Eio0000004273 00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 510

SQL Gateway

EIO0000002417 04/2020

Modicon M251
Logic Controller
User Guide
08/2020
EIO0000004273.00

www.schneider-electric.com
Table of Contents

1 Modicon M251 Logic Controller - Programming Guide. . . . . . . . . . . . Part I

2 Modicon M251 Logic Controller - System Functions and Variables


Part II
PLCSystem Library Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Modicon M251 Logic Controller - Hardware Guide. . . . . . . . . . . . . Part III

EIO0000004273 08/2020 2
Modicon M251 Logic Controller

EIO0000003089 12/2019

Modicon M251
Logic Controller
Programming Guide
12/2019
EIO0000003089.02

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.

2 EIO0000003089 12/2019
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 About the Modicon M251 Logic Controller . . . . . . . . . . . 15
M251 Logic Controller Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 2 How to Configure the Controller . . . . . . . . . . . . . . . . . . . 19
How to Configure the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter 3 Libraries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Libraries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 4 Supported Standard Data Types . . . . . . . . . . . . . . . . . . 23
Supported Standard Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chapter 5 Memory Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Controller Memory Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
RAM Memory Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Flash Memory Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Relocation Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 6 Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Maximum Number of Tasks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Task Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Task Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
System and Task Watchdogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Task Priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Default Task Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 7 Controller States and Behaviors . . . . . . . . . . . . . . . . . . . 47
7.1 Controller State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Controller State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.2 Controller States Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Controller States Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3 State Transitions and System Events . . . . . . . . . . . . . . . . . . . . . . . . . 57
Controller States and Output Behavior . . . . . . . . . . . . . . . . . . . . . . . . 58
Commanding State Transitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Error Detection, Types, and Management. . . . . . . . . . . . . . . . . . . . . . 67
Remanent Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

EIO0000003089 12/2019 3
Chapter 8 Controller Device Editor . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Controller Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Communication Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
PLC Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Users Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Chapter 9 Expansion Modules Configuration . . . . . . . . . . . . . . . . . . 81
TM3 I/O Configuration General Description . . . . . . . . . . . . . . . . . . . . . 82
TM3 I/O Bus Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
TM4 Expansion Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 88
TM3/TM2 Expansion Module Configuration. . . . . . . . . . . . . . . . . . . . . 89
Optional I/O Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Chapter 10 Ethernet Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
10.1 Ethernet Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
IP Address Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Modbus TCP Client/Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
FTP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
FTP Client . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
SNMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Controller as a Target Device on EtherNet/IP . . . . . . . . . . . . . . . . . . . 124
Controller as a Slave Device on Modbus TCP. . . . . . . . . . . . . . . . . . . 150
Changing the Modbus TCP Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
10.2 Firewall Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Dynamic Changes Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Firewall Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Firewall Script Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Chapter 11 Industrial Ethernet Manager . . . . . . . . . . . . . . . . . . . . . . . 169
Industrial Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
DHCP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Fast Device Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Chapter 12 Serial Line Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 177
Serial Line Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Machine Expert Network Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Modbus Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181

4 EIO0000003089 12/2019
ASCII Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Modbus Serial IOScanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Adding a Device on the Modbus Serial IOScanner . . . . . . . . . . . . . . . 189
Adding a Modem to a Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Chapter 13 CANopen Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 197
CANopen Interface Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Chapter 14 J1939 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
J1939 Interface Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Chapter 15 OPC UA Server Configuration . . . . . . . . . . . . . . . . . . . . 205
OPC UA Server Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
OPC UA Server Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
OPC UA Server Symbols Configuration . . . . . . . . . . . . . . . . . . . . . . . 210
OPC UA Server Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Chapter 16 Post Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Post Configuration Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Post Configuration File Management . . . . . . . . . . . . . . . . . . . . . . . . . 218
Post Configuration Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Chapter 17 Connecting a Modicon M251 Logic Controller to a PC . . 223
Connecting the Controller to a PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Chapter 18 SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Script Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
SD Card Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Updating Modicon M251 Logic Controller Firmware . . . . . . . . . . . . . . 236
Chapter 19 Firmware Management . . . . . . . . . . . . . . . . . . . . . . . . . 239
Updating TM3 Expansion Modules Firmware . . . . . . . . . . . . . . . . . . . 239
Appendices ......................................... 243
Appendix A How to Change the IP Address of the Controller . . . . . . 245
changeIPAddress: Change the IP address of the controller . . . . . . . . 245
Appendix B Functions to Get/Set Serial Line Configuration in User
Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
GetSerialConf: Get the Serial Line Configuration . . . . . . . . . . . . . . . . 250
SetSerialConf: Change the Serial Line Configuration . . . . . . . . . . . . . 251
SERIAL_CONF: Structure of the Serial Line Configuration Data Type 253
Appendix C Controller Performance. . . . . . . . . . . . . . . . . . . . . . . . . . 255
Processing Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Glossary ......................................... 257
Index ......................................... 267

EIO0000003089 12/2019 5
6 EIO0000003089 12/2019
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.

EIO0000003089 12/2019 7
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.

8 EIO0000003089 12/2019
About the Book

At a Glance

Document Scope
The purpose of this document is to help you to program and operate your Modicon M251 Logic
Controller with the EcoStruxure Machine Expert software.
NOTE: Read and understand this document and all related documents (see page 9) before
installing, operating, or maintaining your Modicon M251 Logic Controller.
The Modicon M251 Logic Controller users should read through the entire document to understand
all features.

Validity Note
This document has been updated for the release of EcoStruxureTM Machine Expert V1.2.
The technical characteristics of the devices described in the present document also appear online.
To access the information online, go to the Schneider Electric home page www.schneider-
electric.com.
The characteristics that are described in the present document should be the same as those
characteristics that appear online. In line with our policy of constant improvement, we may revise
content over time to improve clarity and accuracy. If you see a difference between the document
and online information, use the online information as your reference.

Related Documents

Title of Documentation Reference Number


EcoStruxure Machine Expert Programming Guide EIO0000002854 (ENG)
EIO0000002855 (FRE)
EIO0000002856 (GER)
EIO0000002858 (SPA)
EIO0000002857 (ITA)
EIO0000002859 (CHS)
Modicon M251 Logic Controller Hardware Guide EIO0000003101 (ENG)
EIO0000003102 (FRE)
EIO0000003103 (GER)
EIO0000003104 (SPA)
EIO0000003105 (ITA)
EIO0000003106 (CHS)

EIO0000003089 12/2019 9
Title of Documentation Reference Number
EcoStruxure Machine Expert Industrial Ethernet User Guide EIO0000003053 (ENG)
EIO0000003054 (FRE)
EIO0000003055 (GER)
EIO0000003056 (SPA)
EIO0000003057 (ITA)
EIO0000003058 (CHS)
Modicon TM4 Expansion Modules Programming Guide EIO0000003149 (ENG)
EIO0000003150 (FRE)
EIO0000003151 (GER)
EIO0000003152 (SPA)
EIO0000003153 (ITA)
EIO0000003154 (CHS)
Modicon TM3 Modules Configuration Programming Guide EIO0000003119 (ENG)
EIO0000003120 (FRE)
EIO0000003121 (GER)
EIO0000003122 (SPA)
EIO0000003123 (ITA)
EIO0000003124 (CHS)
Modicon TM3 Bus Coupler - Programming Guide (EcoStruxure EIO0000003635 (ENG)
Machine Expert) EIO0000003636 (FRA)
EIO0000003637 (GER)
EIO0000003638 (SPA)
EIO0000003639 (ITA)
EIO0000003640 (CHS)
Modicon TM2 Modules Configuration Programming Guide EIO0000003432 (ENG)
EIO0000003433 (FRE)
EIO0000003434 (GER)
EIO0000003435 (SPA)
EIO0000003436 (ITA)
EIO0000003437 (CHS)
Modicon M251 Logic Controller System Functions and Variables EIO0000003095 (ENG)
PLCSystem Library Guide EIO0000003096 (FRE)
EIO0000003097 (GER)
EIO0000003098 (SPA)
EIO0000003099 (ITA)
EIO0000003100 (CHS)

10 EIO0000003089 12/2019
Title of Documentation Reference Number
Modicon TM3 Expert I/O Modules - HSC Library Guide EIO0000003683 (ENG)
EIO0000003684 (FRE)
EIO0000003685 (GER)
EIO0000003686 (SPA)
EIO0000003687 (ITA)
EIO0000003688 (CHS)
EIO0000003689 (POR)
EIO0000003690 (TUR)
EcoStruxure Machine Expert Controller Assistant User Guide EIO0000001671 (ENG)
EIO0000001672 (FRE)
EIO0000001673 (GER)
EIO0000001675 (SPA)
EIO0000001674 (ITA)
EIO0000001676 (CHS)
FTPRemoteFileHandling Library Guide EIO0000002779 (ENG)
EIO0000002780 (FRE)
EIO0000002781 (GER)
EIO0000002783 (SPA)
EIO0000002782 (ITA)
EIO0000002784 (CHS)
SNMP Library Guide EIO0000002797 (ENG)
EIO0000002798 (FRE)
EIO0000002799 (GER)
EIO0000002801 (SPA)
EIO0000002800 (ITA)
EIO0000002802 (CHS)

You can download these technical publications and other technical information from our website
at https://www.se.com/ww/en/download/ .

EIO0000003089 12/2019 11
Product Related Information

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths
and, for certain critical control functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are emergency stop and overtravel
stop, power outage and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.1
 Each implementation of this equipment must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest
edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

12 EIO0000003089 12/2019
Terminology Derived from Standards
The technical terms, terminology, symbols and the corresponding descriptions in this manual, or
that appear in or on the products themselves, are generally derived from the terms or definitions
of international standards.
In the area of functional safety systems, drives and general automation, this may include, but is not
limited to, terms such as safety, safety function, safe state, fault, fault reset, malfunction, failure,
error, error message, dangerous, etc.
Among others, these standards include:

Standard Description
IEC 61131-2:2007 Programmable controllers, part 2: Equipment requirements and tests.
ISO 13849-1:2015 Safety of machinery: Safety related parts of control systems.
General principles for design.
EN 61496-1:2013 Safety of machinery: Electro-sensitive protective equipment.
Part 1: General requirements and tests.
ISO 12100:2010 Safety of machinery - General principles for design - Risk assessment and risk
reduction
EN 60204-1:2006 Safety of machinery - Electrical equipment of machines - Part 1: General
requirements
ISO 14119:2013 Safety of machinery - Interlocking devices associated with guards - Principles
for design and selection
ISO 13850:2015 Safety of machinery - Emergency stop - Principles for design
IEC 62061:2015 Safety of machinery - Functional safety of safety-related electrical, electronic,
and electronic programmable control systems
IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: General requirements.
IEC 61508-2:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: Requirements for electrical/electronic/programmable
electronic safety-related systems.
IEC 61508-3:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: Software requirements.
IEC 61784-3:2016 Industrial communication networks - Profiles - Part 3: Functional safety
fieldbuses - General rules and profile definitions.
2006/42/EC Machinery Directive
2014/30/EU Electromagnetic Compatibility Directive
2014/35/EU Low Voltage Directive

EIO0000003089 12/2019 13
In addition, terms used in the present document may tangentially be used as they are derived from
other standards such as:

Standard Description
IEC 60034 series Rotating electrical machines
IEC 61800 series Adjustable speed electrical power drive systems
IEC 61158 series Digital data communications for measurement and control – Fieldbus for use in
industrial control systems

Finally, the term zone of operation may be used in conjunction with the description of specific
hazards, and is defined as it is for a hazard zone or danger zone in the Machinery Directive
(2006/42/EC) and ISO 12100:2010.
NOTE: The aforementioned standards may or may not apply to the specific products cited in the
present documentation. For more information concerning the individual standards applicable to the
products described herein, see the characteristics tables for those product references.

14 EIO0000003089 12/2019
Modicon M251 Logic Controller
About the Modicon M251 Logic Controller
EIO0000003089 12/2019

Chapter 1
About the Modicon M251 Logic Controller

About the Modicon M251 Logic Controller

M251 Logic Controller Description

Overview
The M251 Logic Controller has various powerful features and can service a wide range of
applications.
Software configuration, programming, and commissioning are achieved with the EcoStruxure
Machine Expert software described in the EcoStruxure Machine Expert Programming Guide and
in the M251 Logic Controller Programming Guide.

Programming Languages
The M251 Logic Controller is configured and programmed with the EcoStruxure Machine Expert
software, which supports the following IEC 61131-3 programming languages:
 IL: Instruction list
 ST: Structured text
 FBD: Function block diagram
 SFC: Sequential function chart
 LD: Ladder diagram

EcoStruxure Machine Expert software can also be used to program this controller using CFC
(continuous function chart) language.

Power Supply
The power supply of the M251 Logic Controller is 24 Vdc.

Real Time Clock


The M251 Logic Controller includes a Real Time Clock (RTC) system (see Modicon M251 Logic
Controller, Hardware Guide).

Run/Stop
The M251 Logic Controller can be operated externally by the following:
 a hardware Run/Stop switch
 an EcoStruxure Machine Expert software command

EIO0000003089 12/2019 15
About the Modicon M251 Logic Controller

Memory
This table describes the different types of memory:

Memory Type Size Used


RAM 64 Mbytes, of which 8 Mbytes To execute the application.
available for the application
Flash 128 Mbytes To save the program and data in case of a
power interruption.

Removable Storage
M251 Logic Controllers include an embedded SD card slot (see Modicon M251 Logic Controller,
Hardware Guide).
The main uses of the SD card are:
 Initializing the controller with a new application
 Updating the controller firmware
 Applying post configuration files to the controller
 Applying recipes
 Receiving data logging files

Embedded Communication Features


The M251 Logic Controller native communication ports include (depending on the controller
reference):
 CANopen Master
 Ethernet
 USB Mini-B
 Serial Line

Expansion Module and Bus Coupler Compatibility


Refer to the compatibility tables in the EcoStruxure Machine Expert - Compatiblity and Migration
User Guide.

16 EIO0000003089 12/2019
About the Modicon M251 Logic Controller

M251 Logic Controllers

Reference Digital Inputs Digital Outputs Communication Ports


TM251MESC 0 0 1 serial line port
1 USB mini-B programming port
1 dual port Ethernet switch
1 CANopen port
TM251MESE 0 0 1 serial line port
(see Modicon 1 USB mini-B programming port
M251 Logic 1 dual port Ethernet switch
Controller, 1 Ethernet port for fieldbus
Hardware
Guide)

EIO0000003089 12/2019 17
About the Modicon M251 Logic Controller

18 EIO0000003089 12/2019
Modicon M251 Logic Controller
How to Configure the Controller
EIO0000003089 12/2019

Chapter 2
How to Configure the Controller

How to Configure the Controller

How to Configure the Controller

Introduction
First, create a new project or open an existing project in the EcoStruxure Machine Expert software.
Refer to the EcoStruxure Machine Expert Programming Guide for information on how to:
 add a controller to your project
 add expansion modules to your controller
 replace an existing controller
 convert a controller to a different but compatible device

Devices Tree
The Devices tree presents a structured view of the current hardware configuration. When you add
a controller to your project, a number of nodes are added to the Devices tree, depending on the
functions the controller provides.

EIO0000003089 12/2019 19
How to Configure the Controller

Item Use to Configure...


IO_Bus Expansion modules connected to the logic controller
COM_Bus Communications bus of the logic controller
Ethernet_x Embedded Ethernet, serial line, or CANopen communications interfaces
Serial_Line_x NOTE: Ethernet and CANopen are only available on some references.
CAN_x

Applications Tree
The Applications tree allows you to manage project-specific applications as well as global
applications, POUs, and tasks.

Tools Tree
The Tools tree allows you to configure the HMI part of your project and to manage libraries.

20 EIO0000003089 12/2019
Modicon M251 Logic Controller
Libraries
EIO0000003089 12/2019

Chapter 3
Libraries

Libraries

Libraries

Introduction
Libraries provide functions, function blocks, data types, and global variables that can be used to
develop your project.
The Library Manager of EcoStruxure Machine Expert provides information about the libraries
included in your project and allows you to install new ones. For more information on the Library
Manager, refer to the EcoStruxure Machine Expert Programming Guide.

Modicon M251 Logic Controller


When you select a Modicon M251 Logic Controller for your application, EcoStruxure Machine
Expert automatically loads these libraries:

Library Name Description


IoStandard CmpIoMgr configuration types, ConfigAccess, Parameters, and help
functions: manages the I/Os in the application.
Standard Contains functions and function blocks that are required matching
IEC61131-3 as standard POUs for an IEC programming system. The
standard POUs must be tied to the project (standard.library).
Util Analog Monitors, BCD Conversions, Bit/Byte Functions, Controller
Datatypes, Function Manipulators, Mathematical Functions, Signals.
M251 PLCSystem (see Modicon Contains functions and variables to get information and send
M251 Logic Controller, System commands to the controller system.
Functions and Variables,
PLCSystem Library Guide)
PLCCommunication SysMem, Standard. These functions facilitate communications
(see EcoStruxure Machine Expert, between specific devices. Most of them are dedicated to Modbus
Modbus and ASCII Read/Write exchange. Communication functions are asynchronously processed
Functions, PLCCommunication regarding the application task that called the function.
Library Guide)
Relocation Table (see page 34) The relocation table allows you to organize data to optimize exchanges
between the Modbus client and the controller, by regrouping non-
contiguous data into a contiguous table of registers.
ModbusTCPIOScanner TM251MESE only. Provides Modbus TCP IOScanner function blocks.
(see EcoStruxure Machine Expert
Modbus TCP, User Guide)

EIO0000003089 12/2019 21
Libraries

Library Name Description


EtherNetIP Scanner TM251MESE only. Infrastructure function blocks to establish and close
(see EcoStruxure Machine Expert CIP connections and to build Explicit Messaging request over
EtherNet/IP, User Guide) EtherNet/IP.
EtherNetIP Explicit Messaging TM251MESE only. Explicit Messaging over EtherNet/IP, to
(see EcoStruxure Machine Expert communicate with generic devices (e.g. cameras) for which
EtherNet/IP, User Guide) EcoStruxure Machine Expert does not offer a device integration.
Additional libraries: The CAA CiA 405 library offers a set of function blocks to meet the
 3S CANopenStack requirements of the CiA405 for the access to the CANopen network
 FDT_CANOpenDriver from the application (IEC61131-3 program) of the controller (CANopen
 CAA CiA 405 master).

22 EIO0000003089 12/2019
Modicon M251 Logic Controller
Supported Standard Data Types
EIO0000003089 12/2019

Chapter 4
Supported Standard Data Types

Supported Standard Data Types

Supported Standard Data Types

Supported Standard Data Types


The controller supports the following IEC data types:

Data Type Lower Limit Upper Limit Information Content


BOOL FALSE TRUE 1 Bit
BYTE 0 255 8 Bit
WORD 0 65,535 16 Bit
DWORD 0 4,294,967,295 32 Bit
LWORD 0 264-1 64 Bit
SINT -128 127 8 Bit
USINT 0 255 8 Bit
INT -32,768 32,767 16 Bit
UINT 0 65,535 16 Bit
DINT -2,147,483,648 2,147,483,647 32 Bit
UDINT 0 4,294,967,295 32 Bit
LINT -263 263-1 64 Bit
ULINT 0 264-1 64 Bit
REAL 1.175494351e-38 3.402823466e+38 32 Bit
LREAL 2.2250738585072014e-308 1.7976931348623158e+308 64 Bit
STRING 1 character 255 characters 1 character = 1 byte
WSTRING 1 character 255 characters 1 character = 1 word
TIME - - 32 Bit

For more information on ARRAY, LTIME, DATE, TIME, DATE_AND_TIME, and TIME_OF_DAY, refer
to the EcoStruxure Machine Expert Programming Guide.

EIO0000003089 12/2019 23
Supported Standard Data Types

24 EIO0000003089 12/2019
Modicon M251 Logic Controller
Memory Mapping
EIO0000003089 12/2019

Chapter 5
Memory Mapping

Memory Mapping

Introduction
This chapter describes the memory maps and sizes of the different memory areas in the Modicon
M251 Logic Controller. These memory areas are used to store user program logic, data and the
programming libraries.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Controller Memory Organization 26
RAM Memory Organization 28
Flash Memory Organization 30
Relocation Table 34

EIO0000003089 12/2019 25
Memory Mapping

Controller Memory Organization

Introduction
The controller memory is composed of two types of physical memory:
 The Flash memory (see page 30) contains files (application, configuration files, and so on).
 The Random Access Memory (RAM) (see page 28) is used for application execution.

Files Transfers in Memory

26 EIO0000003089 12/2019
Memory Mapping

Item Controller State File Transfer Events Connection Description


1 – Initiated automatically Internal Files transfer from Flash memory to RAM.
at Power ON and The content of the RAM is overwritten.
Reboot
2 All states except Initiated by user Ethernet or USB Files can be transferred via:
INVALID_OS (1) programming  Web server (see page 105)
port  FTP server (see page 121)
 Controller Assistant
 EcoStruxure Machine Expert
(see EcoStruxure Machine Expert,
Programming Guide)
3 All states Initiated automatically SD card Up/download with SD card(1).
by script (data
transfer) or by power
cycle (cloning) when
an SD card is inserted
(1) If the controller is in the INVALID_OS state, the only accessible memory is the SD card and only for firmware
upgrades.

NOTE: The modification of files in Flash memory does not affect a running application. Any
changes to files in Flash memory are taken into account at the next reboot.

EIO0000003089 12/2019 27
Memory Mapping

RAM Memory Organization

Introduction
This section describes the RAM (Random Access Memory) size for different areas of the Modicon
M251 Logic Controller.

Memory Mapping
The RAM size is 64 Mbytes.
The RAM is composed of 2 areas:
 dedicated application memory
 OS memory

This table describes the dedicated application memory:

Area Element Size


System area System Area Mappable Addresses 128 Kbytes
192 Kbytes %MW0...%MW59999
System and diagnostic variables
(%MW60000...%MW60199)
This memory is accessible through Modbus requests only.
These must be read-only requests.
Dynamic Memory Area: Read Relocation Table (see page 34)
(%MW60200...%MW61999)
This memory is accessible through Modbus requests only.
These must be read-only requests.
System and diagnostic variables
(%MW62000...%MW62199)
This memory is accessible through Modbus requests only.
These can be read or write requests.
Dynamic Memory Area: Write Relocation Table (see page 34)
(%MW62200...%MW63999)
This memory is accessible through Modbus requests only.
These can be read or write requests.
%MW64000…%MW65535
Reserved
Retain and Persistent data (see page 30) 64 Kbytes
User area Symbols Dynamic
8 Mbytes allocation
Variables
Application
Libraries

28 EIO0000003089 12/2019
Memory Mapping

System and Diagnostic Variables

Variables Description
PLC_R Structure of controller read-only system variables.
PLC_W Structure of controller read/write system variables.
ETH_R Structure of Ethernet read-only system variables.
ETH_W Structure of Ethernet read/write system variables.
PROFIBUS_R Structure of PROFIBUS DP read-only system variables.
SERIAL_R Structure of Serial Lines read-only system variables.
SERIAL_W Structure of Serial Lines read/write system variables.
TM3_MODULE_R Structure of TM3 modules read-only system variables.

For more information on system and diagnostic variables, refer to M251 PLCSystem Library Guide.

Memory Addressing
This table describes the memory addressing for the address sizes Double Word (%MD), Word
(%MW), Byte (%MB), and Bit (%MX):

Double Words Words Bytes Bits


%MD0 %MW0 %MB0 %MX0.7 ... %MX0.0
%MB1 %MX1.7 ... %MX1.0
%MW1 %MB2 %MX2.7 ... %MX2.0
%MB3 %MX3.7 ... %MX3.0
%MD1 %MW2 %MB4 %MX4.7 ... %MX4.0
%MB5 %MX5.7 ... %MX5.0
%MW3 %MB6 %MX6.7 ... %MX6.0
%MB7 %MX7.7 ... %MX7.0
%MD2 %MW4 %MB8 %MX8.7 ... %MX8.0
... ... ... ...
... ... ... ... ...
... ... ... ...

Example of overlap of memory ranges:


%MD0 contains %MB0 (...) %MB3, %MW0 contains %MB0 and %MB, %MW1 contains %MB2 and
%MB3.
NOTE: The Modbus communication is asynchronous with the application.

EIO0000003089 12/2019 29
Memory Mapping

Flash Memory Organization

Introduction
The Flash memory contains the file system used by the controller.

File Type
The Modicon M251 Logic Controller manages the following file types:

Type Description
Boot application This file resides in Flash memory and contains the compiled binary code of the
executable application. Each time the controller is rebooted, the executable
application is extracted from the boot application and copied into the controller
RAM (1).
Application source Source file that can be uploaded from Flash memory to the PC if the source file is
not available on the PC (2).
Post configuration File that contains Ethernet, serial line, and firewall parameters.
The parameters specified in the file override the parameters in the executable
application at each reboot.
Data logging Files in which the controller logs events as specified by the application.
HTML page HTML pages displayed by the web server for the website embedded in the
controller.
Operating System (OS) Controller firmware that can be written to Flash memory. The firmware file is
applied at next reboot of the controller.
Retain variable Remanent variables
Retain-persistent
variable
(1) The creation of a boot application is optional in EcoStruxure Machine Expert, according to application
properties. Default option is to create the boot application on download. When you download an
application from EcoStruxure Machine Expert to the controller, you are transferring only the binary
executable application directly to RAM.
(2) EcoStruxure Machine Expert does not support uploading of either the executable application or the boot
application to a PC for modification. Program modifications must be made to the application source. When
you download your application, you have the option to store the source file to Flash memory.

30 EIO0000003089 12/2019
Memory Mapping

File Organization
This table shows the file organization of the flash memory:

Disk Directory File Content Up/Downloaded


Data Type
/sys OS M241M251FW1v_XX.YY (1) Firmware of core 1 Firmware

M241M251FW2v_XX.YY (1) Firmware of core 2


Version.ini Control file for firmware version
Web Index.htm HTML pages served by the web server Website
for the website embedded in the
Conf.htm –
controller.
... –
/usr App Application.app Boot application Application
Application.crc –
Application.map –
Archive.prj (2) Application source –

settings.conf (3) OPC UA configuration Configuration

OpcUASymbolConf.map (3) OPC UA symbols configuration Configuration


Cfg Machine.cfg (2) Post configuration file (see page 215) Configuration

CodesysLateConf.cfg (2)  Name of application to launch Configuration


 Routing table (main/sub net)
(1):
v_XX.YY represents the version
(2):
if any
(3): if OPC UA (see page 207) is configured
(4)
: the Fdr/FDRS directory is hidden

EIO0000003089 12/2019 31
Memory Mapping

Disk Directory File Content Up/Downloaded


Data Type
/usr Log UserDefinedLogName_1.log All *.log files created using the data log file
logging functions (see SoMachine, Data
Logging Functions, DataLogging Library
Guide). You must specify the total
number of files created and the names
and contents of each log file.
... – –
UserDefinedLogName_n.log – –
Rcp Main directory for Recipe –
Syslog crashC1.txt (2) This file contains a record of detected Log file
crashC2.txt(2) system errors. For use by
Schneider Electric Technical Support.
crashBoot.txt(2)
PlcLog.txt (2) This file contains system event data that –
is also visible online in EcoStruxure
Machine Expert by viewing the Log tab
of the Controller Device Editor
(see page 72).
FwLog.txt This file contains a record of firmware –
system events. For use by
Schneider Electric Technical Support.
/usr Fdr/FDRS (4) Device1.prm Parameter files stored by the FDR client FDR
only for device1 (see page 175)
TM251MESE Device2.prm Parameter files stored by the FDR client
device2
... –
/data – – Retained and persistent data –
/sd0 – – SD card. Removable –
– User files – –
(1)
: v_XX.YY represents the version
(2)
: if any
(3): if OPC UA (see page 207) is configured
(4)
: the Fdr/FDRS directory is hidden

NOTE: For more information on libraries and available function blocks, refer to Libraries
(see page 21).

32 EIO0000003089 12/2019
Memory Mapping

Files Redirection
When system, program or certain user activity creates specific file types, the M251 Logic Controller
examines the file extension and automatically moves the file to a corresponding folder in flash
memory.
The following table lists the file types that are moved in this way and the destination folder in flash
memory:

File extensions Flash memory folder


*.app, *.ap_, *.err, *.crc, *.frc, *.prj /usr/App
*.cfg, *.cf_ /usr/Cfg
*.log /usr/Log
*.rcp, *.rsi /usr/Rcp

Backup Data Logging File


Data logging files can become large to the point of exceeding the space available in the file system.
Therefore, you should develop a method to archive the log data periodically on an SD card. You
could split the log data into several files, for example LogMonth1, LogMonth2, and use the
ExecuteScript (see Modicon M251 Logic Controller, System Functions and Variables, PLCSystem
Library Guide) command to copy the first file to an SD card. Afterwards, you may remove it from
the internal file system while the second file is accumulating data. If you allow the data logging file
to grow and exceed the limits of the file size, you could lose data.

NOTICE
LOSS OF APPLICATION DATA
 Backup SD card data regularly.
 Do not remove power or reset the controller, and do not insert or remove the SD card while it
is being accessed.
Failure to follow these instructions can result in equipment damage.

EIO0000003089 12/2019 33
Memory Mapping

Relocation Table

Introduction
The Relocation Table allows you to organize data to optimize communication between the
controller and other equipment by regrouping non-contiguous data into a contiguous table of
located registers, accessible through Modbus.
NOTE: A relocation table is considered as an object. Only one relocation table object can be added
to a controller.

Relocation Table Description


This table describes the Relocation Table organization:

Register Description
60200...61999 Dynamic Memory Area: Read Relocation Table
62200...63999 Dynamic Memory Area: Write Relocation Table

For further information, refer to M251 PLCSystem Library Guide.

Adding a Relocation Table


This table describes how to add a Relocation Table to your project:

Step Action
1 Select the Application node in the Applications tree tab.
2
Click .
3 Click Add other objects → Relocation Table....
Result: The Add Relocation Table window is displayed.
4 Click Add.
Result: The new relocation table is created and initialized.
NOTE: As a Relocation Table is unique for a controller, its name is Relocation Table and cannot
be changed.

34 EIO0000003089 12/2019
Memory Mapping

Relocation Table Editor


The relocation table editor allows you to organize your variables in the relocation table.
To access the relocation table editor, double-click the Relocation Table node in the Tools tree tab:

This picture describes the relocation table editor:

EIO0000003089 12/2019 35
Memory Mapping

Icon Element Description


New Item Adds an element to the list of system variables.

Move Down Moves down the selected element of the list.

Move Up Moves up the selected element of the list.

Delete Item Removes the selected elements of the list.

Copy Copies the selected elements of the list.

Paste Pastes the elements copied.

Erase Empty Item Removes all the elements of the list for which the "Variable" column is empty.

- ID Automatic incremental integer (not editable).


- Variable The name or the full path of a variable (editable).
- Address The address of the system area where the variable is stored (not editable).
- Length Variable length in word.
- Validity Indicates if the entered variable is valid (not editable).

NOTE: If a variable is undefined after program modifications, the content of the cell is displayed in
red, the related Validity cell is False, and Address is set to -1.

36 EIO0000003089 12/2019
Modicon M251 Logic Controller
Tasks
EIO0000003089 12/2019

Chapter 6
Tasks

Tasks

Introduction
The Task Configuration node in the Applications tree allows you to define one or more tasks to
control the execution of your application program.
The task types available are:
 Cyclic
 Freewheeling
 Event
 External event

This chapter begins with an explanation of these task types and provides information regarding the
maximum number of tasks, the default task configuration, and task prioritization. In addition, this
chapter introduces the system and task watchdog functions and explains its relationship to task
execution.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Maximum Number of Tasks 38
Task Configuration Screen 39
Task Types 41
System and Task Watchdogs 44
Task Priorities 45
Default Task Configuration 46

EIO0000003089 12/2019 37
Tasks

Maximum Number of Tasks

Maximum Number of Tasks


The maximum number of tasks you can define for the Modicon M251 Logic Controller is:
 Total number of tasks = 19
 Cyclic tasks = 5
 Freewheeling tasks = 1
 Event tasks = 8
 External event task = 1 (TM251MESC only)

Special Considerations for Freewheeling


A Freewheeling task (see page 42) does not have a fixed duration. In Freewheeling mode, each
task scan starts when the previous scan has been completed and after a period of system
processing (30% of the total duration of the Freewheeling task). If the system processing period is
reduced to less than 15% for more than 3 seconds due to interruptions by other tasks, a system
error is detected. For more information, refer to the System Watchdog (see page 44).
NOTE: You may wish to avoid using a Freewheeling task in a multi-task application when some
high priority and time-consuming tasks are running. Doing so may provoke a task Watchdog
Timeout. You should not assign CANopen to a freewheeling task. CANopen should be assigned
to a cyclic task.

38 EIO0000003089 12/2019
Tasks

Task Configuration Screen

Screen Description
This screen allows you to configure the tasks. Double-click the task that you want to configure in
the Applications tree to access this screen.
Each configuration task has its own parameters that are independent of the other tasks.
The Configuration window is composed of 4 parts:

EIO0000003089 12/2019 39
Tasks

The table describes the fields of the Configuration screen:

Field Name Definition


Priority Configure the priority of each task with a number from 0 to 31 (0 is the highest priority, 31 is
the lowest).
Only one task at a time can be running. The priority determines when the task will run:
 a higher priority task will pre-empt a lower priority task
 tasks with same priority will run in turn (2 ms time-slice)

NOTE: Do not assign tasks with the same priority. If there are yet other tasks that attempt
to pre-empt tasks with the same priority, the result could be indeterminate and unpredicable.
For important safety information, refer to Task Priorities (see page 45).
Type These task types are available:
 Cyclic (see page 41)
 Event (see page 43)
 External (see page 43)
 Freewheeling (see page 42)

Watchdog To configure the watchdog (see page 44), define these 2 parameters:
 Time: enter the timeout before watchdog execution.
 Sensitivity: defines the number of expirations of the watchdog timer before the controller
stops program execution and enters a HALT state.
POUs The list of POUs (Programming Organization Units) controlled by the task is defined in the
task configuration window:
 To add a POU linked to the task, use the command Add Call and select the POU in the
Input Assistant editor.
 To remove a POU from the list, use the command Remove Call.
 To replace the currently selected POU of the list by another one, use the command
Change Call.
 POUs are executed in the order shown in the list. To move the POUs in the list, select a
POU and use the command Move Up or Move Down.
NOTE: You can create as many POUs as you want. An application with several small
POUs, as opposed to one large POU, can improve the refresh time of the variables in online
mode.

40 EIO0000003089 12/2019
Tasks

Task Types

Introduction
The following section describes the various task types available for your program, along with a
description of the task type characteristics.

Cyclic Task
A Cyclic task is assigned a fixed cycle time using the Interval setting in the Type section of
Configuration subtab for that task. Each Cyclic task type executes as follows:

1. Read Inputs: The physical input states are written to the %I input memory variables and other
system operations are executed.
2. Task Processing: The user code (POU, and so on) defined in the task is processed. The %Q
output memory variables are updated according to your application program instructions but not
yet written to the physical outputs during this operation.
3. Write Outputs: The %Q output memory variables are modified with any output forcing that has
been defined; however, the writing of the physical outputs depends upon the type of output and
instructions used.
For more information on defining the bus cycle task, refer to the EcoStruxure Machine Expert
Programming Guide and Modicon M251 Logic Controller Settings (see page 75).
4. Remaining Interval time: The controller firmware carries out system processing and any other
lower priority tasks.
NOTE: If you define too short a period for a cyclic task, it will repeat immediately after the write of
the outputs and without executing other lower priority tasks or any system processing. This will
affect the execution of all tasks and cause the controller to exceed the system watchdog limits,
generating a system watchdog exception.
NOTE: When the task cycle time is set to a value less than 3 ms, the actual task duration should
first be monitored through the Task Monitoring screen during commissioning to ensure that it is
consistently lower than the configured task cycle time. If greater, the task cycle may not be
respected without causing a task cycle watchdog time-out and the controller transitioning to a
HALT state. To avoid this condition to a certain degree, when the task cycle time is set to a value
of less than 3 ms, real limits of +1 ms are imposed if, on any given cycle, the calculated cycle time
slightly exceeds the configured cycle time.

EIO0000003089 12/2019 41
Tasks

NOTE: Get and set the interval of a Cyclic Task by application using the GetCurrentTaskCycle and
SetCurrentTaskCycle function. (Refer to Toolbox Advance Library Guide for further details.)

Freewheeling Task
A Freewheeling task does not have a fixed duration. In Freewheeling mode, each task scan begins
when the previous scan has been completed and after a short period of system processing. Each
Freewheeling task type executes as follows:

1. Read Inputs: The physical input states are written to the %I input memory variables and other
system operations are executed.
2. Task Processing: The user code (POU, and so on) defined in the task is processed. The %Q
output memory variables are updated according to your application program instructions but not
yet written to the physical outputs during this operation.
3. Write Outputs: The %Q output memory variables are modified with any output forcing that has
been defined; however, the writing of the physical outputs depends upon the type of output and
instructions used.
For more information on defining the bus cycle task, refer to the EcoStruxure Machine Expert
Programming Guide and Modicon M251 Logic Controller Settings (see page 75).
4. System Processing: The controller firmware carries out system processing and any other lower
priority tasks (for example: HTTP management, Ethernet management, parameters
management).
NOTE: If you want to define the task interval, refer to Cyclic Task (see page 41).

42 EIO0000003089 12/2019
Tasks

Event Task
This type of task is event-driven and is initiated by a program variable. It starts at the rising edge
of the boolean variable associated to the trigger event unless pre-empted by a higher priority task.
In that case, the Event task will start as dictated by the task priority assignments.
For example, if you have defined a variable called my_Var and would like to assign it to an Event,
proceed as follows:

Step Action
1 Double-click the TASK in the Applications tree.
2 Select Event from the Type list in the Configuration tab.
3
Click the Input Assistant button to the right of the Event field.
Result: The Input Assistant window appears.
4 Navigate in the tree of the Input Assistant dialog box to find and assign the my_Var variable.

NOTE: When the event task is triggered at a too high frequency, the controller will go to the HALT
state (Exception). The maximum rate of events is 6 events per millisecond. If the event task is
triggered at a higher frequency than this, the message 'ISR Count Exceeded' is logged in the
application log page.

External Event Task


This type of task is event-driven and is initiated by the detection of a hardware or hardware-related
function event. It starts when the event occurs unless pre-empted by a higher priority task. In that
case, the External Event task will start as dictated by the task priority assignments.
The external event task is associated with the CAN Sync event. To associate the CAN_1_SYNC
event to an external event task, select it from the External event dropdown list in the Configuration
tab.
NOTE: CAN Sync is a specific event object, depending on the CANopen manager configuration.

EIO0000003089 12/2019 43
Tasks

System and Task Watchdogs

Introduction
Two types of watchdog functionality are implemented for the Modicon M251 Logic Controller:
 System Watchdogs: These watchdogs are defined in and managed by the controller firmware.
These are not configurable by the user.
 Task Watchdogs: These watchdogs are optional watchdogs that you can define for each task.
These are managed by your application program and are configurable in EcoStruxure Machine
Expert.

System Watchdogs
Three system watchdogs are defined for the Modicon M251 Logic Controller. They are managed
by the controller firmware and are therefore sometimes referred to as hardware watchdogs in the
EcoStruxure Machine Expert online help. When one of the system watchdogs exceeds its
threshold conditions, an error is detected.
The threshold conditions for the 3 system watchdogs are defined as follows:
 If all of the tasks require more than 85% of the processor resources for more than 3 seconds, a
system error is detected. The controller enters the HALT state.
 If the total execution time of the tasks with priorities between 0 and 24 reaches 100% of
processor resources for more than 1 second, an application error is detected. The controller
responds with an automatic reboot into the EMPTY state.
 If the lowest priority task of the system is not executed during an interval of 10 seconds, a
system error is detected. The controller responds with an automatic reboot into the EMPTY
state.
NOTE: System watchdogs are not configurable by the user.

Task Watchdogs
EcoStruxure Machine Expert allows you to configure an optional task watchdog for every task
defined in your application program. (Task watchdogs are sometimes also referred to as software
watchdogs or control timers in the EcoStruxure Machine Expert online help). When one of your
defined task watchdogs reaches its threshold condition, an application error is detected and the
controller enters the HALT state.
When defining a task watchdog, the following options are available:
 Time: This defines the allowable maximum execution time for a task. When a task takes longer
than this, the controller will report a task watchdog exception.
 Sensitivity: The sensitivity field defines the number of task watchdog exceptions that must occur
before the controller detects an application error.
To access the configuration of a task watchdog, double-click the Task in the Applications tree.
NOTE: For more information on watchdogs, refer to EcoStruxure Machine Expert Programming
Guide.

44 EIO0000003089 12/2019
Tasks

Task Priorities

Task Priority Configuration


You can configure the priority of each task between 0 and 31 (0 is the highest priority, 31 is the
lowest). Each task must have a unique priority. Assigning the same priority to more than one task
leads to a build error.

Task Priority Suggestions


 Priority 0 to 24: Controller tasks. Assign these priorities to tasks with a high availability
requirement.
 Priority 25 to 31: Background tasks. Assign these priorities to tasks with a low availability
requirement.

Task Priorities of TM2/TM3 Modules and CANopen I/Os


You can select the task that drives TM3 and CANopen physical exchanges. In the PLC settings,
select Bus cycle task to define the task for the exchange. By default, the task is set to MAST. This
definition at the controller level can be overridden by the I/O bus configuration (see page 87).
During the read and write phases, all physical I/Os are refreshed at the same time. TM3/TM2 and
CANopen data is copied into a virtual I/O image during a physical exchanges phase, as shown in
this figure:

Inputs are read from the I/O image table at the beginning of the task cycle. Outputs are written to
the I/O image table at the end of the task.
NOTE: Event tasks cannot drive the TM3/TM2 bus cycle.

EIO0000003089 12/2019 45
Tasks

Default Task Configuration

Default Task Configuration


The MAST task can be configured in Freewheeling or Cyclic mode. The MAST task is automatically
created by default in Cyclic mode. Its preset priority is medium (15), its preset interval is 20 ms,
and its task watchdog service is activated with a time of 100 ms and a sensitivity of 1. Refer to Task
Priorities (see page 45) for more information on priority settings. Refer to Task Watchdogs
(see page 44) for more information on watchdogs.
Designing an efficient application program is important in systems approaching the maximum
number of tasks. In such an application, it can be difficult to keep the resource utilization below the
system watchdog threshold. If priority reassignments alone are not sufficient to remain below the
threshold, some lower priority tasks can be made to use fewer system resources if the
SysTaskWaitSleep function is added to those tasks. For more information about this function, see
the optional SysTask library of the system / SysLibs category of libraries.
NOTE: Do not delete or change the name of the MAST task. Otherwise, EcoStruxure Machine
Expert detects an error when you attempt to build the application, and you will not be able to
download it to the controller.

46 EIO0000003089 12/2019
Modicon M251 Logic Controller
Controller States and Behaviors
EIO0000003089 12/2019

Chapter 7
Controller States and Behaviors

Controller States and Behaviors

Introduction
This chapter provides you with information on controller states, state transitions, and behaviors in
response to system events. It begins with a detailed controller state diagram and a description of
each state. It then defines the relationship of output states to controller states before explaining the
commands and events that result in state transitions. It concludes with information about
Remanent variables and the effect of EcoStruxure Machine Expert task programming options on
the behavior of your system.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
7.1 Controller State Diagram 48
7.2 Controller States Description 53
7.3 State Transitions and System Events 57

EIO0000003089 12/2019 47
Controller States and Behaviors

Section 7.1
Controller State Diagram

Controller State Diagram

48 EIO0000003089 12/2019
Controller States and Behaviors

Controller State Diagram

Controller State Diagram


This diagram describes the controller operating mode:

EIO0000003089 12/2019 49
Controller States and Behaviors

Legend:
 Controller states are indicated in ALL-CAPS BOLD
 User and application commands are indicated in Bold
 System events are indicated in Italics
 Decisions, decision results, and general information are indicated in normal text

(1)
For details on STOPPED to RUNNING state transition, refer to Run Command (see page 61).
(2)
For details on RUNNING to STOPPED state transition, refer to Stop Command (see page 61).

Note 1
The Power Cycle (Power Interruption followed by a Power ON) deletes all output forcing settings.
Refer to Controller State and Output Behavior (see page 58) for further details.

Note 2
The outputs will assume their hardware initialization values.

Note 3
In some cases, when a system error is detected, it will cause the controller to reboot automatically
into the EMPTY state as if no Boot application were present in the Flash memory. However, the
Boot application is not deleted from the Flash memory. In this case, the ERR LED (Red) flashes
regularly.

Note 4
After verification of a valid Boot application the following events occur:
 The application is loaded into RAM.
 The Post Configuration (see page 215) file settings (if any) are applied.

During the load of the boot application, a Check context test occurs to assure that the Remanent
variables are valid. If the Check context test is invalid, the boot application will load but the
controller will assume STOPPED state (see page 64).

Note 5a
The Starting Mode is set in the PLC settings tab of the Controller Device Editor (see page 75).

Note 5b
Not applicable

Note 6
During a successful application download the following events occur:
 The application is loaded directly into RAM.
 By default, the Boot application is created and saved into the Flash memory.

50 EIO0000003089 12/2019
Controller States and Behaviors

Note 7
The default behavior after downloading an application program is for the controller to enter the
STOPPED state irrespective of the switch position or the last controller state before the download.
However, there are 2 considerations in this regard:
Online Change: An online change (partial download) initiated while the controller is in the
RUNNING state returns the controller to the RUNNING state if successful and provided the
Run/Stop switch is set to Run. Before using the Login with online change option, test the
changes to your application program in a virtual or non-production environment and confirm that
the controller and attached equipment assume their expected conditions in the RUNNING state.

WARNING
UNINTENDED EQUIPMENT OPERATION
Always verify that online changes to a RUNNING application program operate as expected
before downloading them to controllers.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: Online changes to your program are not automatically written to the Boot application,
and will be overwritten by the existing Boot application at the next reboot. If you wish your
changes to persist through a reboot, manually update the Boot application by selecting Create
boot application in the online menu (the controller must be in the STOPPED state to achieve
this operation).
Multiple Download: EcoStruxure Machine Expert has a feature that allows you to perform a full
application download to multiple targets on your network or fieldbus. One of the default options
when you select the Multiple Download... command is the Start all applications after download
or online change option, which restarts all download targets in the RUNNING state, irrespective
of their last controller state before the multiple download was initiated. Deselect this option if you
do not want all targeted controllers to restart in the RUNNING state. In addition, before using
the Multiple Download option, test the changes to your application program in a virtual or non-
production environment and confirm that the targeted controllers and attached equipment
assume their expected conditions in the RUNNING state.

