts are closed when no
power is applied. Under normal operating conditions the alarm
contacts are held open.
Step 5. Connect loads to one or more of the output ports. See Figure 1
for the output connector pinouts.
4
5 3 1. Ground and Common
2. Power Fail Detect Output
9 3, 4, 5. No Connections
6 2 6. +5 V Output
7. +12/+15 V Output
7 1 8. –12/–15 V Output
8 9. Ground and Common
6.500"
8.000"
.750"
1.000" 7.500"
.375" 7.918"
9.500"
4.10" Max
3.04"
.46" Max
Instruction Manual
K101 SCHWEITZER ENGINEERING LABORATORIES
SEL-PSM BOARD COPYRIGHT 1988 MADE IN U.S.A. D104
MOV102
X4-0406
ALARM
R110
C104
D107
SEL Part
Identifier Description Manufacturer Part
No.
Specifications
Input Voltage Ranges
48 V: 30–60 Vdc
125 V: 85–280 Vdc
85–265 Vac
Outputs
+5 V: 3 A max current
+12/+15 V: 0.3 A max current
–12/–15 V: 0.3 A max current
Ripple: 20 mV peak-to-peak maximum
Switching noise: 2 MHz at 20 kHz repetition rate; 1% or
100 mV peak-to-peak maximum,
whichever is less
Short circuit protection limits current; automatic resets upon removal
of overload.
Output tolerance: +5/–5%
Power Fail Detect Output
One signal per output port
Normal level: +5 V through 3.3 kΩ
Power failure level: less than 1 V when sinking up to 50 mA
(maximum)
Isolation
Input power and alarm circuits are routine tested at 3000 Vdc. Power
and power-fail detect outputs are ground-referenced.
Temperature Ranges
Operating: –20° to + 55°C
Storage: –55° to +85°C
Standards
ANSI/IEEE C37.90-1978 “IEEE Standard Relay and Relay Systems
Associated with Electrical Power Apparatus” applies to power input
and alarm output.
Protection
Internal fuse is easily accessible by removing cover.
MOV and surge capacitors protect power input.
MOV and surge capacitors protect alarm contact outputs.
Capacitors and low-voltage MOVs protect power outputs.
Back diodes protect power-fail output transistors.
Dimensions
4.1" H x 8.0" W x 9.5" D
Weight
Unit: 2.6 lbs (1.2 kb)
Shipped: 4.0 lbs (1.8 kg)
Factory Assistance
We appreciate your interest in SEL products and services. If you have questions
or comments, please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 USA
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
Internet: www.selinc.com
Email: info@selinc.com
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under
federal and international copyright and patent laws in its products, including without lim-
itation software, firmware, and documentation.
The information in this document is provided for informational use only and is subject to
change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the
English language document.
This product is covered by the standard SEL 10-year warranty. For warranty details, visit
www.selinc.com or contact your customer service representative. *PMPSM-01*
SEL-PSM Power Supply Module Instruction Manual Date Code 20080530