WARNING
UNINTENDED EQUIPMENT OPERATION
Always verify that your application program will operate as expected for all targeted controllers
and equipment before issuing the "Multiple Download..." command with the "Start all
applications after download or online change" option selected.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003089 12/2019 51
Controller States and Behaviors

NOTE: During a multiple download, unlike a normal download, EcoStruxure Machine Expert
does not offer the option to create a Boot application. You can manually create a Boot
application at any time by selecting Create boot application in the Online menu on all targeted
controllers.

Note 8
The EcoStruxure Machine Expert software platform allows many powerful options for managing
task execution and output conditions while the controller is in the STOPPED or HALT states. Refer
to Controller States Description (see page 53) for further details.

Note 9
To exit the HALT state it is necessary to issue one of the Reset commands (Reset Warm, Reset
Cold, Reset Origin), download an application or cycle power.
In case of non-recoverable event (hardware watchdog or internal error), a cycle power is
mandatory.

Note 10
The RUNNING state has 2 exception conditions:
 RUNNING with External Error: this exception condition is indicated by the I/O LED, which
displays solid Red. You may exit this state by clearing the external error (probably changing the
application configuration). No controller commands are required, but may however include the
need of a power cycle of the controller. For more information, refer to I/O Configuration General
Description (see page 82).
 RUNNING with Breakpoint: this exception condition is indicated by the RUN LED, which
displays a single flash. Refer to Controller States Description (see page 53) for further details.

Note 11
The boot application can be different from the application loaded. It can happen when the boot
application was downloaded through SD card, FTP, or file transfer or when an online change was
performed without creating the boot application.

52 EIO0000003089 12/2019
Controller States and Behaviors

Section 7.2
Controller States Description

Controller States Description

Controller States Description

Introduction
This section provides a detailed description of the controller states.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Never assume that your controller is in a certain controller state before commanding a change
of state, configuring your controller options, uploading a program, or modifying the physical
configuration of the controller and its connected equipment.
 Before performing any of these operations, consider the effect on all connected equipment.
 Before acting on a controller, always positively confirm the controller state by viewing its LEDs,
verifying the presence of output forcing, and reviewing the controller status information via
EcoStruxure Machine Expert.(1)
Failure to follow these instructions can result in death, serious injury, or equipment damage.

(1)
The controller states can be read in the PLC_R.i_wStatus system variable of the M251
PLCSystem library (see Modicon M251 Logic Controller, System Functions and Variables,
PLCSystem Library Guide)

EIO0000003089 12/2019 53
Controller States and Behaviors

Controller States Table


The following table describes the controller states:

Controller State Description LED


RUN ERR I/O
(Green) (Red) (Red)
BOOTING The controller executes the boot firmware and its own OFF OFF ON
internal self-tests. It then checks the checksum of the OFF ON ON
firmware and user applications.
OFF ON OFF
INVALID_OS There is not a valid firmware file present in the flash OFF Regular OFF
memory. The controller does not execute the application. flash
Refer to the Firmware Upgrade section to restore a correct
state.
EMPTY The controller has no application. OFF Single OFF
flash
EMPTY after a This state is the same as the normal EMPTY state. But the OFF Fast OFF
system error application is present, and is intentionally not loaded. A next flash
detected reboot (power cycle), or a new application download, will
restore correct state.
RUNNING The controller is executing a valid application. ON OFF OFF
RUNNING with This state is same as the RUNNING state with the following Single OFF OFF
breakpoint exceptions: flash
 The task-processing portion of the program does not
resume until the breakpoint is cleared.
 The LED indications are different.
 For more information on breakpoint management, refer
to EcoStruxure Machine Expert Programming Guide.
RUNNING with Configuration, TM3, SD card, or other I/O error detected. ON OFF ON
external error When I/O LED is ON, the details about the detected error
detected can be found in PLC_R.i_lwSystemFault_1 and
PLC_R.i_lwSystemFault_2. Any of the detected error
conditions reported by these variables cause the I/O LED to
be ON.
STOPPED The controller has a valid application that is stopped. See Regular OFF OFF
details of the STOPPED state (see page 55) for an flash
explanation of the behavior of outputs and field buses in this
state.
STOPPED with Configuration, TM3, SD card, or other I/O error detected. Regular OFF ON
external error flash
detected

54 EIO0000003089 12/2019
Controller States and Behaviors

Controller State Description LED


RUN ERR I/O
(Green) (Red) (Red)
HALT The controller stops executing the application because it Regular ON –
has detected an application error flash
Boot Application The controller has an application in memory that differs from ON or Single OFF
not saved the application in Flash memory. At next power cycle, the regular flash
application will be changed by the one from Flash memory. flash

This figure shows the difference between the regular flash and single flash:

Details of the STOPPED State


The following statements are true for the STOPPED state:
 Ethernet, Serial (Modbus, ASCII, and so on), and USB communication services remain
operational and commands written by these services can continue to affect the application, the
controller state, and the memory variables.
 All outputs initially assume their configured default state (Keep current values or Set all outputs
to default) or the state dictated by output forcing if used. The subsequent state of the outputs
depends on the value of the Update IO while in stop setting and on commands received from
remote devices.
Task and I/O Behavior When Update IO While In Stop Is Selected
When the Update IO while in stop setting is selected:
 The Read Inputs operation continues normally. The physical inputs are read and then written
to the %I input memory variables.
 The Task Processing operation is not executed.
 The Write Outputs operation continues. The %Q output memory variables are updated to
reflect either the Keep current values configuration or the Set all outputs to default
configuration, adjusted for any output forcing, and then written to the physical outputs.

EIO0000003089 12/2019 55
Controller States and Behaviors

CAN Behavior When Update IO While In Stop Is Selected


The following is true for the CAN buses when the Update IO while in stop setting is selected:
 The CAN bus remains fully operational. Devices on the CAN bus continue to perceive the
presence of a functional CAN Master.
 TPDO and RPDO continue to be exchanged.
 The optional SDO, if configured, continue to be exchanged.
 The Heartbeat and Node Guarding functions, if configured, continue to operate.
 If the Behaviour for outputs in Stop field is set to Keep current values, the TPDOs continue
to be issued with the last actual values.
 If the Behaviour for outputs in Stop field is Set all outputs to default the last actual values are
updated to the default values and subsequent TPDOs are issued with these default values.
Task and I/O Behavior When Update IO While In Stop Is Not Selected
When the Update IO while in stop setting is not selected, the controller sets the I/O to either the
Keep current values or Set all outputs to default condition (as adjusted for output forcing if used).
After this, the following becomes true:
 The Read Inputs operation ceases. The %I input memory variables are frozen at their last
values.
 The Task Processing operation is not executed.
 The Write Outputs operation ceases. The %Q output memory variables can be updated via
the Ethernet, Serial, and USB connections. However, the physical outputs are unaffected
and retain the state specified by the configuration options.
CAN Behavior When Update IO While In Stop Is Not Selected
The following is true for the CAN buses when the Update IO while in stop setting is not selected:
 The CAN Master ceases communications. Devices on the CAN bus assume their configured
fallback states.
 TPDO and RPDO exchanges cease.
 Optional SDO, if configured, exchanges cease.
 The Heartbeat and Node Guarding functions, if configured, stop.
 The current or default values, as appropriate, are written to the TPDOs and sent once before
stopping the CAN Master.

56 EIO0000003089 12/2019
Controller States and Behaviors

Section 7.3
State Transitions and System Events

State Transitions and System Events

Overview
This section begins with an explanation of the output states possible for the controller. It then
presents the system commands used to transition between controller states and the system events
that can also affect these states. It concludes with an explanation of the Remanent variables, and
the circumstances under which different variables and data types are retained through state
transitions.

What Is in This Section?


This section contains the following topics:
Topic Page
Controller States and Output Behavior 58
Commanding State Transitions 61
Error Detection, Types, and Management 67
Remanent Variables 68

EIO0000003089 12/2019 57
Controller States and Behaviors

Controller States and Output Behavior

Introduction
The Modicon M251 Logic Controller defines output behavior in response to commands and system
events in a way that allows for greater flexibility. An understanding of this behavior is necessary
before discussing the commands and events that affect controller states. For example, typical
controllers define only two options for output behavior in stop: fallback to default value or keep
current value.
The possible output behaviors and the controller states to which they apply are:
 Managed by Application Program
 Keep current values
 Set all outputs to default
 Hardware Initialization Values
 Software Initialization Values
 Output Forcing

Managed by Application Program


Your application program manages outputs normally. This applies in the RUNNING and RUNNING
with External Error Detected states.
NOTE: An exception to this is if the RUNNING with External Error Detected state has been
provoked by a I/O expansion bus error. For more information, refer to I/O Configuration General
Description (see page 82).

Keep Current Values


Select this option by choosing Controller Editor → PLC settings → Behavior for outputs in Stop →
Keep current values. To access the Controller Editor, right-click on the controller in the device tree
and select Edit Object.
This output behavior applies in the STOPPED controller state. It also applies to CAN bus in the
HALT controller state. Outputs are set to and maintained in their current state, although the details
of the output behavior vary greatly depending on the setting of the Update I/O while in stop option
and the actions commanded via configured fieldbusses. Refer to Controller States Description
(see page 53) for more details on these variations.

58 EIO0000003089 12/2019
Controller States and Behaviors

Set All Outputs to Default


Select this option by choosing Controller Editor → PLC settings → Behavior for outputs in Stop →
Set all outputs to default. To access the Controller Editor, right-click on the controller in the device
tree and select Edit Object.
This output behavior applies:
 when the controller is going from RUN state to STOPPED state.
 if the controller is going from RUN state to HALT state.
 after application download.
 after reset warm/cold command.
 after a reboot.

It also applies to CAN bus in the HALT controller state. Outputs are set to and maintained in their
current state, although the details of the output behavior vary greatly depending on the setting of
the Update I/O while in stop option and the actions commanded via configured fieldbusses.Refer
to Controller States Description (see page 53) for more details on these variations.

Hardware Initialization Values


This output state applies in the BOOTING, EMPTY (following power cycle with no boot application
or after the detection of a system error), and INVALID_OS states.
In the initialization state, analog, transistor, and relay outputs assume the following values:
 For an analog output: Z (high impedance)
 For a fast transistor output: Z (high impedance)
 For a regular transistor output: 0 Vdc
 For a relay output: Open

Software Initialization Values


This output state applies when downloading or when resetting the application. It applies at the end
of the download or at the end of a reset warm or cold.
The software Initialization Values are the initialization values of outputs images (%I, %Q, or
variables mapped on %I or %Q).
By default, they are set to 0 but it is possible to map the I/O in a GVL and assign to the outputs a
value different than 0.

EIO0000003089 12/2019 59
Controller States and Behaviors

Output Forcing
The controller allows you to force the state of selected outputs to a defined value for the purposes
of system testing, commissioning, and maintenance.
You are only able to force the value of an output while your controller is connected to EcoStruxure
Machine Expert.
To do so, use the Force values command in the Debug menu.
Output forcing overrides all other commands (except write immediate) to an output irrespective of
the task programming that is being executed.
When you logout of EcoStruxure Machine Expert when output forcing has been defined, you are
presented with the option to retain output forcing settings. If you select this option, the output
forcing continues to control the state of the selected outputs until you download an application or
use one of the Reset commands.
When the option Update I/O while in stop, if supported by your controller, is checked (default state),
the forced outputs keep the forcing value even when the logic controller is in STOP.

Output Forcing Considerations


The output you wish to force must be contained in a task that is currently being executed by the
controller. Forcing outputs in unexecuted tasks, or in tasks whose execution is delayed either by
priorities or events has no effect on the output. However, once the task that had been delayed is
executed, the forcing takes effect at that time.
Depending on task execution, the forcing could impact your application in ways that may not be
obvious to you. For example, an event task could turn on an output. Later, you may attempt to turn
off that output but the event is not being triggered at the time. This would have the effect of the
forcing being apparently ignored. Further, at a later time, the event could trigger the task at which
point the forcing would take effect.

WARNING
UNINTENDED EQUIPMENT OPERATION
 You must have a thorough understanding of how forcing will affect the outputs relative to the
tasks being executed.
 Do not attempt to force I/O that is contained in tasks that you are not certain will be executed
in a timely manner, unless your intent is for the forcing to take affect at the next execution of
the task whenever that may be.
 If you force an output and there is no apparent affect on the physical output, do not exit
EcoStruxure Machine Expert without removing the forcing.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

60 EIO0000003089 12/2019
Controller States and Behaviors

Commanding State Transitions

Run Command
Effect: Commands a transition to the RUNNING controller state.
Starting Conditions: BOOTING or STOPPED state.
Methods for Issuing a Run Command:
 Run/Stop switch goes from stop to run.
 EcoStruxure Machine Expert Online Menu: Select the Start command.
 RUN command from Web Server
 By an external call via Modbus request using the PLC_W.q_wPLCControl and
PLC_W.q_uiOpenPLCControl system variables of the M251 PLCSystem library (see Modicon
M251 Logic Controller, System Functions and Variables, PLCSystem Library Guide).
 Login with online change option: An online change (partial download) initiated while the
controller is in the RUNNING state returns the controller to the RUNNING state if successful.
 Multiple Download Command: sets the controllers into the RUNNING state if the Start all
applications after download or online change option is selected, irrespective of whether the
targeted controllers were initially in the RUNNING, STOPPED, HALT, or EMPTY state.
 The controller is restarted into the RUNNING state automatically under certain conditions.

Refer to Controller State Diagram (see page 49) for further details.

Stop Command
Effect: Commands a transition to the STOPPED controller state.
Starting Conditions: BOOTING, EMPTY, or RUNNING state.
Methods for Issuing a Stop Command:
 Run/Stop switch goes from run to stop.
 EcoStruxure Machine Expert Online Menu: Select the Stop command.
 STOP command from WebServer
 By an internal call by the application or an external call via Modbus request using the PLC_W.
q_wPLCControl and PLC_W. q_uiOpenPLCControl system variables of the M251 PLCSystem
library (see Modicon M251 Logic Controller, System Functions and Variables, PLCSystem
Library Guide).
 Login with online change option: An online change (partial download) initiated while the
controller is in the STOPPED state returns the controller to the STOPPED state if successful.
 Download Command: implicitly sets the controller into the STOPPED state.
 Multiple Download Command: sets the controllers into the STOPPED state if the Start all
applications after download or online change option is not selected, irrespective of whether the
targeted controllers were initially in the RUNNING, STOPPED, HALT, or EMPTY state.

EIO0000003089 12/2019 61
Controller States and Behaviors

 REBOOT by Script: The file transfer script on an SD card can issue a REBOOT as its final
command. The controller is rebooted into the STOPPED state provided the other conditions of
the boot sequence allow this to occur. Refer to Reboot (see page 64) for further details.
 The controller is restarted into the STOPPED state automatically under certain conditions.
Refer to Controller State Diagram (see page 49) for further details.

Reset Warm
Effect: Resets all variables, except for the remanent variables, to their default values. Places the
controller into the STOPPED state.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Warm Command:
 EcoStruxure Machine Expert Online Menu: Select the Reset warm command.
 By an internal call by the application or an external call via Modbus request using the PLC_W.
q_wPLCControl and PLC_W. q_uiOpenPLCControl system variables of the M251 PLCSystem
library (see Modicon M251 Logic Controller, System Functions and Variables, PLCSystem
Library Guide).
Effects of the Reset Warm Command:
1. The application stops.
2. Forcing is erased.
3. Diagnostic indications for errors are reset.
4. The values of the retain variables are maintained.
5. The values of the retain-persistent variables are maintained.
6. All non-located and non-remanent variables are reset to their initialization values.
7. The values of the first 1000 %MW registers are maintained.
8. The values of %MW1000 to %MW59999 registers are reset to 0.
9. All fieldbus communications are stopped and then restarted after the reset is complete.
10.All inputs are reset to their initialization values. All outputs are reset to their software initialization
values or their default values if no software initialization values are defined.
11.The Post Configuration file is read (see page 215).
For details on variables, refer to Remanent Variables (see page 68).

Reset Cold
Effect: Resets all variables, except for the retain-persistent type of remanent variables, to their
initialization values. Places the controller into the STOPPED state.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Cold Command:
 EcoStruxure Machine Expert Online Menu: Select the Reset cold command.
 By an internal call by the application or an external call via Modbus request using the PLC_W.
q_wPLCControl and PLC_W. q_uiOpenPLCControl system variables of the M251 PLCSystem
library (see Modicon M251 Logic Controller, System Functions and Variables, PLCSystem
Library Guide).

62 EIO0000003089 12/2019
Controller States and Behaviors

Effects of the Reset Cold Command:


1. The application stops.
2. Forcing is erased.
3. Diagnostic indications for errors are reset.
4. The values of the retain variables are reset to their initialization value.
5. The values of the retain-persistent variables are maintained.
6. All non-located and non-remanent variables are reset to their initialization values.
7. The values of the first 1000 %MW registers are maintained.
8. The values of %MW1000 to %MW59999 registers are reset to 0.
9. All fieldbus communications are stopped and then restarted after the reset is complete.
10.All inputs are reset to their initialization values. All outputs are reset to their software initialization
values or their default values if no software initialization values are defined.
11.The Post Configuration file is read (see page 215).
For details on variables, refer to Remanent Variables (see page 68).

Reset Origin
Effect: Resets all variables, including the remanent variables, to their initialization values. Erases
all user files on the controller. Places the controller into the EMPTY state.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Origin Command:
 EcoStruxure Machine Expert Online Menu: Select the Reset origin command.
Effects of the Reset Origin Command:
1. The application stops.
2. Forcing is erased.
3. The web visu files are erased.
4. All user files (Boot application, data logging, Post Configuration) are erased.
5. Diagnostic indications for errors are reset.
6. The values of the retain variables are reset.
7. The values of the retain-persistent variables are reset.
8. All non-located and non-remanent variables are reset.
9. The values of the first 1000 %MW registers are reset to 0.
10.The values of %MW1000 to %MW59999 registers are reset to 0.
11.All fieldbus communications are stopped.
12.All other inputs are reset to their initialization values.
All other outputs are reset to their hardware initialization values.
For details on variables, refer to Remanent Variables (see page 68).

EIO0000003089 12/2019 63
Controller States and Behaviors

Reboot
Effect: Commands a reboot of the controller.
Starting Conditions: Any state.
Methods for Issuing the Reboot Command:
 Power cycle
 REBOOT by Script (see page 229)

Effects of the Reboot:


1. The state of the controller depends on a number of conditions:
a. The controller state is RUNNING if:
The Reboot was provoked by a power cycle and:
- the Starting Mode is set to Start in run, and if the Run/Stop input is not configured, and if
the controller was not in HALT state before the power cycle, and if the remanent variables
are valid.
- the Starting Mode is set to Start in run, and if the Run/Stop input is configured and set to
RUN, and if the controller was not in HALT state before the power cycle, and if the remanent
variables are valid.
- the Starting Mode is set to Start as previous state, and Controller state was RUNNING
before the power cycle, and if the Run/Stop input is set to not configured and the boot
application has not changed and the remanent variables are valid.
- the Starting Mode is set to Start as previous state, and Controller state was RUNNING
before the power cycle, and if the Run/Stop input is configured and is set to RUN.
The Reboot was provoked by a script and:
- the Starting Mode is set to Start in run, and if the Run/Stop input or switch is configured and
set to RUN, and if the controller was not in HALT state before the power cycle, and if the
remanent variables are valid.
b. The controller state is STOPPED if:
The Reboot was provoked by a power cycle and:
- the Starting Mode is set to Start in stop.
- the Starting Mode is set to Start as previous state and the controller state was not
RUNNING before the power cycle.
- the Starting Mode is set to Start as previous state and the controller state was RUNNING
before the power cycle, and if the Run/Stop input is set to not configured, and if the boot
application has changed.
- the Starting Mode is set to Start as previous state and the controller state was RUNNING
before the power cycle, and if the Run/Stop input is set to not configured, and if the boot
application has not changed, and if the remanent variables are not valid.
- the Starting Mode is set to Start as previous state and the controller state was RUNNING
before the power cycle, and if the Run/Stop input is configured and is set to STOP.
- the Starting Mode is set to Start in run and if the controller state was HALT before the power
cycle.
- the Starting Mode is set to Start in run, and if the controller state was not HALT before the
power cycle, and if the Run/Stop input is configured and is set to STOP.
- the Starting Mode is set to Start as previous state and if the Run/Stop input or switch is
configured and set to RUN, and if the controller was not in HALT state before the power cycle.

64 EIO0000003089 12/2019
Controller States and Behaviors

- the Starting Mode is set to Start as previous state and if the Run/Stop input or switch is not
configured, and if the controller was not in HALT state before the power cycle.
c. The controller state is EMPTY if:
- There is no boot application or the boot application is invalid, or
- The reboot was provoked by specific System Errors.
d. The controller state is INVALID_OS if there is no valid firmware.
2. Forcing is maintained if the boot application is loaded successfully. If not, forcing is erased.
3. Diagnostic indications for errors are reset.
4. The values of the retain variables are restored if saved context is valid.
5. The values of the retain-persistent variables are restored if saved context is valid.
6. All non-located and non-remanent variables are reset to their initialization values.
7. The values of the first 1000 %MW registers are restored if saved context is valid.
8. The values of %MW1000 to %MW59999 registers are reset to 0.
9. All fieldbus communications are stopped and restarted after the boot application is loaded
successfully.
10.All inputs are reset to their initialization values. All outputs are reset to their hardware
initialization values and then to their software initialization values or their default values if no
software initialization values are defined.
11.The Post Configuration file is read (see page 215).
12.The controller file system is initialized and its resources (sockets, file handles, and so on) are
deallocated.
The file system employed by the controller needs to be periodically re-established by a power
cycle of the controller. If you do not perform regular maintenance of your machine, or if you are
using an Uninterruptible Power Supply (UPS), you must force a power cycle (removal and
reapplication of power) to the controller at least once a year.

NOTICE
DEGRADATION OF PERFORMANCE
Reboot your controller at least once a year by removing and then reapplying power.
Failure to follow these instructions can result in equipment damage.

For details on variables, refer to Remanent Variables (see page 68).


NOTE: The Check context test concludes that the context is valid when the application and the
remanent variables are the same as defined in the Boot application.
NOTE: If you make an online change to your application program while your controller is in the
RUNNING or STOPPED state but do not manually update your Boot application, the controller
detects a difference in context at the next reboot, the remanent variables are reset as per a Reset
cold command, and the controller enters the STOPPED state.

EIO0000003089 12/2019 65
Controller States and Behaviors

Download Application
Effect: Loads your application executable into the RAM memory. Optionally, creates a Boot
application in the Flash memory.
Starting Conditions: RUNNING, STOPPED, HALT, and EMPTY states.
Methods for Issuing the Download Application Command:
 EcoStruxure Machine Expert:
2 options exist for downloading a full application:
 Download command.
 Multiple Download command.

For important information on the application download commands, refer to Controller State
Diagram.
 FTP: Load Boot application file to the Flash memory using FTP. The updated file is applied at
the next reboot.
 SD card: Load Boot application file using an SD card in the controller SD card slot. The updated
file is applied at the next reboot. Refer to File Transfer with SD Card (see page 235) for further
details.
Effects of the EcoStruxure Machine Expert Download Command:
1. The existing application stops and then is erased.
2. If valid, the new application is loaded and the controller assumes a STOPPED state.
3. Forcing is erased.
4. Diagnostic indications for errors are reset.
5. The values of the retain variables are reset to their initialization values.
6. The values of any existing retain-persistent variables are maintained.
7. All non-located and non-remanent variables are reset to their initialization values.
8. The values of the first 1000 %MW registers are maintained.
9. The values of %MW1000 to %MW59999 registers are reset to 0.
10.All fieldbus communications are stopped and then any configured fieldbus of the new
application is started after the download is complete.
11.All inputs are reset to their initialization values. All outputs are reset to their hardware
initialization values and then to their software initialization values or their default values if no
software initialization values are defined, after the download is complete.
12.The Post Configuration file is read (see page 215).
For details on variables, refer to Remanent Variables (see page 68).
Effects of the FTP or SD Card Download Command:
There are no effects until the next reboot. At the next reboot, the effects are the same as a reboot
with an invalid context. Refer to Reboot (see page 64).

66 EIO0000003089 12/2019
Controller States and Behaviors

Error Detection, Types, and Management

Error Management
The controller detects and manages three types of errors:
 External errors
 Application errors
 System errors

This table describes the types of errors that may be detected:

Type of Error Description Resulting Controller


Detected State
External Error External errors are detected by the system while RUNNING or RUNNING with
STOPPED but do not affect the ongoing controller state. An External Error
external error is detected in the following cases: Detected
 A connected device reports an error to the controller. Or
 The controller detects an error with an external device, for STOPPED with
example, when the external device is communicating but External Error
not properly configured for use with the controller. Detected
 The controller detects an error with an output.
 The controller detects a communication interruption with a
device.
 The controller is configured for an expansion module that is
not present or not detected, and has not otherwise been
declared as an optional module(1).
 The boot application in Flash memory is not the same as the
one in RAM.
Application Error An application error is detected when improper programming is HALT
encountered or when a task watchdog threshold is exceeded.

System Error A system error is detected when the controller enters a BOOTING → EMPTY
condition that cannot be managed during runtime. Most such
conditions result from firmware or hardware exceptions, but
there are some cases when incorrect programming can result
in the detection of a system error, for example, when
attempting to write to memory that was reserved during
runtime, or when a system watchdog occurs.
NOTE: There are some system errors that can be managed by
runtime and are therefore treated like application errors.
(1) Expansion modules may appear to be absent for any number of reasons, even if the absent I/O module
is physically present on the bus. For more information, refer to I/O Configuration General Description
(see page 82).

NOTE: Refer to the M251 PLCSystem library Guide for more detailed information on diagnostics.

EIO0000003089 12/2019 67
Controller States and Behaviors

Remanent Variables

Overview
Remanent variables can either be reinitialized or retain their values in the event of power outages,
reboots, resets, and application program downloads. There are multiple types of remanent
variables, declared individually as retain or persistent, or in combination as retain-persistent.
NOTE: For this controller, variables declared as persistent behave in the same way as variables
declared as retain-persistent.
This table describes the behavior of remanent variables in each case:

Action VAR VAR RETAIN VAR GLOBAL RETAIN


PERSISTENT
Online change to application program X X X
Online change modifying the boot – X X
application (1)
Stop X X X
Power cycle – X X
Reset warm – X(2) X
Reset cold – – X
Reset origin – – –

Download of application program (3) – – X


X The value is maintained.
– The value is reinitialized.
(1) Retain variable values are maintained if an online change modifies only the code part of the boot
application (for example, a:=a+1; => a:=a+2;). In all other cases, retain variables are reinitialized.
(2) For more details on VAR RETAIN, refer to Effects of the Reset warm Command (see page 62).
(3) If the application is downloaded using an SD card, any existing retain-persistent variables used by the
application are reinitialized. If the application is downloaded using EcoStruxure Machine Expert, however,
existing retain-persistent variables maintain their values. In both cases, if the downloaded application
contains the same retain-persistent variables as the existing application, the existing retain variables
maintain their values.

NOTE: The first 1000 %MW are automatically retained and persistent if no variable is associated to
them. Their values are kept after a reboot / Reset warm / Reset cold. The other %MW are managed
as VAR.
For example, if you have in your program:
VAR myVariable AT %MW0 : WORD; END_VAR
%MW0 behaves like myVariable (not retained and not persistent).

68 EIO0000003089 12/2019
Controller States and Behaviors

Adding Retain-Persistent Variables


Declare retain-persistent (VAR GLOBAL PERSISTENT RETAIN) symbols in the PersistentVars
window:

Step Action
1 In the Applications tree, select the Application node.
2 Click the right mouse button.
3 Choose Add Objects → Persistent variables
4 Click Add.
Result: The PersistentVars window is displayed.

Retain and Persistent Variables: Performance Impact


Retain or retain-persistent variables are located in a dedicated non-volatile memory. Each time
these variables are accessed during Programming Organization Unit (POU) execution, the non-
volatile memory is accessed. The access time of these variables is slower than the access time of
regular variables, which can impact performance. This is an important fact to take into account
when writing performance-sensitive POUs.

EIO0000003089 12/2019 69
Controller States and Behaviors

70 EIO0000003089 12/2019
Modicon M251 Logic Controller
Controller Device Editor
EIO0000003089 12/2019

Chapter 8
Controller Device Editor

Controller Device Editor

Introduction
This chapter describes how to configure the controller.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Controller Parameters 72
Communication Settings 74
PLC Settings 75
Services 77
Users Rights 79

EIO0000003089 12/2019 71
Controller Device Editor

Controller Parameters

Controller Parameters
To open the device editor, double-click MyController in the Devices tree:

Tabs Description

Tab Description Restriction


Communication Manages the connection between the PC and the controller: Online mode
Settings  helping you find a controller in a network, only
(see page 74)  presenting the list of available controllers, so you can connect to
the selected controller and manage the application in the
controller,
 helping you physically identify the controller from the device
editor,
 helping you change the communication settings of the controller.

The controller list is detected through NetManage or through the


Active Path based on the communication settings. To access the
Communication settings, click Project → Project Settings... in the
menu bar. For more information, refer to the EcoStruxure Machine
Expert Programming Guide (Communication Settings).
Applications Presents the application running on the controller and allows Online mode
removing the application from the controller. only
Files (see page 30) File management between the PC and the controller. Online mode
Only one logic controller disk at a time can be seen through this tab. only
When an SD card is inserted, this file displays the content of the SD
card. Otherwise, this tab displays the content of the /usr directory of
the internal flash memory of the controller.
Log View the controller log file. Online mode
only
PLC settings Configuration of: –
(see page 75)  application name
 I/O behavior in stop
 bus cycle options

Services Lets you configure the online services of the controller (RTC, device Online mode
(see page 77) identification). only

72 EIO0000003089 12/2019
Controller Device Editor

Tab Description Restriction


I/O Mapping Mapping of the input and output channels of an I/O device on project –
(application) variables.
Task deployment Displays a list of I/Os and their assignments to tasks. After
compilation
only
Users and Groups The Users and Groups tab is provided for devices supporting online –
user management. It allows setting up users and access-rights
groups and assigning them access rights to control the access on
EcoStruxure Machine Expert projects and devices in online mode.
For more details, refer to the EcoStruxure Machine Expert
Programming Guide.
OPC UA Server Displays the OPC UA Server Configuration (see page 207) window. –
Configuration
Access Rights The Access Rights tab is provided for devices supporting online user –
management. It serves to grant or deny the currently defined user
groups certain permissions, thus defining the access rights for users
on files or objects (for example, an application) on the controller
during runtime.
For more details, refer to the EcoStruxure Machine Expert
Programming Guide.
Status No information delivered. –
Information Displays general information about the device (name, description, –
provider, version, image).

EIO0000003089 12/2019 73
Controller Device Editor

Communication Settings

Introduction
This tab allows you to manage the connection from the PC to the controller:
 Helping you find a controller in a network.
 Presenting the list of controllers, so you can connect to the selected controller and manage the
application inside the controller.
 Helping you physically identify the controller from the device editor.
 Helping you change the communication settings of the controller.

You can change the display mode of the Communication Settings tab:
 Simple mode. Refer to EcoStruxure Machine Expert, Programming Guide.
 Classic mode. Refer to EcoStruxure Machine Expert, Programming Guide.
 Controller selection mode. Refer to EcoStruxure Machine Expert, Programming Guide.

Edit Communication Settings


In Controller selection mode, the Edit communication settings window lets you change the Ethernet
communication settings. To do so, click Communication Settings tab. The list of controllers
available in the network appears. Select and right-click the required row and click Edit
communication settings ... in the context menu.
You can configure the Ethernet settings in the Edit communication settings window in 2 ways:
 Without the Save settings permanently option:
Configure the communication parameters and click OK. These settings are immediately taken
into account and are not kept if the controller is reset. For the next resets, the communication
parameters configured into the application are taken into account.
 With the Save settings permanently option:
You can also activate the Save settings permanently option before you click OK. Once this
option is activated, the Ethernet parameters configured here are always taken into account on
reset instead of the Ethernet parameters configured into the EcoStruxure Machine Expert
application.
For more information on the Communication Settings view of the device editor, refer to the
EcoStruxure Machine Expert Programming Guide.

74 EIO0000003089 12/2019
Controller Device Editor

PLC Settings

Overview
The figure below presents the PLC Settings tab:

Element Description
Application for I/O handling By default, set to Application because there is only one application in the
controller.
PLC settings Update IO while in If this option is activated (default), the values of the input and output channels
stop get also updated when the controller is stopped.
Behavior for outputs From the selection list, choose one of the following options to configure how the
in Stop values at the output channels should be handled in case of controller stop:
 Keep current values
 Set all outputs to default

Always update By default, set to Enabled 1 (use bus cycle task if not used in task) and not
variables editable.

EIO0000003089 12/2019 75
Controller Device Editor

Element Description
Bus cycle Bus cycle task This configuration setting is the parent for all Bus cycle task parameters used
options in the application device tree.
Some devices with cyclic calls, such as a CANopen manager, can be attached
to a specific task. In the device, when this setting is set to Use parent bus cycle
setting, the setting set for the controller is used.
The selection list offers all tasks currently defined in the active application. The
default setting is the MAST task.
NOTE: <unspecified> means that the task is in "slowest cyclic task" mode.
Additional Generate force Not used.
settings variables for IO
mapping
Enable Diagnosis for Not used.
devices
Show I/O warnings Not used.
as errors
Starting mode Starting mode This option defines the starting mode on a power-on. For further information,
Options refer to State behavior diagram (see page 49).
Select with this option one of these starting modes:
 Start as previous state
 Start in stop
 Start in run

76 EIO0000003089 12/2019
Controller Device Editor

Services

Services Tab
The Services tab is divided in three parts:
 RTC Configuration
 Device Identification
 Post Configuration

The figure below shows the Services tab:

NOTE: To have controller information, you must be connected to the controller.

EIO0000003089 12/2019 77
Controller Device Editor

Element Description
RTC PLC Time Displays the date and time read from the controller when the Read
Configuration button is clicked, with no conversion applied. This read-only field is
initially empty. If Write as UTC is selected, PLC Time is in UTC.
Read Reads the date and time saved on the controller and displays the
values in the PLC Time field.
Local Time Lets you define a date and a time that are sent to the controller
when the Write button is clicked. If necessary, modify the default
values before clicking the Write button. A message box informs
you about the result of the command. The date and time fields are
initially filled with the current PC settings.
Write Writes the date and time defined in the Local time field to the logic
controller. A message box informs you of the result of the
command. Select the Write as UTC checkbox before running this
command to write the values in UTC format.
Synchronize with Lets you directly send the PC settings. A message box informs you
local date/time of the result of the command. Select Write as UTC before running
this command to use UTC format. Use UTC time when using
secure communication.
Device Identification Displays the Firmware Version, the Boot Version, and the
Coprocessor Version of the selected controller, if connected.
Post Configuration Displays the application parameters overwritten by the Post
configuration (see page 215).

78 EIO0000003089 12/2019
Controller Device Editor

Users Rights

Introduction
Users and Groups and Access Right tabs (see page 72) allows to manage user accounts, user
access rights groups and the associated access rights, to control the access on projects. For more
informations, refer to the EcoStruxure Machine Expert Programming Guide.

Login and passwords


Login and password are set by default. They must be activated and can be reset as origin.
This table describes how to log in:

Server/feature First connection User rights Connection after reset


Login / Password Login / Password to default
Login / Password
EcoStruxure Machine Expert Administrator / Administrator / Administrator /
Administrator configured password Administrator
HTTP No login possible Administrator / No login possible
configured password
FTP No login possible Administrator / No login possible
configured password
OPC-UA No login possible Administrator / No login possible
configured password
Change Device Name feature No login possible Administrator / No login possible
configured password

WARNING
UNAUTHORIZED DATA AND/OR APPLICATION ACCESS
 Secure access to the FTP/Web/OPC-UA server(s) using User Rights.
 If you disable User Rights, disable the server(s) to prevent any unwanted or unauthorized
access to your application and/or data.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: Anonymous login can be restored by removing the user rights in the User Management
page (see page 118) of the web server.
NOTE: Password should not contain any of the following special characters: “ !”#$%&’()*+,-
./:;<=>?@[\]^_‘{|}~”.

EIO0000003089 12/2019 79
Controller Device Editor

Default users and groups


One user and two groups are set by default:
 User: Administrator
 Groups: Administrator and Everyone

Access Rights
You can give Access Rights to groups.
You can allow the following operations through the access rights:
 VIEW
 MODIFY
 EXECUTE
 ADD_REMOVE

Troubleshooting
The only way to gain access to a controller that has user access-rights enabled and for which you
do not have the password(s) is by performing an Update Firmware operation. This clearing of User
Rights can only be accomplished by using a SD card or USB key (depending on the support of your
particular controller) to update the controller firmware. In addition, you may clear the User Rights
in the controller by running a script (for more information, refer to EcoStruxure Machine Expert
Programming Guide) . This effectively removes the existing application from the controller
memory, but restores the ability to access the Controller.

80 EIO0000003089 12/2019
Modicon M251 Logic Controller
Expansion Modules Configuration
EIO0000003089 12/2019

Chapter 9
Expansion Modules Configuration

Expansion Modules Configuration

Overview
This chapter describes how to configure the TM4, TM3, and TM2 expansion modules for the
Modicon M251 Logic Controller.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
TM3 I/O Configuration General Description 82
TM3 I/O Bus Configuration 87
TM4 Expansion Module Configuration 88
TM3/TM2 Expansion Module Configuration 89
Optional I/O Expansion Modules 90

EIO0000003089 12/2019 81
Expansion Modules Configuration

TM3 I/O Configuration General Description

Introduction
In your project, you can add I/O expansion modules to your M251 Logic Controller to increase the
number of digital and analog inputs and outputs to the controller.
You can add either TM3 or TM2 I/O expansion modules to the logic controller, and further expand
the number of I/O via TM3 transmitter and receiver modules to create remote I/O configurations.
Special rules apply in all cases when creating local and remote I/O expansions, and when mixing
TM2 and TM3 I/O expansion modules (refer to Maximum Hardware Configuration (see Modicon
M251 Logic Controller, Hardware Guide)).
The I/O expansion bus of the M251 Logic Controller is created when you assemble the I/O
expansion modules to the logic controller. I/O expansion modules are considered as external
devices in the logic controller architecture and, as such, are treated differently than the embedded
I/Os of the logic controller.

I/O Expansion Bus Errors


If the logic controller cannot communicate with one or more I/O expansion modules contained in
the program configuration, and those modules are not configured as optional modules (refer to
Optional I/O Expansion Modules (see page 90)), the logic controller considers it as an I/O
expansion bus error. The unsuccessful communication may be detected during the startup of the
logic controller or during runtime, and there may be any number of causes. Causes of
communication exceptions on the I/O expansion bus include, among other things, disconnection
of or physically missing I/O modules, electromagnetic radiation beyond published environmental
specifications, or otherwise inoperative modules.
If an I/O expansion bus error is detected:
 The system status LED I/O of the logic controller is illuminated indicating an I/O error.
 When EcoStruxure Machine Expert is in online mode, a red triangle appears next to the TM3
expansion module or modules in error and next to the IO_Bus node on the Devices tree window:

82 EIO0000003089 12/2019
Expansion Modules Configuration

The following diagnostic information is also available:


 Bit 0 and bit 1 of the PLC_R.i_lwSystemFault_1 system variable are set to 0.
 The PLC_R.i_wIOStatus1 and PLC_R.i_wIOStatus2 system variables are set to
PLC_R_IO_BUS_ERROR.
 The TM3_MODULE_R[i].i_wModuleState system variable, where [i] identifies the TM3
expansion module in error, is set to TM3_BUS_ERROR.
 The TM3_GetModuleBusStatus function block returns the TM3_ERR_BUS error code.

Refer to PLC_R (see Modicon M251 Logic Controller, System Functions and Variables,
PLCSystem Library Guide) and TM3_MODULE_R (see Modicon M251 Logic Controller, System
Functions and Variables, PLCSystem Library Guide) structures for details on system variables.

Active I/O Expansion Bus Error Handling


The TM3_BUS_W.q_wIOBusErrPassiv system variable is set to ERR_ACTIVE by default to
specify the use of active I/O error handling. The application can set this bit to ERR_PASSIVE to use
passive I/O error handling instead.
By default, when the logic controller detects a TM3 module in bus communication error it sets the
bus to a "bus off" condition whereby the TM3 expansion module outputs, the input image value and
the output image value are set to 0. A TM3 expansion module is considered to be in bus
communication error when an I/O exchange with the expansion module has been unsuccessful for
at least two consecutive bus task cycles. When a bus communication error occurs, the
TM3_MODULE_R[i].i_wModuleState system variable, where [i] is the expansion module
number in error, is set to TM3_BUS_ERROR. All other bits are set to TM3_OK.
Normal I/O expansion bus operation can only be restored after eliminating the source of the error
and performing one of the following:
 Power cycle
 New application download
 Restarting the I/O Bus by setting the TM3_BUS_W.q_wIOBusRestart system variable to 1.
The bus is restarted if at least one expansion module is in error
(TM3_MODULE_R[i].i_wModuleState = TM3_BUS_ERROR). Refer to Restarting the I/O
Expansion Bus (see page 85).
 Issuing a Reset Warm or Reset Cold command with EcoStruxure Machine Expert
(see page 61).

EIO0000003089 12/2019 83
Expansion Modules Configuration

Passive I/O Expansion Bus Handling


The application can set the system variable TM3_BUS_W.q_wIOBusErrPassiv to
ERR_PASSIVE to use passive I/O error handling. This error handling is provided to afford
compatibility with previous firmware versions.
When passive I/O error handling is in use, the logic controller attempts to continue data bus
exchanges with the modules during bus communication errors. While the expansion bus error
persists, the logic controller attempts to re-establish communication on the bus with incommuni-
cative modules, depending on the type of I/O expansion module:
 For TM3 I/O expansion modules, the value of the I/O channels is maintained (Keep current
values) for approximately 10 seconds while the logic controller attempts to re-establish
communication. If the logic controller cannot re-establish communications within that time, all
affected TM3 I/O expansion outputs are set to 0.
 For TM2 I/O expansion modules that may be part of the configuration, the value of the I/O
channels is maintained indefinitely. That is to say, the outputs of the TM2 I/O expansion
modules are set to “Keep current values” until either power is cycled on the logic controller
system, or you issue a Reset Warm or Reset Cold command with EcoStruxure Machine Expert
(see page 61).
In either case, the logic controller continues to solve logic and, if your controller is so equipped, the
embedded I/O continues to be managed by the application (“managed by application program
(see page 58)”) while it attempts to re-establish communication with the incommunicative I/O
expansion modules. If the communication is successful, the I/O expansion modules resume to be
managed by the application. If communication with the I/O expansion modules is unsuccessful, you
must resolve the reason for the unsuccessful communication, and then cycle power on the logic
controller system, or issue a Reset Warm or Reset Cold command with EcoStruxure Machine
Expert (see page 61).
The value of the incommunicative I/O expansion modules input image is maintained and the output
image value is set by the application.
Further, if the incommunicative I/O module(s) disturb the communication with unaffected modules,
the unaffected modules are also considered to be in error and the
TM3_MODULE_R[i].i_wModuleState system variable (where [i] is the expansion module
number) is set to TM3_BUS_ERROR. However, with the ongoing data exchanges that characterize
the Passive I/O Expansion Bus Error Handling, the unaffected modules apply the data sent, and
do not apply the fallback values as for the incommunicative module.

84 EIO0000003089 12/2019
Expansion Modules Configuration

Therefore, you must monitor within your application the state of the bus and the error state of the
module(s) on the bus, and take the appropriate action necessary given your particular application.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Include in your risk assessment the possibility of unsuccessful communication between the
logic controller and any I/O expansion modules.
 If the “Keep current values” option deployed during an I/O expansion module external error is
incompatible with your application, use alternate means to control your application for such an
event.
 Monitor the state of the I/O expansion bus using the dedicated system variables and take
appropriate actions as determined by your risk assessment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

For more information on the actions taken upon startup of the logic controller when an I/O
expansion bus error is detected, refer to Controller States Description (see page 53).

Restarting the I/O Expansion Bus


When active I/O error handling is being applied, that is, embedded and TM3 outputs set to 0 when
a bus communication error is detected, the application can request a restart of the I/O expansion
bus while the logic controller is still running (without the need for a Cold Start, Warm Start, power
cycle, or application download).
The TM3_BUS_W. q_wIoBusRestart system variable is available to request restarts of the I/O
expansion bus. The default value of this bit is 0. Provided at least one TM3 expansion module is
in error (TM3_MODULE_R[i].i_wModuleState set to TM3_BUS_ERROR), the application can set
TM3_BUS_W. q_wIoBusRestart to 1 to request a restart of the I/O expansion bus. On detection
of a rising edge of this bit, the logic controller reconfigures and restarts the I/O expansion bus if all
of the following conditions are met:
 The TM3_BUS_W.q_wIOBusErrPassiv system variable is set to ERR_ACTIVE (that is, I/O
expansion bus activity is stopped)
 Bit 0 and bit 1 of the PLC_R.i_lwSystemFault_1 system variable are set to 0 (I/O expansion
bus is in error)
 The TM3_MODULE_R[i].i_wModuleState system variable is set to TM3_BUS_ERROR (at
least one expansion module is in bus communication error)
If the TM3_BUS_W.q_wIoBusRestart system variable is set to 1 and any of the above conditions
is not met, the logic controller takes no action.

EIO0000003089 12/2019 85
Expansion Modules Configuration

Match Software and Hardware Configuration


The I/O that may be embedded in your controller is independent of the I/O that you may have
added in the form of I/O expansion. It is important that the logical I/O configuration within your
program matches the physical I/O configuration of your installation. If you add or remove any
physical I/O to or from the I/O expansion bus or, depending on the controller reference, to or from
the controller (in the form of cartridges), then you must update your application configuration. This
is also true for any field bus devices you may have in your installation. Otherwise, there is the
potential that the expansion bus or field bus no longer function while the embedded I/O that may
be present in your controller continues to operate.

WARNING
UNINTENDED EQUIPMENT OPERATION
Update the configuration of your program each time you add or delete any type of I/O expansions
on your I/O bus, or you add or delete any devices on your field bus.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Presentation of the Optional Feature for I/O Expansion Modules


I/O expansion modules can be marked as optional in the configuration. The Optional module
feature provides a more flexible configuration by the acceptance of the definition of modules that
are not physically attached to the logic controller. Therefore, a single application can support
multiple physical configurations of I/O expansion modules, allowing a greater degree of scalability
without the necessity of maintaining multiple application files for the same application.
You must be fully aware of the implications and impacts of marking I/O modules as optional in your
application, both when those modules are physically absent and present when running your
machine or process. Be sure to include this feature in your risk analysis.

WARNING
UNINTENDED EQUIPMENT OPERATION
Include in your risk analysis each of the variations of I/O configurations that can be realized
marking I/O expansion modules as optional, and in particular the establishment of TM3 Safety
modules (TM3S…) as optional I/O modules, and make a determination whether it is acceptable
as it relates to your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: For more details about this feature, refer to Optional I/O Expansion Modules (see page 90).

86 EIO0000003089 12/2019
Expansion Modules Configuration

TM3 I/O Bus Configuration

Overview
TM3 I/O bus configuration enables you to select the task that drives TM3 physical exchanges. It
can also override the configuration defined in the PLC settings (see page 75) bus cycle task.

Configuring the I/O Bus


Follow these steps to configure the TM3 I/O bus:

Step Description
1 In the Devices tree, double-click IO_Bus.
Result: The IO_Bus editor tab appears:

2 Set the Bus cycle task from the list to either of the following:
 Use parent bus cycle setting (default)
Sets the task for bus exchange as defined in the PLC settings.
 MAST
Sets the Master task for bus exchange irrespective of the task defined in the PLC settings.

EIO0000003089 12/2019 87
Expansion Modules Configuration

TM4 Expansion Module Configuration

Introduction
The Modicon M251 Logic Controller supports the TM4 communication expansion modules.
For further information about the TM4 expansion modules configuration, refer to the TM4
Expansion Modules Configuration Programming Guide.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Adding an Expansion Module


To add an expansion module to your controller, select the expansion module in the Hardware
Catalog, drag it to the Devices tree, and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
 Using the Drag-and-drop Method
 Using the Contextual Menu or Plus Button

88 EIO0000003089 12/2019
Expansion Modules Configuration

TM3/TM2 Expansion Module Configuration

Introduction
The Modicon M251 Logic Controller supports the following expansion modules:
 TM3 expansion modules
 Digital I/O modules
 Analog I/O modules
 Expert I/O modules
 Safety modules
 Transmitter and receiver modules

 TM2 expansion modules


 Digital I/O modules
 Analog I/O modules
 Expert modules
 Communication modules

For further information about the TM3 and TM2 expansion modules configuration, refer to the TM3
Expansion Modules Configuration Programming Guide and TM2 Expansion Modules
Configuration Programming Guide respectively.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Adding an Expansion Module


To add an expansion module to your controller, select the expansion module in the Hardware
Catalog, drag it to the Devices tree, and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
 Using the Drag-and-Drop Method
 Using the Contextual Menu or Plus Button

EIO0000003089 12/2019 89
Expansion Modules Configuration

Optional I/O Expansion Modules

Presentation
I/O expansion modules can be marked as optional in the configuration. The Optional module
feature provides a more flexible configuration by the acceptance of the definition of modules that
are not physically attached to the controller. Therefore, a single application can support multiple
physical configurations of I/O expansion modules, allowing a greater degree of scalability without
the necessity of maintaining multiple application files for the same application.
Without the Optional module feature, when the controller starts up the I/O expansion bus (following
a power cycle, application download or initialization command), it compares the configuration
defined in the application with the physical I/O modules attached to the I/O bus. Among other
diagnostics made, if the controller determines that there are I/O modules defined in the
configuration that are not physically present on the I/O bus, an error is detected and the I/O bus
does not start.
With the Optional module feature, the controller ignores the absent I/O expansion modules that you
have marked as optional, which then allows the controller to start the I/O expansion bus.
The controller starts the I/O expansion bus at configuration time (following a power cycle,
application download, or initialization command) even if optional expansion modules are not
physically connected to the controller.
The following module types can be marked as optional:
 TM3 I/O expansion modules
 TM2 I/O expansion modules

NOTE: TM3 Transmitter/Receiver modules (the TM3XTRA1 and the TM3XREC1) and TMC4
cartridges cannot be marked as optional.
You must be fully aware of the implications and impacts of marking I/O modules as optional in your
application, both when those modules are physically absent and present when running your
machine or process. Be sure to include this feature in your risk analysis.

WARNING
UNINTENDED EQUIPMENT OPERATION
Include in your risk analysis each of the variations of I/O configurations that can be realized
marking I/O expansion modules as optional, and in particular the establishment of TM3 Safety
modules (TM3S…) as optional I/O modules, and make a determination whether it is acceptable
as it relates to your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

90 EIO0000003089 12/2019
Expansion Modules Configuration

Marking an I/O Expansion Module as Optional


To add an expansion module and mark it as optional in the configuration:

Step Action
1 Add the expansion module to your controller .
2 In the Devices tree, double-click the expansion module.
3 Select the I/O Configuration tab.
4 In the Optional module line, select Yes in the Value column:

Shared Internal ID Codes


Controllers and bus couplers identify expansion modules by a simple internal ID code. This ID code
is not specific to each reference, but identifies the logical structure of the expansion module.
Therefore, different references can share the same ID code.
You cannot have two modules with the same internal ID code declared as optional without at least
one mandatory module placed between them.
This table groups the module references sharing the same internal ID code:

Modules sharing the same internal ID code


TM2DDI16DT, TM2DDI16DK
TM2DRA16RT, TM2DDO16UK, TM2DDO16TK
TM2DDI8DT, TM2DAI8DT
TM2DRA8RT, TM2DDO8UT, TM2DDO8TT
TM2DDO32TK, TM2DDO32UK
TM3DI16K, TM3DI16, TM3DI16G
TM3DQ16R, TM3DQ16RG, TM3DQ16T, TM3DQ16TG, TM3DQ16TK, TM3DQ16U, TM3DQ16UG,
TM3DQ16UK
TM3DQ32TK, TM3DQ32UK
TM3DI8, TM3DI8G, TM3DI8A
TM3DQ8R, TM3DQ8RG, TM3DQ8T, TM3DQ8TG, TM3DQ8U, TM3DQ8UG
TM3DM8R, TM3DM8RG
TM3DM24R, TM3DM24RG
TM3SAK6R, TM3SAK6RG

EIO0000003089 12/2019 91
Expansion Modules Configuration

Modules sharing the same internal ID code


TM3SAF5R, TM3SAF5RG
TM3SAC5R, TM3SAC5RG
TM3SAFL5R, TM3SAFL5RG
TM3AI2H, TM3AI2HG
TM3AI4, TM3AI4G
TM3AI8, TM3AI8G
TM3AQ2, TM3AQ2G
TM3AQ4, TM3AQ4G
TM3AM6, TM3AM6G
TM3TM3, TM3TM3G
TM3TI4, TM3TI4G
TM3TI4D, TM3TI4DG
TM3TI8T, TM3TI8TG
TM3XHSC202, TM3XHSC202G

92 EIO0000003089 12/2019
Modicon M251 Logic Controller
Ethernet Configuration
EIO0000003089 12/2019

Chapter 10
Ethernet Configuration

Ethernet Configuration

Introduction
This chapter describes how to configure the Ethernet network interface of the Modicon M251 Logic
Controller.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
10.1 Ethernet Services 94
10.2 Firewall Configuration 157

EIO0000003089 12/2019 93
Ethernet Configuration

Section 10.1
Ethernet Services

Ethernet Services

What Is in This Section?


This section contains the following topics:
Topic Page
Presentation 95
IP Address Configuration 97
Modbus TCP Client/Server 103
Web Server 105
FTP Server 121
FTP Client 122
SNMP 123
Controller as a Target Device on EtherNet/IP 124
Controller as a Slave Device on Modbus TCP 150
Changing the Modbus TCP Port 155

94 EIO0000003089 12/2019
Ethernet Configuration

Presentation

Ethernet Services
The controller supports the following services:
 Modbus TCP Server (see page 103)
 Modbus TCP Client (see page 103)
 Web Server (see page 105)
 FTP Server (see page 121)
 SNMP (see page 123)
 Controller as Target Device On EtherNet/IP (see page 124)
 Controller as Slave Device On Modbus TCP (see page 150)
 IEC VAR ACCESS (see page 96)

TM251MESE Specific Considerations


The TM251MESE has two different Ethernet networks. Each one gets its own and unique IP and
MAC address.
The two Ethernet networks are called Ethernet 1 and Ethernet 2:
 Ethernet 1 is a dual port Ethernet switch dedicated to communication between machines or with
the control network.
 Ethernet 2 is a separate Ethernet port dedicated to device network connections.

For example, you can:


 Connect your PC to the Ethernet 1
 Use a Modbus TCP I/O scanner with the Ethernet 2.

The Network Variables List (NVL) communication works on the:


 Ethernet 1 port.
 Ethernet 2 port only if the Ethernet 1 port has a valid IP address and is connected to a device.

Ethernet Protocols
The controller supports the following protocols:
 IP (Internet Protocol)
 UDP (User Datagram Protocol)
 TCP (Transmission Control Protocol)
 ARP (Address Resolution Protocol)
 ICMP (Internet Control Messaging Protocol)
 IGMP (Internet Group Management Protocol)

EIO0000003089 12/2019 95
Ethernet Configuration

Connections
This table shows the maximum number of connections:

Connection Type Maximum Number of Connections


Modbus Server 8
Modbus Client 8
EtherNet/IP Target 16
FTP Server 4
Web Server 10
Machine Expert Protocol (EcoStruxure Machine 8
Expert software, trace, Web visualization, HMI
devices)

NOTE: When at least one EtherNet/IP target is configured, the total number of connections
(EtherNet/IP plus Modbus TCP) is limited to 16. Only if the Modbus TCP IOScanner is exclusively
used may the total number of slave devices can be up to 64. These maximums are controlled for
at build time.
Each connection based on TCP manages its own set of connections as follows:
1. When a client tries to open a connection that exceeds the poll size, the controller closes the
oldest connection.
2. If all connections are busy (exchange in progress) when a client tries to open a new one, the
new connection is denied.
3. All server connections stay open as long as the controller stays in operational states (RUNNING,
STOPPED, HALT).
4. All server connections are closed when leaving or entering operational states (RUNNING,
STOPPED, HALT), except in case of power outage (because the controller does not have time to
close the connections).
Connections can be closed when the originator of the connection requests to close the connection
it had previously opened.

Services Available
With an Ethernet communication, the IEC VAR ACCESS service is supported by the controller.
With the IEC VAR ACCESS service, data can be exchanged between the controller and an HMI.
The NetWork variables service is also supported by the controller. With the NetWork variables
service, data can be exchanged between controllers.
NOTE: For more information, refer to the EcoStruxure Machine Expert Programming Guide.

96 EIO0000003089 12/2019
Ethernet Configuration

IP Address Configuration

Introduction
There are different ways to assign the IP address to the added Ethernet interface of the controller:
 Address assignment by DHCP server
 Address assignment by BOOTP server
 Fixed IP address
 Post configuration file (see page 215). If a post configuration file exists, this assignment method
has priority over the others.
The IP address can also be changed dynamically through the:
 Communication Settings (see EcoStruxure Machine Expert, Programming Guide) tab in
EcoStruxure Machine Expert
 changeIPAddress function block (see page 245)

NOTE: If the attempted addressing method is unsuccessful, the link uses a default IP address
(see page 100) derived from the MAC address.
Carefully manage the IP addresses because each device on the network requires a unique
address. Having multiple devices with the same IP address can cause unintended operation of
your network and associated equipment.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Verify that there is only one master controller configured on the network or remote link.
 Verify that all devices have unique addresses.
 Obtain your IP address from your system administrator.
 Confirm that the IP address of the device is unique before placing the system into service.
 Do not assign the same IP address to any other equipment on the network.
 Update the IP address after cloning any application that includes Ethernet communications to
a unique address.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: Verify that your system administrator maintains a record of assigned IP addresses on the
network and subnetwork, and inform the system administrator of any configuration changes
performed.

EIO0000003089 12/2019 97
Ethernet Configuration

Address Management
This diagram shows the different types of address systems for the controller:

NOTE: If a device programmed to use the DHCP or BOOTP addressing methods is unable to
contact its respective server, the controller uses the default IP address. It repeats its request
constantly.
The IP process restarts in the following cases:
 Controller reboot
 Ethernet cable reconnection
 Application download (if IP parameters change)
 DHCP or BOOTP server detected after a prior addressing attempt was unsuccessful.

98 EIO0000003089 12/2019
Ethernet Configuration

Ethernet Configuration
In the Devices tree, double-click Ethernet_1:

Note: If you are in online mode, you see the two windows. You cannot edit them. If you are in offline mode,
you see the Configured Parameters window. You can edit it.

This table describes the configured parameters:

Configured Parameters Description


Network Name Used as device name to retrieve IP address through
DHCP, maximum 15 characters.
IP Address by DHCP IP address is obtained by DHCP server.
IP Address by BOOTP IP address is obtained by BOOTP server.
Fixed IP Address IP address, Subnet Mask, and Gateway Address are
defined by the user.

EIO0000003089 12/2019 99
Ethernet Configuration

Configured Parameters Description


Ethernet Protocol Protocol type used (Ethernet 2 or IEEE 802.3)
NOTE: If you change the Ethernet Protocol, a power cycle
is required before it will be recognized by the controller.
Transfer Rate Speed and Duplex are in auto-negotiation mode.

Default IP Address
The default IP addresses are:
 10.11.x.x. for Ethernet_1
 10.10.x.x. for Ethernet_2 (only available on TM251MESE)

NOTE: The two IP addresses must not be in the same IP network.


The last two fields in the default IP address are composed of the decimal equivalent of the last two
hexadecimal bytes of the MAC address of the port.
The MAC address of the port can be retrieved on the label placed on the front side of the controller.
The default subnet mask is Default Class A Subnet Mask of 255.0.0.0.
NOTE: A MAC address is written in hexadecimal format and an IP address in decimal format.
Convert the MAC address to decimal format.
Example: If the MAC address is 00.80.F4.01.80.F2, the default IP address is 10.10.128.242.

Address Classes
The IP address is linked:
 to a device (the host)
 to the network to which the device is connected

An IP address is always coded using 4 bytes.


The distribution of these bytes between the network address and the device address may vary.This
distribution is defined by the address classes.
The different IP address classes are defined in this table:

Address Class Byte1 Byte 2 Byte 3 Byte 4


Class A 0 Network ID Host ID
Class B 1 0 Network ID Host ID
Class C 1 1 0 Network ID Host ID
Class D 1 1 1 0 Multicast Address
Class E 1 1 1 1 0 Address reserved for subsequent use

100 EIO0000003089 12/2019


Ethernet Configuration

Subnet Mask
The subnet mask is used to address several physical networks with a single network address. The
mask is used to separate the subnetwork and the device address in the host ID.
The subnet address is obtained by retaining the bits of the IP address that correspond to the
positions of the mask containing 1, and replacing the others with 0.
Conversely, the subnet address of the host device is obtained by retaining the bits of the IP
address that correspond to the positions of the mask containing 0, and replacing the others with 1.
Example of a subnet address:

IP address 192 (11000000) 1 (00000001) 17 (00010001) 11 (00001011)


Subnet mask 255 (11111111) 255 (11111111) 240 (11110000) 0 (00000000)
Subnet address 192 (11000000) 1 (00000001) 16 (00010000) 0 (00000000)

NOTE: The device does not communicate on its subnetwork when there is no gateway.

Gateway Address
The gateway allows a message to be routed to a device that is not on the current network.
If there is no gateway, the gateway address is 0.0.0.0.
The gateway address must be defined on Ethernet_1 interface. The traffic to unknown networks is
sent through this interface.

Security Parameters
This table describes the different security parameters:

Security Parameters Description Default settings


Discovery protocol This parameter deactivates Discovery protocol. When deactivated, Active
Discovery requests are ignored.
FTP Server This parameter deactivates the FTP Server of the controller. When Inactive
deactivated, FTP requests are ignored.
Machine Expert This parameter deactivates the Machine Expert protocol on Ethernet Active
protocol interfaces. When deactivated, every Machine Expert request from
every device is rejected, , including those from the UDP or TCP
connection. Therefore, no connection is possible on Ethernet from a
PC with EcoStruxure Machine Expert, from an HMI target that wants to
exchange variables with this controller, from an OPC server, or from
Controller Assistant.
Modbus Server This parameter deactivates the Modbus Server of the controller. When Inactive
deactivated, every Modbus request to the controller is ignored.

EIO0000003089 12/2019 101


Ethernet Configuration

Security Parameters Description Default settings


IP Forwarding This parameter deactivates the IP forwarding service of the controller. Inactive
When deactivated, devices on the device network are no longer
accessible from the control network (Web pages, DTM, and so on).
NOTE: This parameter is only available on the Ethernet_1 network.
SNMP protocol This parameter deactivates the SNMP server of the controller. When Inactive
deactivated, SNMP requests are ignored.
Web Server (HTTP) This parameter deactivates the Web Server of the controller. When Active
deactivated, HTTP requests to the controller Web Server are ignored.
WebVisualisation This parameter deactivates the Web visualization pages of the Inactive
protocol controller. When deactivated, HTTP requests to the logic controller
WebVisualisation protocol are ignored.

Slave Device Identification


When DHCP Server active is selected, devices added to the fieldbus can be configured to be
identified by their name or MAC address, instead of their IP address. Refer to DHCP Server
(see page 174).
NOTE: This parameter is only available on the Ethernet_2 network.

102 EIO0000003089 12/2019


Ethernet Configuration

Modbus TCP Client/Server

Introduction
Unlike Modbus serial link, Modbus TCP is not based on a hierarchical structure, but on a
client/server model.
The Modicon M251 Logic Controller implements both client and server services so that it can
initiate communications to other controllers and I/O devices, and to respond to requests from other
controllers, SCADA, HMIs, and other devices. By default, Modbus Server functionality is not active.
Without any configuration, the embedded Ethernet port of the controller supports Modbus server.
The Modbus client/server is included in the firmware and does not require any programming action
from the user. Due to this feature, it is accessible in RUNNING, STOPPED and EMPTY states.

Modbus TCP Client


The Modbus TCP client supports the following function blocks from the PLCCommunication library
without any configuration:
 ADDM
 READ_VAR
 SEND_RECV_MSG
 SINGLE_WRITE
 WRITE_READ_VAR
 WRITE_VAR

For further information, refer to the Function Block Descriptions (see EcoStruxure Machine Expert,
Modbus and ASCII Read/Write Functions, PLCCommunication Library Guide).

EIO0000003089 12/2019 103


Ethernet Configuration

Modbus TCP Server


The Modbus server supports the Modbus requests:

Function Code Subfunction Function


Dec (Hex) Dec (Hex)
1 (1) – Read digital outputs (%Q)
2 (2) – Read digital inputs (%I)
3 (3) – Read holding register (%MW)
6 (6) – Write single register (%MW)
8 (8) – Diagnostic
15 (F) – Write multiple digital outputs (%Q)
16 (10) – Write multiple registers (%MW)
23 (17) – Read/write multiple registers (%MW)
43 (2B) 14 (E) Read device identification

NOTE: The embedded Modbus server only ensures time-consistency for a single word (2 bytes).
If your application requires time-consistency for more than 1 word, add and configure
(see page 150) a Modbus TCP Slave Device so that the contents of the %IW and %QW buffers are
time-consistent in the associated IEC task (MAST by default).

104 EIO0000003089 12/2019


Ethernet Configuration

Web Server

Introduction
As standard equipment, the controller provides an embedded Web server with a predefined, built-
in website. You can use the pages of the website for module setup and control as well as
application diagnostics and monitoring. These pages are ready to use with a Web browser. No
configuration or programming is required.
The Web server can be accessed by the web browsers listed below:
 Google Chrome (version 30.0 or greater)
 Mozilla Firefox (version 1.5 or greater)

The Web server is limited to 10 TCP connections (see page 96).


NOTE: The Web server can be disabled by unchecking the Web Server active parameter in the
Ethernet Configuration tab (see page 99).
The Web server is a tool for reading and writing data, and controlling the state of the controller, with
full access to all data in your application. However, if there are security concerns over these
functions, you must at a minimum assign a secure password to the Web Server or disable the Web
server to prevent unauthorized access to the application. By enabling the Web server, you enable
these functions.
The Web server allows you to monitor a controller and its application remotely, to perform various
maintenance activities including modifications to data and configuration parameters, and change
the state of the controller. Care must be taken to ensure that the immediate physical environment
of the machine and process is in a state that will not present safety risks to people or property
before exercising control remotely.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Define a secure password for the Web Server and do not allow unauthorized or otherwise
unqualified personnel to use this feature.
 Ensure that there is a local, competent, and qualified observer present when operating on the
controller from a remote location.
 You must have a complete understanding of the application and the machine/process it is
controlling before attempting to adjust data, stopping an application that is operating, or
starting the controller remotely.
 Take the precautions necessary to assure that you are operating on the intended controller by
having clear, identifying documentation within the controller application and its remote
connection.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003089 12/2019 105


Ethernet Configuration

NOTE: The Web server must only be used by authorized and qualified personnel. A qualified
person is one who has the skills and knowledge related to the construction and operation of the
machine and the process controlled by the application and its installation, and has received safety
training to recognize and avoid the hazards involved. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this feature.

Web Server Access


Access to the Web server is controlled by User Rights when they are enabled in the controller. For
more information, refer to Users and Groups Tab Description (see page 72).
To access the Web server you must first connect to the controller with EcoStruxure Machine Expert
or Controller Assistant and modify the default user password.

WARNING
UNAUTHORIZED DATA ACCESS
 Secure access to the FTP/Web server using User Rights.
 If you disable User Rights, disable the FTP/Web server to prevent any unwanted or
unauthorized access to data in your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

In order to change the password, go to Users and Groups tab of the device editor. For more
information, refer to the EcoStruxure Machine Expert Programming Guide (see SoMachine,
Programming Guide).
NOTE: The only way to gain access to a controller that has user access-rights enabled and for
which you do not have the password(s) is by performing an Update Firmware operation. This
clearing of User Rights can only be accomplished by using a SD card or USB key (depending on
the support of your particular controller) to update the controller firmware. In addition, you may
clear the User Rights in the controller by running a script (for more information, refer to EcoStruxure
Machine Expert Programming Guide (see SoMachine, Programming Guide)) . This effectively
removes the existing application from the controller memory, but restores the ability to access the
Controller.

106 EIO0000003089 12/2019


Ethernet Configuration

Home Page Access


To access the website home page, type in your navigator the IP address of the controller.
This figure shows the Web Server site login page:

This figure shows the home page of the Web Server site once you have logged in:

EIO0000003089 12/2019 107


Ethernet Configuration

NOTE: Schneider Electric adheres to industry best practices in the development and implemen-
tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict
access to authorized personnel and protocols only.

WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
 Evaluate whether your environment or your machines are connected to your critical
infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
 Limit the number of devices connected to a network to the minimum necessary.
 Isolate your industrial network from other networks inside your company.
 Protect any network against unintended access by using firewalls, VPN, or other, proven
security measures.
 Monitor activities within your systems.
 Prevent subject devices from direct access or direct link by unauthorized parties or unauthen-
ticated actions.
 Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Monitoring: Data Parameters


Monitoring Web Server Variables
To monitor Web server variables, you must add a Web Data Configuration object to your project.
Within this object, you can select all variables you want to monitor.
This table describes how to add a Web Data Configuration object:

Step Action
1 Right click the Application node in the Applications tree tab.
2 Click Add Object → Web Data Configuration....
Result: The Add Web Data Configuration window is displayed.
3 Click Add.
Result: The Web Data Configuration object is created and the Web Data Configuration
editor is open.
NOTE: As a Web Data Configuration object is unique for a controller, its name cannot be
changed.

108 EIO0000003089 12/2019


Ethernet Configuration

Web Data Configuration Editor


Click the Refresh button to be able to select variables, this action will display all the variables
defined in the application.

EIO0000003089 12/2019 109


Ethernet Configuration

Select the variables you want to monitor in the web server:

NOTE: The variable selection is possible only in offline mode.

110 EIO0000003089 12/2019


Ethernet Configuration

Monitoring: Data Parameters Submenu


The Data Parameters submenu allows you to create and monitor some lists of variables. You can
create several lists of variables (maximum 10 lists), each one containing several variables of the
controller application (maximum 20 variables per list).
Each list has a name, and a refresh period. The lists are saved in the Flash memory of the
controller, so that a created list can be accessed (loaded, modified, saved) from any Web client
application accessing this controller.
The Data Parameters submenu allows you to display and modify variable values:

Element Description
Add Adds a list description or a variable
Del Deletes a list description or a variable
Refresh period Refreshing period of the variables contained in the list description (in ms)
Refresh Enables I/O refreshing:
 Gray button: refreshing disabled
 Orange button: refreshing enabled

Load Loads saved lists from the controller internal Flash to the Web server page
Save Saves the selected list description in the controller (/usr/web directory)

NOTE: The IEC objects (%IX, %QX) are not directly accessible. To access IEC objects you must
first group their contents in located registers (refer to Relocation Table (see page 34)).
NOTE: Bit memory variables (%MX) cannot be selected.

EIO0000003089 12/2019 111


Ethernet Configuration

Monitoring: IO Viewer Submenu


The IO Viewer submenu allows you to display and modify the current I/O values:

Element Description
Refresh Enables I/O refreshing:
 Gray button: refreshing disabled
 Orange button: refreshing enabled

1000 ms I/O refreshing period in ms


<< Goes to previous I/O list page
>> Goes to next I/O list page

112 EIO0000003089 12/2019


Ethernet Configuration

Monitoring: Oscilloscope Submenu


The Oscilloscope submenu can display up to 2 variables in the form of a recorder time chart:

Element Description
Reset Erases the memorization
Refresh Starts/stops refreshing
Load Loads parameter configuration of Item0 and Item1
Save Saves parameter configuration of Item0 and Item1 in the controller
Item0 Variable to be displayed
Item1 Variable to be displayed
Min Minimum value of the variable axis
Max Maximum value of the variable axis
Period(ms) Page refresh period in milliseconds

EIO0000003089 12/2019 113


Ethernet Configuration

Diagnostics: Ethernet Submenu


This figure shows the remote ping service:

114 EIO0000003089 12/2019


Ethernet Configuration

Diagnostics: Scanner Status Submenu


The Scanner Status submenu displays status of the Modbus TCP I/O Scanner (IDLE, STOPPED,
OPERATIONAL) and the health bit of up to 64 Modbus slave devices:

For more information, refer to EcoStruxure Machine Expert Modbus TCP User guide.

EIO0000003089 12/2019 115


Ethernet Configuration

Diagnostics: EtherNet/IP Status Submenu


The EtherNet/IP Status submenu displays the status of the EtherNet/IP Scanner (IDLE,
STOPPED, OPERATIONAL) and the health bit of up to 16 EtherNet/IP target devices:

For more information, refer to EcoStruxure Machine Expert EtherNet/IP User guide.

Maintenance Page
The Maintenance page provides access to the controller data for maintenance capabilities.

116 EIO0000003089 12/2019


Ethernet Configuration

Maintenance: Post Conf Submenu


The Post Conf submenu allows you to update the post configuration file (see page 215) saved on
the controller:

Step Action
1 Click Load.
2 Modify the parameters (see page 219).
3 Click Save.
NOTE: The new parameters will be considered at next Post Configuration file reading
(see page 216).

EIO0000003089 12/2019 117


Ethernet Configuration

Maintenance: EIP Config Files Submenu


The file tree only appears when the Ethernet IP service is configured on the controller.
Index of /usr:

File Description
My Machine Controller.gz GZIP file
My Machine Controller.ico Icon file
My Machine Controller.eds Electronic Data Sheet file

Maintenance: User Management Submenu


The User Management submenu displays a screen that allows you to access four different actions,
all restricted by using secure protocol (HTTPS):
 Change password (of current user):
allows you to change your password.

118 EIO0000003089 12/2019


Ethernet Configuration

 User accounts management:


Allows you to manage user accounts management, removing all password and returning all user
accounts on the controller to default settings.

Click Disable to remove all passwords on the controller.


Click OK on the window that appears to confirm. As a result:
 Users no longer have to set and enter a password to connect to the controller.
 FTP, HTTP, and OPC UA Server connections accept anonymous user connections.
 Cloning the controller no longer requires authorization by using the FB_ControlClone function
block.
NOTE: The Disable button is only active if the current user has administrative privileges.
Click Reset to default to return all user accounts on the controller to their default setting state.
Click OK on the window that appears to confirm.
NOTE: Connections to FTP, HTTP, and the OPC UA Server are blocked until a new password is
set.
 Clone management:
allows you to control whether user rights are copied and applied to the target controller when
cloning a controller

Click Exclude users rights to exclude copying user rights to the target controller when cloning a
controller.
NOTE: By default, the users rights are excluded.
Click Include users rights to copy user rights to the target controller when cloning a controller. A
popup prompts you to confirm copying the user rights. Click OK to continue.
NOTE: The Exclude users rights and Include users rights buttons are only active if the current user
is connected to the controller using a secure protocol.

EIO0000003089 12/2019 119


Ethernet Configuration

 System use notification:


allows you to customize a message which will be displayed at login.

120 EIO0000003089 12/2019


Ethernet Configuration

FTP Server

Introduction
Any FTP client installed on a computer that is connected to the controller (Ethernet port), without
EcoStruxure Machine Expert installed, can be used to transfer files to and from the data storage
area of the controller.
NOTE: Schneider Electric adheres to industry best practices in the development and implemen-
tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict
access to authorized personnel and protocols only.

WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
 Evaluate whether your environment or your machines are connected to your critical
infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
 Limit the number of devices connected to a network to the minimum necessary.
 Isolate your industrial network from other networks inside your company.
 Protect any network against unintended access by using firewalls, VPN, or other, proven
security measures.
 Monitor activities within your systems.
 Prevent subject devices from direct access or direct link by unauthorized parties or unauthen-
ticated actions.
 Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: Make use of the security-related commands (see EcoStruxure Machine Expert, Menu
Commands, Online Help) which provide a way to add, edit, and remove a user in the online user
management of the target device where you are currently logged in.
The FTP server is deactivated by default.

Files Access
See File Organization (see page 30).

EIO0000003089 12/2019 121


Ethernet Configuration

FTP Client

Introduction
The FtpRemoteFileHandling library provides the following FTP client functionalities for remote file
handling:
 Reading files
 Writing files
 Deleting files
 Listing content of remote directories
 Adding directories
 Removing directories

NOTE: Schneider Electric adheres to industry best practices in the development and implemen-
tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict
access to authorized personnel and protocols only.

WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
 Evaluate whether your environment or your machines are connected to your critical
infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
 Limit the number of devices connected to a network to the minimum necessary.
 Isolate your industrial network from other networks inside your company.
 Protect any network against unintended access by using firewalls, VPN, or other, proven
security measures.
 Monitor activities within your systems.
 Prevent subject devices from direct access or direct link by unauthorized parties or unauthen-
ticated actions.
 Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

For further information, refer to FtpRemoteFileHandling Library Guide.

122 EIO0000003089 12/2019


Ethernet Configuration

SNMP

Introduction
The Simple Network Management Protocol (SNMP) is used to provide the data and services
required for managing a network.
The data is stored in a Management Information Base (MIB). The SNMP protocol is used to read
or write MIB data. Implementation of the Ethernet SNMP services is minimal, as only the
compulsory objects are handled.

SNMP Server
This table presents the supported standard MIB-2 server objects:

Object Description Access Value


sysDescr Text description of the device Read SCHNEIDER M241-51 Fast
Ethernet TCP/IP
sysName Node administrative name Read/Write Controller reference

The size of these character strings is limited to 50 characters.


The values written are saved to the controller via SNMP client tool software. The Schneider Electric
software for this is ConneXview. ConneXview is not supplied with the controller or bus coupler. For
more details, refer to www.schneider-electric.com.

SNMP Client
The M251 Logic Controller supports an SNMP client library to allow you to query SNMP servers.
For details, refer to the SNMP Library Guide.

EIO0000003089 12/2019 123


Ethernet Configuration

Controller as a Target Device on EtherNet/IP

Introduction
This section describes the configuration of the M251 Logic Controller as an EtherNet/IP target
device.
For further information about EtherNet/IP, refer to the www.odva.org website.

EtherNet/IP Target Configuration


To configure your M251 Logic Controller as an EtherNet/IP target device, you must:

Step Action
1 Select EthernetIP in the Hardware Catalog.
2 Drag and drop it to the Devices tree on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button

EtherNet/IP Parameters Configuration


To configure the EtherNet/IP parameters, double-click Ethernet_1 (Ethernet Network) →
EthernetIP in the Devices tree.
This dialog box is displayed:

124 EIO0000003089 12/2019


Ethernet Configuration

The EtherNet/IP configuration parameters are defined as:


 Instance:
Number referencing the input or output Assembly.
 Size:
Number of channels of an input or output Assembly.
The memory size of each channel is 2 bytes that stores the value of an %IWx or %QWx object,
where x is the channel number.
For example, if the Size of the Output Assembly is 20, it represents that there are 20 input
channels (IW0...IW19) addressing %IWy...%IW(y+20-1), where y is the first available channel
for the Assembly.

Element Admissible Controller EcoStruxure Machine Expert


Range Default Value
Output Assembly Instance 150...189 150
Size 2...120 20
Input Assembly Instance 100...149 100
Size 2...120 20

EDS File Generation


You can generate an EDS file to configure EtherNet/IP cyclic data exchanges.
To generate the EDS file:

Step Action
1 In the Devices tree, right-click the EthernetIP node and choose the Export as EDS command
from the context menu.
2 Modify the default file name and location as required.
3 Click Save.

NOTE: The Major Revision and Minor Revision objects of the EDS file, defined in the file, are used
to ensure uniqueness of the EDS file. The values of these objects do not reflect the actual controller
revision level.
A generic EDS file for the M251 Logic Controller is also available on the Schneider website. You
must adapt this file to your application by editing it and defining the required Assembly instances
and sizes.

EIO0000003089 12/2019 125


Ethernet Configuration

EthernetIP Slave I/O Mapping Tab


Variables can be defined and named in the EthernetIP Slave I/O Mapping tab. Additional
information such as topological addressing is also provided in this tab.

126 EIO0000003089 12/2019


Ethernet Configuration

The table below describes the EthernetIP Slave I/O Mapping configuration:

Channel Type Default Description


Value
Input IW0 WORD - Command word of controller outputs (%QW)
IWxxx
Output QW0 WORD - State of controller inputs (%IW)
QWxxx

The number of words depends on the size parameter configured in EtherNet/IP Target
Configuration (see page 124).
Output means OUTPUT from Originator controller (= %IW for the controller).
Input means INPUT from Originator controller (= %QW for the controller).

Connections on EtherNet/IP
To access a target device, an Originator opens a connection which can include several sessions
that send requests.
One explicit connection uses one session (a session is a TCP or UDP connection).
One I/O connection uses 2 sessions.
The following table shows the EtherNet/IP connections limitations:

Characteristic Maximum
Explicit connections 8 (Class 3)
I/O connections 1 (Class 1)
Connections 8
Sessions 16
Simultaneous requests 32

NOTE: The M251 Logic Controller supports cyclic connections only. If an Originator opens a
connection using a change of state as a trigger, packets are sent at the RPI rate.

EIO0000003089 12/2019 127


Ethernet Configuration

Profile
The controller supports the following objects:

Object class Class ID Cat. Number of Effect on Interface Behavior


(hex) Instances
Identity Object (see page 128) 01 1 1 Supports the reset service
Message Router Object 02 1 1 Explicit message connection
(see page 131)
Assembly Object 04 2 2 Defines I/O data format
(see page 133)
Connection Manager Object 06 1 –
(see page 134)
TCP/IP Interface Object F5 1 1 TCP/IP configuration
(see page 137)
Ethernet Link Object F6 1 1 Counter and status information
(see page 139)
Interface Diagnostic Object 350 1 1 –
(see page 140)
IOScanner Diagnostic Object 351 1 1 –
(see page 144)
Connection Diagnostic Object 352 1 1 –
(see page 145)
Explicit Connection Diagnostic 353 1 1 –
Object (see page 147)
Explicit Connections Diagnostic 354 1 1 –
List Object (see page 148)

Identity Object (Class ID = 01 hex)


The following table describes the class attributes of the Identity Object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 01 Implementation revision of the
Identity Object
2 Get Max Instances UINT 01 The largest instance number
3 Get Number of UINT 01 The number of object instances
Instances
4 Get Optional UINT, UINT [ ] 00 The first 2 bytes contain the
Instance number of optional instance
Attribute List attributes. Each following pair of
bytes represents the number of
other optional instance attributes.

128 EIO0000003089 12/2019


Ethernet Configuration

Attribute ID Access Name Data Type Value Details


(hex) (hex)
6 Get Max Class UINT 07 The largest class attributes value
Attribute
7 Get Max Instance UINT 07 The largest instance attributes
Attribute value

The following table describes the Class Services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all class attributes
0E Get Attribute Single Returns the value of the specified attribute

The following table describes the Instance Services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all class attributes
05 Reset (1) Initializes EtherNet/IP component (controller reboot)
0E Get Attribute Single Returns the value of the specified attribute

(1)
Reset Service description:
When the Identity Object receives a Reset request, it:
 determines whether it can provide the type of reset requested
 responds to the request
 attempts to perform the type of reset requested

The Reset common service has one specific parameter, Type of Reset (USINT), with the following
values:

Value Type of Reset


0 Reboots the controller
NOTE: This is the default value if this parameter is omitted.
1 Not supported
2 Not supported
3...99 Reserved
100...199 Vendor specific
200...255 Reserved

EIO0000003089 12/2019 129


Ethernet Configuration

The following table describes the Instance attributes:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Vendor ID UINT F3 Schneider Automation ID
2 Get Device type UINT 0E Controller
3 Get Product code UINT 1002 Controller product code
4 Get Revision Struct of – Product revision number of the
USINT, controller (1).
USINT Equivalent to the 2 low bytes of the
controller version
5 Get Status WORD – Status word(2)
6 Get Serial number UDINT – Serial number of the controller:
XX + 3 LSB of MAC address
7 Get Product name Struct of – –
USINT,
STRING

(1)
Mapped in a WORD:
 MSB: minor revision (second USINT)
 LSB: major revision (first USINT)
Example: 0205 hex means revision V5.2.
(2) Status word (Attribute 5):

Bit Name Description


0 Owned Unused
1 Reserved –
2 Configured TRUE indicates the device application has been reconfigured.
3 Reserved –
4...7 Extended Device  0: Self-testing or undetermined
Status  1: Firmware update in progress
 2: At least one invalid I/O connection detected
 3: No I/O connections established
 4: Non-volatile configuration invalid
 5: Unrecoverable error detected
 6: At least one I/O connection in RUNNING state
 7: At least one I/O connection established, all in idle mode
 8: Reserved
 9...15: Unused

130 EIO0000003089 12/2019


Ethernet Configuration

Bit Name Description


8 Minor TRUE indicates the device detected an error, which, under most circumstances,
Recoverable is recoverable.
Fault This type of event does not lead to a change in the device state.
9 Minor TRUE indicates the device detected an error, which, under most circumstances,
Unrecoverable is unrecoverable.
Fault This type of event does not lead to a change in the device state.
10 Major TRUE indicates the device detected an error, which requires the device to
Recoverable report an exception and enter into the HALT state.
Fault This type of event leads to a change in the device state, but, under most
circumstances, is recoverable.
11 Major TRUE indicates the device detected an error, which requires the device to
Unrecoverable report an exception and enter into the HALT state.
Fault This type of event leads to a change in the device state, but, under most
circumstances, is not recoverable.
12...15 Reserved –

Message Router Object (Class ID = 02 hex)


The following table describes the class attributes of the Message Router object:

Attribute Access Name Data Type Value Details


ID (hex) (hex)
1 Get Revision UINT 01 Implementation revision number of the
Message Router Object
2 Get Max UINT 02 The largest instance number
Instances
3 Get Number of UINT 01 The number of object instances
Instance
4 Get Optional Struct of UINT, 02 The first 2 bytes contain the number of
Instance UINT [ ] optional instance attributes. Each
Attribute following pair of bytes represents the
List number of other optional instance
attributes (from 100 to 119).
5 Get Optional UINT 0A The number and list of any implemented
Service optional services attribute (0: no optional
List services implemented)
6 Get Max Class UINT 07 The largest class attributes value
Attribute
7 Get Max UINT 02 The largest instance attributes value
Instance
Attribute

EIO0000003089 12/2019 131


Ethernet Configuration

The following table describes the Class services:

Service Code (hex) Name Description


01 Get_Attribute_All Returns the value of all class attributes
0E Get_Attribute_Single Returns the value of the specified attribute

The following table describes the Instance services:

Service Code (hex) Name Description


01 Get_Attribute_All Returns the value of all class attributes
0E Get_Attribute_Single Returns the value of the specified attribute

The following table describes the Instance attributes:

Attribute ID (hex) Access Name Data Type Value Description


1 Get Implemented Object Struct of UINT, – Implemented Object list. The
List UINT [ ] first 2 bytes contain the
number of implemented
objects. Each 2 bytes that
follow represents another
implemented class number.
This list contains the
following objects:
 Identity
 Message Router
 Assembly
 Connection Manager
 Parameter
 File Object
 Modbus
 Port
 TCP/IP
 Ethernet Link

2 Get Number available UINT 512 Maximum number of


concurrent CIP (Class 1 or
Class 3) connections
supported

132 EIO0000003089 12/2019


Ethernet Configuration

Assembly Object (Class ID = 04 hex)


The following table describes the class attributes of the Assembly object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 02 Implementation revision of the
Assembly Object
2 Get Max Instances UINT BE The largest instance number
3 Get Number of Instances UINT 03 The number of object
instances
4 Get Optional Instance Struct of: The first 2 bytes contain the
Attribute List UINT 01 number of optional instance
UINT [ ] 04 attributes. Each following pair
of bytes represents the
number of other optional
instance attributes.
5 Get Optional Service List UINT Not The number and list of any
supported implemented optional services
attribute (0: no optional
services implemented)
6 Get Max Class Attribute UINT 07 The largest class attributes
value
7 Get Max Instance UINT 04 The largest instance attributes
Attribute value

The following table describes the Class Services:

Service Code (hex) Name Description


0E Get Attribute Single Returns the value of the specified attribute

The following table describes the Instance Services:

Service Code (hex) Name Description


0E Get Attribute Single Returns the value of the specified attribute
10 Set Attribute Single Modifies the value of the specified attribute

Instances Supported
Output means OUTPUT from Originator controller (= %IW for the controller).
Input means INPUT from Originator controller (= %QW for the controller).

EIO0000003089 12/2019 133


Ethernet Configuration

The controller supports 2 Assemblies:

Name Instance Data Size


Controller Output (%IW) Configurable: must be between 100 and 149 2...40 words
Controller Input (%QW) Configurable: must be between 150 and 189 2...40 words

NOTE: The Assembly object binds together the attributes of multiple objects so that information to
or from each object can be communicated over a single connection. Assembly objects are static.
The Assemblies in use can be modified through the parameter access of the network configuration
tool (RSNetWorx). The controller needs to recycle power to register a new Assembly assignment.
The following table describes the Instance attributes:

Attribute ID Access Name Data Type Value Description


(hex)
3 Get/Set Instance Data ARRAY of – Data Set service only
Byte available for Controller
output
4 Get Instance Data Size UINT 4...80 Size of data in byte

Access from a EtherNet/IP Scanner


When a EtherNet/IP Scanner needs to exchange assemblies with a M251 Logic Controller, it uses
the following access parameters (Connection path):
 Class 4
 Instance xx where xx is the instance value (example: 2464 hex = instance 100).
 Attribute 3

In addition, a configuration assembly must be defined in the Originator.


For example: Class 4, Instance 3, Attribute 3, the resulting Connection Path will be:
 2004 hex
 2403 hex
 2c<xx> hex

Connection Manager Object (Class ID = 06 hex)


The following table describes the class attributes of the Assembly Object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 01 Implementation revision of the
Connection Manager Object
2 Get Max UINT 01 The largest instance number
Instances

134 EIO0000003089 12/2019


Ethernet Configuration

Attribute ID Access Name Data Type Value Details


(hex) (hex)
3 Get Number of UINT 01 The number of object instances
Instances
4 Get Optional Struct of: – The number and list of the optional
Instance UINT attributes. The first word contains the
Attribute List UINT [ ] number of attributes to follow and each
following word contains another attribute
code.
Following optional attributes include:
 total number of incoming connection
open requests
 the number of requests rejected due to
non-conforming format of the Forward
Open
 the number of requests rejected
because of insufficient resources
 the number of requests rejected due to
parameter value sent with the Forward
Open
 the number of Forward Close requests
received
 the number of Forward Close requests
with an invalid format
 the number of Forward Close requests
that could not be matched to an active
connection
 the number of connections that have
timed out because the other side
stopped producing, or a network
disconnection occurred
6 Get Max Class UINT 07 The largest class attributes value
Attribute
7 Get Max UINT 08 The largest instance attributes value
Instance
Attribute

The following table describes the Class Services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all class attributes
0E Get Attribute Single Returns the value of the specified attribute

EIO0000003089 12/2019 135


Ethernet Configuration

The following table describes the Instance Services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all instance attributes
0E Get Attribute Single Returns the value of the specified attribute
4E Forward Close Closes an existing connection
52 Unconnected Send Sends a multi-hop unconnected request
54 Forward Open Opens a new connection

The following table describes the Instance attributes:

Attribute ID Access Name Data Type Value Description


(hex)
1 Get Open Requests UINT – Number of Forward Open service
requests received
2 Get Open Format Rejects UINT – Number of Forward Open service
requests which were rejected due
to invalid format
3 Get Open Resource ARRAY of – Number of Forward Open service
Rejects Byte requests which were rejected due
to lack of resources
4 Get Open Other Rejects UINT – Number of Forward Open service
requests which were rejected for
reasons other than invalid format
or lack of resources
5 Get Close Requests UINT – Number of Forward Close service
requests received
6 Get Close Format UINT – Number of Forward Close service
Requests requests which were rejected due
to invalid format
7 Get Close Other UINT – Number of Forward Close service
Requests requests which were rejected for
reasons other than invalid format
8 Get Connection Timeouts UINT – Total number of connection
timeouts that have occurred in
connections controlled by this
Connection Manager

136 EIO0000003089 12/2019


Ethernet Configuration

TCP/IP Interface Object (Class ID = F5 hex)


This object maintains link specific counters and status information for an Ethernet 802.3
communications interface.
The following table describes the class attributes of the TCP/IP Interface Object:

Attribute ID Access Name Data Type Value Details


(hex)
1 Get Revision UINT 4 Implementation revision of the
TCP/IP Interface Object
2 Get Max Instances UINT 2 The largest instance number
3 Get Number of Instances UINT 2 The number of object
instances

The following table describes the Class Services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all class attributes
0E Get Attribute Single Returns the value of the specified attribute

Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all instance attributes
0E Get Attribute Single Returns the value of the specified instance attribute

The following table describes the Instance Attributes:

Attribute ID Access Name Data Type Value Description


(hex)
1 Get Status DWORD Bit level  0: The interface configuration
attribute has not been configured.
 1: The interface configuration
contains a valid configuration.
 2...15: Reserved.

EIO0000003089 12/2019 137


Ethernet Configuration

Attribute ID Access Name Data Type Value Description


(hex)
2 Get Configuration DWORD Bit level  0: BOOTP Client
Capability  1: DNS Client
 2: DHCP Client
 5: Configured in EcoStruxure
Machine Expert
All other bits are reserved and set to
0.
3 Get Configuration DWORD Bit level  0: The interface configuration is
valid.
 1: The interface configuration is
obtained with BOOTP.
 2: The interface configuration is
obtained with DHCP.
 3: reserved
 4: DNS Enable

All other bits are reserved and set to


0.
4 Get Physical Link UINT Path size Number of 16 bits word in the
element Path
Padded Path Logical segments identifying the
EPATH physical link object. The path is
restricted to one logical class
segment and one logical instance
segment. The maximum size is
12 bytes.
5 Get Interface UDINT IP Address –
configuration
UDINT Network –
Mask
UDINT Gateway –
Address
UDINT Primary –
Name
UDINT Secondary 0: no secondary name server
Name address has been configured.
STRING Default 0: no Domain Name is configured
Domain
Name
6 Get Host Name STRING – ASCII characters.
0: no host name is configured

138 EIO0000003089 12/2019


Ethernet Configuration

Ethernet Link Object (Class ID = F6 hex)


This object provides the mechanism to configure a TCP/IP network interface device.
The following table describes the class attributes of the Ethernet Link object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 4 Implementation revision of the
Ethernet Link Object
2 Get Max Instances UINT 3 The largest instance number
3 Get Number of Instances UINT 3 The number of object
instances

The following table describes the class services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all class attributes
0E Get Attribute Single Returns the value of the specified attribute

Instance Codes
Only instance 1 is supported.
The following table describes the instance services:

Service Code (hex) Name Description


01 Get Attribute All Returns the value of all instance attributes
0E Get Attribute Single Returns the value of the specified instance attribute

The following table describes the instance attributes:

Attribute ID Access Name Data Type Value Description


(hex)
1 Get Interface Speed UDINT – Speed in Mbit/s (10 or 100)
2 Get Interface Flags DWORD Bit level  0: link status
 1: half/full duplex
 2...4: negotiation status
 5: manual setting / requires
reset
 6: local hardware error detected

All other bits are reserved and set


to 0.

EIO0000003089 12/2019 139


Ethernet Configuration

Attribute ID Access Name Data Type Value Description


(hex)
3 Get Physical ARRAY of – This array contains the MAC
Address 6 USINT address of the product.
Format: XX-XX-XX-XX-XX-XX

EtherNet/IP Interface Diagnostic Object (Class ID = 350 hex)


The following table describes the class attributes of the EtherNet/IP Interface Diagnostic object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 01 Increased by 1 on each new update
of the object
2 Get Max Instance UINT 01 Maximum instance number of the
object

The following table describes the instance attributes of the EtherNet/IP Interface Diagnostic object:

Attribute ID (hex) Access Name Data Type Details


1 Get Protocols supported UINT Protocol(s) supported (0=not
supported, 1=supported):
 Bit 0: EtherNet/IP
 Bit 1: Modbus TCP
 Bit 2: Modbus Serial
 Bits 3...15: Reserved, 0

140 EIO0000003089 12/2019


Ethernet Configuration

Attribute ID (hex) Access Name Data Type Details


2 Get Connection Diag STRUCT of
Max CIP IO UINT Maximum number of CIP I/O
Connections opened connections opened.
Current CIP IO UINT Number of CIP I/O connections
Connections currently opened.
Max CIP Explicit UINT Maximum number of CIP explicit
Connections opened connections opened.
Current CIP Explicit UINT Number of CIP explicit connections
Connections currently opened
CIP Connections UINT Incremented on each unsuccessful
Opening Errors attempt to open a CIP connection.
CIP Connections UINT Incremented when a CIP connection
Timeout Errors times out.
Max EIP TCP UINT Maximum number of TCP
Connections opened connections opened and used for
EtherNet/IP communications.
Current EIP TCP UINT Number of TCP connections
Connections currently open and being used for
EtherNet/IP communications.
3 Get Clear IO Messaging Diag STRUCT of
IO Production Counter UDINT Incremented each time a Class 0/1
CIP message is sent.
IO Consumption UDINT Incremented each time a Class 0/1
Counter CIP message is received.
IO Production Send UINT Incremented each Time a Class 0/1
Errors Counter message is not sent.
IO Consumption UINT Incremented each time a
Receive Errors Counter consumption is received that
contains an error.
4 Get Clear Explicit Messaging Diag STRUCT of
Class3 Msg Send UDINT Incremented each time a Class 3
Counter CIP message is sent.
Class3 Msg Receive UDINT Incremented each time a Class 3
Counter CIP message is received.
UCMM Msg Send UDINT Incremented each time a UCMM
Counter message is sent.
UCMM Msg Receive UDINT Incremented each time a UCMM
Counter message is received.

EIO0000003089 12/2019 141


Ethernet Configuration

Attribute ID (hex) Access Name Data Type Details


5 Get Com Capacity STRUCT of
Max CIP Connections UINT Maximum number of supported CIP
connections.
Max TCP Connections UINT Maximum number of supported TCP
connections.
Max Urgent priority rate UINT Maximum number of CIP transport
class 0/1 Urgent priority message
packets per second.
Max Scheduled priority UINT Maximum number of CIP transport
rate class 0/1 Scheduled priority
message packets per second.
Max High priority rate UINT Maximum number of CIP transport
class 0/1 High priority message
packets per second.
Max Low priority rate UINT Maximum number of CIP transport
class 0/1 Low priority message
packets per second.
Max Explicit Messaging UINT Max CIP transport class 2/3 or other
rate EtherNet/IP messages packets per
second

142 EIO0000003089 12/2019


Ethernet Configuration

Attribute ID (hex) Access Name Data Type Details


6 Get Bandwidth Diag STRUCT of
Current sending Urgent UINT CIP transport class 0/1 Urgent
priority rate priority message packets sent per
second.
Current reception UINT CIP transport class 0/1 Urgent
Urgent priority rate priority message packets received
per second.
Current sending UINT CIP transport class 0/1 Scheduled
Scheduled priority rate priority message packets sent per
second.
Current reception UINT CIP transport class 0/1 Scheduled
Scheduled priority rate priority message packets received
per second.
Current sending High UINT CIP transport class 0/1 High priority
priority rate message packets sent per second.
Current reception High UINT CIP transport class 0/1 High priority
priority rate message packets received per
second.
Current sending Low UINT CIP transport class 0/1 Low priority
priority rate message packets sent per second.
Current reception Low UINT CIP transport class 0/1 Low priority
priority rate message packets received per
second.
Current sending Explicit UINT CIP transport class 2/3 or other
Messaging rate EtherNet/IP message packets sent
per second.
Current reception UINT CIP transport class 2/3 or other
Explicit Messaging rate EtherNet/IP message packets
received per second.
7 Get Modbus Diag STRUCT of
Max. Modbus TCP UINT Maximum number of TCP
Connections opened connections opened and used for
Modbus communications.
Current Modbus TCP UINT Number of TCP connections
Connections currently opened and used for
Modbus communications.
Modbus TCP Msg Send UDINT Incremented each time a Modbus
Counter TCP message is sent.
Modbus TCP Msg UDINT Incremented each time a Modbus
Receive Counter TCP message is received.

EIO0000003089 12/2019 143


Ethernet Configuration

The following table describes the class services:

Service Code (hex) Name Description


01 Get_Attributes_All Returns the value of all class attributes.
0E Get_Attribute_Single Returns the value of a specified attribute.
4C Get_and_Clear Gets and clears a specified attribute.

IOScanner Diagnostic Object (Class ID = 351 hex)


The following table describes the class attributes of the IOScanner Diagnostic object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 1 Increased by 1 on each new update
of the object.
2 Get Max Instance UINT 1 Maximum instance number of the
object.

The following table describes the instance attributes of the IOScanner Diagnostic object:

Attribute ID (hex) Access Name Data Type Details


1 Get IO Status Table STRUCT of
Size UINT Size in bytes of the Status attribute.
Status ARRAY of I/O status. Bit n, where n is instance
UINT n of the object, provides the status
of the I/O exchanged on the I/O
connection:
 0: The input or output status of
the I/O connection is in error, or
no device.
 1: The input or output status of
the I/O connection is correct.

The following table describes the class services:

Service Code (hex) Name Description


01 Get_Attributes_All Returns the value of all class attributes.

144 EIO0000003089 12/2019


Ethernet Configuration

IO Connection Diagnostic Object (Class ID = 352 hex)


The following table describes the class attributes of the IO Connection Diagnostic object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 01 Increased by 1 on each new update
of the object.
2 Get Max Instance UINT 01 Maximum instance number of the
object
0...n
where n is the maximum number of
CIP I/O connections.
NOTE: There is an IO Connection
Diagnostic object instance for both
O->T and T->O paths.

The following table describes the instance attributes of the I/O Connection Diagnostic object:

Attribute ID Access Name Data Type Details


(hex)
1 Get IO Com Diag STRUCT of
Clear
IO Production Counter UDINT Incremented each time a production is
sent.
IO Consumption Counter UDINT Incremented each time a consumption
is received.
IO Production Send Errors UINT Incremented each time a production is
Counter not sent due to an error.
IO Consumption Receive UINT Incremented each time a consumption
Errors Counter is received that contains an error.
CIP Connection TimeOut UINT Incremented each time a connection
Errors times out.
CIP Connection Opening UINT Incremented on each unsuccessful
Errors attempt to open a connection.
CIP Connection State UINT State of the CIP IO connection.
CIP Last Error General UINT General status of the last error detected
Status on the connection.
CIP Last Error Extended UINT Extended status of the last error
Status detected on the connection.
Input Com Status UINT Communication status of the inputs.
Output Com Status UINT Communication status of the outputs.

EIO0000003089 12/2019 145


Ethernet Configuration

Attribute ID Access Name Data Type Details


(hex)
2 Get Connection Diag STRUCT of
Production Connection ID UDINT Connection ID for production.
Consumption Connection UDINT Connection ID for consumption.
ID
Production RPI UDINT Requested Packet Interval (RPI) for
productions, in μs.
Production API UDINT Actual Packet Interval (API) for
productions.
Consumption RPI UDINT RPI for consumptions.
Consumption API UDINT API for consumptions.
Production Connection UDINT Connection parameters for
Parameters productions.
Consumption Connection UDINT Connection parameters for
Parameters consumptions.
Local IP UDINT Local IP address for I/O
communication.
Local UDP Port UINT Local UDP port number for I/O
communication.
Remote IP UDINT Remote IP address for I/O
communication.
Remote UDP Port UINT Remote UDP port number for I/O
communication.
Production Multicast IP UDINT Multicast IP address for productions, or
0 if multicast is not used.
Consumption Multicast IP UDINT Multicast IP address for consumptions,
or 0 if multicast is not used.
Protocols supported UINT Protocol(s) supported (0=not
supported, 1=supported):
 Bit 0: EtherNet/IP
 Bit 1: Modbus TCP
 Bit 2: Modbus Serial
 Bits 3...15: Reserved, 0

146 EIO0000003089 12/2019


Ethernet Configuration

Instance Attributes
The following table describes the class services:

Service Code (hex) Name Description


01 Get_Attributes_All Returns the value of all class attributes.
0E Get_Attribute_Single Returns the value of the specified attribute.
4C Get_and_Clear Gets and clears a specified attribute.

Explicit Connection Diagnostic Object (Class ID = 353 hex)


The following table describes the class attributes of the Explicit Connection Diagnostic object:

Attribute ID Access Name Data Type Value (hex) Details


(hex)
1 Get Revision UINT 01 Increased by 1 at each new update
of the object.
2 Get Max Instance UINT 0...n Maximum instance number of the
(maximum object.
number of
CIP IO
connections)

The following table describes the instance attributes of the Explicit Connection Diagnostic object:

Attribute ID Access Name Data Type Details


(hex)
1 Get Originator UDINT O to T Connection ID
Connection ID
2 Get Originator IP UDINT
3 Get Originator TCP UINT
Port
4 Get Target UDINT T to O Connection ID
Connection ID
5 Get Target IP UDINT
6 Get Target TCP Port UINT
7 Get Msg Send UDINT Incremented each time a Class 3 CIP
Counter Message is sent on the connection
8 Get Msg UDINT Incremented each time a Class 3 CIP
ReceiveCounter Message is received on the connection

EIO0000003089 12/2019 147


Ethernet Configuration

Explicit Connections Diagnostic List Object (Class ID = 354 hex)


The following table describes the class attributes of the Explicit Connections Diagnostic List object:

Attribute ID Access Name Data Type Value Details


(hex) (hex)
1 Get Revision UINT 01 Increased by 1 at each new update
of the object.
2 Get Max Instance UINT 0...n n is the maximum number of
concurrent list accesses
supported.

The following table describes the instance attributes of the Explicit Connections Diagnostic List
object:

Attribute ID (hex) Access Name Data Type Details


1 Get Number of Connections UINT Total number of open Explicit
connections
2 Get Explicit Messaging ARRAY of Contents of instantiated Explicit
Connections Diagnostic STRUCT Connection Diagnostic objects
List
Originator Connection UDINT Originator to Target connection ID
ID
Originator IP UDINT Originator to Target IP address
Originator TCP Port UINT Originator to Target port number
Target Connection ID UDINT Target to Originator connection ID
Target IP UDINT Target to Originator IP address
Target TCP Port UINT Target to Originator port number
Msg Send Counter UDINT Incremented each time a Class 3
CIP message is sent on the
connection
Msg Receive Counter UDINT Incremented each time a Class 3
CIP message is sent on the
connection

148 EIO0000003089 12/2019


Ethernet Configuration

The following table describes the class services:

Service Code (hex) Name Description


08 Create Creates an instance of the Explicit Connections Diagnostic
List object.
09 Delete Deletes an instance of the Explicit Connections Diagnostic
List object.
33 Explicit_Connec- Explicit corrections diagnostic read object.
tions_Diagnostic_Read

EIO0000003089 12/2019 149


Ethernet Configuration

Controller as a Slave Device on Modbus TCP

Overview
This section describes the configuration of the M251 Logic Controller as a Modbus TCP Slave
Device.
The Modbus TCP Slave Device adds another Modbus server function to the controller. This server
is addressed by the Modbus client application by specifying a configured Unit ID (Modbus address)
in the range 1...247. The embedded Modbus server of the slave controller needs no configuration,
and is addressed by specifying a Unit ID equal to 255. Refer to Modbus TCP Configuration
(see page 151).
To configure your M251 Logic Controller as a Modbus TCP Slave Device, you must add Modbus
TCP Slave Device functionality to your controller (see Adding a Modbus TCP Slave Device
thereafter). This functionality creates a specific I/O area in the controller that is accessible with the
Modbus TCP protocol. This I/O area is used whenever an external master needs to access the %IW
and %QW objects of the controller. This Modbus TCP Slave Device functionality allows you to
furnish to this area the controller I/O objects which can then be accessed with a single Modbus
read/write registers request.
Only one Modbus TCP Slave Device at a time can be configured on one of the Ethernet ports of
the M251 Logic Controller (Ethernet_1 or Ethernet_2). Once configured, however, the Modbus
TCP slave device can be addressed through both Ethernet ports.
Inputs/outputs are seen from the slave controller: inputs are written by the master, and outputs are
read by the master.
The Modbus TCP Slave Device can define a privileged Modbus client application, whose
connection is not forcefully closed (embedded Modbus connections may be closed when more
than 8 connections are needed).
The watchdog associated to the privileged connection allows you to verify whether the controller
is being polled by the privileged master. If no Modbus request is received within the timeout
duration, the diagnostic information i_byMasterIpLost is set to 1 (TRUE). For more
information, refer to the Ethernet Port Read-Only System Variables (see Modicon M251 Logic
Controller, System Functions and Variables, PLCSystem Library Guide).
For further information about Modbus TCP, refer to the www.odva.org website.

Adding a Modbus TCP Slave Device


To configure your M251 Logic Controller as a Modbus TCP slave device, you must:

Step Action
1 Select Modbus TCP Slave Device in the Hardware Catalog.
2 Drag and drop it to the Devices tree on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button

150 EIO0000003089 12/2019


Ethernet Configuration

Modbus TCP Configuration


To configure the Modbus TCP slave device, double-click Ethernet_x →
ModbusTCP_Slave_Device in the Devices tree.
This dialog box appears:

Element Description
IP Master Address IP address of the Modbus master
The connections are not closed on this address.
Watchdog Watchdog in 500 ms increments
NOTE: The watchdog applies to the IP master Address unless the address is
0.0.0.0.
Slave Port Modbus communication port (502)
NOTE: The port number can be modified using the changeModbusPort script
command (see page 163).
Unit ID Sends the requests to the Modbus TCP slave device (1...247), instead of to the
embedded Modbus server (255).
Holding Registers (%IW) Number of %IW registers to be used in the exchange (2...120) (each register is
2 bytes)
Input Registers (%QW) Number of %QW registers to be used in the exchange (2...120) (each register
is 2 bytes)

EIO0000003089 12/2019 151


Ethernet Configuration

Modbus TCP Slave Device I/O Mapping Tab


The I/Os are mapped to Modbus registers from the master perspective as follows:
 %IWs are mapped from register 0 to n-1 and are R/W (n = Holding register quantity, each %IW
register is 2 bytes).
 %QWs are mapped from register n to n+m -1 and are read only (m = Input registers quantity,
each %QW register is 2 bytes).
Once a Modbus TCP Slave Device has been configured, Modbus commands sent to its Unit ID
(Modbus address) are handled differently than the same command would be when addressed to
any other Modbus device on the network. For example, when the Modbus command 3 (3 hex) is
sent to a standard Modbus device, it reads and returns the value of one or more registers. When
this same command is sent to the Modbus TCP (see page 103) Slave, it facilitates a read operation
by the external I/O scanner.
Once a Modbus TCP Slave Device has been configured, Modbus commands sent to its Unit ID
(Modbus address) access the %IW and %QW objects of the controller instead of the regular Modbus
words (accessed when the Unit ID is 255). This facilitates read/write operations by a Modbus TCP
IOScanner application.
The Modbus TCP Slave Device responds to a subset of the Modbus commands with the purpose
of exchanging data with the external I/O scanner. The following Modbus commands are supported
by the Modbus TCP slave device:

Function Code Function Comment


Dec (Hex)
3 (3) Read holding register Allows the master to read %IW and %QW objects of the device
6 (6) Write single register Allows the master to write %IW objects of the device
16 (10) Write multiple registers Allows the master to write %IW objects of the device
23 (17) Read/write multiple Allows the master to read %IW and %QW objects of the device
registers and write %IW objects of the device
Other Not supported –

NOTE: Modbus requests that attempt to access registers above n+m-1 are answered by the 02 -
ILLEGAL DATA ADDRESS exception code.

152 EIO0000003089 12/2019


Ethernet Configuration

To link I/O objects to variables, select the Modbus TCP Slave Device I/O Mapping tab:

Channel Type Description


Input IW0 WORD Holding register 0
... ... ...
IWx WORD Holding register x
Output QW0 WORD Input register 0
... ... ...
QWy WORD Input register y

The number of words depends on the Holding Registers (%IW) and Input Registers (%QW)
parameters of the Modbus TCP tab.
NOTE: Output means OUTPUT from Originator controller (= %IW for the controller). Input means
INPUT from Originator controller (= %QW for the controller).
NOTE: The Modbus TCP Slave Device refreshes the %IW and %QW registers as a single time-
consistent unit, synchronized with the IEC tasks (MAST task by default). By contrast, the
embedded Modbus TCP server only ensures time-consistency for 1 word (2 bytes). If your
application requires time-consistency for more than 1 word (2 bytes), use the Modbus TCP Slave
Device.
The parameter Always update variables is set to Enabled 1 (use bus cycle task if not used in any
task) and is not editable.

EIO0000003089 12/2019 153


Ethernet Configuration

Bus Cycle Options


In the Modbus TCP Slave Device I/O Mapping tab, select the Bus cycle task to use:
 Use parent bus cycle setting (the default),
 MAST
 An existing task of the project: you can select an existing task and associate it to the scanner.
For more information about the application tasks, refer to the EcoStruxure Machine Expert
Programming Guide.
NOTE: There is a corresponding Bus cycle task parameter in the I/O mapping editor of the device
that contains the Modbus TCP Slave Device. This parameter defines the task responsible for
refreshing the %IW and %QW registers.

154 EIO0000003089 12/2019


Ethernet Configuration

Changing the Modbus TCP Port

changeModbusPort Command
The changeModbusPort command can be used to change the port used for data exchanges with
a Modbus TCP master.
The current Modbus Slave Port is displayed on the Modbus TCP configuration window
(see page 151).
The default Modbus port number is 502.

Command Description
changeModbusPort “portnum” portnum is the new Modbus port number to use is passed as
a string of characters.
Before running the command, refer to Used Ports
(see page 167) to ensure that portnum is not being used by
any other TCP/UDP protocols or processes.
An error is logged in the /usr/Syslog/FWLog.txt file if the
specified port number is already in use.

To limit the number of open sockets, the changeModbusPort command can only be run twice.
A power cycle of the logic controller returns the Modbus port number to the default value (502).
The changeModbusPort command must therefore be executed after each power cycle.
NOTE: After changing the port number, the Modbus Server Active checkbox on the Ethernet
Configuration window (see page 99) is no longer taken into account, as the Modbus server always
uses port 502.

Running the Command from an SD Card Script

Step Action
1 Create a script file (see page 228), for example:
; Change Modbus slave port
changeModbusPort "1502";
2 Name the script file Script.cmd.
3 Copy the script file to the SD card.
4 Insert the SD card in the controller.

EIO0000003089 12/2019 155


Ethernet Configuration

Running the Command Using ExecuteScript


The changeModbusPort command can be run from within an application using the ExecuteScript
function block.
The following sample code changes the Modbus TCP slave port from the default (502) to 1502.
IF (myBExe = FALSE AND (PortNum <> 502)) THEN

myExecSc( // falling edge for a second change


xExecute:=FALSE ,
sCmd:=myCmd ,
xDone=>myBDone ,
xBusy=> myBBusy,
xError=> myBErr,
eError=> myIerr);
string1 := 'changeModbusPort "';
string2 := WORD_TO_STRING(PortNum);
myCmd := concat(string1,string2);
myCmd := concat(myCmd,'"');
myBExe := TRUE;
END_IF

myExecSc(
xExecute:=myBExe ,
sCmd:=myCmd ,
xDone=>myBDone ,
xBusy=> myBBusy,
xError=> myBErr,
eError=> myIerr);

156 EIO0000003089 12/2019


Ethernet Configuration

Section 10.2
Firewall Configuration

Firewall Configuration

Introduction
This section describes how to configure the firewall of the Modicon M251 Logic Controller.

What Is in This Section?


This section contains the following topics:
Topic Page
Introduction 158
Dynamic Changes Procedure 160
Firewall Behavior 161
Firewall Script Commands 163

EIO0000003089 12/2019 157


Ethernet Configuration

Introduction

Firewall Presentation
In general, firewalls help protect network security zone perimeters by blocking unauthorized
access and permitting authorized access. A firewall is a device or set of devices configured to
permit, deny, encrypt, decrypt, or proxy traffic between different security zones based upon a set
of rules and other criteria.
Process control devices and high-speed manufacturing machines require fast data throughput and
often cannot tolerate the latency introduced by an aggressive security strategy inside the control
network. Firewalls, therefore, play a significant role in a security strategy by providing levels of
protection at the perimeters of the network. Firewalls are an important part of an overall, system
level strategy. By default, firewall rules do not allow the transfer of incoming IP telegrams from a
controller network to a fieldbus network.
NOTE: Schneider Electric adheres to industry best practices in the development and implemen-
tation of control systems. This includes a "Defense-in-Depth" approach to secure an Industrial
Control System. This approach places the controllers behind one or more firewalls to restrict
access to authorized personnel and protocols only.

WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
 Evaluate whether your environment or your machines are connected to your critical
infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
 Limit the number of devices connected to a network to the minimum necessary.
 Isolate your industrial network from other networks inside your company.
 Protect any network against unintended access by using firewalls, VPN, or other, proven
security measures.
 Monitor activities within your systems.
 Prevent subject devices from direct access or direct link by unauthorized parties or unauthen-
ticated actions.
 Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Firewall Configuration
There are three ways to manage the controller firewall configuration:
 Static configuration
 Dynamic changes
 Application settings

Script files are used in the static configuration and for dynamic changes.

158 EIO0000003089 12/2019


Ethernet Configuration

Static Configuration
The static configuration is loaded at the controller boot.
The controller firewall can be statically configured by managing a default script file located in the
controller. The path to this file is /usr/Cfg/FirewallDefault.cmd.

Dynamic Changes
After the controller boot, the controller firewall configuration can be changed by the use of script
files.
There are two ways to load these dynamic changes using:
 A physical SD card (see page 160).
 A function block (see page 160) in the application.

EIO0000003089 12/2019 159


Ethernet Configuration

Dynamic Changes Procedure

Using an SD Card
This table describes the procedure to execute a script file from an SD card:

Step Action
1 Create a valid script file (see page 163).
For example, name the script file FirewallMaintenance.cmd.
2 Load the script file on the SD card.
For example, load the script file in the usr/Cfg folder.
3 In the file Sys/Cmd/Script.cmd, add a code line with the command
Firewall_install "/pathname/FileName"
For example, the code line is
Firewall_install "/sd0/usr/Cfg/FirewallMaintenance.cmd"
4 Insert the SD card on the controller.

Using a Function Block in the Application


This table describes the procedure to execute a script file from an application:

Step Action
1 Create a valid script file (see page 163).
For example, name the script file FirewallMaintenance.cmd.
2 Load the script file in the controller memory.
For example, load the script file in the usr/Syslog folder with FTP.
3 Use an ExecuteScript (see Modicon M251 Logic Controller, System Functions and Variables,
PLCSystem Library Guide) function block.
For example, the [SCmd] input is 'Firewall_install
"/usr/Syslog/FirewallMaintenance.cmd"'

160 EIO0000003089 12/2019


Ethernet Configuration

Firewall Behavior

Introduction
The firewall configuration depends on the action done on the controller and the initial configuration
state. There are five possible initial states:
 There is no default script file in the controller.
 A correct script file is present.
 An incorrect script file is present.
 There is no default script file and the application has configured the firewall.
 A dynamic script file configuration has already been executed.

No Default Script File

If... Then ...


Boot of the controller Firewall is not configured. No protection is activated.
Execute dynamic script file Firewall is configured according to the dynamic script file.
Execute dynamic incorrect script Firewall is not configured. No protection is activated.
file
Download application Firewall is configured according to the application settings.

Default Script File Present

If... Then ...


Boot of the controller Firewall is configured according to the default script file.
Execute dynamic script file The whole configuration of the default script file is deleted.
Firewall is configured according to the dynamic script file.
Execute dynamic incorrect script Firewall is configured according to the default script file.
file The dynamic script file is not taken into account.
Download application The whole configuration of the application is ignored.
Firewall is configured according to the default script file.

Incorrect Default Script File Present

If... Then ...


Boot of the controller Firewall is not configured. No protection is activated
Execute dynamic script file Firewall is configured according to the dynamic script file.
Execute dynamic incorrect script Firewall is not configured. No protection is activated.
file
Download application Firewall is configured according to the application settings.

EIO0000003089 12/2019 161


Ethernet Configuration

Application Settings with No Default Script File

If... Then ...


Boot of the controller Firewall is configured according to the application settings.
Execute dynamic script file The whole configuration of the application settings is deleted.
Firewall is configured according to the dynamic script file.
Execute dynamic incorrect Firewall is configured according to the application settings. The dynamic script file is
script file not taken into account.
Download application The whole configuration of the previous application is deleted.
Firewall is configured according to the new application settings.

Execute Dynamic Script File Already Executed

If... Then ...


Boot of the controller Firewall is configured according to the dynamic script file configuration (see note).
Execute dynamic script file The whole configuration of the previous dynamic script file is deleted.
Firewall is configured according to the new dynamic script file.
Execute dynamic incorrect Firewall is configured according to the previous dynamic script file configuration. The
script file dynamic incorrect script file is not taken into account.
Download application The whole configuration of the application is ignored
Firewall is configured according to the dynamic script file.
NOTE: If an SD card containing a cybersecurity script is plugged into the controller, booting is blocked. First remove
the SD card to correctly boot the controller.

162 EIO0000003089 12/2019


Ethernet Configuration

Firewall Script Commands

Overview
This section describes how script files (default script files or dynamic script files) are written so that
they can be executed during the booting of the controller or during a specific command triggered.
NOTE: The MAC layer rules are managed separately and have more priority over other packet filter
rules.

Script File Syntax


The syntax of script files is described in Script Syntax Guidelines (see page 228).

General Firewall Commands


The following commands are available to manage the Ethernet firewall of the M251 Logic
Controller:

Command Description
Firewall Enable Blocks the frames from the Ethernet interfaces. If no specific
IP address is authorized, it is not possible to communicate on
the Ethernet interfaces.
NOTE: By default, when the firewall is enabled, the frames
are rejected.
Firewall Disable Firewall rules are not applied. Frames are not blocked
Firewall Ethx Default Allow (1) Frames are accepted by the controller.

Firewall Ethx Default Reject(1) Frames are rejected by the controller.


NOTE: By default, if this line is not present, it corresponds
to the command Firewall Eth1 Default Reject.
(1)Where Ethx =
For TM251MESC:
 Eth1: Ethernet_1

For TM251MESE:
 Eth1: Ethernet_1
 Eth2: Ethernet_2

EIO0000003089 12/2019 163


Ethernet Configuration

Specific Firewall Commands


The following commands are available to configure firewall rules for specific ports and addresses:

Command Range Description


Firewall Eth1 • = 0...255 Frames from the specified IP address are allowed on all port
Allow IP •.•.•.• numbers and port types.
Firewall Eth1 • = 0...255 Frames from the specified IP address are rejected on all port
Reject IP •.•.•.• numbers and port types.
Firewall Eth1 • = 0...255 Frames from the IP addresses in the specified range are
Allow IPs •.•.•.• allowed for all port numbers and port types.
to •.•.•.•
Firewall Eth1 • = 0...255 Frames from the IP addresses in the specified range are
Reject IPs rejected for all port numbers and port types.
•.•.•.• to
•.•.•.•
Firewall Eth1 Y = (destination port Frames with the specified destination port number are allowed.
Allow port_type numbers (see page 167))
port Y
Firewall Eth1 Y = (destination port Frames with the specified destination port number are rejected.
Reject port_type numbers (see page 167))
port Y
NOTE: When IP forwarding is activated, rules with reject port
only filter frames with current controller as destination. They are
not applied for the frames routed by the current controller.
Firewall Eth1 Y = (destination port Frames with a destination port number in the specified range
Allow port_type numbers (see page 167)) are allowed.
ports Y1 to Y2
Firewall Eth1 Y = (destination port Frames with a destination port number in the specified range
Reject port_type numbers (see page 167)) are rejected.
ports Y1 to Y2
Firewall Eth1 • = 0...255 Frames from the specified IP address and with the specified
Allow IP •.•.•.• Y = (destination port destination port number are allowed.
on port_type port numbers (see page 167))
Y
Firewall Eth1 • = 0...255 Frames from the specified IP address and with the specified
Reject IP •.•.•.• Y = (destination port destination port number are rejected.
on port_type port numbers (see page 167))
Y
Firewall Eth1 • = 0...255 Frames from the specified IP address and with a destination
Allow IP •.•.•.• Y = (destination port port number in the specified range are allowed.
on port_type numbers (see page 167))
ports Y1 to Y2
Firewall Eth1 • = 0...255 Frames from the specified IP address and with a destination
Reject IP •.•.•.• Y = (destination port port number in the specified range are rejected.
on port_type numbers (see page 167))
ports Y1 to Y2

164 EIO0000003089 12/2019


Ethernet Configuration

Command Range Description


Firewall Eth1 • = 0...255 Frames from an IP address in the specified range and with the
Allow IPs Y = (destination port specified destination port number are allowed.
•1.•1.•1.•1 to numbers (see page 167))
•2.•2.•2.•2 on
port_type port Y
Firewall Eth1 • = 0...255 Frames from an IP address in the specified range and with the
Reject IPs Y = (destination port specified destination port number are rejected.
•1.•1.•1.•1 to numbers (see page 167))
•2.•2.•2.•2 on
port_type port Y
Firewall Eth1 • = 0...255 Frames from an IP address in the specified range and with a
Allow IPs Y = (destination port destination port number in the specified range are allowed.
•1.•1.•1.•1 to numbers (see page 167))
•2.•2.•2.•2 on
port_type ports
Y1 to Y2
Firewall Eth1 • = 0...255 Frames from an IP address in the specified range and with a
Reject IPs Y = (destination port destination port number in the specified range are rejected.
•1.•1.•1.•1 to numbers (see page 167))
•2.•2.•2.•2 on
port_type ports
Y1 to Y2
Firewall Eth1 • = 0...F Frames from the specified MAC address ••:••:••:••:•• are
Allow MAC allowed.
••:••:••:••:••:••
NOTE: When the rules to allow the MAC address are applied,
only the listed MAC addresses can communicate with the
controller, even if other rules are allowed.
Firewall Eth1 • = 0...F Frames with the specified MAC address ••:••:••:••:•• are
Reject MAC rejected.
••:••:••:••:••:••

NOTE: The port_type can be TCP or UDP.

EIO0000003089 12/2019 165


Ethernet Configuration

Script Example
; Enable FireWall. All frames are rejected;
FireWall Enable;
; Allow frames on Eth1
FireWall Eth1 Default Allow;
; Block all Modbus Requests on all IP address
Firewall Eth1 Reject tcp port 502;
; Reject frames on Eth2
FireWall Eth2 Default Reject;
; Allow FTP active connection for IP address 85.16.0.17
FireWall Eth2 Allow IP 85.16.0.17 on tcp ports 20 to 21;
NOTE: IP addresses are converted to CIDR format.
For example:
"FireWall Eth2 Allow IPs 192.168.100.66 to 192.168.100.99 on tcp port
44818;", is separated into 7:
 192.168.100.66/31
 192.168.100.68/30
 192.168.100.72/29
 192.168.100.80/28
 192.168.100.96/27
 192.168.100.128/26
 192.168.100.192/29

To prevent a firewall error, use the entire subnet configuration.


NOTE: Characters are limited to 200 per line, including comments.

166 EIO0000003089 12/2019


Ethernet Configuration

Ports Used

Protocol Destination Port Numbers


Machine Expert UDP 1740, 1741, 1742, 1743
TCP 1105
FTP TCP 21, 20
HTTP TCP 80
Modbus TCP 502 (1)
Machine Expert Discovery UDP 27126, 27127
SNMP UDP 161, 162
NVL UDP Default value: 1202
EtherNet/IP UDP 2222
TCP 44818
TFTP UDP 69 (used for FDR server only)
(1)The default value can be changed using the change ModbusPort command (see page 155).

EIO0000003089 12/2019 167


Ethernet Configuration

168 EIO0000003089 12/2019


Modicon M251 Logic Controller
Industrial Ethernet Manager
EIO0000003089 12/2019

Chapter 11
Industrial Ethernet Manager

Industrial Ethernet Manager

Introduction
This chapter describes how to add and configure the Industrial Ethernet.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Industrial Ethernet 170
DHCP Server 174
Fast Device Replacement 175

EIO0000003089 12/2019 169


Industrial Ethernet Manager

Industrial Ethernet

Overview
Industrial Ethernet is the term used to represent the industrial protocols that use the standard
Ethernet physical layer and standard Ethernet protocols.
NOTE: The following information only applies to the TM251MESE controller.
On an Industrial Ethernet network, you can connect:
 industrial devices.(industrial protocols)
 non-industrial devices (other Ethernet protocols)

For more information, refer to Industrial Ethernet User Guide (see EcoStruxure Machine Expert
Industrial Ethernet Overview, User Guide).

Industrial Ethernet Architecture


This figure presents a typical Industrial Ethernet architecture:

A Control network
B Device network
1 Logic controller (see EcoStruxure Machine Expert Industrial Ethernet Overview, User Guide)
2 Daisy-chained devices
3 Ethernet switch
4 I/O island (Modbus TCP)
5 Vision sensor (EtherNet/IP)
6 PC and HMI (TCP/UDP)
2, 4, and 5 Industrial Ethernet slave devices (EtherNet/IP / Modbus TCP)
This architecture is configurable with EcoStruxure Machine Expert.

170 EIO0000003089 12/2019


Industrial Ethernet Manager

Industrial Ethernet Description

TM251MESE logic controller


Features Description
Topology Daisy chain and Star via switches
Bandwidth 10/100 Mbit/s
EtherNet/IP Scanner
Performance Up to 16 EtherNet/IP target devices managed by the logic
controller, monitored within a timeslot of 10 ms
Number of connections 0...16
Number of input words 0...1024
Number of output words 0...1024
I/O communications EtherNet/IP Scanner service
Function block for configuration and data transfer
Originator/Target
Modbus TCP IOScanner
Performance Up to 64 Modbus TCP slave devices managed by the logic
controller, monitored within a timeslot of 64 ms.
Number of connections 0...64
Number of input words 0...2048
Number of output words 0...2048
I/O communications Modbus TCP IOScanner service
Function block for data transfer
Master/Slave

EIO0000003089 12/2019 171


Industrial Ethernet Manager

TM251MESE logic controller


Features Description
Other services FDT/DTM/EDS management
FDR (Fast Device Replacement)
DHCP server
Security management (refer to Security Parameters
(see page 101) and Firewall Configuration (see page 157))
Modbus TCP server
Modbus TCP client
EtherNet/IP adapter (controller as a target on EtherNet/IP)
EtherNet/IP Originator
Modbus TCP server (controller as a slave on Modbus TCP)
Web server
FTP Server (FTP and TFTP protocols)
SNMP
IEC VAR ACCESS
Additional features Possible to mix up to 16 EtherNet/IP and Modbus TCP server
devices.
Devices can be directly accessed for configuration, monitoring,
and management purposes.
Network transparency between control network and device
network (logic controller can be used as a gateway).
NOTE: Using the logic controller as a gateway can impact the
performance of the logic controller.

EtherNet/IP Overview
EtherNet/IP is the implementation of the CIP protocol over standard Ethernet.
The EtherNet/IP protocol uses an Originator/Target architecture for data exchange.
Originators are devices that initiate data exchanges with Target devices on the network. This
applies to both I/O communications and service messaging. This is the equivalent of the role of a
client in a Modbus network.
Targets are devices that respond to data requests generated by Originators. This applies to both
I/O communications and service messaging. This is the equivalent of the role of a server in a
Modbus network.
EtherNet/IP Adapter is an end-device in an EtherNet/IP network. I/O blocks and drives can be
EtherNet/IP Adapter devices.
The communication between an EtherNet/IP Originator and Target is accomplished using an
EtherNet/IP connection.

172 EIO0000003089 12/2019


Industrial Ethernet Manager

Modbus TCP Overview


The Modbus TCP protocol uses a Client/Server architecture for data exchange.
The Modbus TCP explicit (non-cyclic) data exchanges are managed by the application.
Modbus TCP implicit (cyclic) data exchanges are managed by the Modbus TCP IOScanner. The
Modbus TCP IOScanner is a service based on Ethernet that polls slave devices continuously to
exchange data, status, and diagnostic information. This process monitors inputs and controls
outputs of slave devices.
Clients are devices that initiate data exchange with other devices on the network. This applies to
both I/O communications and service messaging.
Servers are devices that address any data requests generated by a Client. This applies to both I/O
communications and service messaging.
The communication between the Modbus TCP IOScanner and the slave device is accomplished
using Modbus TCP channels.

Adding the Industrial Ethernet Manager


The Industrial_Ethernet_manager must be present on the Ethernet_2 (Device Network) node of the
device tree to activate these functions and services:
 EtherNet/IP Scanner
 Modbus TCP IOScanner

The Industrial_Ethernet_manager is available by default under the Ethernet_2 (Device Network)


node. It is automatically added when a slave device is added on the Ethernet_2 (Device Network)
node.
To manually add the Industrial_Ethernet_manager to the Ethernet_2 (Device Network) :

Step Action
1 In the Devices Tree, select Ethernet_2 (Device Network) and click the green plus button of the
node or right-click Ethernet_2 (Device Network) and execute the Add Device... command from
the context menu.
Result: The Add Device dialog box displays.
2 In the Add Device dialog box, select Protocol Managers → Industrial Ethernet manager.
3 Click the Add Device button.
4 Click the Close button.

For more information, refer to Industrial Ethernet Manager Configuration (see EcoStruxure
Machine Expert EtherNet/IP, User Guide), EtherNet/IP Target Settings (see EcoStruxure Machine
Expert EtherNet/IP, User Guide) and Modbus TCP Settings (see EcoStruxure Machine Expert
Modbus TCP, User Guide).

EIO0000003089 12/2019 173


Industrial Ethernet Manager

DHCP Server

Overview
It is possible to configure a DHCP server on the Ethernet 2 network of the TM251MESE.
The DHCP server offers addresses to the devices connected on the Ethernet 2 network. The
DHCP server only delivers static addresses. A unique identified slave gets a unique address.
DHCP slave devices are identified either by their MAC address or their DHCP device name. The
DHCP server configuration table defines the relation between addresses and identified slave
devices.
The DHCP server addresses are given with an infinite lease time. There is no need for the slave
devices to refresh the leased IP address.
For more information, refer to IP Addressing Methods (see EcoStruxure Machine Expert Modbus
TCP, User Guide).

174 EIO0000003089 12/2019


Industrial Ethernet Manager

Fast Device Replacement

Overview
The Fast Device Replacement (FDR) helps facilitate replacing and reconfiguring a network device.
This function is available on the Ethernet 2 port of the TM251MESE.
For more information, refer to Slave Device Replacement with FDR (see EcoStruxure Machine
Expert Modbus TCP, User Guide).

EIO0000003089 12/2019 175


Industrial Ethernet Manager

176 EIO0000003089 12/2019


Modicon M251 Logic Controller
Serial Line Configuration
EIO0000003089 12/2019

Chapter 12
Serial Line Configuration

Serial Line Configuration

Introduction
This chapter describes how to configure the serial line communication of the Modicon M251 Logic
Controller.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Serial Line Configuration 178
Machine Expert Network Manager 180
Modbus Manager 181
ASCII Manager 185
Modbus Serial IOScanner 187
Adding a Device on the Modbus Serial IOScanner 189
Adding a Modem to a Manager 196

EIO0000003089 12/2019 177


Serial Line Configuration

Serial Line Configuration

Introduction
The Serial Line configuration window allows you to configure the physical parameters of a serial
line (baud rate, parity, and so on).

Serial Line Configuration


To configure a Serial Line, double-click Serial line in the Devices tree.
The Configuration window is displayed as below:

The following parameters must be identical for each serial device connected to the port.

Element Description
Baud rate Transmission speed in bits/s
Parity Used for error detection
Data bits Number of bits for transmitting data
Stop bits Number of stop bits
Physical Medium Specify the medium to use:
 RS485 (using polarisation resistor or not)
 RS232

Polarization Polarization resistors are integrated in the controller. They are switched on or off by this
Resistor parameter.

178 EIO0000003089 12/2019


Serial Line Configuration

The serial line ports of your controller are configured for the Machine Expert protocol by default
when new or when you update the controller firmware. The Machine Expert protocol is
incompatible with that of other protocols such as Modbus Serial Line. Connecting a new controller
to, or updating the firmware of a controller connected to, an active Modbus configured serial line
can cause the other devices on the serial line to stop communicating. Make sure that the controller
is not connected to an active Modbus serial line network before first downloading a valid application
having the concerned port or ports properly configured for the intended protocol.

NOTICE
INTERRUPTION OF SERIAL LINE COMMUNICATIONS
Be sure that your application has the serial line ports properly configured for Modbus before
physically connecting the controller to an operational Modbus Serial Line network.
Failure to follow these instructions can result in equipment damage.

This table indicates the maximum baud rate value of the managers:

Manager Maximum Baud Rate (Bits/S)


Machine Expert Network Manager 115200
Modbus Manager
ASCII Manager
Modbus IOScanner

EIO0000003089 12/2019 179


Serial Line Configuration

Machine Expert Network Manager

Introduction
Use the Machine Expert Network Manager to exchange variables with a XBTGT/XBTGK
Advanced Panel with Machine Expert software protocol, or when the Serial Line is used for
EcoStruxure Machine Expert programming.

Adding the Manager


To add a Machine Expert Network Manager to your controller, select the Machine Expert-Network
Manager in the Hardware Catalog, drag it to the Devices tree, and drop it on one of the highlighted
nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button

Configuring the Manager


There is no configuration for Machine Expert Network Manager.

Adding a Modem
To add a modem to the Machine Expert Network Manager, refer to Adding a Modem to a Manager
(see page 196).

180 EIO0000003089 12/2019


Serial Line Configuration

Modbus Manager

Introduction
The Modbus Manager is used for Modbus RTU or ASCII protocol in master or slave mode.

Adding the Manager


To add a Modbus manager to your controller, select the Modbus Manager in the Hardware
Catalog, drag it to the Devices tree, and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button

Modbus Manager Configuration


To configure the Modbus Manager of your controller, double-click Modbus Manager in the Devices
tree.
The Modbus Manager configuration window is displayed as below:

Set the parameters as described in this table:

Element Description
Transmission Specify the transmission mode to use:
Mode  RTU: uses binary coding and CRC error-checking (8 data bits)
 ASCII: messages are in ASCII format, LRC error-checking (7 data bits)

Set this parameter identical for each Modbus device on the link.
Addressing Specify the device type:
 Master
 Slave

EIO0000003089 12/2019 181


Serial Line Configuration

Element Description
Address Modbus address of the device, when slave is selected.
Time between Time to avoid bus-collision.
Frames (ms) Set this parameter identical for each Modbus device on the link.
Serial Line Parameters specified in the Serial Line configuration window.
Settings

Modbus Master
When the controller is configured as a Modbus Master, the following function blocks are supported
from the PLCCommunication Library:
 ADDM
 READ_VAR
 SEND_RECV_MSG
 SINGLE_WRITE
 WRITE_READ_VAR
 WRITE_VAR

For further information, see Function Block Descriptions (see EcoStruxure Machine Expert,
Modbus and ASCII Read/Write Functions, PLCCommunication Library Guide) of the PLCCommu-
nication Library.

Modbus Slave
When the controller is configured as Modbus Slave, the following Modbus requests are supported:

Function Code Sub-Function Function


Dec (Hex) Dec (Hex)
1 (1 hex) – Read digital outputs (%Q)
2 (2 hex) – Read digital inputs (%I)
3 (3 hex) – Read multiple register (%MW)
6 (6 hex) – Write single register (%MW)
8 (8 hex) – Diagnostic
15 (F hex) – Write multiple digital outputs (%Q)
16 (10 hex) – Write multiple registers (%MW)
23 (17 hex) – Read/write multiple registers (%MW)
43 (2B hex) 14 (E hex) Read device identification

182 EIO0000003089 12/2019


Serial Line Configuration

This table contains the sub-function codes supported by the diagnostic Modbus request 08:

Sub-Function Code Function


Dec Hex
10 0A Clears Counters and Diagnostic Register
11 0B Returns Bus Message Count
12 0C Returns Bus Communication Error Count
13 0D Returns Bus Exception Error Count
14 0E Returns Slave Message Count
15 0F Returns Slave No Response Count
16 10 Returns Slave NAK Count
17 11 Returns Slave Busy Count
18 12 Returns Bus Character Overrun Count

This table lists the objects that can be read with a read device identification request (basic identifi-
cation level):

Object ID Object Name Type Value


00 hex Vendor code ASCII String Schneider Electric
01 hex Product code ASCII String Controller reference
for example: TM251MESE
02 hex Major / Minor revision ASCII String aa.bb.cc.dd (same as device descriptor)

The following section describes the differences between the Modbus memory mapping of the
controller and HMI Modbus mapping. If you do not program your application to recognize these
differences in mapping, your controller and HMI will not communicate correctly. Thus it will be
possible for incorrect values to be written to memory areas responsible for output operations.

WARNING
UNINTENDED EQUIPMENT OPERATION
Program your application to translate between the Modbus memory mapping used by the
controller and that used by any attached HMI devices.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

When the controller and the Magelis HMI are connected via Modbus (HMI is master of Modbus
requests), the data exchange uses simple word requests.

EIO0000003089 12/2019 183


Serial Line Configuration

There is an overlap on simple words of the HMI memory while using double words but not for the
controller memory (see following diagram). In order to have a match between the HMI memory
area and the controller memory area, the ratio between double words of HMI memory and the
double words of controller memory has to be 2.

The following gives examples of memory match for the double words:
 %MD2 memory area of the HMI corresponds to %MD1 memory area of the controller because
the same simple words are used by the Modbus request.
 %MD20 memory area of the HMI corresponds to %MD10 memory area of the controller
because the same simple words are used by the Modbus request.
The following gives examples of memory match for the bits:
 %MW0:X9 memory area of the HMI corresponds to %MX1.1 memory area of the controller
because the simple words are split in 2 distinct bytes in the controller memory.

Adding a Modem
To add a Modem to the Modbus Manager, refer to Adding a Modem to a Manager (see page 196).

184 EIO0000003089 12/2019


Serial Line Configuration

ASCII Manager

Introduction
The ASCII manager is used on a Serial Line, to transmit and/or receive data with a simple device.

Adding the Manager


To add an ASCII manager to your controller, select the ASCII Manager in the Hardware Catalog,
drag it to the Devices tree, and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button

ASCII Manager Configuration


To configure the ASCII manager of your controller, double-click ASCII Manager in the Devices
tree.
The ASCII Manager configuration window is displayed as below:

EIO0000003089 12/2019 185


Serial Line Configuration

Set the parameters as described in this table:

Parameter Description
Start Character If 0, no start character is used in the frame. Otherwise, in Receiving Mode, the
corresponding character in ASCII is used to detect the beginning of a frame. In Sending
Mode, this character is added at the beginning of the frame.
First End If 0, no first end character is used in the frame. Otherwise, in Receiving Mode, the
Character corresponding character in ASCII is used to detect the end of a frame. In Sending Mode,
this character is added at the end of the frame.
Second End If 0, no second end character is used in the frame. Otherwise, in Receiving Mode, the
Character corresponding character in ASCII is used to detect the end of a frame. In Sending Mode,
this character is added at the end of the frame.
Frame Length If 0, this parameter is not used. This parameter allows the system to conclude an end of
Received frame at reception when the controller received the specified number of characters.
Note: This parameter cannot be used simultaneously with Frame Received Timeout (ms).
Frame Received If 0, this parameter is not used. This parameter allows the system to conclude the end of
Timeout (ms) frame at reception after a silence of the specified number of ms.
Serial Line Parameters specified in the Serial Line configuration window (see page 178).
Settings

NOTE: In the case of using several frame termination conditions, the first condition to be TRUE
terminates the exchange.

Adding a Modem
To add a Modem to the ASCII manager, refer to Adding a Modem to a Manager (see page 196).

186 EIO0000003089 12/2019


Serial Line Configuration

Modbus Serial IOScanner

Introduction
The Modbus IOScanner is used to simplify exchanges with Modbus slave devices.

Add a Modbus IOScanner


To add a Modbus IOScanner on a Serial Line, select the Modbus_IOScanner in the Hardware
Catalog, drag it to the Devices tree, and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button

Modbus IOScanner Configuration


To configure a Modbus IOScanner on a Serial Line, double-click Modbus IOScanner in the Devices
tree.
The configuration window is displayed as below:

Set the parameters as described in this table:

Element Description
Transmission Specifies the transmission mode to use:
Mode  RTU: uses binary coding and CRC error-checking (8 data bits)
 ASCII: messages are in ASCII format, LRC error-checking (7 data bits)

Set this parameter identical for each Modbus device on the network.
Response Timeout Timeout used in the exchanges.
(ms)
Time between Delay to reduce data collision on the bus.
Frames (ms) Set this parameter identical for each Modbus device on the network.

NOTE: Do not use function blocks of the PLCCommunication library on a serial line with a Modbus
IOScanner configured. This disrupts the Modbus IOScanner exchange.

EIO0000003089 12/2019 187


Serial Line Configuration

Bus Cycle Task Selection


The Modbus IOScanner and the devices exchange data at each cycle of the chosen application
task.
To select this task, select the Modbus Master IO Mapping tab. The configuration window is
displayed as below:

The Bus cycle task parameter allows you to select the application task that manages the scanner:
 Use parent bus cycle setting: associate the scanner with the application task that manages the
controller.
 MAST: associate the scanner with the MAST task.
 Another existing task: you can select an existing task and associate it to the scanner. For more
information about the application tasks, refer to the EcoStruxure Machine Expert Programming
Guide (see EcoStruxure Machine Expert, Programming Guide).
The scan time of the task associated with the scanner must be less than 500 ms.

188 EIO0000003089 12/2019


Serial Line Configuration

Adding a Device on the Modbus Serial IOScanner

Introduction
This section describes how to add a device on the Modbus IOScanner.

Adding a Device on the Modbus IOScanner


To add a device on the Modbus IOScanner, select the Generic Modbus Slave in the Hardware
Catalog, drag it to the Devices tree, and drop it on the Modbus_IOScanner node of the Devices
tree.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button
NOTE: The variable for the exchange is automatically created in the %IWx and %QWx of the Modbus
Serial Master I/O Mapping tab.

Configuring a Device Added on the Modbus IOScanner


To configure the device added on the Modbus IOScanner, proceed as follows:

Step Action
1 In the Devices tree, double-click Generic Modbus Slave.
Result: The configuration window is displayed.

2 Enter a Slave Address value for your device (choose a value from 1 to 247).
3 Choose a value for the Response Timeout (in ms).

EIO0000003089 12/2019 189


Serial Line Configuration

To configure the Modbus Channels, proceed as follows:

Step Action
1 Click the Modbus Slave Channel tab:

190 EIO0000003089 12/2019


Serial Line Configuration

Step Action
2 Click the Add Channel button:

EIO0000003089 12/2019 191


Serial Line Configuration

Step Action
3 Configure an exchange:
In the field Channel, you can add the following values:
 Channel: Enter a name for your channel.
 Access Type: Choose the exchange type: Read or Write or Read/Write multiple requests
(see page 195).
 Trigger: Choose the trigger of the exchange. It can be CYCLIC with the period defined in Cycle Time
(ms) field, started by a RISING EDGE on a boolean variable (this boolean variable is then created
in the Modbus Master I/O Mapping tab), or by the Application.
 Comment: Add a comment about this channel.

In the field READ Register (if your channel is Read or Read/Write one), you can configure the %MW to
be read on the Modbus slave. Those are mapped on %IW (see Modbus Master I/O Mapping tab):
 Offset: Offset of the %MW to read. 0 means that the first object that is read is %MW0.
 Length: Number of %MW to be read. For example, if 'Offset' = 2 and 'Length' = 3, the channel reads
%MW2, %MW3 and %MW4.
 Error Handling: choose the behavior of the related %IW in case of loss of communication.

In the field WRITE Register (if your channel is Write or Read/Write one), you can configure the %MW to
be written to the Modbus slave. Those are mapped on %QW (see Modbus Master I/O Mapping tab):
 Offset: Offset of the %MW to write. 0 means that the first object that is written is %MW0.
 Length: Number of %MW to be written. For example, if 'Offset' = 2 and 'Length' = 3, the channel writes
%MW2, %MW3 and %MW4.
4 Click OK to validate the configuration of this channel.
NOTE: You can also:
 Click the Delete button to remove a channel.
 Click the Edit button to change the parameters of a channel.

192 EIO0000003089 12/2019


Serial Line Configuration

To configure your Modbus Initialization Value, proceed as follows:

Step Action
1 Click the Modbus Slave Init tab:

2 Click New to create a new initialization value:

The Initialization Value window contains the following parameters:


 Access Type: Enter the exchange type: Write requests (see page 195).
 Register Offset: Register number of register to be initialized.
 Length: Number of %MW to be read. For example, if 'Offset' = 2 and 'Length' = 3, the channel reads
%MW2, %MW3 and %MW4.
 Initialization Value: Value the registers are initialized with.
 Comment: Add a comment about this channel.

EIO0000003089 12/2019 193


Serial Line Configuration

Step Action
3 Click OK to create a new Initialization Value.
NOTE: You can also:
 Click Move up or Move down to change the position of a value in the list.
 Click Delete to remove a value in the list.
 Click Edit to change the parameters of a value.

To configure your Modbus Master I/O Mapping, proceed as follows:

Step Action
1 Click the Modbus Master I/O Mapping tab:

2 Double-click in a cell of the Variable column to open a text field.


Enter the name of a variable or click the browse button [...] and chose a variable with the Input Assistant.
3 For more information on I/O mapping, refer to EcoStruxure Machine Expert Programming Guide.

194 EIO0000003089 12/2019


Serial Line Configuration

Access Types
This table describes the different access types available:

Function Function Code Availability


Read Coils 1 ModbusChannel
Read Discrete Inputs 2 ModbusChannel
Read Holding Registers (default 3 ModbusChannel
setting for the channel configuration)
Read Input Registers 4 ModbusChannel
Write Single Coil 5 ModbusChannel
Initialization Value
Write Single Register 6 ModbusChannel
Initialization Value
Write Multiple Coils 15 ModbusChannel
Initialization Value
Write Multiple Registers (default 16 ModbusChannel
setting for the slave initialization) Initialization Value
Read/Write Multiple Registers 23 ModbusChannel

EIO0000003089 12/2019 195


Serial Line Configuration

Adding a Modem to a Manager

Introduction
A modem can be added to the following managers:
 ASCII Manager
 Modbus Manager
 Machine Expert Network Manager

NOTE: Use a modem which implements Hayes commands if you need a modem connection with
Machine Expert Network Manager.

Adding a Modem to a Manager


To add a modem to your controller, select the modem you want in the Hardware Catalog, drag it
to the Devices tree, and drop it on the manager node.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button
For further information, refer to Modem Library Guide (see EcoStruxure Machine Expert, Modem
Functions, Modem Library Guide).

196 EIO0000003089 12/2019


Modicon M251 Logic Controller
CANopen Configuration
EIO0000003089 12/2019

Chapter 13
CANopen Configuration

CANopen Configuration

CANopen Interface Configuration

CAN Bus Configuration


To configure the CAN bus of your controller, proceed as follows:

Step Action
1 In the Devices tree, double-click CAN_1.
2 Configure the baudrate (by default: 250000 bits/s):

NOTE: The Online Bus Access option allows you to block SDO, DTM, and NMT sending
through the status screen.

When connecting a DTM to a device using the network, the DTM communicates in parallel with the
running application. The overall performance of the system is impacted and may overload the
network, and therefore have consequences for the coherency of data across devices under
control.

WARNING
UNINTENDED EQUIPMENT OPERATION
Place your machine or process in a state such that DTM communications will not impact its
performance.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003089 12/2019 197


CANopen Configuration

CANopen Manager Creation and Configuration


If the CANopen Manager is not already present below the CAN node, proceed as follows to create
and configure it:

Step Action
1
Click the Plus Button next to the CAN_1 node in the Devices Tree. In the Add Device window,
select CANopen Performance and click the Add Device button.
For more information on adding a device to your project, refer to:
 Using the Drag-and-Drop Method (see EcoStruxure Machine Expert, Programming Guide)
 Using the Contextual Menu or Plus button (see EcoStruxure Machine Expert, Programming
Guide)
2 Double-click CANopen_Performance.
Result: The CANopen Manager configuration window appears:

198 EIO0000003089 12/2019


CANopen Configuration

NOTE: If Enable Sync Producing is checked, the CAN_x_Sync task is added to the Application →
Task Configuration node in the Applications tree tab.
Do not delete or change the Type or External event attributes of CAN_x_Sync tasks. If you do so,
EcoStruxure Machine Expert will detect an error when you attempt to build the application, and you
will not be able to download it to the controller.
If you uncheck the Enable Sync Producing option on the CANopen Manager subtab of the
CANopen_Performance tab, the CAN0_Sync task is automatically deleted from your program.

Adding a CANopen Device


Refer to the EcoStruxure Machine Expert Programming Guide for more information on Adding
Communication Managers and Adding Slave Devices to a Communication Manager.

CANopen Operating Limits


The Modicon M251 Logic Controller CANopen master has the following operating limits:

Maximum number of slave devices 63


Maximum number of Received PDO (RPDO) 252
Maximum number of Transmitted PDO (TPDO) 252

WARNING
UNINTENDED EQUIPMENT OPERATION
 Do not connect more than 63 CANopen slave devices to the controller.
 Program your application to use 252 or fewer Transmit PDO (TPDO).
 Program your application to use 252 or fewer Receive PDO (RPDO).
Failure to follow these instructions can result in death, serious injury, or equipment damage.

CAN Bus Format


The CAN bus format is CAN2.0A for CANopen.

EIO0000003089 12/2019 199


CANopen Configuration

200 EIO0000003089 12/2019


Modicon M251 Logic Controller
J1939 Configuration
EIO0000003089 12/2019

Chapter 14
J1939 Configuration

J1939 Configuration

J1939 Interface Configuration

CAN Bus Configuration


To configure the CAN bus of your controller, refer to CAN Bus Configuration (see page 197).
The CAN bus format is CAN2.0B for J1939.

J1939 Manager Creation and Configuration


Proceed as follows to create and configure a J1939 Manager, if not already present, below the
CAN_1 node:

Step Action
1 Click the Plus button next to the CAN_1 node in the Devices tree.
2 In the Add Device window, select J1939_Manager and click the Add Device button.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button
3 Close the Add Device window.
4 Double-click J1939_Manager (J1939_Manager).
Result: The J1939_Manager configuration window appears:

5 To configure the J1939_Manager, refer to Programming with EcoStruxure Machine Expert /


Device Editors / J1939 Configuration Editor / J1939 Manager Editor / Manager Editor found in
the EcoStruxure Machine Expert online help.

EIO0000003089 12/2019 201


J1939 Configuration

ECU Creation and Configuration


Proceed as follows to create and configure Electronic Control Units (ECUs):

Step Action
1 Click the Plus button next to the J1939_Manager (J1939_Manager) node in the Devices
tree.
2 In the Add Device window, select J1939_ECU and click the Add Device button.
For more information on adding a device to your project, refer to:
• Using the Drag-and-drop Method
• Using the Contextual Menu or Plus Button
3 Close the Add Device window.
4 Double-click J1939_ECU (J1939_ECU).
Result: The J1939_ECU configuration window appears:

5 To configure the J1939_ECU, refer to Configuring J1939 ECUs (see page 203).

202 EIO0000003089 12/2019


J1939 Configuration

Configuring J1939 ECUs


As an overview, the following tasks must be generally accomplished:
 Add one J1939_ECU node for each physical J1939 device connected on the CAN bus.
 For each J1939 device, specify a unique Preferred Address in the range 1...253.
 For each J1939 device, configure the signals (SPNs) in the TX Signals tab. These signals are
broadcast by the J1939 device to the other J1939 devices.
Refer to the device documentation for information on the supported SPNs.
 Associate the SPN signals with variables in the J1939 I/O Mapping tab so that they can be
processed by the application.
 When signals have been added, verify their settings in the Conversion window of the TX signals
tab, for example, Scaling, Offset, and Unit. The J1939 protocol does not directly support REAL
values, which are instead encoded in the protocol and so must be converted in the application.
Similarly, in J1939 units are defined according to the International System of Units (SI) and
therefore may need to be converted to values of other unit systems.
Examples:
 The Engine Speed signal of parameter group EEC1 has a property Scaling=0.125 that is
encoded into a raw variable of type ARRAY[0..1] OF BYTE. Use the following ST code to
convert this to a REAL variable:
rRPM:=(Engine_Speed[1]*256 + Engine_Speed[0])*0.125;
 The Total Vehicle Distance signal has properties Scaling=0.125 and Unit=km, which are
received in a (raw) variable of type ARRAY[0..3] OF BYTE. Use the following ST code to
convert this to a REAL variable in mile units:
rTVD := (Total_Vehicle_Distance[3]*EXPT(256,3) +
Total_Vehicle_Distance[2]*EXPT(256,2) + Total_Vehicle_Distance[1]*2
56 +
Total_Vehicle_Distance[0])*0.125*0.621371;
 The Engine Coolant Temperature signal of parameter group ET1 has properties Offset=-
40 and Unit=C(Celsius), which are received in a (raw) variable of type BYTE. Use the
following ST code to convert it to a REAL variable in Fahrenheit units:
rEngineCoolantTemperature := (Engine_Coolant_Temperature -
40)*1.8 + 32;
For more details on how to configure the J1939_ECU, refer to Programming with EcoStruxure
Machine Expert / Device Editors / J1939 Configuration Editor / J1939 ECU Editor / ECU Editor
found in the EcoStruxure Machine Expert online help.

EIO0000003089 12/2019 203


J1939 Configuration

Configuring the M251 Logic Controller as an ECU Device


The controller can also be configured as a J1939 ECU device:

Step Action
1 Add a J1393_ECU node to the J1939_Manager. Refer to ECU Creation and Configuration
(see page 202).
2 Select the Local Device option in the General tab.
3 Configure signals sent from the controller to other J1939 devices in the TX Signals tab.
Parameter groups are either of type Broadcast, that is, sent to all devices, or P2P (Peer-to-
Peer), that is, sent to one specified device.
4 For P2P signals, configure the Destination Address of the receiving J1939 ECU device in the
parameter group properties window.
5 Add P2P signals sent by another J1939 device to the controller in the RX Signals (P2P) tab of
the J1939 (local) device representing the controller.
6 Configure the Source Address of the parameter group by specifying the address of the sending
J1939 device.

204 EIO0000003089 12/2019


Modicon M251 Logic Controller
OPC UA Server Configuration
EIO0000003089 12/2019

Chapter 15
OPC UA Server Configuration

OPC UA Server Configuration

Introduction
This chapter describes how to configure the OPC UA server of the M251 Logic Controller.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
OPC UA Server Overview 206
OPC UA Server Configuration 207
OPC UA Server Symbols Configuration 210
OPC UA Server Performance 212

EIO0000003089 12/2019 205


OPC UA Server Configuration

OPC UA Server Overview

Overview
The OPC Unified Architecture server (OPC UA server) allows the M251 Logic Controller to
exchange data with OPC UA clients. Server and client communicate through sessions.
The monitored items of data (also referred to as symbols) to be shared by the OPC UA server are
manually selected from a list of the IEC variables used in the application.
OPC UA uses a subscription model; clients subscribe to symbols. The OPC UA server reads the
values of symbols from devices at a fixed sampling rate, places the data in a queue, then sends
them to clients as notifications at a regular publishing interval. The sampling interval can be shorter
than the publishing interval, in which case notifications may be queued until the publishing interval
elapses.
Symbols that have not changed value since the previous sample are not re-published. Instead, the
OPC UA server sends regular KeepAlive messages to indicate to the client that the connection is
still active.

User and Group Access Rights


Access to the OPC UA server is controlled by user rights. Refer to Users and Groups in the
EcoStruxure Machine Expert Programming Guide.

OPC UA Services
The following table describes the supported OPC UA services:

OPC UA Service Description


Address Space Model Yes
Session services Yes
Attribute services Yes
Monitored item services Yes
Queued items Yes
Subscription services Yes
Publishing method Yes

206 EIO0000003089 12/2019


OPC UA Server Configuration

OPC UA Server Configuration

Introduction
The OPC UA Server Configuration window allows you to configure the OPC UA server.

Accessing the OPC UA Server Configuration Tab


To configure the OPC UA Server:

Step Action
1 In the Devices tree, double-click MyController.
2 Select the OPC UA Server Configuration tab.

OPC UA Server Configuration Tab


The following figure shows the OPC UA Server Configuration window:

EIO0000003089 12/2019 207


OPC UA Server Configuration

OPC UA Server Configuration Description


This table describes the OPC UA Server Configuration parameters:

Parameter Value Default value Description


Security Settings
Disable anonymous login Enabled/ Disabled Disabled By default, this checkbox is cleared, meaning
that OPC UA clients can connect to the server
anonymously. Select this checkbox to require
that clients provide a valid user name and
password to connect to the OPC UA server.
Server Configuration
Server port 0...65535 4840 The port number of the OPC UA server.
OPC UA clients must append this port number
to the TCP URL of the controller to connect to
the OPC UA server.
Max. subscriptions per session 1...100 20 Specify the maximum number of subscriptions
allowed within each session.
Min. publishing interval 200...5000 1000 The publishing interval defines how frequently
the OPC UA server sends notification
packages to clients. Specify the minimum time
that must elapse between notifications, in ms.
Max. monitored items per 1...1000 100 The maximum number of monitored items in
subscription each subscription that the server assembles
into a notification package.
Min. KeepAlive interval 500...5000 500 The OPC UA server only sends notifications
when the values of monitored items of data are
modified. A KeepAlive notification is an empty
notification sent by the server to inform the
client that although no data has been modified,
the subscription is still active. Specify the
minimum interval between KeepAlive
notifications, in ms.
Max. number of sessions 1...4 2 The maximum number of clients that can
connect simultaneously to the OPC UA server.
Identifier type Numeric Numeric Certain OPC UA clients require a specific
String format of unique symbol identifier (node ID).
Select the format of the identifiers:
 Numeric values
 Text strings

208 EIO0000003089 12/2019


OPC UA Server Configuration

Parameter Value Default value Description


Diagnostic
Enable trace Enabled/disabled Enabled Select this checkbox to include OPC UA
diagnostic messages in the controller log file.
Traces are available from the Log tab or from
the System Log File of the Web Server.
You can select the category of events to write
to the log file:
 None
 Error
 Warning
 System
 Information
 Debug
 Content
 All (default)

Sampling rates (ms) 200...5000 500 The sampling rate indicates a time interval, in
1000 milliseconds (ms). When this interval has
2000 elapsed, the server sends the notification
package to the client. The sampling rate can
be shorter than the publishing interval, in
which case notifications are queued until the
publishing interval has elapsed.
Sampling rates must be in the range
200...5000 (ms).
Up to 3 different sampling rates can be
configured.
Double-click on a sampling rate to edit its
value.
To add a sampling rate to the list, right-click
and choose Add a new rate.
To remove a sample rate from the list, select
the value and click

Click Reset to default to return the configuration parameters on this window to their default values.

EIO0000003089 12/2019 209


OPC UA Server Configuration

OPC UA Server Symbols Configuration

Introduction
Symbols are the items of data shared with OPC UA clients. Symbols are selected from a list of all
the IEC variables used in the application. The selected symbols are then sent to the logic controller
as part of the application download.
Each symbol is assigned a unique identifier. As certain client types may require a specific format,
identifiers can be configured to be in either string or numeric format.
The OPC UA server supports the following IEC variable types:
 Boolean
 Byte
 Int16, Int32, Int64
 UInt16, UInt32, UInt64
 Float
 Double
 String (255 bytes)
 Sbyte

Bit memory variables (%MX) cannot be selected.

Displaying the List of Variables


To display the list of variables:

Step Action
1 On the Applications tree tab, right-click Application and choose Add object → OPC UA Symbol
Configuration.
Result: The OPC UA Symbols window is displayed. The logic controller starts the OPC UA
server.
2 Click Add.

NOTE: The IEC objects %MX, %IX, %QX are not directly accessible. To access IEC objects you must
first group their contents in located registers (refer to Relocation Table (see page 34)).

210 EIO0000003089 12/2019


OPC UA Server Configuration

Selecting OPC UA Server Symbols


The OPC UA Symbols window displays the variables available for selection as symbols:

Select IoConfig_Globals_Mapping to select all the available variables. Otherwise, select individual
symbols to share with OPC UA clients. A maximum of 1000 symbols can be selected.
Each symbol has the following properties:

Name Description
Symbols The variable name followed by the address of the variable.
Type The data type of the variable.
Access type
Click repeatedly to specify the access rights of the symbol: read-only ( )
(default), write-only ( ), or read/write ( ).
NOTE: Click in the Access type column of IoConfig_Globals_Mapping to set
the access rights of all the symbols at once.
Comment An optional comment.

Click Refresh to update the list of available variables.

EIO0000003089 12/2019 211


OPC UA Server Configuration

OPC UA Server Performance

Overview
The following provides capacity and performance information for the OPC UA server of the M251
Logic Controller. Design considerations are also provided to help optimize the performance of the
OPC UA server.

System Configurations Used to Evaluate Performance


OPC UA server performance is determined by the system configuration, the number of symbols
being published, and the percentage of symbols being refreshed.
The following table presents the number of elements in small, medium, and large sample
configurations used for evaluating OPC UA server performance:

Elements Small Medium Large


EtherNet/IP adapters 0 7 0
Expansion modules 0 5 7
CANopen slave devices 0 1 63
PTO functions 0 4 4
HSC functions 0 8 8
Profibus connections 0 0 1
Modbus TCP slave devices 0 6 64

This table presents average read/write request times for each of the sample configurations and for
different numbers of symbols:

Average Read/Write Request Times


Number of Symbols
Configuration 50 100 250 400 500 1000
Small 42 ms 70 ms 151 ms 232 ms 284 ms 554 ms
Medium 73 ms 121 ms 265 ms 412 ms 514 ms 1024 ms
Large 520 ms 895 ms 2045 ms 3257 ms 4071 ms 7153 ms

The following tables present the average time required to refresh a monitored set of symbols using
a sampling rate of 200 ms and a publishing interval of 200 ms.

212 EIO0000003089 12/2019


OPC UA Server Configuration

This table presents the average time required to refresh 100% of symbols for each of the sample
configurations:

Average Time to Refresh 100% of Symbols


Number of Symbols
Configuration 100 400 1000
Small 214 ms 227 ms 254 ms
Medium 224 ms 250 ms 292 ms
Large 234 ms 330 ms 800 ms

This table presents the average time required to refresh 50% of symbols for each of the sample
configurations:

Average Time to Refresh 50% of Symbols


Number of Symbols
Configuration 100 400 1000
Small 211 ms 220 ms 234 ms
Medium 219 ms 234 ms 254 ms
Large 284 ms 300 ms 660 ms

This table presents the average time required to refresh 1% of symbols for each of the sample
configurations:

Average Time to Refresh 1% of Symbols


Number of Symbols
Configuration 100 400 1000
Small 210 ms 210 ms 212 ms
Medium 215 ms 217 ms 220 ms
Large 270 ms 277 ms 495 ms

EIO0000003089 12/2019 213


OPC UA Server Configuration

Optimizing OPC UA Server Performance


The OPC UA server functionality is dependent on external communication networks, external
device performance, and other external parameters. Data transmitted may be delayed or other
possible communication errors may arise that impose practical limits on machine control. Do not
use the OPC UA server functionality for safety-related data or other time-dependent purposes.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Do not allow safety-related data in OPC UA server data exchanges.
 Do not use OPC UA server data exchanges for any critical or time-dependent purposes.
 Do not use OPC UA server data exchanges to change equipment states without having done
a risk analysis and implementing appropriate safety-related measures.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The above tables can be useful in determining whether OPC UA server performance is within
acceptable limits. Be aware, however, that other external factors influence overall system
performance, such as the volume of Ethernet traffic.
To optimize OPC UA server performance, consider the following:
 Minimize Ethernet traffic by setting the Min. publishing interval to the lowest value that yields an
acceptable response time.
 The task cycle time (see page 41) configured for the M251 Logic Controller must be less than
the configured Min. publishing interval value.
 Configuring a Max. number of sessions (the number of OPC UA clients that can simultaneously
connect to the OPC UA server) value of greater than 1 decreases the performance of all
sessions.
 The sampling rate determines the frequency at which data is exchanged. Tune the Sampling
rates (ms) value to product the lowest response time that does not adversely affect the overall
performance of the logic controller.

214 EIO0000003089 12/2019


Modicon M251 Logic Controller
Post Configuration
EIO0000003089 12/2019

Chapter 16
Post Configuration

Post Configuration

Introduction
This chapter describes how to generate and configure the post configuration file of the Modicon
M251 Logic Controller.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Post Configuration Presentation 216
Post Configuration File Management 218
Post Configuration Example 220

EIO0000003089 12/2019 215


Post Configuration

Post Configuration Presentation

Introduction
Post configuration is an option that allows you to modify some parameters of the application
without changing the application. Post configuration parameters are defined in a file called
Machine.cfg, which is stored in the controller.
By default, all parameters are set in the application.The parameters defined in the Post
Configuration file are used instead of the corresponding parameters defined in the application. Not
all parameters have to be specified in the Post Configuration file (for example: one parameter can
change the IP address without changing the Gateway Address).

Parameters
The Post Configuration file allows you to change network parameters.
Ethernet parameters:
 IP Address
 Subnet Mask
 Gateway Address
 Transfer Rate
 IP Config Mode
 Device Name
 IP Master Address (see page 151)

Serial Line parameters, for each serial line in the application (embedded port or PCI module):
 Baud rate
 Parity
 Data bits
 Stop bit

Profibus parameters, for each Profibus in the application (TM4 module):


 Station address
 Baud rate

NOTE: Parameter updates with a Post Configuration file that impacts parameters used by other
devices via a communication port are not updated in the other devices.
For example, if the IP address used by an HMI is updated in the configuration with a Post
Configuration file, the HMI uses the previous address. You must update the address used by the
HMI independently.

216 EIO0000003089 12/2019


Post Configuration

Operating Mode
The Post Configuration file is read after:
 A Reset Warm command (see page 62)
 A Reset Cold command (see page 62)
 A reboot (see page 64)
 An application download (see page 66)

Refer to Controller States and Behaviors (see page 47) for further details on controller states and
transitions.

EIO0000003089 12/2019 217


Post Configuration

Post Configuration File Management

Introduction
The file Machine.cfg is located in the directory /usr/cfg.
Each parameter is specified by a variable type, variable ID, and value. The format is:
id[moduleType].pos[param1Id].id[param2Id].param[param3Id].paramField=va
lue
where you have to modify only value.
Each parameter is defined on three lines in the Post Configuration file:
 The first line describes the internal 'path' for this parameter.
 The second line is a comment describing the parameter in a comprehensive way.
 The third line is the definition of the parameter (as described above) with its value.

Post Configuration File Generation


The Post Configuration file (Machine.cfg) is generated by EcoStruxure Machine Expert.
To generate the file, proceed as follows:

Step Action
1 In the menu bar, choose Build → Post Configuration → Generate...
Result: An explorer window is displayed.
2 Select the destination folder of the Post Configuration file.
3 Click OK.

When you use EcoStruxure Machine Expert to create a Post Configuration file (Generate), it reads
the value of each parameter assigned in your application program and then writes the values to
the Machine.cfg Post Configuration file. After generating a Post Configuration file, review the file
and remove any parameter assignments that you wish to remain under the control of your
application. Keep only those parameter assignments that you wish changed by the Post
Configuration function that are necessary to make your application portable and then modify those
values appropriately.

Post Configuration File Transfer


After creating and modifying your Post Configuration file, transfer it to the /usr/cfg directory of
the controller. The controller does not read the Machine.cfg file unless it is in this directory.
You can transfer the Post Configuration file by the following methods:
 SD card (see page 228) (with the proper script)
 Download through the FTP server (see page 121)
 Download with EcoStruxure Machine Expert controller device editor (see page 72)

218 EIO0000003089 12/2019


Post Configuration

Modifying a Post Configuration File


If the Post Configuration file is located in the PC, use a text editor to modify it.
NOTE: Do not change the text file encoding. The default encoding is ANSI.
To modify the Post Configuration file directly in the controller, use the Setup menu of the Web
server (see page 105).
To modify the Post Configuration file in the controller with EcoStruxure Machine Expert in online
mode:

Step Action
1 In the Devices tree, click the controller name.
2 Click Build → Post Configuration → Edit...
Result: The Post Configuration file opens in a text editor.
3 Edit the file.
4 If you want to apply the modifications after saving them, select Reset device after sending.
5 Click Save as.
6 Click Close.

NOTE: If the parameters are invalid, they are ignored.

Deleting the Post Configuration File


You can delete the Post Configuration file by the following methods:
 SD card (with the delete script)
 Through the FTP server (see page 121)
 Online with EcoStruxure Machine Expert controller device editor (see page 72), Files tab

For more information on Files tab of the Device Editor, refer to EcoStruxure Machine Expert
Programming Guide.
NOTE:
The parameters defined in the application are used instead of the corresponding parameters
defined in the Post Configuration file after:
 A Reset Warm command (see page 62)
 A Reset Cold command (see page 62)
 A reboot (see page 64)
 An application download (see page 66)

EIO0000003089 12/2019 219


Post Configuration

Post Configuration Example

Post Configuration File Example for the TM251MESE


# TM251MESE / Ethernet_1 / IPAddress
# Ethernet IP address
id[45000].pos[2].id[45111].param[0] = [192, 168, 2, 24]

# TM251MESE / Ethernet_1 / SubnetMask


# Ethernet IP mask
id[45000].pos[2].id[45111].param[1] = [255, 255, 255, 0]

# TM251MESE / Ethernet_1 / GatewayAddress


# Ethernet IP gateway address
id[45000].pos[2].id[45111].param[2] = [0, 0, 0, 0]

# TM251MESE / Ethernet_1 / IPConfigMode


# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP
id[45000].pos[2].id[45111].param[4] = 0

# TM251MESE / Ethernet_1 / DeviceName


# Name of the device on the Ethernet network
id[45000].pos[2].id[45111].param[5] = 'my_Device'

# TM251MESE / Ethernet_2 / IPAddress


# Ethernet IP address
id[45000].pos[3].id[111].param[0] = [192, 168, 1, 24]

# TM251MESE / Ethernet_2 / SubnetMask


# Ethernet IP mask
id[45000].pos[3].id[111].param[1] = [255, 255, 255, 0]

# TM251MESE / Ethernet_2 / GatewayAddress


# Ethernet IP gateway address
id[45000].pos[3].id[111].param[2] = [0, 0, 0, 0]

220 EIO0000003089 12/2019


Post Configuration

# TM251MESE / Ethernet_2 / IPConfigMode


# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP
id[45000].pos[3].id[111].param[4] = 0

# TM251MESE / Ethernet_2 / DeviceName


# Name of the device on the Ethernet network
id[45000].pos[3].id[111].param[5] = 'my_Device'

# TM251MESE / Serial_Line_1 / Serial Line Configuration / Baudrate


# Serial Line Baud Rate in bit/s
id[45000].pos[4].id[40101].param[10000].Bauds = 115200

# TM251MESE / Serial_Line_1 / Serial Line Configuration / Parity


# Serial Line Parity (0=None, 1=Odd, 2=Even)
id[45000].pos[4].id[40101].param[10000].Parity = 0

# TM251MESE / Serial_Line_1 / Serial Line Configuration / DataBits


# Serial Line Data bits (7 or 8)
id[45000].pos[4].id[40101].param[10000].DataFormat = 8

# TM251MESE / Serial_Line_1 / Serial Line Configuration / StopBits


# Serial Line Stop bits (1 or 2)
id[45000].pos[4].id[40101].param[10000].StopBit = 1

Post Configuration File Example for the TM251MESC


# TM251MESC / Ethernet_1 / IPAddress
# Ethernet IP address
id[45000].pos[2].id[45111].param[0] = [0, 0, 0, 0]

# TM251MESC / Ethernet_1 / SubnetMask


# Ethernet IP mask
id[45000].pos[2].id[45111].param[1] = [0, 0, 0, 0]

EIO0000003089 12/2019 221


Post Configuration

# TM251MESC / Ethernet_1 / GatewayAddress


# Ethernet IP gateway address
id[45000].pos[2].id[45111].param[2] = [0, 0, 0, 0]

# TM251MESC / Ethernet_1 / IPConfigMode


# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP
id[45000].pos[2].id[45111].param[4] = 0

# TM251MESC / Ethernet_1 / DeviceName


# Name of the device on the Ethernet network
id[45000].pos[2].id[45111].param[5] = 'my_Device'

# TM251MESC / Serial_Line_1 / Serial Line Configuration / Baudrate


# Serial Line Baud Rate in bit/s
id[45000].pos[4].id[40101].param[10000].Bauds = 115200

# TM251MESC / Serial_Line_1 / Serial Line Configuration / Parity


# Serial Line Parity (0=None, 1=Odd, 2=Even)
id[45000].pos[4].id[40101].param[10000].Parity = 0

# TM251MESC / Serial_Line_1 / Serial Line Configuration / DataBits


# Serial Line Data bits (7 or 8)
id[45000].pos[4].id[40101].param[10000].DataFormat = 8

# TM251MESC / Serial_Line_1 / Serial Line Configuration / StopBits


# Serial Line Stop bits (1 or 2)
id[45000].pos[4].id[40101].param[10000].StopBit = 1

222 EIO0000003089 12/2019


Modicon M251 Logic Controller
Connecting a Modicon M251 Logic Controller to a PC
EIO0000003089 12/2019

Chapter 17
Connecting a Modicon M251 Logic Controller to a PC

Connecting a Modicon M251 Logic Controller to a PC

Connecting the Controller to a PC

Overview
To transfer, run, and monitor the applications, connect the controller to a computer, that has
EcoStruxure Machine Expert installed, using either a USB cable or an Ethernet connection (for
those references that support an Ethernet port).

NOTICE
INOPERABLE EQUIPMENT
Always connect the communication cable to the PC before connecting it to the controller.
Failure to follow these instructions can result in equipment damage.

USB Powered Download


In order to execute limited operations, the M251 Logic Controller has the capability to be powered
through the USB Mini-B port. A diode mechanism avoids having the logic controller both powered
by USB and by the normal power supply, or to supply voltage on the USB port.
When powered only by USB, the logic controller executes the firmware and the boot project (if any)
and the I/O board is not powered during boot (same duration as a normal boot). USB powered
download initializes the internal flash memory with some firmware or some application and
parameters when the controller is powered by USB. The preferred tool to connect to the controller
is the Controller Assistant. Refer to the EcoStruxure Machine Expert Controller Assistant User
Guide.
The controller packaging allows easy access to USB Mini-B port with minimum opening of the
packaging. You can connect the controller to the PC with a USB cable. Long cables are not suitable
for the USB powered download.

WARNING
INSUFFICENT POWER FOR USB DOWNLOAD
Do not use a USB cable longer than 3m (9.8 ft) for USB powered download.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003089 12/2019 223


Connecting a Modicon M251 Logic Controller to a PC

NOTE: It is not intended that you use the USB Powered Download on an installed controller.
Depending on the number of I/O expansion modules in the physical configuration of the installed
controller, there may be insufficient power from your PC USB port to accomplish the download.

USB Mini-B Port Connection


TCSXCNAMUM3P: This USB cable is suitable for short duration connections such as quick
updates or retrieving data values.
BMXXCAUSBH018: Grounded and shielded, this USB cable is suitable for long duration
connections.
NOTE: You can only connect 1 controller or any other device associated with EcoStruxure Machine
Expert and its component to the PC at any one time.
The USB Mini-B Port is the programming port you can use to connect a PC with a USB host port
using EcoStruxure Machine Expert software. Using a typical USB cable, this connection is suitable
for quick updates of the program or short duration connections to perform maintenance and inspect
data values. It is not suitable for long-term connections such as commissioning or monitoring
without the use of specially adapted cables to help minimize electromagnetic interference.

WARNING
UNINTENDED EQUIPMENT OPERATION OR INOPERABLE EQUIPMENT
 You must use a shielded USB cable such as a BMX XCAUSBH0•• secured to the functional
ground (FE) of the system for any long-term connection.
 Do not connect more than one controller or bus coupler at a time using USB connections.
 Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The communication cable should be connected to the PC first to minimize the possibility of
electrostatic discharge affecting the controller.

224 EIO0000003089 12/2019


Connecting a Modicon M251 Logic Controller to a PC

To connect the USB cable to your controller, follow the steps below:

Step Action
1 1a If making a long-term connection using the cable BMXXCAUSBH018, or other cable with a
ground shield connection, be sure to securely connect the shield connector to the functional
ground (FE) or protective ground (PE) of your system before connecting the cable to your
controller and your PC.
1b If making a short-term connection using the cable TCSXCNAMUM3P or other non-grounded
USB cable, proceed to step 2.
2 Connect your USB cable to the computer.
3 Open the hinged access cover.
4 Connect the Mini connector of your USB cable to the controller USB connector.

Ethernet Port Connection


You can also connect the controller to a PC using an Ethernet cable.

To connect the controller to the PC, do the following:

Step Action
1 Connect the Ethernet cable to the PC.
2 Connect the Ethernet cable to either of the Ethernet 1 ports on the controller.

EIO0000003089 12/2019 225


Connecting a Modicon M251 Logic Controller to a PC

226 EIO0000003089 12/2019


Modicon M251 Logic Controller
SD Card
EIO0000003089 12/2019

Chapter 18
SD Card

SD Card

Introduction
This chapter describes how to transfer firmware, application, using an SD card to the Modicon
M251 Logic Controller.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Script Files 228
SD Card Commands 229
Updating Modicon M251 Logic Controller Firmware 236

EIO0000003089 12/2019 227


SD Card

Script Files

Overview
The following describes how to write script files (default script file or dynamic script file) to be
executed from an SD card or by an application using the ExecScript function block.
Script files can be used to:
 Configure the Ethernet firewall (see page 163).
 Perform file transfer operations. The script files for these commands can be generated
automatically and the necessary files copied to the SD card using the Mass Storage (USB or
SD Card) command.
 Change the Modbus slave port (see page 155) for Modbus TCP data exchanges.

Script Syntax Guidelines


The following describes the script syntax guidelines:
 End every line of a command in the script with a ";".
 If the line begins with a ";", the line is a comment.
 The maximum number of lines in a script file is 50.
 The syntax is not case-sensitive.
 If the syntax is not respected in the script file, the script file is not executed. This means, for
example, that the firewall configuration remains in the previous state.
NOTE: If the script file is not executed, a log file is generated. The log file location in the controller
is /usr/Syslog/FWLog.txt.

228 EIO0000003089 12/2019


SD Card

SD Card Commands

Introduction
The Modicon M251 Logic Controller allows file transfers with an SD card.
To upload or download files to the controller with an SD card, use one of the following methods:
 The clone function (see page 230) (use of an empty SD card)
 A script stored in the SD card

When an SD card is inserted into the SD card slot of the controller, the firmware searches and
executes the script contained in the SD card (/sys/cmd/Script.cmd).
NOTE: The controller operation is not modified during file transfer.
For file transfer commands, the Mass Storage (USB or SDCard) editor lets you generate and copy
the script and all necessary files into the SD card.
NOTE: The Modicon M251 Logic Controller accepts only SD cards formatted in FAT or FAT32.
The SD card must have a label. To add a label, insert the SD card in your PC, right-click on the
drive in Windows Explorer and choose Properties.

WARNING
UNINTENDED EQUIPMENT OPERATION
 You must have operational knowledge of your machine or process before connecting this
device to your controller.
 Ensure that guards are in place so that any potential unintended equipment operation will not
cause injury to personnel or damage to equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003089 12/2019 229


SD Card

If you remove power to the device, or there is a power outage or communication interruption during
the transfer of the application, your device may become inoperative. If a communication
interruption or a power outage occurs, reattempt the transfer. If there is a power outage or
communication interruption during a firmware update, or if an invalid firmware is used, your device
will become inoperative. In this case, use a valid firmware and reattempt the firmware update.

NOTICE
INOPERABLE EQUIPMENT
 Do not interrupt the transfer of the application program or a firmware change once the transfer
has begun.
 Re-initiate the transfer if the transfer is interrupted for any reason.
 Do not attempt to place the device into service until the file transfer has completed
successfully.
Failure to follow these instructions can result in equipment damage.

Clone Function
The clone function allows you to upload the application from one controller and to download it only
to a same controller reference.
This function clones every parameter of the controller (for example applications, firmware, data file,
post configuration). Refer to Memory Mapping (see page 25).
NOTE: User access rights can only be copied if the Include User Rights button has previously been
clicked on the Clone Management subpage of the Web server.
By default, clone is allowed without using the function block FB_ControlClone. If you want to restrict
access to the clone feature, you can remove the access rights of the USBExecCommand object
on Everyone group (see page 80). As a result, cloning will be not allowed without using
FB_ControlClone. For more details about this function block, refer to the M262 System Library
Guide (see Modicon M251 Logic Controller, System Functions and Variables, PLCSystem Library
Guide). For more details about Access Rights, refer to the EcoStruxure Machine Expert
Programming Guide.
If you wish to control access to the cloned application in the target controller, you must use the
Include users rights button (on the Clone Management subpage of the Web Server
(see page 118)) of the source controller before doing the clone operation. For more details about
Access Rights, refer to the EcoStruxure Machine Expert Programming Guide.

230 EIO0000003089 12/2019


SD Card

This procedure describes how to upload the application stored in the controller to your SD card:

Step Action
1 Erase an SD card and set the card label as follows:
CLONExxx
NOTE: The label must begin with ‘CLONE’ (not case sensitive), followed by any normal character.
2 Select if you want to clone the Users Rights. Refer to the Clone Management subpage
(see page 118) of the web server.
3 Remove power from the controller.
4 Insert the prepared SD card in the controller.
5 Restore power to the controller.
Result: The clone procedure starts automatically. During the clone procedure, the PWR and I/O
LEDs are ON and the SD LED flashes regularly.
NOTE: The clone procedure lasts 2 or 3 minutes.
Result: At the end of the clone procedure, the SD LED is ON and the controller starts in normal
application mode. If an error was detected, the ERR LED is ON and the controller is in STOPPED
state.
6 Remove the SD card from the controller.

This procedure describes how to download the application stored in the SD card to your controller:

Step Action
1 Remove power from the controller.
2 Insert the SD card into the controller.
3 Restore power to the controller.
Result: The download procedure starts and the SD LED is flashing during this procedure.
4 Wait until the end of the download:
 If the SD LED (green) is ON, and the ERR LED (red) flashes regularly, the download ended
successfully.
 If the SD LED (green) is OFF, and the ERR and I/O LEDs (red) flash regularly, an error is
detected.
5 Remove the SD card to restart the controller.

NOTE: If you wish to control access to the cloned application in the target controller, you will need
to enable and establish user access-rights, and any Web Server/FTP passwords, which are
controller-specific. For more details about Access Rights, refer to the EcoStruxure Machine Expert
Programming Guide.
NOTE: Downloading a cloned application to the controller will first remove the existing application
from controller memory, regardless of any user access-rights that may be enabled in the target
controller.

EIO0000003089 12/2019 231


SD Card

Script and Files Generation with Mass Storage


Click Project → Mass Storage (USB or SDCard) in the main menu:

Element Description
New Create a new script.
Open Open a script.
Macros Insert a Macro.
A macro is a sequence of unitary commands. A macro helps to perform many common
operations such as upload application, download application, and so on.
Generate Generate the script and all necessary files on the SD card.
Command Basic instructions.
Source Source file path on the PC or the controller.
Destination Destination directory on the PC or the controller.
Add New Add a script command.
Move Up/Down Change the script commands order.
Delete Delete a script command.

232 EIO0000003089 12/2019


SD Card

Commands descriptions:

Command Description Source Destination Syntax


Download Downloads a file from Select the file to Select the 'Download
the SD card to the download. controller "/usr/Cfg/*"'
controller. destination
directory.
SetNodeName Sets the node name of New node name. Controller node 'SetNodeName
the controller. name "Name_PLC"'
Resets the node name Default node name. Controller node 'SetNodeName ""'
of the controller. name
Upload Uploads files contained Select the directory. - 'Upload "/usr/*"'
in a controller directory
to the SD card.
Delete Deletes files contained Select the directory and - 'Delete
in a controller directory. enter a specific file name "/usr/SysLog/*"'
Important: by default, all
NOTE: Delete "*" does
directory files are
not delete system files.
selected.

Removes the - - 'Delete "/usr/*"'


UserRights from the
controller.
Deletes the files - - 'Delete "/sd0/*"' or
contained in the SD 'Delete
card or a folder of the "/sd0/folder name"'
SD card
Reboot Restarts the controller - - 'Reboot'
(only available at the
end of the script).

NOTE: When User Rights are activated on a controller and if the user is not allowed to
read/write/delete file system, scripts used to Upload/Download/Delete files are disabled. It includes
the clone operation. For more details about User Rights, refer to the EcoStruxure Machine Expert
Programming Guide.

EIO0000003089 12/2019 233


SD Card

This table describes the macros:

Macros Description Directory/Files


Download App Download the application from the SD card to the /usr/App/*.app
controller. /usr/App/*.crc
/usr/App/*.map
Upload App Upload the application from the controller to the SD
card. /usr/App/*.conf(1)

Download Sources Download the project archive from the SD card to /usr/App/*.prj
the controller.
Upload Sources Upload the project archive from the controller to the
SD card.
Download Multi-files Download multiple files from the SD card to a Defined by user
controller directory.
Upload Log Upload the log files from the controller to the SD /usr/Log/*.log
card.
(1) If OPC UA (see page 207) is configured.

Reset the User Rights to Default


You can manually create a script to remove the user rights, along with the application, from the
controller. This script must contain this command:
delete /usr/*
Reboot
NOTE: This command also removes user application and data.

Step Action
1 Remove power from the controller.
2 Insert the prepared SD card in the source controller.
3 Restore power to the source controller.
Result: The copy starts automatically. During the copy, the PWR and I/O LEDs are ON and the SD
LED flashes regularly.
4 Wait until the copy is completed.
Result: The SD LED is ON and the controller reboots with default user rights. If an error was
detected, the ERR LED is ON and the controller is in STOPPED state.

234 EIO0000003089 12/2019


SD Card

Transfer Procedure

WARNING
UNINTENDED EQUIPMENT OPERATION
 You must have operational knowledge of your machine or process before connecting this
device to your controller.
 Ensure that guards are in place so that any potential unintended equipment operation will not
cause injury to personnel or damage to equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Step Action
1 Create the script with the Mass Storage (USB or SDCard) editor.
2 Click Generate... and select the SD card root directory.
Result: The script and files are transferred on the SD card.
3 Insert the SD card into the controller.
Result: The transfer procedure starts and the SD LED is flashing during this procedure.
4 Wait until the end of the download:
 If the SD LED (green) is ON, and the ERR LED (red) flashes regularly, the download ended
successfully.
 If the SD LED (green) is OFF, and the ERR and I/O LEDs (red) flash regularly, an error is
detected.
5 Remove the SD card from the controller.
NOTE: Changes will be applied after next restart.

When the controller has executed the script, the result is logged on the SD card (file
/sys/cmd/Cmd.log).

WARNING
UNINTENDED EQUIPMENT OPERATION
Consult the controller state and behavior diagram in this document to understand the state that
will be assumed by the controller after you cycle power.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003089 12/2019 235


SD Card

Updating Modicon M251 Logic Controller Firmware

Introduction
The firmware updates for Modicon M251 Logic Controller are available on the
http://www.schneider-electric.com website (in .zip format).
Updating the firmware is possible by:
 Using an SD card with a compatible script file
 Using the Controller Assistant

Performing a firmware update deletes the current application program in the device, including the
Boot Application in Flash memory.

NOTICE
LOSS OF APPLICATION DATA
 Perform a backup of the application program to the hard disk of the PC before attempting a
firmware update.
 Restore the application program to the device after a successful firmware update.
Failure to follow these instructions can result in equipment damage.

If you remove power to the device, or there is a power outage or communication interruption during
the transfer of the application, your device may become inoperative. If a communication
interruption or a power outage occurs, reattempt the transfer. If there is a power outage or
communication interruption during a firmware update, or if an invalid firmware is used, your device
will become inoperative. In this case, use a valid firmware and reattempt the firmware update.

NOTICE
INOPERABLE EQUIPMENT
 Do not interrupt the transfer of the application program or a firmware change once the transfer
has begun.
 Re-initiate the transfer if the transfer is interrupted for any reason.
 Do not attempt to place the device into service until the file transfer has completed
successfully.
Failure to follow these instructions can result in equipment damage.

236 EIO0000003089 12/2019


SD Card

The serial line ports of your controller are configured for the Machine Expert protocol by default
when new or when you update the controller firmware. The Machine Expert protocol is
incompatible with that of other protocols such as Modbus Serial Line. Connecting a new controller
to, or updating the firmware of a controller connected to, an active Modbus configured serial line
can cause the other devices on the serial line to stop communicating. Make sure that the controller
is not connected to an active Modbus serial line network before first downloading a valid application
having the concerned port or ports properly configured for the intended protocol.

NOTICE
INTERRUPTION OF SERIAL LINE COMMUNICATIONS
Be sure that your application has the serial line ports properly configured for Modbus before
physically connecting the controller to an operational Modbus Serial Line network.
Failure to follow these instructions can result in equipment damage.

Updating Firmware by SD Card


Follow these steps to update the firmware by an SD card:

Step Action
1 Extract the .zip file to the root of the SD card.
NOTE: The SD card folder \sys\cmd\ contains the download script file.
2 Remove power from the controller.
3 Insert the SD card into the controller.
4 Restore power to the controller.
NOTE: The SD LED (green) is flashing during the operation.
5 Wait until the end of the download:
 If the SD LED (green) is ON, and the ERR LED (red) flashes regularly, the download ended
successfully.
 If the SD LED (green) is OFF, and the ERR and I/O LEDs (red) flash regularly, an error is
detected.
6 Remove the SD card from the controller.
Result: The controller restarts automatically with new firmware if the download ended successfully.

EIO0000003089 12/2019 237


SD Card

Updating Firmware by Controller Assistant


To update the firmware, you must open the Controller Assistant. Click Tools → External Tools →
Open Controller Assistant.
To execute a complete firmware update of a controller without replacing the Boot application and
data, proceed as follows:

Step Action
1 On the Home dialog, click the Read from.... controller button.
Result: The Controller selection dialog opens.
2 Select the required connection type and controller and click the Reading button.
Result: The image is transmitted from the controller to the computer.
After this has been accomplished successfully, you are automatically redirected to the Home dialog.
3 Click the button New / Process... and then Update firmware....
Result: The dialog for updating the firmware opens.
4 Execute individual steps for updating the firmware in the current image (Changes are only effected in
the image on your computer).
In the final step, you can decide whether you want to create a backup copy of the image read by the
controller.
Result: Following the update of the firmware, you are automatically returned to the Home dialog.
5 On the Home dialog, click the Write on.... controller button.
Result: The Controller selection dialog opens.
6 Select the required connection type and controller and click the Write button.
Result: The image is transmitted from your computer to the controller.
After the transmission, you are automatically returned to the Home dialog.

For more information about the firmware update and creating a new flash disk with firmware, refer
to Project Settings - Firmware Update and Flash Memory Organization (see page 30).

238 EIO0000003089 12/2019


Modicon M251 Logic Controller

EIO0000003089 12/2019

Chapter 19
Firmware Management

Firmware Management

Updating TM3 Expansion Modules Firmware

Overview
The firmware update for the controller and the expansion modules are available on the Schneider
Electric website (in .zip format).

Downloading Firmware to TM3 Expansion Modules

The firmware can be updated in:


 TM3X•HSC•
 TM3DI16 and TM3DI16G with firmware version (SV) ≥ 2.0
 TM3A• and TM3T• with firmware version (SV) ≥ 2.0

NOTE: The firmware version (SV) is found on the packaging and product labels.
Firmware updates are performed if, during a power on, at least one firmware file is present in the
/usr/TM3fwupdate/ directory of controller. You can download the file(s) to the controller using
the SD card, an FTP file transfer or through EcoStruxure Machine Expert.
The controller updates the firmware of the TM3 expansion modules on the I/O bus, including those
that are:
 Connected remotely, using a TM3 Transmitter/Receiver module.
 In configurations comprising a mix of TM3 and TM2 expansion modules.

The following table describes how to download firmware to one or more TM3 expansion modules
using an SD card:

Step Action
1 Insert an empty SD card into the PC.
2 Create the folder path /sys/Cmd and create a file called Script.cmd.
3 Edit the file and insert the following command for each firmware file you wish to transfer to the
controller:
Download "usr/TM3fwupdate/<filename>"
4 Create the folder path /usr/TM3fwupdate/ in the SD card root directory and copy the
firmware files to the TM3fwupdate folder.
5 Ensure that power is removed from controller.
6 Remove the SD card from the PC and insert it into the SD card slot of the controller.

EIO0000003089 12/2019 239


Step Action
7 Restore power to the controller. Wait until the end of the operation (until the SD LED is green
ON).
Result: The controller begins transferring the firmware file(s) from the SD card to the
/usr/TM3fwupdate in the controller. During this operation, the SD LED on the controller is
flashing. A SCRIPT.log file is created on the SD card and contains the result of the file transfer.
If an error is detected, the SD and ERR LEDs flash and the detected error is logged in
SCRIPT.log file.
8 Remove power from the controller.
9 Remove SD card from the controller.
10 Restore power to the controller.
Result: The controller transfers the firmware file(s) to the appropriate TM3 I/O module(s).
NOTE: The TM3 update process adds approximatively 15 seconds to the controller boot
duration.
11 Verify in the message logger of the controller that the firmware is successfully updated: Your
TM3 Module X successfully updated. X corresponds to the position of the module on
the bus.
NOTE: You can also obtain the logger information in the PlcLog.txt file in the
/usr/Syslog/ directory of the controller file system.
NOTE: If the controller encounters an error during the update, the update terminates with that
module.
12 If all targeted modules were successfully updated, delete the firmware file(s) from
/usr/TM3fwupdate/ folder on the controller.
You can delete the files directly using EcoStruxure Machine Expert or by creating and executing
a script containing the following command:
Delete "usr/TM3fwupdate/*"
NOTE: If a targeted module was not updated successfully, or there are no message logger
messages for all the targeted modules, see the Recovery Procedure (see page 241) below.

240 EIO0000003089 12/2019


Recovery Procedure
If you remove power to the device, or there is a power outage or communication interruption during
the transfer of the application, your device may become inoperative. If a communication
interruption or a power outage occurs, reattempt the transfer. If there is a power outage or
communication interruption during a firmware update, or if an invalid firmware is used, your device
will become inoperative. In this case, use a valid firmware and reattempt the firmware update.

NOTICE
INOPERABLE EQUIPMENT
 Do not interrupt the transfer of the application program or a firmware change once the transfer
has begun.
 Re-initiate the transfer if the transfer is interrupted for any reason.
 Do not attempt to place the device into service until the file transfer has completed
successfully.
Failure to follow these instructions can result in equipment damage.

If, during the reattempted firmware update, the update prematurely terminates with an error, it
means that the communication interruption or power outage had damaged the firmware of one of
your modules in your configuration, and that module must be reinitialized.
NOTE: Once the firmware update process detects an error with the firmware in the destination
module, the update process is terminated. After you have reinitialized the damaged module
following the recovery procedure, any modules that followed the damaged module remain
unchanged and will need to have their firmware updated.
The following table describes how to reinitialize the firmware on TM3 expansion modules:

Step Action
1 Ensure that the correct firmware is present in the /usr/TM3fwupdate/ directory of the
controller.
2 Remove power from the controller.
3 Disassemble from the controller all TM3 expansion modules that are functioning normally, up to
the first module to recover. Refer to the hardware guides of the modules for disassembly
instructions.
4 Apply power to the controller.
NOTE: The TM3 update process adds approximatively 15 seconds to the controller boot
duration.
5 Verify in the message logger of the controller that the firmware is successfully updated: Your
TM3 Module X successfully updated. X corresponds to the position of the module on the
bus.
6 Remove power from the controller.

EIO0000003089 12/2019 241


Step Action
7 Reassemble the TM3 expansion module configuration to the controller. Refer to the hardware
guides of the modules for assembly instructions.
8 Restore power to the controller.
Result: The controller transfers the firmware file(s) to the appropriate and yet to be updated TM3
I/O module(s).
NOTE: The TM3 update process adds approximatively 15 seconds to the controller boot
duration.
9 Verify in the message logger of the controller that the firmware is successfully updated: Your
TM3 Module X successfully updated. X corresponds to the position of the module on the
bus.
NOTE: You can also obtain the logger information in the Sys.log file in the /usr/Log
directory of the controller file system.
10 Delete the firmware file(s) from /usr/TM3fwupdate/ folder on the controller.

242 EIO0000003089 12/2019


Modicon M251 Logic Controller

EIO0000003089 12/2019

Appendices

Overview
This appendix lists the documents necessary for technical understanding of the Modicon M251
Logic Controller Programming Guide.

What Is in This Appendix?


The appendix contains the following chapters:
Chapter Chapter Name Page
A How to Change the IP Address of the Controller 245
B Functions to Get/Set Serial Line Configuration in User Program 249
C Controller Performance 255

EIO0000003089 12/2019 243


244 EIO0000003089 12/2019
Modicon M251 Logic Controller
ChangeIPAddress: Change IP Address of the Controller
EIO0000003089 12/2019

Appendix A
How to Change the IP Address of the Controller

How to Change the IP Address of the Controller

changeIPAddress: Change the IP address of the controller

Function Block Description


The changeIPAddress function block provides the capability to change dynamically a controller
IP address, its subnet mask and its gateway address. The function block can also save the
IP address so that it is used in subsequent reboots of the controller.
NOTE: Changing the IP addresses is only possible if the IP mode is configured to fixed IP address.
For more details, refer to IP Address Configuration (see page 97).
NOTE: For more information on the function block, use the Documentation tab of EcoStruxure
Machine Expert Library Manager Editor. For the use of this editor, refer EcoStruxure Machine
Expert Programming Guide (see EcoStruxure Machine Expert, Functions and Libraries User
Guide).

Graphical Representation

EIO0000003089 12/2019 245


ChangeIPAddress: Change IP Address of the Controller

Parameter Description

Input Type Comment


xExecute BOOL  Rising edge: action starts.
 Falling edge: resets outputs. If a falling edge occurs before the
function block has completed its action, the outputs operate in the
usual manner and are only reset if either the action is completed
or in the event that an error is detected. In this case, the
corresponding output values (xDone, xError, iError) are
present at the outputs for exactly one cycle.
xSave BOOL TRUE: save configuration for subsequent reboots of the controller.
eChannel changeIPAd- The input eChannel is the Ethernet port to be configured.
dress_Channel Depending on the number of the ports available on the controller, it is
one of 5 values (see page 247) in changeIPAddress_Channel (0
or 1).
i_abyIPAddress ARRAY[0..3] OF The new IP Address to be configured. Format: 0.0.0.0.
BYTE
NOTE: If this input is set to 0.0.0.0 then the controller default IP
addresses (see page 100) is configured.
i_abyIPMask ARRAY[0..3] OF The new subnet mask. Format: 0.0.0.0
BYTE
i_abyIPGateway ARRAY[0..3] OF The new gateway IP address. Format: 0.0.0.0
BYTE

Output Type Comment


xDone BOOL TRUE: if IP Addresses have been successfully configured or if
default IP Addresses have been successfully configured because
input i_abyIPAddress is set to 0.0.0.0.
xBusy BOOL Function block active.
xError BOOL  TRUE: error detected, function block aborts action.
 FALSE: no error has been detected.
eError changeIPAd- Error code of the detected error (see page 247).
dress_Error
xSaved BOOL Configuration saved for the subsequent reboots of the controller.
q_abyIPAddress ARRAY[0..3] Current controller IP address. Format: 0.0.0.0.
OF BYTE
q_abyIPMask ARRAY[0..3] Current subnet mask. Format: 0.0.0.0.
OF BYTE
q_abyIPGateway ARRAY[0..3] Current gateway IP address. Format: 0.0.0.0.
OF BYTE

246 EIO0000003089 12/2019


ChangeIPAddress: Change IP Address of the Controller

changeIPAddress_Channel: Ethernet port to be configured


The changeIPAddress_Channel enumeration data type contains the following values:

Enumerator Value Description


CHANNEL_ETHERNET_NETWORK 0 M241, M251MESC, M258, LMC058, LMC078: Ethernet port
M251MESE: Ethernet_2 port
CHANNEL_DEVICE_NETWORK 1 M241: TM4ES4 Ethernet port
M251MESE: Ethernet_1 port

changeIPAddress_Error: Error Codes


The changeIPAddress_Error enumeration data type contains the following values:

Enumerator Value Description


ERR_NO_ERROR 00 hex No error detected.
ERR_UNKNOWN 01 hex Internal error detected.
ERR_INVALID_MODE 02 hex IP address is not configured as a fixed IP address.
ERR_INVALID_IP 03 hex Invalid IP address.
ERR_DUPLICATE_IP 04 hex The new IP address is already used in the network.
ERR_WRONG_CHANNEL 05 hex Incorrect Ethernet communication port.
ERR_IP_BEING_SET 06 hex IP address is already being changed.
ERR_SAVING 07 hex IP addresses not saved due to a detected error or no non-volatile
memory present.
ERR_DHCP_SERVER 08 hex A DHCP server is configured on this Ethernet communication
port.

EIO0000003089 12/2019 247


ChangeIPAddress: Change IP Address of the Controller

248 EIO0000003089 12/2019


Modicon M251 Logic Controller
Functions to Get/Set Serial Line Configuration in User Program
EIO0000003089 12/2019

Appendix B
Functions to Get/Set Serial Line Configuration in User Program

Functions to Get/Set Serial Line Configuration in User Program

Overview
This section describes the functions to get/set the serial line configuration in your program.
To use these functions, add the M2xx Communication library.
For further information on adding a library, refer to the EcoStruxure Machine Expert Programming
Guide.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
GetSerialConf: Get the Serial Line Configuration 250
SetSerialConf: Change the Serial Line Configuration 251
SERIAL_CONF: Structure of the Serial Line Configuration Data Type 253

EIO0000003089 12/2019 249


Functions to Get/Set Serial Line Configuration in User Program

GetSerialConf: Get the Serial Line Configuration

Function Description
GetSerialConf returns the configuration parameters for a specific serial line communication
port.

Graphical Representation

Parameter Description

Input Type Comment


Link LinkNumber Link is the communication port number.
(see EcoStruxure
Machine Expert,
Modbus and ASCII
Read/Write
Functions,
PLCCommunication
Library Guide)
PointerToSerialConf POINTER TO PointerToSerialConf is the address of the configuration
SERIAL_CONF structure (variable of SERIAL_CONF type) in which the
(see page 253) configuration parameters are stored. The ADR standard function
must be used to define the associated pointer. (See the example
below.)

Output Type Comment


GetSerialConf WORD This function returns:
 0: The configuration parameters are returned
 255: The configuration parameters are not returned because:
 the function was not successful
 the function is in progress

Example
Refer to the SetSerialConf (see page 252) example.

250 EIO0000003089 12/2019


Functions to Get/Set Serial Line Configuration in User Program

SetSerialConf: Change the Serial Line Configuration

Function Description
SetSerialConf is used to change the serial line configuration.

Graphical Representation

NOTE: Changing the configuration of the Serial Line(s) port(s) during programming execution can
interrupt ongoing communications with other connected devices.

WARNING
LOSS OF CONTROL DUE TO CONFIGURATION CHANGE
Validate and test all the parameters of the SetSerialConf function before putting your program
into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Parameter Description

Input Type Comment


Link LinkNumber LinkNumber is the communication port number.
(see SoMachine,
Modbus and ASCII
Read/Write
Functions,
PLCCommunication
Library Guide)
PointerToSerialConf POINTER TO PointerToSerialConf is the address of the configuration
SERIAL_CONF structure (variable of SERIAL_CONF type) in which the new
(see page 253) configuration parameters are stored. The ADR standard function
must be used to define the associated pointer. (See the example
below.) If 0, set the application default configuration to the serial
line.

EIO0000003089 12/2019 251


Functions to Get/Set Serial Line Configuration in User Program

Output Type Comment


SetSerialConf WORD This function returns:
 0: The new configuration is set
 255: The new configuration is refused because:
 the function is in progress
 the input parameters are not valid

Example
VAR
MySerialConf: SERIAL_CONF
result: WORD;
END_VAR

(*Get current configuration of serial line 1*)


GetSerialConf(1, ADR(MySerialConf));

(*Change to modbus RTU slave address 9*)


MySerialConf.Protocol := 0; (*Modbus RTU/Machine Expert protocol
(in this case CodesysCompliant selects the protocol)*)
MySerialConf.CodesysCompliant := 0; (*Modbus RTU*)
MySerialConf.address := 9; (*Set modbus address to 9*)

(*Reconfigure the serial line 1*)


result := SetSerialConf(1, ADR(MySerialConf));

252 EIO0000003089 12/2019


Functions to Get/Set Serial Line Configuration in User Program

SERIAL_CONF: Structure of the Serial Line Configuration Data Type

Structure Description
The SERIAL_CONF structure contains configuration information about the serial line port. It
contains these variables:

Variable Type Description


Bauds DWORD baud rate
InterframeDelay WORD minimum time (in ms) between 2 frames in Modbus (RTU, ASCII)
FrameReceivedTimeout WORD In the ASCII protocol, FrameReceivedTimeout allows the system to
conclude the end of a frame at reception after a silence of the specified
number of ms. If 0 this parameter is not used.
FrameLengthReceived WORD In the ASCII protocol, FrameLengthReceived allows the system to
conclude the end of a frame at reception, when the controller received
the specified number of characters. If 0, this parameter is not used.
Protocol BYTE 0: Modbus RTU or Machine Expert (see CodesysCompliant)
1: Modbus ASCII
2: ASCII
Address BYTE Modbus address 0 to 255 (0 for Master)
Parity BYTE 0: none
1: odd
2: even
Rs485 BYTE 0: RS232
1: RS485
ModPol (polarizartion BYTE 0: no
resistor)
1: yes
DataFormat BYTE 7 bits or 8 bits
StopBit BYTE 1: 1 stop bit
2: 2 stop bits
CharFrameStart BYTE In the ASCII protocol, 0 means there is no start character in the frame.
Otherwise, the corresponding ASCII character is used to detect the
beginning of a frame in receiving mode. In sending mode, this character
is added at the beginning of the user frame.
CharFrameEnd1 BYTE In the ASCII protocol, 0 means there is no second end character in the
frame. Otherwise, the corresponding ASCII character is used to detect
the end of a frame in receiving mode. In sending mode, this character
is added at the end of the user frame.

EIO0000003089 12/2019 253


Functions to Get/Set Serial Line Configuration in User Program

Variable Type Description


CharFrameEnd2 BYTE In the ASCII protocol, 0 means there is no second end character in the
frame. Otherwise, the corresponding ASCII character is used (along
with CharFrameEnd1) to detect the end of a frame in receiving mode.
In sending mode, this character is added at the end of the user frame.
CodesysCompliant BYTE 0: Modbus RTU
1: Machine Expert (when Protocol = 0)
CodesysNetType BYTE not used

254 EIO0000003089 12/2019


Modicon M251 Logic Controller
M251 - Controller Performance
EIO0000003089 12/2019

Appendix C
Controller Performance

Controller Performance

Processing Performance

Introduction
This chapter provides information about the M251 processing performance.

Logic Processing
This table presents logic processing performance for various logical instructions:

IL Instruction Type Duration for 1000 Instructions


Addition/subtraction/multiplication of INT 42 μs
Addition/subtraction/multiplication of DINT 41 μs
Addition/subtraction/multiplication of REAL 336 μs
Division of REAL 678 μs
Operation on BOOLEAN, for example, Status:= Status 75 μs
and value
LD INT + ST INT 64 μs
LD DINT + ST DINT 49 μs
LD REAL + ST REAL 50 μs

Communication and System Processing Time


The communication processing time varies, depending on the number of sent/received requests.

EIO0000003089 12/2019 255


M251 - Controller Performance

256 EIO0000003089 12/2019


Modicon M251 Logic Controller
Glossary
EIO0000003089 12/2019

Glossary

A
analog output
Converts numerical values within the logic controller and sends out proportional voltage or current
levels.
application
A program including configuration data, symbols, and documentation.
application source
The collection of human-readable controller instructions, configuration data, HMI instructions,
symbols, and other program documentation. The application source file is saved on the PC and
you can download the application source file to most logic controllers. The application source file
is used to build the executable program that runs in the logic controller.
ARP
(address resolution protocol) An IP network layer protocol for Ethernet that maps an IP address to
a MAC (hardware) address.

B
BCD
(binary coded decimal) The format that represents decimal numbers between 0 and 9 with a set of
4 bits (a nybble/nibble, also titled as half byte). In this format, the 4 bits used to encode decimal
numbers have an unused range of combinations.
For example, the number 2,450 is encoded as 0010 0100 0101 0000.

BOOL
(boolean) A basic data type in computing. A BOOL variable can have one of these values: 0
(FALSE), 1 (TRUE). A bit that is extracted from a word is of type BOOL; for example, %MW10.4 is a
fifth bit of memory word number 10.
Boot application
(boot application) The binary file that contains the application. Usually, it is stored in the controller
and allows the controller to boot on the application that the user has generated.

EIO0000003089 12/2019 257


Glossary

BOOTP
(bootstrap protocol) A UDP network protocol that can be used by a network client to automatically
obtain an IP address (and possibly other data) from a server. The client identifies itself to the server
using the client MAC address. The server, which maintains a pre-configured table of client device
MAC addresses and associated IP addresses, sends the client its pre-configured IP address.
BOOTP was originally used as a method that enabled diskless hosts to be remotely booted over a
network. The BOOTP process assigns an infinite lease of an IP address. The BOOTP service
utilizes UDP ports 67 and 68.
byte
A type that is encoded in an 8-bit format, ranging from 00 hex to FF hex.

C
CFC
(continuous function chart) A graphical programming language (an extension of the IEC 61131-3
standard) based on the function block diagram language that works like a flowchart. However, no
networks are used and free positioning of graphic elements is possible, which allows feedback
loops. For each block, the inputs are on the left and the outputs on the right. You can link the block
outputs to the inputs of other blocks to create complex expressions.
configuration
The arrangement and interconnection of hardware components within a system and the hardware
and software parameters that determine the operating characteristics of the system.
continuous function chart language
A graphical programming language (an extension of the IEC61131-3 standard) based on the
function block diagram language that works like a flowchart. However, no networks are used and
free positioning of graphic elements is possible, which allows feedback loops. For each block, the
inputs are on the left and the outputs on the right. You can link the block outputs to inputs of other
blocks to create complex expressions.
control network
A network containing logic controllers, SCADA systems, PCs, HMI, switches, ...
Two kinds of topologies are supported:
 flat: all modules and devices in this network belong to same subnet.
 2 levels: the network is split into an operation network and an inter-controller network.

These two networks can be physically independent, but are generally linked by a routing device.
controller
Automates industrial processes (also known as programmable logic controller or programmable
controller).

258 EIO0000003089 12/2019


Glossary

CRC
(cyclical redundancy check) A method used to determine the validity of a communication
transmission. The transmission contains a bit field that constitutes a checksum. The message is
used to calculate the checksum by the transmitter according to the content of the message.
Receiving nodes, then recalculate the field in the same manner. Any discrepancy in the value of
the 2 CRC calculations indicates that the transmitted message and the received message are
different.

D
data log
The controller logs events relative to the user application in a data log.
device network
A network that contains devices connected to a specific communication port of a logic controller.
This controller is seen as a master from the devices point of view.
DHCP
(dynamic host configuration protocol) An advanced extension of BOOTP. DHCP is more
advanced, but both DHCP and BOOTP are common. (DHCP can handle BOOTP client requests.)
DINT
(double integer type) Encoded in 32-bit format.
DNS
(domain name system) The naming system for computers and devices connected to a LAN or the
Internet.
DTM
(device type manager) Classified into 2 categories:
 Device DTMs connect to the field device configuration components.
 CommDTMs connect to the software communication components.

The DTM provides a unified structure for accessing device parameters and configuring, operating,
and diagnosing the devices. DTMs can range from a simple graphical user interface for setting
device parameters to a highly sophisticated application capable of performing complex real-time
calculations for diagnosis and maintenance purposes.
DWORD
(double word) Encoded in 32-bit format.

E
EDS
(electronic data sheet) A file for fieldbus device description that contains, for example, the
properties of a device such as parameters and settings.

EIO0000003089 12/2019 259


Glossary

equipment
A part of a machine including sub-assemblies such as conveyors, turntables, and so on.
Ethernet
A physical and data link layer technology for LANs, also known as IEEE 802.3.
expansion bus
An electronic communication bus between expansion I/O modules and a controller or bus coupler.

F
FBD
(function block diagram) One of 5 languages for logic or control supported by the standard IEC
61131-3 for control systems. Function block diagram is a graphically oriented programming
language. It works with a list of networks, where each network contains a graphical structure of
boxes and connection lines, which represents either a logical or arithmetic expression, the call of
a function block, a jump, or a return instruction.
FE
(functional Earth) A common grounding connection to enhance or otherwise allow normal
operation of electrically sensitive equipment (also referred to as functional ground in North
America).
In contrast to a protective Earth (protective ground), a functional earth connection serves a purpose
other than shock protection, and may normally carry current. Examples of devices that use
functional earth connections include surge suppressors and electromagnetic interference filters,
certain antennas, and measurement instruments.
firmware
Represents the BIOS, data parameters, and programming instructions that constitute the operating
system on a controller. The firmware is stored in non-volatile memory within the controller.
flash memory
A non-volatile memory that can be overwritten. It is stored on a special EEPROM that can be
erased and reprogrammed.
freewheeling
When a logic controller is in freewheeling scan mode, a new task scan starts as soon as the
previous scan has been completed. Contrast with periodic scan mode.
FTP
(file transfer protocol) A standard network protocol built on a client-server architecture to exchange
and manipulate files over TCP/IP based networks regardless of their size.

260 EIO0000003089 12/2019


Glossary

H
HE10
Rectangular connector for electrical signals with frequencies below 3 MHz, complying with IEC
60807-2.

I
I/O
(input/output)
ICMP
(Internet control message protocol) Reports errors detected and provides information related to
datagram processing.
IEC
(international electrotechnical commission) A non-profit and non-governmental international
standards organization that prepares and publishes international standards for electrical,
electronic, and related technologies.
IEC 61131-3
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with
controller programming languages and defines 2 graphical and 2 textual programming language
standards. The graphical programming languages are ladder diagram and function block diagram.
The textual programming languages include structured text and instruction list.
IL
(instruction list) A program written in the language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (refer to IEC 61131-3).
instruction list language
A program written in the instruction list language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (see IEC 61131-3).
INT
(integer) A whole number encoded in 16 bits.
IP
(Internet protocol Part of the TCP/IP protocol family that tracks the Internet addresses of devices,
routes outgoing messages, and recognizes incoming messages.

EIO0000003089 12/2019 261


Glossary

K
KeepAlive
Messages sent by the OPC UA server to keep a subscription active. This is necessary when none
of the monitored items of data have been updated since the previous publication.

L
ladder diagram language
A graphical representation of the instructions of a controller program with symbols for contacts,
coils, and blocks in a series of rungs executed sequentially by a controller (see IEC 61131-3).
LD
(ladder diagram) A graphical representation of the instructions of a controller program with symbols
for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to
IEC 61131-3).
LINT
(long integer) A whole number encoded in a 64-bit format (4 times INT or 2 times DINT).

LRC
(longitudinal redundancy checking) An error-detection method for determining the correctness of
transmitted and stored data.
LREAL
(long real) A floating-point number encoded in a 64-bit format.
LWORD
(long word) A data type encoded in a 64-bit format.

M
MAC address
(media access control address) A unique 48-bit number associated with a specific piece of
hardware. The MAC address is programmed into each network card or device when it is
manufactured.
MAST
A processor task that is run through its programming software. The MAST task has 2 sections:
 IN: Inputs are copied to the IN section before execution of the MAST task.
 OUT: Outputs are copied to the OUT section after execution of the MAST task.

MIB
(management information base) An object database that is monitored by a network management
system like SNMP. SNMP monitors devices are defined by their MIBs. Schneider Electric has
obtained a private MIB, groupeschneider (3833).

262 EIO0000003089 12/2019


Glossary

monitored items
In OPC UA, the items of data (samples) made available by the OPC UA server that clients
subscribe to.
ms
(millisecond)
MSB
(most significant bit/byte The part of a number, address, or field that is written as the left-most
single value in conventional hexadecimal or binary notation.

N
network
A system of interconnected devices that share a common data path and protocol for
communications.
NMT
(network management) CANopen protocols that provide services for network initialization,
detected error control, and device status control.
node
An addressable device on a communication network.
notifications
In OPC UA, messages sent by the OPC UA server to inform clients that new items of data are
available.

P
PDO
(process data object) An unconfirmed broadcast message or sent from a producer device to a
consumer device in a CAN-based network. The transmit PDO from the producer device has a
specific identifier that corresponds to the receive PDO of the consumer devices.
PE
(Protective Earth) A common grounding connection to help avoid the hazard of electric shock by
keeping any exposed conductive surface of a device at earth potential. To avoid possible voltage
drop, no current is allowed to flow in this conductor (also referred to as protective ground in North
America or as an equipment grounding conductor in the US national electrical code).
post configuration
(post configuration) An option that allows to modify some parameters of the application without
changing the application. Post configuration parameters are defined in a file that is stored in the
controller. They are overloading the configuration parameters of the application.

EIO0000003089 12/2019 263


Glossary

program
The component of an application that consists of compiled source code capable of being installed
in the memory of a logic controller.
protocol
A convention or standard definition that controls or enables the connection, communication, and
data transfer between 2 computing system and devices.
publishing interval
In OPC UA, the frequency at which the OPC_UA server sends notifications to clients informing
them that data updates are available.

R
REAL
A data type that is defined as a floating-point number encoded in a 32-bit format.
RJ45
A standard type of 8-pin connector for network cables defined for Ethernet.
RPDO
(receive process data object) An unconfirmed broadcast message or sent from a producer device
to a consumer device in a CAN-based network. The transmit PDO from the producer device has a
specific identifier that corresponds to the receive PDO of the consumer devices.
RPI
(requested packet interval) The time period between cyclic data exchanges requested by the
scanner. EtherNet/IP devices publish data at the rate specified by the RPI assigned to them by the
scanner, and they receive message requests from the scanner with a period equal to RPI.
RTC
(real-time clock) A battery-backed time-of-day and calender clock that operates continuously, even
when the controller is not powered for the life of the battery.

S
sampling rate
In OPC UA, the frequency at which the OPC UA server reads items of data from connected
devices.
scan
A function that includes:
 reading inputs and placing the values in memory
 executing the application program 1 instruction at a time and storing the results in memory
 using the results to update outputs

264 EIO0000003089 12/2019


Glossary

SDO
(service data object) A message used by the field bus master to access (read/write) the object
directories of network nodes in CAN-based networks. SDO types include service SDOs (SSDOs)
and client SDOs (CSDOs).
SFC
(sequential function chart) A language that is composed of steps with associated actions,
transitions with associated logic condition, and directed links between steps and transitions. (The
SFC standard is defined in IEC 848. It is IEC 61131-3 compliant.)
SINT
(signed integer) A 15-bit value plus sign.
SNMP
(simple network management protocol) A protocol that can control a network remotely by polling
the devices for their status and viewing information related to data transmission. You can also use
it to manage software and databases remotely. The protocol also permits active management
tasks, such as modifying and applying a new configuration.
ST
(structured text) A language that includes complex statements and nested instructions (such as
iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
string
A variable that is a series of ASCII characters.

T
task
A group of sections and subroutines, executed cyclically or periodically for the MAST task or
periodically for the FAST task.
A task possesses a level of priority and is linked to inputs and outputs of the controller. These I/O
are refreshed in relation to the task.
A controller can have several tasks.
TCP
(transmission control protocol) A connection-based transport layer protocol that provides a
simultaneous bi-directional transmission of data. TCP is part of the TCP/IP protocol suite.
terminal block
(terminal block) The component that mounts in an electronic module and provides electrical
connections between the controller and the field devices.
TPDO
(transmit process data object) An unconfirmed broadcast message or sent from a producer device
to a consumer device in a CAN-based network. The transmit PDO from the producer device has a
specific identifier that corresponds to the receive PDO of the consumer devices.

EIO0000003089 12/2019 265


Glossary

U
UDINT
(unsigned double integer) Encoded in 32 bits.
UDP
(user datagram protocol) A connectionless mode protocol (defined by IETF RFC 768) in which
messages are delivered in a datagram (data telegram) to a destination computer on an IP network.
The UDP protocol is typically bundled with the Internet protocol. UDP/IP messages do not expect
a response, and are therefore ideal for applications in which dropped packets do not require
retransmission (such as streaming video and networks that demand real-time performance).
UINT
(unsigned integer) Encoded in 16 bits.

V
variable
A memory unit that is addressed and modified by a program.

W
watchdog
A watchdog is a special timer used to ensure that programs do not overrun their allocated scan
time. The watchdog timer is usually set to a higher value than the scan time and reset to 0 at the
end of each scan cycle. If the watchdog timer reaches the preset value, for example, because the
program is caught in an endless loop, an error is declared and the program stopped.
WORD
A type encoded in a 16-bit format.

266 EIO0000003089 12/2019


Modicon M251 Logic Controller
Index
EIO0000003089 12/2019

Index

A F
ASCII Manager, 185 Fast Device Replacement, 175
features
key features, 15
C file transfer with SD card, 229
changeIPAddress, 245 firewall
changing the controller IP address, 245 configuration, 161
changeModbusPort default script file, 161
command syntax, 155 script commands, 163
script example, 156 firmware
Controller Configuration downloading to TM3 expansion modules,
Communication Settings, 74 239
PLC Settings, 75 FTP client, 122
Services, 77 FTP Server
cyclic data exchanges, generating EDS file Ethernet, 121
for, 125 FTPRemoteFileHandling library, 122

D G
DHCP server, 174 GetSerialConf
Download application, 66 getting the serial line configuration, 250

E H
ECU, creating for J1939, 202 Hardware Initialization Values, 59
EDS file, generating, 125
Ethernet
changeIPAddress function block, 245 I
EtherNet I/O bus configuration, 87
EtherNet/IP device, 124 I/O configuration general information
Ethernet general practices, 82
FTP Server, 121 Industrial Ethernet
Modbus TCP Client/Server, 103 overview, 170
Modbus TCP slave device, 150 IP address
Services, 95 changeIPAddress, 245
SNMP, 123
Web server, 105
ExecuteScript example, 156
External Event, 43

EIO0000003089 12/2019 267


Index

J P
J1939 Post Configuration, 215
creating ECU for, 202 baud rate, 216, 216
interface configuration, 201 data bits, 216
device name, 216
Example, 220
K file management, 218
KeepAlive (OPC UA), 206 gateway address, 216
KeepAlive interval (OPC UA), 208 IP address, 216
IP configuration mode, 216
IP master name, 216
L parity, 216
libraries, 21 presentation, 216
Libraries station address, 216
FTPRemoteFileHandling, 122 stop bit, 216
subnet mask, 216
transfer rate, 216
M programming languages
M2•• communication IL, LD, grafcet, 15
GetSerialConf, 250 Protocols, 95
SetSerialConf, 251 IP, 97
Memory Mapping, 25 Modbus, 103
Modbus protocols
Protocols, 103 SNMP, 123
Modbus Ioscanner, 187 publishing interval (OPC UA), 206, 208
Modbus Manager, 181
Modbus TCP Client/Server
Ethernet, 103 R
Modbus TCP port, changing, 155 Reboot, 64
monitored items (OPC UA), 206 Remanent variables, 68
Reset cold, 62
Reset origin, 63
O Reset warm, 62
OPC UA server Run command, 61
configuration, 207
KeepAlive interval, 208
overview, 206 S
publishing interval, 208 sampling interval (OPC UA), 206, 208
sampling interval, 208 script commands
selecting symbols, 211 firewall, 163
symbols configuration, 210 script file
Output Behavior, 59, 59, 60 syntax rules, 228
Output Forcing, 60 SD card
commands, 229

268 EIO0000003089 12/2019


Index

serial line
ASCII Manager, 185
GetSerialConf, 250
Modbus Manager, 181
SetSerialConf, 251
SERIAL_CONF, 253
SetSerialConf, 251
setting the serial line configuration, 251
SNMP
Ethernet, 123
protocols, 123
Software Initialization Values, 59
State diagram, 49
Stop command, 61
symbols (OPC UA), 210

T
Task
Cyclic task, 41
Event task, 43
External Event Task, 43
Freewheeling task, 42
Types, 41
Watchdogs, 44
TM3 analog I/O modules
downloading firmware to, 239

U
updating the firmware of TM3 expansion
modules, 239

W
Web server
Ethernet, 105

EIO0000003089 12/2019 269


Index

270 EIO0000003089 12/2019


Modicon M251 Logic Controller

EIO0000003095 12/2019

Modicon M251
Logic Controller
System Functions and
Variables PLCSystem
Library Guide
12/2019
EIO0000003095.01

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.

2 EIO0000003095 12/2019
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 M251 System Variables . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1 System Variables: Definition and Use . . . . . . . . . . . . . . . . . . . . . . . . . 12
Understanding System Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Using System Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.2 PLC_R and PLC_W Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PLC_R: Controller Read-Only System Variables . . . . . . . . . . . . . . . . . 18
PLC_W: Controller Read/Write System Variables . . . . . . . . . . . . . . . . 22
1.3 SERIAL_R and SERIAL_W Structures . . . . . . . . . . . . . . . . . . . . . . . . 23
SERIAL_R[0...1]: Serial Line Read-Only System Variables . . . . . 24
SERIAL_W[0...1]: Serial Line Read/Write System Variables . . . . . 25
1.4 ETH_R and ETH_W Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
ETH_R: Ethernet Port Read-Only System Variables . . . . . . . . . . . . . 27
ETH_W: Ethernet Port Read/Write System Variables. . . . . . . . . . . . . . 33
1.5 TM3_MODULE_R Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TM3_MODULE_R[0...13]: TM3 Modules Read-Only System
Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1.6 TM3_BUS_W Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TM3_BUS_W: TM3 Bus System Variables . . . . . . . . . . . . . . . . . . . . . . 35
1.7 PROFIBUS_R Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
PROFIBUS_R: PROFIBUS Read-Only System Variables . . . . . . . . . 36
Chapter 2 M251 System Functions . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.1 M251 Read Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
GetRtc: Get Real Time Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
IsFirstMastColdCycle: Indicate if this Cycle is the First MAST
Cold Start Cycle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
IsFirstMastCycle: Indicate if this Cycle is the First MAST Cycle . 41
IsFirstMastWarmCycle: Indicate if this Cycle is the First MAST
Warm Start Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.2 M251 Write Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
SetRTCDrift: Set Compensation Value to the RTC. . . . . . . . . . . . . 44

EIO0000003095 12/2019 3
2.3 M251 User Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
FB_ControlClone: Clone the Controller. . . . . . . . . . . . . . . . . . . . . . 47
DataFileCopy: Copy File Commands. . . . . . . . . . . . . . . . . . . . . . . . 48
ExecuteScript: Run Script Commands . . . . . . . . . . . . . . . . . . . . . . 51
2.4 M251 Disk Space Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
FC_GetFreeDiskSpace: Gets the Free Memory Space . . . . . . . . . . 54
FC_GetLabel: Gets the Label of Memory . . . . . . . . . . . . . . . . . . . . . 55
FC_GetTotalDiskSpace: Gets the Size of Memory . . . . . . . . . . . . 56
2.5 TM3 Read Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
TM3_GetModuleBusStatus: Get TM3 Module Bus Status. . . . . . . . 58
TM3_GetModuleFWVersion: Get TM3 Module Firmware Version . . 59
TM3_GetModuleInternalStatus: Get TM3 Module Internal Status 60
Chapter 3 M251 PLCSystem Library Data Types . . . . . . . . . . . . . . . 63
3.1 PLC_RW System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . . 64
PLC_R_APPLICATION_ERROR: Detected Application Error Status
Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes . . . . 67
PLC_R_IO_STATUS: I/O Status Codes. . . . . . . . . . . . . . . . . . . . . . . . 68
PLC_R_SDCARD_STATUS: SD Card Slot Status Codes . . . . . . . . . . 69
PLC_R_STATUS: Controller Status Codes . . . . . . . . . . . . . . . . . . . . . 70
PLC_R_STOP_CAUSE: From RUN State to Other State Transition
Cause Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection
Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes . . . . . . . . . . . . . . 74
PLC_W_COMMAND: Control Command Codes . . . . . . . . . . . . . . . . . 75
3.2 DataFileCopy System Variables Data Types . . . . . . . . . . . . . . . . . . . . 76
DataFileCopyError: Detected Error Codes. . . . . . . . . . . . . . . . . . . . . . 77
DataFileCopyLocation: Location Codes. . . . . . . . . . . . . . . . . . . . . . . . 78
3.3 ExecScript System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . 79
ExecuteScriptError: Detected Error Codes . . . . . . . . . . . . . . . . . . . . . 79
3.4 ETH_RW System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . . 80
ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes . 81
ETH_R_IP_MODE: IP Address Source Codes . . . . . . . . . . . . . . . . . . 82
ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes . . . . . 83

4 EIO0000003095 12/2019
ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes . . . 84
ETH_R_PORT_LINK_STATUS: Communication Link Status Codes . 85
ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes . . . . . . . 87
3.5 TM3_MODULE_RW System Variables Data Types . . . . . . . . . . . . . . 88
TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes . . 89
TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read
Array Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
TM3_MODULE_STATE: TM3 Expansion Module State Codes . . . . . 91
TM3_BUS_W_IOBUSERRMOD: TM3 bus error mode . . . . . . . . . . . . 92
3.6 System Function Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Appendices ......................................... 95
Appendix A Function and Function Block Representation . . . . . . . . 97
Differences Between a Function and a Function Block . . . . . . . . . . . . 98
How to Use a Function or a Function Block in IL Language . . . . . . . . 99
How to Use a Function or a Function Block in ST Language . . . . . . . 103
Glossary ......................................... 107
Index ......................................... 115

EIO0000003095 12/2019 5
6 EIO0000003095 12/2019
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.

EIO0000003095 12/2019 7
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.

8 EIO0000003095 12/2019
About the Book

At a Glance

Document Scope
This document acquaints you with the system functions and variables offered within the Modicon
M251 Logic Controller. The M251 PLCSystem library contains functions and variables to get
information from and send commands to the controller system.
This document describes the data type functions and variables of the M251 PLCSystem library.
The following knowledge is required:
 Basic information on the functionality, structure, and configuration of the M251 Logic Controller
 Programming in the FBD, LD, ST, IL, or CFC language
 System variables (global variables)

Validity Note
This document has been updated for the release of EcoStruxureTM Machine Expert V1.2.

Related Documents

Title of Documentation Reference Number


EcoStruxure Machine Expert Programming Guide EIO0000002854 (ENG);
EIO0000002855 (FRE);
EIO0000002856 (GER);
EIO0000002858 (SPA);
EIO0000002857 (ITA);
EIO0000002859 (CHS)
Modicon M251 Logic Controller Hardware Guide EIO0000003101 (ENG);
EIO0000003102 (FRE);
EIO0000003103 (GER);
EIO0000003104 (SPA);
EIO0000003105 (ITA);
EIO0000003106 (CHS)
Modicon M251 Logic Controller Programming Guide EIO0000003089 (ENG);
EIO0000003090 (FRE);
EIO0000003091 (GER);
EIO0000003092 (SPA);
EIO0000003093 (ITA);
EIO0000003094 (CHS)

EIO0000003095 12/2019 9
You can download these technical publications and other technical information from our website
at https://www.se.com/ww/en/download/ .

Product Related Information

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths
and, for certain critical control functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are emergency stop and overtravel
stop, power outage and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.1
 Each implementation of this equipment must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest
edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

10 EIO0000003095 12/2019
Modicon M251 Logic Controller
M251 System Variables
EIO0000003095 12/2019

Chapter 1
M251 System Variables

M251 System Variables

Overview
This chapter:
 gives an introduction to the system variables (see page 12)
 describes the system variables (see page 18) included with the M251 PLCSystem library

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
1.1 System Variables: Definition and Use 12
1.2 PLC_R and PLC_W Structures 17
1.3 SERIAL_R and SERIAL_W Structures 23
1.4 ETH_R and ETH_W Structures 26
1.5 TM3_MODULE_R Structure 34
1.6 TM3_BUS_W Structure 35
1.7 PROFIBUS_R Structure 36

EIO0000003095 12/2019 11
M251 System Variables

Section 1.1
System Variables: Definition and Use

System Variables: Definition and Use

Overview
This section defines system variables and how to implement them in the Modicon M251 Logic
Controller.

What Is in This Section?


This section contains the following topics:
Topic Page
Understanding System Variables 13
Using System Variables 15

12 EIO0000003095 12/2019
M251 System Variables

Understanding System Variables

Introduction
This section describes how system variables are implemented. System variables:
 allow you to access general system information, perform system diagnostics, and command
simple actions.
 are structured variables conforming to IEC 61131-3 definitions and naming conventions. You
can access the system variables using the IEC symbolic name PLC_GVL. Some of the PLC_GVL
variables are read-only (for example, PLC_R) and some are read/write (for example, PLC_W).
 are automatically declared as global variables. They have system-wide scope and can be
accessed by any Program Organization Unit (POU) in any task.

Naming Convention
The system variables are identified by:
 a structure name that represents the category of system variable. For example, PLC_R
represents a structure name of read-only variables used for the controller diagnostic.
 a set of component names that identifies the purpose of the variable. For example,
i_wVendorID represents the controller vendor ID.
You can access the system variables by typing the structure name of the variables followed by the
name of the component.
Here is an example of system variable implementation:
VAR
myCtr_Serial : DWORD;
myCtr_ID : DWORD;
myCtr_FramesRx : UDINT;
END_VAR
myCtr_Serial := PLC_GVL.PLC_R.i_dwSerialNumber;
myCtr_ID := PLC_GVL.PLC.R.i_wVendorID;
myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK
NOTE: The fully-qualified name of the system variable in the example above is PLC_GVL.PLC.R.
The PLC_GVL is implicit when declaring a variable using the Input Assistant, but it may also be
entered in full. Good programming practice often dictates the use of the fully-qualified variable
name in declarations.

EIO0000003095 12/2019 13
M251 System Variables

System Variables Location


2 kinds of system variables are defined for use when programming the controller:
 located variables
 unlocated variables

The located variables:


 have a fixed location in a static %MW area: %MW60000 to %MW60199 for read-only system
variables.
 are accessible through Modbus TCP, Modbus serial, and EtherNet/IP requests both in
RUNNING and STOPPED states.
 are used in EcoStruxure Machine Expert programs according to the
structure_name.component_name convention explained previously. %MW addresses
from 0 to 59999 can be accessed directly. Addresses greater than this are considered out of
range by EcoStruxure Machine Expert and can only be accessed through the
structure_name.component_name convention.
The unlocated variables:
 are not physically located in the %MW area.
 are not accessible through any fieldbus or network requests unless you locate them in the
relocation table, and only then these variables can be accessed in RUNNING and STOPPED
states. The relocation table uses the following dynamic %MW areas:
 %MW60200 to %MW61999 for read-only variables
 %MW62200 to %MW63999 for read/write variables

 are used in EcoStruxure Machine Expert programs according to the


structure_name.component_name convention explained previously. %MW addresses
from 0 to 59999 can be accessed directly. Addresses greater than this are considered out of
range by EcoStruxure Machine Expert and can only be accessed through the
structure_name.component_name convention.

14 EIO0000003095 12/2019
M251 System Variables

Using System Variables

Introduction
This section describes the steps required to program and to use system variables in EcoStruxure
Machine Expert.
System variables are global in scope, and you can use them in all the Program Organization Units
(POUs) of the application.
System variables do not need to be declared in the Global Variable List (GVL). They are
automatically declared from the controller system library.

Using System Variables in a POU


EcoStruxure Machine Expert has an auto-completion feature. In a POU, start by entering the
system variable structure name (PLC_R, PLC_W...) followed by a dot. The system variables appear
in the Input Assistant. You can select the desired variable or enter the full name manually.

NOTE: In the example above, after you type the structure name PLC_R., EcoStruxure Machine
Expert offers a pop-up menu of possible component names/variables.

EIO0000003095 12/2019 15
M251 System Variables

Example
The following example shows the use of some system variables:
VAR
myCtr_Serial : DWORD;
myCtr_ID : WORD;
myCtr_FramesRx : UDINT;
END_VAR
myCtr_Serial := PLC_R.i_dwSerialNumber;
myCtr_ID := PLC_R.i_wVendorID;
myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK;

16 EIO0000003095 12/2019
M251 System Variables

Section 1.2
PLC_R and PLC_W Structures

PLC_R and PLC_W Structures

Overview
This section lists and describes the different system variables included in the PLC_R and PLC_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
PLC_R: Controller Read-Only System Variables 18
PLC_W: Controller Read/Write System Variables 22

EIO0000003095 12/2019 17
M251 System Variables

PLC_R: Controller Read-Only System Variables

Variable Structure
This table describes the parameters of the PLC_R system variable (PLC_R_STRUCT type):

Modbus Var Name Type Comment


Address (1)
60000 i_wVendorID WORD Controller Vendor ID.
101A hex = Schneider Electric
60001 i_wProductID WORD Controller Reference ID.
NOTE: Vendor ID and Reference ID are the
components of the Target ID of the controller
displayed in the communication settings view
(Target ID = 101A XXXX hex).
60002 i_dwSerialNumber DWORD Controller Serial Number
60004 i_byFirmVersion ARRAY[0..3] OF Controller Firmware Version
BYTE [aa.bb.cc.dd]:
 i_byFirmVersion[0] = aa
 ...
 i_byFirmVersion[3] = dd

60006 i_byBootVersion ARRAY[0..3] Controller Boot Version [aa.bb.cc.dd]:


OF BYTE  i_byBootVersion[0] = aa
 ...
 i_byBootVersion[3] = dd

60008 i_dwHardVersion DWORD Controller Hardware Version.


60010 i_dwChipVersion DWORD Controller Coprocessor Version.
60012 i_wStatus PLC_R_STATUS State of the controller.
(see page 70)
60013 i_wBootProjectStatus PLC_R_BOOT_ Returns information about the boot application
PROJECT_ stored in FLASH memory.
STATUS
(see page 67)
60014 i_wLastStopCause PLC_R_STOP_ Cause of the last transition from RUN to
CAUSE another state.
(see page 71)
60015 i_wLastApplicationError PLC_R_ Cause of the last controller exception.
APPLICATION_
ERROR
(see page 65)

18 EIO0000003095 12/2019
M251 System Variables

Modbus Var Name Type Comment


Address (1)
60016 i_lwSystemFault_1 LWORD Bit field FFFF FFFF FFFF FFFF hex indicates
no error detected.
A bit at low level means that an error has been
detected:
 bit 0 = Reserved
 bit 1 = TM3 error detected
 bit 2 = Ethernet IF1 error detected
 bit 3 = Ethernet IF2 error detected
 bit 4 = Serial 1 in overcurrent error detected
 bit 5 = Reserved
 bit 6 = CAN 1 error detected
 bit 7 = Reserved
 bit 8 = Reserved
 bit 9 = TM4 error detected
 bit 10 = SD Card error detected
 bit 11 = Firewall error detected
 bit 12 = DHCP server error detected
 bit 13 = OPC UA server error detected

60024 i_wIOStatus1 PLC_R_IO_ Reserved


STATUS
(see page 68)
60025 i_wIOStatus2 PLC_R_IO_ TM3 I/O status.
STATUS
(see page 68)
60026 i_wClockBatterystatus WORD Status of the battery of the RTC:
 0 = Battery change needed
 100 = Battery fully charged

Other values (1...99) represents the


percentage of charge. For example, if the value
is 75, it represents that the battery charge is
75%.
60028 i_dwAppliSignature1 DWORD First DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by the
software during build.
60030 i_dwAppliSignature2 DWORD Second DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by the
software during build.
60032 i_dwAppliSignature3 DWORD Third DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by the
software during build.

EIO0000003095 12/2019 19
M251 System Variables

Modbus Var Name Type Comment


Address (1)
60034 i_dwAppliSignature4 DWORD Fourth DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated by the
software during build.
(1)
Not accessible through the application.

n/a i_sVendorName STRING(31) Name of the vendor: “Schneider Electric”.


n/a i_sProductRef STRING(31) Reference of the controller.
n/a i_sNodeName STRING(99) Node name on EcoStruxure Machine Expert
Network.
n/a i_dwLastStopTime DWORD The time of the last detected STOP in seconds
beginning with January 1, 1970 at 00:00 UTC.
n/a i_dwLastPowerOffDate DWORD The date and time of the last detected power off
in seconds beginning with January 1, 1970 at
00:00 UTC.
NOTE: Convert this value into date and time by
using the function
SysTimeRtcConvertUtcToDate. For more
information about Time and Date conversion,
refer to the Systime Library Guide
(see EcoStruxure Machine Expert, Getting &
Setting Real Time Clock, SysTimeRtc and
SysTimeCore Library Guide).
n/a i_uiEventsCounter UINT Reserved
n/a i_wTerminalPortStatus PLC_R_ Status of the USB Programming Port
TERMINAL_ (USB Mini-B).
PORT_STATUS
(see page 73)
n/a i_wSdCardStatus PLC_R_SDCARD_ Status of the SD card.
STATUS
(see page 69)
n/a i_wUsrFreeFileHdl WORD Number of available File Handles.
A File Handle is the resource allocated by the
system when you open a file.
n/a i_udiUsrFsTotalBytes UDINT User FileSystem total memory size (in bytes).
It is the size of the flash memory for the directory
"/usr/".
n/a i_udiUsrFsFreeBytes UDINT User FileSystem free memory size (in bytes).

20 EIO0000003095 12/2019
M251 System Variables

n/a i_uiTM3BusState PLC_R_TM3_ TM3 bus state.


BUS_STATE i_uiTM3BusState can have the following
(see page 74) values:
 1: TM3_CONF_ERROR
Configuration mismatch between physical
configuration and EcoStruxure Machine
Expert configuration.
 3: TM3_OK
Physical configuration matches EcoStruxure
Machine Expert configuration.
 4: TM3_POWER_SUPPLY_ERROR
TM3 bus is not powered (for example when
the Logic Controller is powered by USB).
n/a i_ExpertIO_RunStop_Input BYTE Reserved
n/a i_x10msClk BOOL TimeBase bit of 10 ms.
This variable is toggling On/Off with period =
10 ms. The value toggles when the logic
controller is in Stop and in Run state.
n/a i_x100msClk BOOL TimeBase bit of 100 ms.
This variable is toggling On/Off with period =
100 ms. The value toggles when the logic
controller is in Stop and in Run state.
n/a i_x1sClk BOOL TimeBase bit of 1 s.
This variable is toggling On/Off with period = 1 s.
The value toggles when the logic controller is in
Stop and in Run state.

NOTE: n/a means that there is no pre-defined Modbus address mapping for this system variable.

EIO0000003095 12/2019 21
M251 System Variables

PLC_W: Controller Read/Write System Variables

Variable Structure
This table describes the parameters of the PLC_W system variable (PLC_W_STRUCT type):

%MW Var Name Type Comment


n/a q_wResetCounterEvent WORD Transition from 0 to 1 resets the events
counter (PLC_R.i_uiEventsCounter).
To reset the counter again, it is necessary to
write 0 to this variable before another
transition from 0 to 1 can take place.
n/a q_uiOpenPLCControl UINT When Value passes from 0 to 6699, the
command previously written in the following
PLC_W.q_wPLCControl is executed.
n/a q_wPLCControl PLC_W_COMMAND Controller RUN / STOP command executed
(see page 75) when the system variable
PLC_W.q_uiOpenPLCControl value
passes from 0 to 6699.

NOTE: n/a means that there is no pre-defined %MW mapping for this system variable.

22 EIO0000003095 12/2019
M251 System Variables

Section 1.3
SERIAL_R and SERIAL_W Structures

SERIAL_R and SERIAL_W Structures

Overview
This section lists and describes the different system variables included in the SERIAL_R and
SERIAL_W structures.

What Is in This Section?


This section contains the following topics:
Topic Page
SERIAL_R[0...1]: Serial Line Read-Only System Variables 24
SERIAL_W[0...1]: Serial Line Read/Write System Variables 25

EIO0000003095 12/2019 23
M251 System Variables

SERIAL_R[0...1]: Serial Line Read-Only System Variables

Introduction
SERIAL_R is an array of 2 SERIAL_R_STRUCT type. Each element of the array returns diagnostic
system variables for the corresponding serial line.
For the M251 Logic Controller:
 Serial_R[0] refers to serial line
 Serial_R[1] is reserved

Variable Structure
This table describes the parameters of the SERIAL_R[0...1] system variables:

%MW Var Name Type Comment


Serial Line
n/a i_udiFramesTransmittedOK UDINT Number of frames successfully transmitted.
n/a i_udiFramesReceivedOK UDINT Number of frames received without any errors
detected.
n/a i_udiRX_MessagesError UDINT Number of frames received with errors
detected (checksum, parity).
Modbus Specific
n/a i_uiSlaveExceptionCount UINT Number of Modbus exception responses
returned by the logic controller.
n/a i_udiSlaveMsgCount UINT Number of messages received from the Master
and addressed to the logic controller.
n/a i_uiSlaveNoRespCount UINT Number of Modbus broadcast requests
received by the logic controller.
n/a i_uiSlaveNakCount UINT Not used
n/a i_uiSlaveBusyCount UINT Not used
n/a i_uiCharOverrunCount UINT Number of character overruns.
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-
zero, it should be considered extraneous.

The SERIAL_R counters are reset on:


 Download.
 Controller reset.
 SERIAL_W[x].q_wResetCounter command.
 Reset command by Modbus request function code number 8.

24 EIO0000003095 12/2019
M251 System Variables

SERIAL_W[0...1]: Serial Line Read/Write System Variables

Introduction
SERIAL_W is an array of 2 SERIAL_W_STRUCT type. Each element of the array resets the
SERIAL_R system variables for the corresponding serial line to be reset.
For the M251 Logic Controller:
 Serial_W[0] refers to serial line
 Serial_W[1] is reserved

Variable Structure
This table describes the parameters of the SERIAL_W[0...1] system variable:

%MW Var Name Type Comment


n/a q_wResetCounter WORD Transition from 0 to 1 resets all
SERIAL_R[0...1] counters.
To reset the counters again, it is necessary to
write 0 to this variable before another transition
from 0 to 1 can take place.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000003095 12/2019 25
M251 System Variables

Section 1.4
ETH_R and ETH_W Structures

ETH_R and ETH_W Structures

Overview
This section lists and describes the different system variables included in the ETH_R and ETH_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
ETH_R: Ethernet Port Read-Only System Variables 27
ETH_W: Ethernet Port Read/Write System Variables 33

26 EIO0000003095 12/2019
M251 System Variables

ETH_R: Ethernet Port Read-Only System Variables

Variable Structure
This table describes the parameters of the ETH_R system variable (ETH_R_STRUCT type):

%MW Var Name Type Comment


60050 i_byIPAddress ARRAY[0..3] OF BYTE IP address of the Ethernet or
Ethernet_1 interface
[aaa.bbb.ccc.ddd]:
 i_byIPAddress[0] = aaa
 ...
 i_byIPAddress[3] = ddd

60052 i_bySubNetMask ARRAY[0..3] OF BYTE Subnet Mask of the Ethernet or


Ethernet_1 interface
[aaa.bbb.ccc.ddd]:
 i_bySub-netMask[0] = aaa
 ...
 i_bySub-netMask[3] = ddd

60054 i_byGateway ARRAY[0..3] OF BYTE Gateway address of the Ethernet


or Ethernet_1 interface
[aaa.bbb.ccc.ddd]:
 i_byGateway[0] = aaa
 ...
 i_byGateway[3] = ddd

60056 i_byMACAddress ARRAY[0..5] OF BYTE MAC address of the Ethernet or


Ethernet_1 interface
[aa.bb.cc.dd.ee.ff]:
 i_byMACAddress[0] = aa
 ...
 i_byMACAddress[5] = ff

60059 i_sDeviceName STRING(15) Name used to get IP address


from server.
n/a i_wIpMode ETH_R_IP_MODE Method used to obtain an IP
(see page 82) address.
n/a means that there is no predefined %MW mapping for this system variable.

EIO0000003095 12/2019 27
M251 System Variables

%MW Var Name Type Comment


n/a i_byFDRServerIPAddress ARRAY[0..3] OF BYTE The IP address
[aaa.bbb.ccc.ddd] of the
DHCP or BootP server:
 i_byFDRServerIPAddress[0]
= aaa
 ...
 i_byFDRServerIPAddress[3]
= ddd
Equals 0.0.0.0 if Stored IP or
Default IP used.
n/a i_udiOpenTcpConnections UDINT Number of open TCP
connections.
n/a i_udiFramesTransmittedOK UDINT Number of frames successfully
transmitted. Reset at Power ON
or with reset command
ETH_W.q_wResetCounter.
n/a i_udiFramedReceivedOK UDINT Number of frames successfully
received. Reset at Power ON or
with reset command
ETH_W.q_wResetCounter.
n/a i_udiTransmitBufferErrors UDINT Numbers of frames transmitted
with detected errors. Reset at
Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiReceiveBufferErrors UDINT Numbers of frames received with
detected errors. Reset at Power
ON or with reset command
ETH_W.q_wResetCounter.
n/a i_wFrameSendingProtocol ETH_R_FRAME_PROTOCOL Ethernet protocol configured for
(see page 81) frames sending (IEEE 802.3 or
Ethernet II).
n/a i_wPortALinkStatus ETH_R_PORT_LINK_STATUS Link of the Ethernet Port (0 = No
(see page 85) Link, 1 = Link connected to
another Ethernet device).
n/a i_wPortASpeed ETH_R_PORT_SPEED Ethernet Port network speed
(see page 86) (10Mb/s, 100Mb/s).
n/a i_wPortADuplexStatus ETH_R_PORT_DUPLEX- Ethernet Port duplex status (0 =
_STATUS (see page 83) Half or 1 = Full duplex).
n/a means that there is no predefined %MW mapping for this system variable.

28 EIO0000003095 12/2019
M251 System Variables

%MW Var Name Type Comment


n/a i_udiPortACollisions UDINT Number of frames involved in
one or more collisions and
subsequently transmitted
successfully. Reset at Power ON
or with reset command
ETH_W.q_wResetCounter.
n/a i_byIPAddress_If2 ARRAY[0..3] OF BYTE IP address of the Ethernet or
Ethernet_2 interface
[aaa.bbb.ccc.ddd]:
 i_byIPAddress[0] = aaa
 ...
 i_byIPAddress[3] = ddd

n/a i_bySubNetMask_If2 ARRAY[0..3] OF BYTE Subnet Mask of the Ethernet or


Ethernet_2 interface
[aaa.bbb.ccc.ddd]:
 i_bySub-netMask[0] = aaa
 ...
 i_bySub-netMask[3] = ddd

n/a i_byGateway_If2 ARRAY[0..3] OF BYTE Gateway address of the Ethernet


or Ethernet_2 interface
[aaa.bbb.ccc.ddd]:
 i_byGateway[0] = aaa
 ...
 i_byGateway[3] = ddd

n/a i_byMACAddress_If2 ARRAY[0..5] OF BYTE MAC address of the Ethernet or


Ethernet_2 interface
[aa.bb.cc.dd.ee.ff]:
 i_byMACAddress[0] = aa
 ...
 i_byMACAddress[5] = ff

n/a i_sDeviceName_If2 STRING(15) Name used to get IP address


from server.
n/a i_wIpMode_If2 ETH_R_IP_MODE Method used to obtain an IP
(see page 82) address.
n/a i_wPortALinkStatus_If2 ETH_R_PORT_LINK_STATUS Link of the Ethernet Port (0 = No
(see page 85) Link, 1 = Link connected to
another Ethernet device).
n/a i_wPortASpeed_If2 ETH_R_PORT_SPEED Ethernet Port network speed
(see page 86) (10Mb/s or 100Mb/s).
n/a means that there is no predefined %MW mapping for this system variable.

EIO0000003095 12/2019 29
M251 System Variables

%MW Var Name Type Comment


n/a i_wPortADuplexStatus_If2 ETH_R_PORT_DUPLEX- Ethernet Port duplex status:
_STATUS (see page 83)  0: Half
 1: Full duplex

n/a i_wPortAIpStatus_If2 ETH_R_PORT_IP_STATUS Ethernet TCP/IP port stack


(see page 84) status.
Modbus TCP/IP Specific
n/a i_udiModbusMessageTransmitted UDINT Number of Modbus messages
transmitted.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiModbusMessageReceived UDINT Number of Modbus messages
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiModbusErrorMessage UDINT Modbus detected error
messages transmitted and
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a means that there is no predefined %MW mapping for this system variable.

%MW Var Name Type Comment


EtherNet/IP Specific
n/a i_udiETHIP_IOMessagingTransmitted UDINT EtherNet/IP Class 1 frames
transmitted.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiETHIP_IOMessagingReceived UDINT EtherNet/IP Class 1 frames received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it
should be considered extraneous.

30 EIO0000003095 12/2019
M251 System Variables

%MW Var Name Type Comment


n/a i_udiUCMM_Request UDINT EtherNet/IP Unconnected Messages
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiUCMM_Error UDINT EtherNet/IP invalid Unconnected
Messages received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiClass3_Request UDINT EtherNet/IP Class 3 requests received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiClass3_Error UDINT EtherNet/IP invalid class 3 requests
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_uiAssemblyInstanceInput UINT Input Assembly Instance number. See
the appropriate Programming Guide of
your controller for more information.
n/a i_uiAssemblyInstanceInputSize UINT Input Assembly Instance size. See the
appropriate Programming Guide of
your controller for more information.
n/a i_uiAssemblyInstanceOutput UINT Output Assembly Instance number.
See the appropriate Programming
Guide of your controller for more
information.
n/a i_uiAssemblyInstanceOutputSize UINT Output Assembly Instance size. See
the appropriate Programming Guide of
your controller for more information.
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it
should be considered extraneous.

EIO0000003095 12/2019 31
M251 System Variables

%MW Var Name Type Comment


n/a i_uiETHIP_ConnectionTimeouts UINT Number of connection timeouts. Reset
at Power ON or with reset command
ETH_W.q_wResetCounter.
n/a i_ucEipRunIdle ETH_R_RUN_ Run (value = 1)/Idle(value = 0) flag for
IDLE EtherNet/IP class 1 connection.
(see page 87)
n/a i_byMasterIpTimeouts BYTE Ethernet Modbus TCP Master timeout
events counter.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_byMasterIpLost BYTE Ethernet Modbus TCP Master link
status: 0 = link OK, 1 = link lost.
n/a i_wPortAIpStatus ETH_R_PORT_ Ethernet TCP/IP port stack status.
IP_STATUS
(see page 84)
n/a means that there is no predefined %MW mapping for this system variable.
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it
should be considered extraneous.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

32 EIO0000003095 12/2019
M251 System Variables

ETH_W: Ethernet Port Read/Write System Variables

Variable Structure
This table describes the parameters of the ETH_W system variable (ETH_W_STRUCT type):

%MW Var Name Type Comment


n/a q_wResetCounter WORD Transition from 0 to 1 resets all ETH_R counters.
To reset again, it is necessary to write 0 to this variable
before another transition from 0 to 1 can take place.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000003095 12/2019 33
M251 System Variables

Section 1.5
TM3_MODULE_R Structure

TM3_MODULE_R Structure

TM3_MODULE_R[0...13]: TM3 Modules Read-Only System Variables

Introduction
The TM3_MODULE_R is an array of 14 TM3_MODULE_R_STRUCT type. Each element of the array
returns diagnostic system variables for the corresponding TM3 expansion module.
For the Modicon M251 Logic Controller:
 TM3_MODULE_R[0] refers to the TM3 expansion module 0
 ...
 TM3_MODULE_R[13] refers to the TM3 expansion module 13

Variable Structure
The following table describes the parameters of the TM3_MODULE_R[0...13] system variable:

%MW Var Name Type Comment


n/a i_wProductID WORD TM3 expansion module ID.
n/a i_wModuleState TM3_MODULE_STATE Describes the state of the TM3 module.
(see page 91)

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

34 EIO0000003095 12/2019
M251 System Variables

Section 1.6
TM3_BUS_W Structure

TM3_BUS_W Structure

TM3_BUS_W: TM3 Bus System Variables

Variable Structure
This table describes the parameters of the TM3_BUS_W system variable (TM3_BUS_W_STRUCT
type):

Var Name Type Comment


q_wIOBusErrPassiv TM3_BUS_W_IOBUSERRMOD When set to ERR_ACTIVE (the default), bus
errors detected on TM3 expansion modules
stop all I/O exchanges.
When set to ERR_PASSIVE, passive I/O error
handing is used: the controller attempts to
continue data bus exchanges.
q_wIOBusRestart TM3_BUS_W_IOBUSINIT When set to 1, restarts the I/O expansion bus.
This is only necessary when
q_wIOBusErrPassiv is set to ERR_ACTIVE
and at least one bit of TM3_MODULE_R[i]
.i_wModuleState is set to
TM3_BUS_ERROR.

For more information, refer to I/O Configuration General Description (see Modicon M251 Logic
Controller, Programming Guide).

EIO0000003095 12/2019 35
M251 System Variables

Section 1.7
PROFIBUS_R Structure

PROFIBUS_R Structure

PROFIBUS_R: PROFIBUS Read-Only System Variables

Variable Structure
This table describes the parameters of the PROFIBUS_R system variable (PROFIBUS_R_STRUCT
type):

%MW Var Name Type Comment


n/a i_wPNOIdentifier WORD Slave identification code.
n/a i_wBusAdr UINT PROFIBUS slave address.
n/a i_CommState UDINT Value representing the state of the PROFIBUS module:
 0x00: Unknown
 0x01: Not configured
 0x02: Stop
 0x03: Idle
 0x04: Operate

n/a i_CommError UDINT Communication error code.


n/a i_ErrorCount UDINT Communication error counter.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

36 EIO0000003095 12/2019
Modicon M251 Logic Controller
M251, System Functions
EIO0000003095 12/2019

Chapter 2
M251 System Functions

M251 System Functions

Overview
This chapter describes the system functions included in the M251 PLCSystem library.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
2.1 M251 Read Functions 38
2.2 M251 Write Functions 44
2.3 M251 User Functions 46
2.4 M251 Disk Space Functions 53
2.5 TM3 Read Functions 57

EIO0000003095 12/2019 37
M251, System Functions

Section 2.1
M251 Read Functions

M251 Read Functions

Overview
This section describes the read functions included in the M251 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
GetRtc: Get Real Time Clock 39
IsFirstMastColdCycle: Indicate if this Cycle is the First MAST Cold Start Cycle 40
IsFirstMastCycle: Indicate if this Cycle is the First MAST Cycle 41
IsFirstMastWarmCycle: Indicate if this Cycle is the First MAST Warm Start Cycle 43

38 EIO0000003095 12/2019
M251, System Functions

GetRtc: Get Real Time Clock

Function Description
This function returns RTC time in seconds in UNIX format (time expired in seconds since January
1, 1970 at 00:00 UTC).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


The following table describes the I/O variable:

Output Type Comment


GetRtc DINT RTC in seconds in UNIX format.

Example
The following example describes how to get the RTC value:
VAR
MyRTC : DINT := 0;
END_VAR
MyRTC := GetRtc();

EIO0000003095 12/2019 39
M251, System Functions

IsFirstMastColdCycle: Indicate if this Cycle is the First MAST Cold Start Cycle

Function Description
This function returns TRUE during the first MAST cycle after a cold start (first cycle after download
or reset cold).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


The table describes the output variable:

Output Type Comment


IsFirstMastColdCycle BOOL TRUE during the first MAST task cycle after
a cold start.

Example
Refer to the function IsFirstMastCycle (see page 41).

40 EIO0000003095 12/2019
M251, System Functions

IsFirstMastCycle: Indicate if this Cycle is the First MAST Cycle

Function Description
This function returns TRUE during the first MAST cycle after a start.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description

Output Type Comment


IsFirstMastCycle BOOL TRUE during the first MAST task cycle after a start.

EIO0000003095 12/2019 41
M251, System Functions

Example
This example describes the three functions IsFirstMastCycle, IsFirstMastColdCycle and
IsFirstMastWarmCycle used together.
Use this example in MAST task. Otherwise, it may run several times or possibly never (an
additional task might be called several times or not called during 1 MAST task cycle):
VAR
MyIsFirstMastCycle : BOOL;
MyIsFirstMastWarmCycle : BOOL;
MyIsFirstMastColdCycle : BOOL;
END_VAR
MyIsFirstMastWarmCycle := IsFirstMastWarmCycle();
MyIsFirstMastColdCycle := IsFirstMastColdCycle();
MyIsFirstMastCycle := IsFirstMastCycle();
IF (MyIsFirstMastWarmCycle) THEN
(*This is the first Mast Cycle after a Warm Start: all variables are set
to their initialization values except the Retain variables*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;
IF (MyIsFirstMastColdCycle) THEN
(*This is the first Mast Cycle after a Cold Start: all variables are set
to their initialization values including the Retain Variables*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;
IF (MyIsFirstMastCycle) THEN
(*This is the first Mast Cycle after a Start, i.e. after a Warm or Cold
Start as well as STOP/RUN commands*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;

42 EIO0000003095 12/2019
M251, System Functions

IsFirstMastWarmCycle: Indicate if this Cycle is the First MAST Warm Start Cycle

Function Description
This function returns TRUE during the first MAST cycle after a warm start.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


This table describes the output variable:

Output Type Comment


IsFirstMastWarmCycle BOOL TRUE during the first MAST task cycle after
a warm start.

Example
Refer to the function IsFirstMastCycle (see page 41).

EIO0000003095 12/2019 43
M251, System Functions

Section 2.2
M251 Write Functions

M251 Write Functions

SetRTCDrift: Set Compensation Value to the RTC

Function Description
This function accelerates or slows down the frequency of the RTC to give control to the application
for RTC compensation, depending on the operating environment (temperature, …). The
compensation value is given in seconds per week. It can be positive (accelerate) or negative (slow
down).
NOTE: The SetRTCDrift function must be called only once. Each new call replaces the
compensation value by the new one. The value is kept in the controller hardware while the RTC is
powered by the main supply or by the battery. If both battery and power supply are removed, the
RTC compensation value is not available.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

44 EIO0000003095 12/2019
M251, System Functions

I/O Variables Description


This table describes the input parameters:

Inputs Type Comment


RtcDrift SINT(-36...+73) Correction in seconds per week (-36 ... +73).

NOTE: The parameters Day, Hour, and Minute are used only to ensure backwards compatibility.
NOTE: If the value entered for RtcDrift exceeds the limit value, the controller firmware sets the
value to its maximum value.
This table describes the output variable:

Output Type Comment


SetRTCDrift RTCSETDRIFT_ERROR Returns RTC_OK (00 hex) if command is correct
(see page 93) otherwise returns the ID code of the detected error.

Example
In this example, the function is called only once during the first MAST task cycle. It accelerates the
RTC by 4 seconds a week (18 seconds a month).
VAR
MyRTCDrift : SINT (-36...+73) := 0;
MyDay : DAY_OF_WEEK;
MyHour : HOUR;
MyMinute : MINUTE;
END_VAR
IF IsFirstMastCycle() THEN
MyRTCDrift := 4;
MyDay := 0;
MyHour := 0;
MyMinute := 0;
SetRTCDrift(MyRTCDrift, MyDay, MyHour, MyMinute);
END_IF

EIO0000003095 12/2019 45
M251, System Functions

Section 2.3
M251 User Functions

M251 User Functions

Overview
This section describes the FB_Control_Clone, DataFileCopy and ExecuteScript
functions included in the M251 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
FB_ControlClone: Clone the Controller 47
DataFileCopy: Copy File Commands 48
ExecuteScript: Run Script Commands 51

46 EIO0000003095 12/2019
M251, System Functions

FB_ControlClone: Clone the Controller

Function Block Description


Cloning is possible by SD card or Controller Assistant. When user rights are enabled, the cloning
function is not allowed, and the function block enables cloning functionality one time on the next
controller power on.
NOTE: You can choose whether user rights are included in the clone on the Clone Management
page of the Web server (see Modicon M251 Logic Controller, Programming Guide).
This table shows how to set the function block and the user rights:

Function block setting When user rights enabled When user rights disabled
xEnable = 1 Cloning is allowed Cloning is still allowed
xEnable = 0 Cloning is not allowed Cloning is not allowed

Read from controller with Controller Assistant is also affected by FB_ControlClone.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


The following table describes the input variables:

Input Type Comment


xEnable BOOL If TRUE, enables the cloning functionality one time.
If FALSE, disables the cloning functionality.

The following table describes the output variables:

Output Type Comment


xError BOOL TRUE indicates that an error is detected and the function block
aborted the action.

EIO0000003095 12/2019 47
M251, System Functions

DataFileCopy: Copy File Commands

Function Block Description


This function block copies memory data to a file and vice versa. The file is located either within the
internal file system or an external file system (SD card).
The DataFileCopy function block can:
 Read data from a formatted file or
 Copy data from memory to a formatted file. For further information, refer to Flash Memory
Organization (see Modicon M251 Logic Controller, Programming Guide).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


This table describes the input variables:

Input Type Comment


xExecute BOOL On rising edge, starts the function block execution.
On falling edge, resets the outputs of the function block when any ongoing
execution terminates.
NOTE: With the falling edge, the function continues until it concludes its
execution and updates its outputs. The outputs are retained for one cycle and
reset.
sFileName STRING File name without extension (the extension .DTA is automatically added). Use
only a...z, A...Z, 0...9 alphanumeric characters.
xRead BOOL TRUE: copy data from the file identified by sFileName to the internal memory
of the controller.
FALSE: copy data from the internal memory of the controller to the file
identified by sFileName.

48 EIO0000003095 12/2019
M251, System Functions

Input Type Comment


xSecure BOOL TRUE: The MAC address is always stored in the file. Only a controller with the
same MAC address can read from the file.
FALSE: Another controller with the same type of memory can read from the
file.
iLocation INT 0: the file location is /usr/DTA in internal file system.
1: the file location is /usr/DTA in external file system (SD card).
NOTE: If the file does not already exist in the directory, the file is created.
uiSize UINT Indicates the size in bytes. Maximum is 65534 bytes.
Only use addresses of variables conforming to IEC 61131-3 (variables, arrays,
structures), for example:
Variable : int;
uiSize := SIZEOF (Variable);
dwAdd DWORD Indicates the address in the memory that the function will read from or write to.
Only use addresses of variables conforming to IEC 61131-3 (variables, arrays,
structures), for example:
Variable : int;
dwAdd := ADR (Variable);

WARNING
UNINTENDED EQUIPMENT OPERATION
Verify that the memory location is of the correct size and the file is of the correct type before
copying the file to memory.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

This table describes the output variables:

Output Type Comment


xDone BOOL TRUE = indicates that the action is successfully completed.
xBusy BOOL TRUE = indicates that the function block is running.
xError BOOL TRUE = indicates that an error is detected and the function block
aborted the action.
eError DataFileCopyError Indicates the type of the data file copy detected error.
(see page 77)

NOTE: If you write to memory variable within the area of the file write, a CRC integrity error results.

EIO0000003095 12/2019 49
M251, System Functions

Example
This example describes how to copy file commands:
VAR
LocalArray : ARRAY [0..29] OF BYTE;
myFileName: STRING := 'exportfile';
EXEC_FLAG: BOOL;
DataFileCopy: DataFileCopy;
END_VAR
DataFileCopy(
xExecute:= EXEC_FLAG,
sFileName:= myFileName,
xRead:= FALSE,
xSecure:= FALSE,
iLocation:= DFCL_INTERNAL,
uiSize:= SIZEOF(LocalArray),
dwAdd:= ADR(LocalArray),
xDone=> ,
xBusy=> ,
xError=> ,
eError=> );

50 EIO0000003095 12/2019
M251, System Functions

ExecuteScript: Run Script Commands

Function Block Description


This function block can run the following SD card script commands:
 Download
 Upload
 SetNodeName
 Delete
 Reboot
 ChangeModbusPort

For information on the required script file format, refer to Script Files for SD Cards.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


This table describes the input variables:

Input Type Comment


xExecute BOOL On detection of a rising edge, starts the function block execution.
On detection of a falling edge, resets the outputs of the function block
when any on-going execution terminates.
NOTE: With the falling edge, the function continues until it concludes its
execution and updates its outputs. The outputs are retained for one cycle
and reset.
sCmd STRING SD card script command syntax.
Simultaneous command executions are not allowed: if a command is
being executed from another function block or from an SD card script
then the function block queues the command and does not execute it
immediately.
NOTE: An SD card script executed from an SD card is considered as
being executed until the SD card has been removed.

EIO0000003095 12/2019 51
M251, System Functions

This table describes the output variables:

Output Type Comment


xDone BOOL TRUE indicates that the action is successfully completed.
xBusy BOOL TRUE indicates that the function block is running.
xError BOOL TRUE indicates error detection; the function block aborts the
action.
eError ExecuteScriptError Indicates the type of the execute script detected error.
(see page 79)

Example
This example describes how to execute an Upload script command:
VAR
EXEC_FLAG: BOOL;
ExecuteScript: ExecuteScript;
END_VAR
ExecuteScript(
xExecute:= EXEC_FLAG,
sCmd:= 'Upload "/usr/Syslog/*"',
xDone=> ,
xBusy=> ,
xError=> ,
eError=> );

52 EIO0000003095 12/2019
M251, System Functions

Section 2.4
M251 Disk Space Functions

M251 Disk Space Functions

Overview
This section describes the disk space functions included in the SystemInterface library.

What Is in This Section?


This section contains the following topics:
Topic Page
FC_GetFreeDiskSpace: Gets the Free Memory Space 54
FC_GetLabel: Gets the Label of Memory 55
FC_GetTotalDiskSpace: Gets the Size of Memory 56

EIO0000003095 12/2019 53
M251, System Functions

FC_GetFreeDiskSpace: Gets the Free Memory Space

Function Description
This function retrieves the amount of free memory space of a memory medium (flash disk, RAM
disk, SD card) in bytes. The name of the memory medium is transferred:
 Flash disk = "ide0:"
 RAM disk = "ram0:"
 SD card = "sd0:"
The free memory space of a remote device cannot be accessed. If a remote device is specified as
parameter, then the function returns "-1".

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


This table describes the input variables:

Input Data type Description


i_sVolumeName STRING[80] Name of the device whose free memory space must be
accessed
iq_uliFreeDiskSpace ULINT Free memory space in bytes

This table describes the output variables:

Output Data type Description


FC_GetFreeDiskSpace DINT 0: The amount of free memory space was retrieved
successfully
-1: Error when attempting to access the amount of free
memory. For example, an invalid device or remote device was
selected
-318: Invalid parameter (i_sVolumeName)

54 EIO0000003095 12/2019
M251, System Functions

FC_GetLabel: Gets the Label of Memory

Function Description
This function retrieves the label of a memory medium. If a device has no label, then an empty string
is returned.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


This table describes the input variables:

Input Data type Description


i_sVolumeName STRING[80] Name of the device whose label must be
accessed
iq_sLabel STRING[11] Label of the device

This table describes the output variables:

Output Data type Description


FC_GetLabel DINT 0: The label was retrieved successfully
-1: Error when accessing the label
-318: Invalid parameter

EIO0000003095 12/2019 55
M251, System Functions

FC_GetTotalDiskSpace: Gets the Size of Memory

Function Description
This function retrieves the size of a memory medium (flash disk, RAM disk, SD card) in bytes.
The name of the memory medium is transferred:
 Flash disk = "ide0:"
 RAM disk = "ram0:"
 SD card = "sd0:"
The size of a remote device cannot be accessed. If a remote device is specified as parameter, then
the function returns "-1".

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


This table describes the input variables:

Input Data type Description


i_sVolumeName STRING[80] Name of the device whose memory size must be
accessed
iq_uliTotalDiskSpace ULINT Size of the memory medium in byte

This table describes the output variables:

Output Data type Description


FC_GetTotalDiskSpace DINT 0: Size was retrieved successfully
-1: Error when reading the size
-318: At least one of the parameters is invalid

56 EIO0000003095 12/2019
M251, System Functions

Section 2.5
TM3 Read Functions

TM3 Read Functions

Overview
This section describes the TM3 read functions included in the M251 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
TM3_GetModuleBusStatus: Get TM3 Module Bus Status 58
TM3_GetModuleFWVersion: Get TM3 Module Firmware Version 59
TM3_GetModuleInternalStatus: Get TM3 Module Internal Status 60

EIO0000003095 12/2019 57
M251, System Functions

TM3_GetModuleBusStatus: Get TM3 Module Bus Status

Function Description
This function returns the bus status of the module. The index of the module is given as an input
parameter.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


The following table describes the input variable:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for the
second, and so on).

The following table describes the output variable:

Output Type Comment


TM3_GetModuleBusStatus TM3_ERR_CODE Returns TM3_OK (00 hex) if command is correct
(see page 89) otherwise returns the ID code of the detected error.

58 EIO0000003095 12/2019
M251, System Functions

TM3_GetModuleFWVersion: Get TM3 Module Firmware Version

Function Description
This function returns the firmware version of a specified TM3 module.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description


The following table describes the input variables:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for
the second, and so on).

The following table describes the output variable:

Output Type Comment


TM3_GetModuleFWVersion UINT Returns the firmware version of the module, or
FFFF hex if the information cannot be read.
For example, 001A hex indicates firmware version
26.

EIO0000003095 12/2019 59
M251, System Functions

TM3_GetModuleInternalStatus: Get TM3 Module Internal Status

Function Description
This function fills the pStatusBuffer with the status table of the module ModuleIndex.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 97).

I/O Variable Description

WARNING
UNINTENDED EQUIPMENT OPERATION
Ensure that the pStatusBuffer is allocated.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The following table describes the input variables:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for
the second, and so on).
StatusOffset BYTE Offset of the first status to be read in the status table.
StatusSize BYTE Number of bytes to be read in the status table.
pStatusBuffer POINTER TO BYTE Buffer containing the read status table.

60 EIO0000003095 12/2019
M251, System Functions

The following table describes the output variable:

Output Type Comment


TM3_GetModuleInternalStatus TM3_ERR_CODE Returns TM3_OK (00 hex) if command is
(see page 89) correct otherwise returns the ID code of the
error.

Example
The following example describes how to get the module internal status:
VAR
AMM3HT_Channel1_Input_Status: BYTE;
END_VAR
TM3_GetModuleInternalStatus(0, 1, 1, ADR(AMM3HT_Channel1_Input_Status));

EIO0000003095 12/2019 61
M251, System Functions

62 EIO0000003095 12/2019
Modicon M251 Logic Controller
M251 PLC System Library Data Types
EIO0000003095 12/2019

Chapter 3
M251 PLCSystem Library Data Types

M251 PLCSystem Library Data Types

Overview
This chapter describes the data types of the M251 PLCSystem Library.
There are 2 kinds of data types available:
 System variable data types are used by the system variables (see page 11) of the M251
PLCSystem Library (PLC_R, PLC_W,...).
 System function data types are used by the read/write system functions (see page 37) of the
M251 PLCSystem Library.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
3.1 PLC_RW System Variables Data Types 64
3.2 DataFileCopy System Variables Data Types 76
3.3 ExecScript System Variables Data Types 79
3.4 ETH_RW System Variables Data Types 80
3.5 TM3_MODULE_RW System Variables Data Types 88
3.6 System Function Data Types 93

EIO0000003095 12/2019 63
M251 PLC System Library Data Types

Section 3.1
PLC_RW System Variables Data Types

PLC_RW System Variables Data Types

Overview
This section lists and describes the system variable data types included in the PLC_R and PLC_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
PLC_R_APPLICATION_ERROR: Detected Application Error Status Codes 65
PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes 67
PLC_R_IO_STATUS: I/O Status Codes 68
PLC_R_SDCARD_STATUS: SD Card Slot Status Codes 69
PLC_R_STATUS: Controller Status Codes 70
PLC_R_STOP_CAUSE: From RUN State to Other State Transition Cause Codes 71
PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection Status Codes 73
PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes 74
PLC_W_COMMAND: Control Command Codes 75

64 EIO0000003095 12/2019
M251 PLC System Library Data Types

PLC_R_APPLICATION_ERROR: Detected Application Error Status Codes

Enumerated Type Description


The PLC_R_APPLICATION_ERROR enumeration data type contains the following values:

Enumerator Value Comment What to do


PLC_R_APP_ERR_UNKNOWN FFFF hex Undefined error detected. Contact your Schneider
Electric service
representative.
PLC_R_APP_ERR_NOEXCEPTION 0000 hex No error detected. –
PLC_R_APP_ERR_WATCHDOG 0010 hex Task watchdog expired. Check your application. A
reset is needed to enter Run
mode.
PLC_R_APP_ERR_ 0011 hex System watchdog expired. If the problem is
HARDWAREWATCHDOG reproducible, verify that
there are no configured but
disconnected
communication ports. If the
problem persists, update the
firmware. If the problem still
persists, contact your
Schneider Electric service
representative.
PLC_R_APP_ERR_IO_CONFIG_ 0012 hex Incorrect I/O configuration Your application might be
ERROR parameters detected. corrupted. To resolve this
issue, use one of the
methods:
1. Build → Clean All
2. Export/Import your
application.
3. Upgrade EcoStruxure
Machine Expert to the
latest version.
PLC_R_APP_ERR_UNRESOLVED_ 0018 hex Undefined functions detected. Delete the unresolved
EXTREFS functions from the
application.

EIO0000003095 12/2019 65
M251 PLC System Library Data Types

Enumerator Value Comment What to do


PLC_R_APP_ERR_IEC_TASK_ 0025 hex Incorrect Task configuration Your application might be
CONFIG_ERROR parameters detected. corrupted. To resolve this
issue, use one of the
methods:
1. Build → Clean All
2. Export/Import your
application.
3. Upgrade EcoStruxure
Machine Expert to the
latest version.
PLC_R_APP_ERR_ILLEGAL_ 0050 hex Undefined instruction detected. Debug your application to
INSTRUCTION resolve the problem.
PLC_R_APP_ERR_ACCESS_ 0051 hex Attempted access to reserved Debug your application to
VIOLATION memory area. resolve the problem.
PLC_R_APP_ERR_DIVIDE_BY_ ZERO 0102 hex Integer division by zero Debug your application to
detected. resolve the problem.
PLC_R_APP_ERR_PROCESSORLOAD_ 0105 hex Processor overloaded by Reduce the application
WATCHDOG Application Tasks. workload by improving the
application architecture.
Increase the task cycle
duration. Reduce event
frequency.
PLC_R_APP_ERR_DIVIDE_REAL_ 0152 hex Real division by zero detected. Debug your application to
BY_ZERO resolve the problem.
PLC_R_APP_ERR_EXPIO_EVENTS_ 4E20 hex Too many events on expert I/Os Reduce the number of event
COUNT_EXCEEDED are detected. tasks.
PLC_R_APP_ERR_APPLICATION_ 4E21 hex Mismatch in the application The application version in
VERSION_MISMATCH version detected. the logic controller does not
match the version in
EcoStruxure Machine
Expert. Refer to Applications
(see EcoStruxure Machine
Expert, Programming
Guide).

66 EIO0000003095 12/2019
M251 PLC System Library Data Types

PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes

Enumerated Type Description


The PLC_R_BOOT_PROJECT_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_NO_BOOT_PROJECT 0000 hex Boot project does not exist in Flash
memory.
PLC_R_BOOT_PROJECT_CREATION_IN_ 0001 hex Boot project is being created.
PROGRESS
PLC_R_DIFFERENT_BOOT_PROJECT 0002 hex Boot project in Flash is different from the
project loaded in RAM.
PLC_R_VALID_BOOT_PROJECT FFFF hex Boot project in Flash is the same as the
project loaded in RAM.

EIO0000003095 12/2019 67
M251 PLC System Library Data Types

PLC_R_IO_STATUS: I/O Status Codes

Enumerated Type Description


The PLC_R_IO_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_IO_OK FFFF hex Inputs/Outputs are operational.
PLC_R_IO_NO_INIT 0001 hex Inputs/Outputs are not initialized.
PLC_R_IO_CONF_FAULT 0002 hex Incorrect I/O configuration parameters
detected.
PLC_R_IO_SHORTCUT_FAULT 0003 hex Inputs/Outputs short-circuit detected.
PLC_R_IO_POWER_SUPPLY_FAULT 0004 hex Inputs/Outputs power supply error
detected.

68 EIO0000003095 12/2019
M251 PLC System Library Data Types

PLC_R_SDCARD_STATUS: SD Card Slot Status Codes

Enumerated Type Description


The PLC_R_SDCARD_STATUS enumeration data type contains the following values:

Enumerator Value Comment


NO_SDCARD 0000 hex No SD card detected in the slot or the slot is not connected.
SDCARD_READONLY 0001 hex SD card is in read-only mode.
SDCARD_READWRITE 0002 hex SD card is in read/write mode.
SDCARD_ERROR 0003 hex Error detected in the SD card. More details on the error that
occurred are written to the file FwLog.txt.

EIO0000003095 12/2019 69
M251 PLC System Library Data Types

PLC_R_STATUS: Controller Status Codes

Enumerated Type Description


The PLC_R_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_EMPTY 0000 hex Controller does not contain an application.
PLC_R_STOPPED 0001 hex Controller is stopped.
PLC_R_RUNNING 0002 hex Controller is running.
PLC_R_HALT 0004 hex Controller is in a HALT state (see the controller
state diagram in your controller programming
guide (see Modicon M251 Logic Controller,
Programming Guide)).
PLC_R_BREAKPOINT 0008 hex Controller has paused at a breakpoint.

70 EIO0000003095 12/2019
M251 PLC System Library Data Types

PLC_R_STOP_CAUSE: From RUN State to Other State Transition Cause Codes

Enumerated Type Description


The PLC_R_STOP_CAUSE enumeration data type contains the following values:

Enumerator Value Comment What to do


PLC_R_STOP_REASON_ 00 hex Initial value or stop cause is Contact your local
UNKNOWN indeterminable. Schneider Electric
representative.
PLC_R_STOP_REASON_HW_ 01 hex Stopped after hardware watchdog timeout. Contact your local
WATCHDOG Schneider Electric
representative.
PLC_R_STOP_REASON_ 02 hex Stopped after reset. See reset possibilities in
RESET Controller State Diagram.
PLC_R_STOP_REASON_ 03 hex Stopped after exception. Verify your application, and
EXCEPTION correct if necessary. See
System and Task
Watchdogs. A reset is
needed to enter Run
mode.
PLC_R_STOP_REASON_ 04 hex Stopped after a user request. Refer to Stop Command in
USER Commanding State
Transitions (see Modicon
M251 Logic Controller,
Programming Guide).
PLC_R_STOP_REASON_ 05 hex Stopped after a program command –
IECPROGRAM request (for example: control command
with parameter
PLC_W.q_wPLCControl:=PLC_W_
COMMAND.PLC_W_STOP;).
PLC_R_STOP_REASON_ 06 hex Stopped after a remove application See the Applications tab of
DELETE command. the Controller Device
Editor (see Modicon M251
Logic Controller,
Programming Guide).
PLC_R_STOP_REASON_ 07 hex Stopped after entering debug mode. –
DEBUGGING
PLC_R_STOP_FROM_ 0A hex Stopped after a request from the network, –
NETWORK_REQUEST the controller Web server, or PLC_W
command.
PLC_R_STOP_FROM_INPUT 0B hex Stop required by a controller input. –
PLC_R_STOP_FROM_RUN_ 0C hex Stop required by the controller switch. –
STOP_SWITCH

EIO0000003095 12/2019 71
M251 PLC System Library Data Types

Enumerator Value Comment What to do


PLC_R_STOP_REASON_ 0D hex Stopped after an unsuccessful check There are retained
RETAIN_MISMATCH context test during rebooting. variables in non-volatile
memory that do not exist in
the executing application.
Verify your application,
correct if necessary, then
reestablish the boot
application.
PLC_R_STOP_REASON_ 0E hex Stopped after an unsuccessful compare Create a valid boot
BOOT_APPLI_MISMATCH between the boot application and the application.
application that was in the memory before
rebooting.
PLC_R_STOP_REASON_ 0F hex Stopped after a power interruption. –
POWERFAIL

For more information on the reasons why the controller has stopped, refer to the Controller State
Description (see Modicon M251 Logic Controller, Programming Guide).

72 EIO0000003095 12/2019
M251 PLC System Library Data Types

PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection Status Codes

Enumerated Type Description


The PLC_R_TERMINAL_PORT_STATUS enumeration data type contains the following values:

Enumerator Value Comment


TERMINAL_NOT_CONNECTED 00 hex No PC is connected to the programming port.
TERMINAL_CONNECTION_IN_ 01 hex Connection is in progress.
PROGRESS
TERMINAL_CONNECTED 02 hex PC is connected to the programming port.
TERMINAL_ERROR 0F hex Error detected during connection.

EIO0000003095 12/2019 73
M251 PLC System Library Data Types

PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes

Enumerated Type Description


The PLC_R_TM3_BUS_STATE enumeration data type contains the following values:

Enumerator Value Comment


TM3_CONF_ERROR 01 hex Error detected due to mismatch in the physical
configuration and the configuration in EcoStruxure Machine
Expert.
TM3_OK 03 hex The physical configuration and the configuration in
EcoStruxure Machine Expert match.
TM3_POWER_SUPPLY_ERROR 04 hex Error detected in power supply.

74 EIO0000003095 12/2019
M251 PLC System Library Data Types

PLC_W_COMMAND: Control Command Codes

Enumerated Type Description


The PLC_W_COMMAND enumeration data type contains the following values:

Enumerator Value Comment


PLC_W_STOP 0001 hex Command to stop the controller.
PLC_W_RUN 0002 hex Command to run the controller.
PLC_W_RESET_COLD 0004 hex Command to initiate a Controller cold reset.
PLC_W_RESET_WARM 0008 hex Command to initiate a Controller warm reset.

EIO0000003095 12/2019 75
M251 PLC System Library Data Types

Section 3.2
DataFileCopy System Variables Data Types

DataFileCopy System Variables Data Types

Overview
This section lists and describes the system variable data types included in the DataFileCopy
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
DataFileCopyError: Detected Error Codes 77
DataFileCopyLocation: Location Codes 78

76 EIO0000003095 12/2019
M251 PLC System Library Data Types

DataFileCopyError: Detected Error Codes

Enumerated Type Description


The DataFileCopyError enumeration data type contains the following values:

Enumerator Value Description


ERR_NO_ERR 00 hex No error detected.
ERR_FILE_NOT_FOUND 01 hex The file does not exist.
ERR_FILE_ACCESS_REFUSED 02 hex The file cannot be opened.
ERR_INCORRECT_SIZE 03 hex The request size is not the same as size
read from file.
ERR_CRC_ERR 04 hex The CRC is not correct and the file is
assumed to be corrupted.
ERR_INCORRECT_MAC 05 hex The controller attempting to read from the
file does not have the same MAC address
as that contained in the file.

EIO0000003095 12/2019 77
M251 PLC System Library Data Types

DataFileCopyLocation: Location Codes

Enumerated Type Description


The DataFileCopyLocation enumeration data type contains the following values:

Enumerator Value Description


DFCL_INTERNAL 00 hex Data file with DTA extension is located in
/usr/Dta directory.
DFCL_EXTERNAL 01 hex Data file with DTA extension is located in
/sd0/usr/Dta directory.
DFCL_TBD 02 hex Not used.

78 EIO0000003095 12/2019
M251 PLC System Library Data Types

Section 3.3
ExecScript System Variables Data Types

ExecScript System Variables Data Types

ExecuteScriptError: Detected Error Codes

Enumerated Type Description


The ExecuteScriptError enumeration data type contains the following values:

Enumerator Value Description


CMD_OK 00 hex No error detected.
ERR_CMD_UNKNOWN 01 hex The command is not recognized.
ERR_SD_CARD_MISSING 02 hex SD card is not present.
ERR_SEE_FWLOG 03 hex There was an error detected during command
execution, see FwLog.txt. For more
information, refer to File Type (see Modicon
M251 Logic Controller, Programming Guide).
ERR_ONLY_ONE_COMMAND_ALLOWED 04 hex An attempt was made to execute several scripts
simultaneously.
CMD_BEING_EXECUTED 05 hex A script is already in progress.

EIO0000003095 12/2019 79
M251 PLC System Library Data Types

Section 3.4
ETH_RW System Variables Data Types

ETH_RW System Variables Data Types

Overview
This section lists and describes the system variable data types included in the ETH_R and ETH_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes 81
ETH_R_IP_MODE: IP Address Source Codes 82
ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes 83
ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes 84
ETH_R_PORT_LINK_STATUS: Communication Link Status Codes 85
ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port Codes 86
ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes 87

80 EIO0000003095 12/2019
M251 PLC System Library Data Types

ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes

Enumerated Type Description


The ETH_R_FRAME_PROTOCOL enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_802_3 00 hex The protocol used for frame transmission is
IEEE 802.3.
ETH_R_ETHERNET_II 01 hex The protocol used for frame transmission is
Ethernet II.

EIO0000003095 12/2019 81
M251 PLC System Library Data Types

ETH_R_IP_MODE: IP Address Source Codes

Enumerated Type Description


The ETH_R_IP_MODE enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_STORED 00 hex Stored IP address is used.
ETH_R_BOOTP 01 hex Bootstrap protocol is used to get an IP address.
ETH_R_DHCP 02 hex DHCP protocol is used to get an IP address.
ETH_DEFAULT_IP FF hex Default IP address is used.

82 EIO0000003095 12/2019
M251 PLC System Library Data Types

ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes

Enumerated Type Description


The ETH_R_PORT_DUPLEX_STATUS enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_PORT_HALF_DUPLEX 00 hex Half duplex transmission mode is used.
ETH_R_FULL_DUPLEX 01 hex Full duplex transmission mode is used.
ETH_R_PORT_NA_DUPLEX 03 hex No duplex transmission mode is used.

EIO0000003095 12/2019 83
M251 PLC System Library Data Types

ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes

Enumerated Type Description


The ETH_R_PORT_IP_STATUS enumeration data type contains the following values:

Enumerator Value Comment


WAIT_FOR_PARAMS 00 hex Waiting for parameters.
WAIT_FOR_CONF 01 hex Waiting for configuration.
DATA_EXCHANGE 02 hex Ready for data exchange.
ETH_ERROR 03 hex Ethernet TCP/IP port error detected (cable
disconnected, invalid configuration, and so on).
DUPLICATE_IP 04 hex IP address already used by another equipment.

84 EIO0000003095 12/2019
M251 PLC System Library Data Types

ETH_R_PORT_LINK_STATUS: Communication Link Status Codes

Enumerated Type Description


The ETH_R_PORT_LINK_STATUS enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_LINK_DOWN 00 hex Communication link not available to another device.
ETH_R_LINK_UP 01 hex Communication link available to another device.

EIO0000003095 12/2019 85
M251 PLC System Library Data Types

ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port Codes

Enumerated Type Description


The ETH_R_PORT_SPEED enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_SPEED_NA 0 dec Network speed is not available.
ETH_R_SPEED_10_MB 10 dec Network speed is 10 megabits per second.
ETH_R_100_MB 100 dec Network speed is 100 megabits per second.

86 EIO0000003095 12/2019
M251 PLC System Library Data Types

ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes

Enumerated Type Description


The ETH_R_RUN_IDLE enumeration data type contains the following values:

Enumerator Value Comment


IDLE 00 hex EtherNet/IP connection is idle.
RUN 01 hex EtherNet/IP connection is running.

EIO0000003095 12/2019 87
M251 PLC System Library Data Types

Section 3.5
TM3_MODULE_RW System Variables Data Types

TM3_MODULE_RW System Variables Data Types

Overview
This section lists and describes the system variable data types included in the TM3_MODULE_R and
TM3_MODULE_W structures.

What Is in This Section?


This section contains the following topics:
Topic Page
TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes 89
TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read Array Type 90
TM3_MODULE_STATE: TM3 Expansion Module State Codes 91
TM3_BUS_W_IOBUSERRMOD: TM3 bus error mode 92

88 EIO0000003095 12/2019
M251 PLC System Library Data Types

TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes

Enumerated Type Description


The TM3_ERR_CODE enumeration data type contains the following values:

Enumerator Value Comment


TM3_NO_ERR 00 hex Last bus exchange with the expansion module was
successful.
TM3_ERR_FAILED 01 hex Error detected due to the last bus exchange with the
expansion module was unsuccessful.
TM3_ERR_PARAMETER 02 hex Parameter error detected in the last bus exchange with the
module.
TM3_ERR_COK 03 hex Temporary or permanent hardware error detected on one
of the TM3 expansion modules.
TM3_ERR_BUS 04 hex Bus error detected in the last bus exchange with the
expansion module.

EIO0000003095 12/2019 89
M251 PLC System Library Data Types

TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read Array Type

Description
The TM3_MODULE_R_ARRAY_TYPE is an array of 0...13 TM3_MODULE_R_STRUCT.

90 EIO0000003095 12/2019
M251 PLC System Library Data Types

TM3_MODULE_STATE: TM3 Expansion Module State Codes

Enumerated Type Description


The TM3_MODULE_STATE enumeration data type contains the following values:

Enumerator Value Comment


TM3_EMPTY 00 hex No module.
TM3_CONF_ERROR 01 hex Physical expansion module does not match with the one
configured in EcoStruxure Machine Expert.
TM3_BUS_ERROR 02 hex Bus error detected in the last exchange with the module.
TM3_OK 03 hex Last bus exchange with this module was successful.
TM3_MISSING_OPT_MOD 05 hex Optional module is not physically present.

EIO0000003095 12/2019 91
M251 PLC System Library Data Types

TM3_BUS_W_IOBUSERRMOD: TM3 bus error mode

Enumerated Type Description


The TM3_BUS_W_IOBUSERRMOD enumeration data type contains the following values:

Enumerator Value Comment


IOBUS_ERR_ACTIVE 00 hex Active mode. The logic controller stops all I/O exchanges
on the TM3 bus on detection of a permanent error. Refer to
I/O Configuration General Description (see Modicon M251
Logic Controller, Programming Guide).
IOBUS_ERR_PASSIVE 01 hex Passive mode. I/O exchanges continue on the TM3 bus
even if an error is detected.

92 EIO0000003095 12/2019
M251 PLC System Library Data Types

Section 3.6
System Function Data Types

System Function Data Types

RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error Codes

Enumerated Type Description


The RTCSETDRIFT_ERROR enumeration data type contains the following values:

Enumerator Value Comment


RTC_OK 00 hex RTC drift correctly configured.
RTC_BAD_DAY 01 hex Not used.
RTC_BAD_HOUR 02 hex Not used.
RTC_BAD_MINUTE 03 hex Not used.
RTC_BAD_DRIFT 04 hex RTC Drift parameter out of range.
RTC_INTERNAL_ERROR 05 hex RTC Drift settings rejected on internal error detected.

EIO0000003095 12/2019 93
M251 PLC System Library Data Types

94 EIO0000003095 12/2019
Modicon M251 Logic Controller

EIO0000003095 12/2019

Appendices

EIO0000003095 12/2019 95
96 EIO0000003095 12/2019
Modicon M251 Logic Controller
Function and Function Block Representation
EIO0000003095 12/2019

Appendix A
Function and Function Block Representation

Function and Function Block Representation

Overview
Each function can be represented in the following languages:
 IL: Instruction List
 ST: Structured Text
 LD: Ladder Diagram
 FBD: Function Block Diagram
 CFC: Continuous Function Chart

This chapter provides functions and function blocks representation examples and explains how to
use them for IL and ST languages.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Differences Between a Function and a Function Block 98
How to Use a Function or a Function Block in IL Language 99
How to Use a Function or a Function Block in ST Language 103

EIO0000003095 12/2019 97
Function and Function Block Representation

Differences Between a Function and a Function Block

Function
A function:
 is a POU (Program Organization Unit) that returns one immediate result.
 is directly called with its name (not through an instance).
 has no persistent state from one call to the other.
 can be used as an operand in other expressions.

Examples: boolean operators (AND), calculations, conversion (BYTE_TO_INT)

Function Block
A function block:
 is a POU (Program Organization Unit) that returns one or more outputs.
 needs to be called by an instance (function block copy with dedicated name and variables).
 each instance has a persistent state (outputs and internal variables) from one call to the other
from a function block or a program.
Examples: timers, counters
In the example, Timer_ON is an instance of the function block TON:

98 EIO0000003095 12/2019
Function and Function Block Representation

How to Use a Function or a Function Block in IL Language

General Information
This part explains how to implement a function and a function block in IL language.
Functions IsFirstMastCycle and SetRTCDrift and Function Block TON are used as
examples to show implementations.

Using a Function in IL Language


This procedure describes how to insert a function in IL language:

Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see EcoStruxure Machine Expert, Programming Guide).
2 Create the variables that the function requires.
3 If the function has 1 or more inputs, start loading the first input using LD instruction.
4 Insert a new line below and:
 type the name of the function in the operator column (left field), or
 use the Input Assistant to select the function (select Insert Box in the context menu).

5 If the function has more than 1 input and when Input Assistant is used, the necessary number of lines
is automatically created with ??? in the fields on the right. Replace the ??? with the appropriate
value or variable that corresponds to the order of inputs.
6 Insert a new line to store the result of the function into the appropriate variable: type ST instruction
in the operator column (left field) and the variable name in the field on the right.

To illustrate the procedure, consider the Functions IsFirstMastCycle (without input parameter)
and SetRTCDrift (with input parameters) graphically presented below:

Function Graphical Representation


without input parameter:
IsFirstMastCycle

with input parameters:


SetRTCDrift

EIO0000003095 12/2019 99
Function and Function Block Representation

In IL language, the function name is used directly in the operator column:

Function Representation in POU IL Editor


IL example of a function
without input parameter:
IsFirstMastCycle

IL example of a function
with input parameters:
SetRTCDrift

100 EIO0000003095 12/2019


Function and Function Block Representation

Using a Function Block in IL Language


This procedure describes how to insert a function block in IL language:

Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see EcoStruxure Machine Expert, Programming Guide).
2 Create the variables that the function block requires, including the instance name.
3 Function Blocks are called using a CAL instruction:
 Use the Input Assistant to select the FB (right-click and select Insert Box in the context menu).
 Automatically, the CAL instruction and the necessary I/O are created.

Each parameter (I/O) is an instruction:


 Values to inputs are set by ":=".
 Values to outputs are set by "=>".

4 In the CAL right-side field, replace ??? with the instance name.
5 Replace other ??? with an appropriate variable or immediate value.

To illustrate the procedure, consider this example with the TON Function Block graphically
presented below:

Function Block Graphical Representation


TON

EIO0000003095 12/2019 101


Function and Function Block Representation

In IL language, the function block name is used directly in the operator column:

Function Block Representation in POU IL Editor


TON

102 EIO0000003095 12/2019


Function and Function Block Representation

How to Use a Function or a Function Block in ST Language

General Information
This part explains how to implement a Function and a Function Block in ST language.
Function SetRTCDrift and Function Block TON are used as examples to show implementations.

Using a Function in ST Language


This procedure describes how to insert a function in ST language:

Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see EcoStruxure Machine Expert, Programming Guide).
2 Create the variables that the function requires.
3 Use the general syntax in the POU ST Editor for the ST language of a function. The general syntax
is:
FunctionResult:= FunctionName(VarInput1, VarInput2,.. VarInputx);

To illustrate the procedure, consider the function SetRTCDrift graphically presented below:

Function Graphical Representation


SetRTCDrift

The ST language of this function is the following:

Function Representation in POU ST Editor


SetRTCDrift PROGRAM MyProgram_ST
VAR myDrift: SINT(-29..29) := 5;
myDay: DAY_OF_WEEK := SUNDAY;
myHour: HOUR := 12;
myMinute: MINUTE;
myRTCAdjust: RTCDRIFT_ERROR;
END_VAR
myRTCAdjust:= SetRTCDrift(myDrift, myDay, myHour, myMinute);

EIO0000003095 12/2019 103


Function and Function Block Representation

Using a Function Block in ST Language


This procedure describes how to insert a function block in ST language:

Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information on
adding, declaring and calling POUs, refer to the related documentation
(see EcoStruxure Machine Expert, Programming Guide).
2 Create the input and output variables and the instance required for the function block:
 Input variables are the input parameters required by the function block
 Output variables receive the value returned by the function block

3 Use the general syntax in the POU ST Editor for the ST language of a Function Block.
The general syntax is:
FunctionBlock_InstanceName(Input1:=VarInput1,
Input2:=VarInput2,... Ouput1=>VarOutput1,
Ouput2=>VarOutput2,...);

To illustrate the procedure, consider this example with the TON function block graphically
presented below:

Function Block Graphical Representation


TON

104 EIO0000003095 12/2019


Function and Function Block Representation

This table shows examples of a function block call in ST language:

Function Block Representation in POU ST Editor


TON

EIO0000003095 12/2019 105


Function and Function Block Representation

106 EIO0000003095 12/2019


Modicon M251 Logic Controller
Glossary
EIO0000003095 12/2019

Glossary

!
%MW
According to the IEC standard, %MW represents a memory word register (for example, a language
object of type memory word).

A
application
A program including configuration data, symbols, and documentation.
ARRAY
The systematic arrangement of data objects of a single type in the form of a table defined in logic
controller memory. The syntax is as follows: ARRAY [<dimension>] OF <Type>
Example 1: ARRAY [1..2] OF BOOL is a 1-dimensional table with 2 elements of type BOOL.
Example 2: ARRAY [1..10, 1..20] OF INT is a 2-dimensional table with 10 x 20 elements of
type INT.

B
BOOL
(boolean) A basic data type in computing. A BOOL variable can have one of these values: 0
(FALSE), 1 (TRUE). A bit that is extracted from a word is of type BOOL; for example, %MW10.4 is a
fifth bit of memory word number 10.
Boot application
(boot application) The binary file that contains the application. Usually, it is stored in the controller
and allows the controller to boot on the application that the user has generated.
BOOTP
(bootstrap protocol) A UDP network protocol that can be used by a network client to automatically
obtain an IP address (and possibly other data) from a server. The client identifies itself to the server
using the client MAC address. The server, which maintains a pre-configured table of client device
MAC addresses and associated IP addresses, sends the client its pre-configured IP address.
BOOTP was originally used as a method that enabled diskless hosts to be remotely booted over a
network. The BOOTP process assigns an infinite lease of an IP address. The BOOTP service
utilizes UDP ports 67 and 68.
byte
A type that is encoded in an 8-bit format, ranging from 00 hex to FF hex.

EIO0000003095 12/2019 107


Glossary

C
CFC
(continuous function chart) A graphical programming language (an extension of the IEC 61131-3
standard) based on the function block diagram language that works like a flowchart. However, no
networks are used and free positioning of graphic elements is possible, which allows feedback
loops. For each block, the inputs are on the left and the outputs on the right. You can link the block
outputs to the inputs of other blocks to create complex expressions.
configuration
The arrangement and interconnection of hardware components within a system and the hardware
and software parameters that determine the operating characteristics of the system.
control network
A network containing logic controllers, SCADA systems, PCs, HMI, switches, ...
Two kinds of topologies are supported:
 flat: all modules and devices in this network belong to same subnet.
 2 levels: the network is split into an operation network and an inter-controller network.

These two networks can be physically independent, but are generally linked by a routing device.
CRC
(cyclical redundancy check) A method used to determine the validity of a communication
transmission. The transmission contains a bit field that constitutes a checksum. The message is
used to calculate the checksum by the transmitter according to the content of the message.
Receiving nodes, then recalculate the field in the same manner. Any discrepancy in the value of
the 2 CRC calculations indicates that the transmitted message and the received message are
different.

D
DHCP
(dynamic host configuration protocol) An advanced extension of BOOTP. DHCP is more
advanced, but both DHCP and BOOTP are common. (DHCP can handle BOOTP client requests.)
DWORD
(double word) Encoded in 32-bit format.

E
element
The short name of the ARRAY element.
equipment
A part of a machine including sub-assemblies such as conveyors, turntables, and so on.

108 EIO0000003095 12/2019


Glossary

Ethernet
A physical and data link layer technology for LANs, also known as IEEE 802.3.
EtherNet/IP
(Ethernet industrial protocol) An open communications protocol for manufacturing automation
solutions in industrial systems. EtherNet/IP is in a family of networks that implement the common
industrial protocol at its upper layers. The supporting organization (ODVA) specifies EtherNet/IP
to accomplish global adaptability and media independence.

F
FB
(function block) A convenient programming mechanism that consolidates a group of programming
instructions to perform a specific and normalized action, such as speed control, interval control, or
counting. A function block may comprise configuration data, a set of internal or external operating
parameters and usually 1 or more data inputs and outputs.
firmware
Represents the BIOS, data parameters, and programming instructions that constitute the operating
system on a controller. The firmware is stored in non-volatile memory within the controller.
flash memory
A non-volatile memory that can be overwritten. It is stored on a special EEPROM that can be
erased and reprogrammed.
function
A programming unit that has 1 input and returns 1 immediate result. However, unlike FBs, it is
directly called with its name (as opposed to through an instance), has no persistent state from one
call to the next and can be used as an operand in other programming expressions.
Examples: boolean (AND) operators, calculations, conversions (BYTE_TO_INT)
function block
A programming unit that has 1 or more inputs and returns 1 or more outputs. FBs are called through
an instance (function block copy with dedicated name and variables) and each instance has a
persistent state (outputs and internal variables) from 1 call to the other.
Examples: timers, counters
function block diagram
One of the 5 languages for logic or control supported by the standard IEC 61131-3 for control
systems. Function block diagram is a graphically oriented programming language. It works with a
list of networks where each network contains a graphical structure of boxes and connection lines
representing either a logical or arithmetic expression, the call of a function block, a jump, or a return
instruction.

EIO0000003095 12/2019 109


Glossary

G
GVL
(global variable list) Manages global variables within an EcoStruxure Machine Expert project.

H
hex
(hexadecimal)

I
ID
(identifier/identification)
IEC
(international electrotechnical commission) A non-profit and non-governmental international
standards organization that prepares and publishes international standards for electrical,
electronic, and related technologies.
IEC 61131-3
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with
controller programming languages and defines 2 graphical and 2 textual programming language
standards. The graphical programming languages are ladder diagram and function block diagram.
The textual programming languages include structured text and instruction list.
IEEE 802.3
A collection of IEEE standards defining the physical layer, and the media access control sublayer
of the data link layer, of wired Ethernet.
IL
(instruction list) A program written in the language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (refer to IEC 61131-3).
INT
(integer) A whole number encoded in 16 bits.
IP
(Internet protocol Part of the TCP/IP protocol family that tracks the Internet addresses of devices,
routes outgoing messages, and recognizes incoming messages.

110 EIO0000003095 12/2019


Glossary

L
LD
(ladder diagram) A graphical representation of the instructions of a controller program with symbols
for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to
IEC 61131-3).
LWORD
(long word) A data type encoded in a 64-bit format.

M
MAC address
(media access control address) A unique 48-bit number associated with a specific piece of
hardware. The MAC address is programmed into each network card or device when it is
manufactured.
MAST
A processor task that is run through its programming software. The MAST task has 2 sections:
 IN: Inputs are copied to the IN section before execution of the MAST task.
 OUT: Outputs are copied to the OUT section after execution of the MAST task.

N
network
A system of interconnected devices that share a common data path and protocol for
communications.

P
PLC
(programmable logic controller) An industrial computer used to automate manufacturing, industrial,
and other electromechanical processes. PLCs are different from common computers in that they
are designed to have multiple input and output arrays and adhere to more robust specifications for
shock, vibration, temperature, and electrical interference among other things.
POU
(program organization unit) A variable declaration in source code and a corresponding instruction
set. POUs facilitate the modular re-use of software programs, functions, and function blocks. Once
declared, POUs are available to one another.
program
The component of an application that consists of compiled source code capable of being installed
in the memory of a logic controller.

EIO0000003095 12/2019 111


Glossary

protocol
A convention or standard definition that controls or enables the connection, communication, and
data transfer between 2 computing system and devices.

R
run
A command that causes the controller to scan the application program, read the physical inputs,
and write to the physical outputs according to solution of the logic of the program.

S
ST
(structured text) A language that includes complex statements and nested instructions (such as
iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
STOP
A command that causes the controller to stop running an application program.
string
A variable that is a series of ASCII characters.
system variable
A variable that provides controller data and diagnostic information and allows sending commands
to the controller.

T
task
A group of sections and subroutines, executed cyclically or periodically for the MAST task or
periodically for the FAST task.
A task possesses a level of priority and is linked to inputs and outputs of the controller. These I/O
are refreshed in relation to the task.
A controller can have several tasks.
TCP
(transmission control protocol) A connection-based transport layer protocol that provides a
simultaneous bi-directional transmission of data. TCP is part of the TCP/IP protocol suite.

U
UDINT
(unsigned double integer) Encoded in 32 bits.

112 EIO0000003095 12/2019


Glossary

UINT
(unsigned integer) Encoded in 16 bits.
unlocated variable
A variable that does not have an address (refer to located variable).

V
variable
A memory unit that is addressed and modified by a program.

W
watchdog
A watchdog is a special timer used to ensure that programs do not overrun their allocated scan
time. The watchdog timer is usually set to a higher value than the scan time and reset to 0 at the
end of each scan cycle. If the watchdog timer reaches the preset value, for example, because the
program is caught in an endless loop, an error is declared and the program stopped.
WORD
A type encoded in a 16-bit format.

EIO0000003095 12/2019 113


Glossary

114 EIO0000003095 12/2019


Modicon M251 Logic Controller
Index
EIO0000003095 12/2019

Index

Specials DataFileCopyLocation
Data Types, 78

C E
cycle
ETH_R
IsFirstMastColdCycle, 40
System Variable, 27
IsFirstMastCycle, 41
ETH_R_FRAME_PROTOCOL
IsFirstMastWarmCycle, 43
Data Types, 81
ETH_R_IP_MODE
Data Types, 82
D ETH_R_PORT_DUPLEX_STATUS
Data Types Data Types, 83
DataFileCopyError, 77 ETH_R_PORT_LINK_STATUS
DataFileCopyLocation, 78 Data Types, 85
ETH_R_FRAME_PROTOCOL, 81 ETH_R_PORT_SPEED
ETH_R_IP_MODE, 82 Data Types, 86
ETH_R_PORT_DUPLEX_STATUS, 83 ETH_W
ETH_R_PORT_IP_STATUS, 84 System Variable, 33
ETH_R_PORT_LINK_STATUS, 85 ExecuteScript
ETH_R_PORT_SPEED, 86 running script commands, 51
ETH_R_RUN_IDLE, 87 ExecuteScriptError
ExecuteScriptError, 79 Data Types, 79
PLC_R_APPLICATION_ERROR, 65
PLC_R_BOOT_PROJECT_STATUS, 67
PLC_R_IO_STATUS, 68 F
PLC_R_SDCARD_STATUS, 69
FB_ControlClone
PLC_R_STATUS, 70
function block, 47
PLC_R_STOP_CAUSE, 71
FC_GetFreeDiskSpace, 54
PLC_R_TERMINAL_PORT_STATUS, 73
FC_GetLabel, 55
PLC_R_TM3_BUS_STATE, 74
FC_GetTotalDiskSpace, 56
PLC_W_COMMAND, 75
file copy commands
RTCSETDRIFT_ERROR, 93
DataFileCopy, 48
TM3_BUS_W_IOBUSERRMOD, 92
functions
TM3_ERR_CODE, 89
differences between a function and a
TM3_MODULE_R_ARRAY_TYPE, 90
function block, 98
TM3_MODULE_STATE, 91
how to use a function or a function block
DataFileCopy
in IL language, 99
copying data to or from a file, 48
how to use a function or a function block
DataFileCopyError
in ST language, 103
Data Types, 77

EIO0000003095 12/2019 115


Index

G PLC_R_TM3_BUS_STATE
Data Types, 74
GetRtc
PLC_W
getting real time clock (RTC) value, 39
System Variable, 22
PLC_W_COMMAND
Data Types, 75
I PROFIBUS_R
IsFirstMastColdCycle System Variable, 36
first cold start cycle, 40
IsFirstMastCycle
first mast cycle, 41 R
IsFirstMastWarmCycle
real time clock
first warm start cycle, 43
GetRtc, 39
SetRTCDrift, 44
M RTC
GetRtc, 39
M241 PLCSystem SetRTCDrift, 44
DataFileCopy, 48 RTCSETDRIFT_ERROR
ExecuteScript, 51 Data Types, 93
GetRtc, 39
IsFirstMastColdCycle, 40
IsFirstMastCycle, 41 S
IsFirstMastWarmCycle, 43
script commands
TM3_GetModuleBusStatus, 58, 60
ExecuteScript, 51
TM3_GetModuleFWVersion, 59
SERIAL_R
System Variable, 24
P SERIAL_W
System Variable, 25
PLC_R SetRTCDrift
System Variable, 18 accelerating or slowing the RTC frequen-
PLC_R_APPLICATION_ERROR cy, 44
Data Types, 65 System Variable
PLC_R_BOOT_PROJECT_STATUS ETH_R, 27
Data Types, 67 ETH_W, 33
PLC_R_IO_STATUS PLC_R, 18
Data Types, 68 PLC_W, 22
PLC_R_SDCARD_STATUS System variable
Data Types, 69 PROFIBUS_R, 36
PLC_R_STATUS System Variable
Data Types, 70 SERIAL_R, 24
PLC_R_STOP_CAUSE SERIAL_W, 25
Data Types, 71 TM3_BUS_W, 35
PLC_R_TERMINAL_PORT_STATUS TM3_MODULE_R, 34
Data Types, 73

116 EIO0000003095 12/2019


Index

System Variables
Definition, 13
Using, 15

T
TM3 module bus status
TM3_GetModuleBusStatus, 58
TM3 module firmware version
TM3_GetModuleFWVersion, 59
TM3 module internal status
TM3_GetModuleInternalStatus, 60
TM3_BUS_W
system variable, 35
TM3_BUS_W_IOBUSERRMOD
Data Types, 92
TM3_ERR_CODE
Data Types, 89
TM3_GetModuleBusStatus
getting the bus status of a TM3 module,
58
TM3_GetModuleFWVersion
getting the firmware version of a TM3
module, 59
TM3_GetModuleInternalStatus
getting the internal status of a TM3 mod-
ule, 60
TM3_MODULE_R
System Variable, 34
TM3_MODULE_R_ARRAY_TYPE
Data Types, 90
TM3_MODULE_STATE
Data Types, 91

U
unction blocks
FB_ControlClone, 47

EIO0000003095 12/2019 117


Index

118 EIO0000003095 12/2019


Modicon M251 Logic Controller

EIO0000003101 12/2019

Modicon M251
Logic Controller
Hardware Guide
12/2019
EIO0000003101.01

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.

2 EIO0000003101 12/2019
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Part I Modicon M251 Logic Controller Introduction . . . . . . 15
Chapter 1 M251 General Overview . . . . . . . . . . . . . . . . . . . . . . . . . 17
M251 Logic Controller Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Maximum Hardware Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TM2 Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
TM3 Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
TM3 Bus Couplers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
TM4 Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
TM5 Fieldbus Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
TM5 CANopen Fieldbus Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
TM7 CANopen Fieldbus Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Chapter 2 M251 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Real Time Clock (RTC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Run/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Chapter 3 M251 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.1 M251 Logic Controller General Rules for Implementing . . . . . . . . . . . 54
Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Certifications and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
3.2 M251 Logic Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Installation and Maintenance Requirements . . . . . . . . . . . . . . . . . . . . 60
M251 Logic Controller Mounting Positions and Clearances . . . . . . . . 63
Top Hat Section Rail (DIN rail) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Installing and Removing the Controller with Expansions. . . . . . . . . . . 70
Direct Mounting on a Panel Surface . . . . . . . . . . . . . . . . . . . . . . . . . . 73
3.3 M251 Electrical Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Wiring Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
DC Power Supply Characteristics and Wiring . . . . . . . . . . . . . . . . . . . 78
Grounding the M251 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

EIO0000003101 12/2019 3
Part II Modicon M251 Logic Controller . . . . . . . . . . . . . . . . 85
Chapter 4 TM251MESC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
TM251MESC Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Chapter 5 TM251MESE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
TM251MESE Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Part III Modicon M251 Logic Controller Communication . . . 95
Chapter 6 Integrated Communication Ports . . . . . . . . . . . . . . . . . . . 97
CAN Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
TM251MESE Specific Considerations . . . . . . . . . . . . . . . . . . . . . . . . . 103
USB Mini-B Programming Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Serial Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Chapter 7 Connecting the M251 Logic Controller to a PC . . . . . . . . 109
Connecting the Controller to a PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

4 EIO0000003101 12/2019
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.

EIO0000003101 12/2019 5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.

QUALIFICATION OF PERSONNEL
Only appropriately trained persons who are familiar with and understand the contents of this
manual and all other pertinent product documentation are authorized to work on and with this
product.
The qualified person must be able to detect possible hazards that may arise from parameterization,
modifying parameter values and generally from mechanical, electrical, or electronic equipment.
The qualified person must be familiar with the standards, provisions, and regulations for the
prevention of industrial accidents, which they must observe when designing and implementing the
system.

INTENDED USE
The products described or affected by this document, together with software, accessories, and
options, are programmable logic controllers (referred to herein as “logic controllers”), intended for
industrial use according to the instructions, directions, examples, and safety information contained
in the present document and other supporting documentation.
The product may only be used in compliance with all applicable safety regulations and directives,
the specified requirements, and the technical data.
Prior to using the product, you must perform a risk assessment in view of the planned application.
Based on the results, the appropriate safety-related measures must be implemented.
Since the product is used as a component in an overall machine or process, you must ensure the
safety of persons by means of the design of this overall system.
Operate the product only with the specified cables and accessories. Use only genuine accessories
and spare parts.
Any use other than the use explicitly permitted is prohibited and can result in unanticipated
hazards.

6 EIO0000003101 12/2019
About the Book

At a Glance

Document Scope
Use this document to:
 Install and operate your M251 Logic Controller.
 Connect the M251 Logic Controller to a programming device equipped with EcoStruxure
Machine Expert software.
 Interface the M251 Logic Controller with I/O expansion modules, HMI and other devices.
 Familiarize yourself with the M251 Logic Controller features.

NOTE: Read and understand this document and all related documents before installing, operating,
or maintaining your controller.

Validity Note
This document has been updated for the release of EcoStruxureTM Machine Expert V1.2.
For product compliance and environmental information (RoHS, REACH, PEP, EOLI, etc.), go to
www.schneider-electric.com/green-premium.
The technical characteristics of the devices described in this manual also appear online
(https://www.se.com/).
The characteristics that are described in the present document should be the same as those
characteristics that appear online. In line with our policy of constant improvement, we may revise
content over time to improve clarity and accuracy. If you see a difference between the document
and online information, use the online information as your reference.

EIO0000003101 12/2019 7
Related Documents

Title of Documentation Reference Number


Modicon M251 Logic Controller - Programming Guide EIO0000003089 (ENG)
EIO0000003090 (FRE)
EIO0000003091 (GER)
EIO0000003092 (SPA)
EIO0000003093 (ITA)
EIO0000003094 (CHS)
EcoStruxure Machine Expert Industrial Ethernet User Guide EIO0000003053 (ENG)
EIO0000003054 (FRE)
EIO0000003055 (GER)
EIO0000003056 (SPA)
EIO0000003057 (ITA)
EIO0000003058 (CHS)
Modicon TM3 Digital I/O Modules - Hardware Guide EIO0000003125 (ENG)
EIO0000003126 (FRE)
EIO0000003127 (GER)
EIO0000003128 (SPA)
EIO0000003129 (ITA)
EIO0000003130 (CHS)
EIO0000003425 (TUR)
EIO0000003424 (POR)
Modicon TM3 Expert I/O Modules - Hardware Guide EIO0000003137 (ENG)
EIO0000003138 (FRE)
EIO0000003139 (GER)
EIO0000003140 (SPA)
EIO0000003141 (ITA)
EIO0000003142 (CHS)
EIO0000003429 (TUR)
EIO0000003428 (POR)
Modicon TM3 Safety Modules - Hardware Guide EIO0000003353 (ENG)
EIO0000003354 (FRE)
EIO0000003355 (GER)
EIO0000003356 (SPA)
EIO0000003357 (ITA)
EIO0000003358 (CHS)
EIO0000003359 (POR)
EIO0000003360 (TUR)

8 EIO0000003101 12/2019
Title of Documentation Reference Number
Modicon TM3 Transmitter and Receiver Modules - Hardware Guide EIO0000003143 (ENG)
EIO0000003144 (FRE)
EIO0000003145 (GER)
EIO0000003146 (SPA)
EIO0000003147 (ITA)
EIO0000003148 (CHS)
EIO0000003431 (TUR)
EIO0000003430 (POR)
Modicon TM3 Bus Coupler - Hardware Guide EIO0000003635 (ENG)
EIO0000003636 (FRE)
EIO0000003637 (GER)
EIO0000003638 (SPA)
EIO0000003639 (ITA)
EIO0000003640 (CHS)
EIO0000003641 (POR)
EIO0000003642 (TUR)
Modicon TM4 Expansion Modules - Hardware Guide EIO0000003155 (ENG)
EIO0000003156 (FRE)
EIO0000003157 (GER)
EIO0000003158 (SPA)
EIO0000003159 (ITA)
EIO0000003160 (CHS)
Modicon TM5 Fieldbus Interface - Hardware Guide EIO0000003715 (ENG)
EIO0000003716 (FRE)
EIO0000003717 (GER)
EIO0000003718 (SPA)
EIO0000003719 (ITA)
EIO0000003720 (CHS)
M251 Logic Controller - Instruction Sheet HRB59604

You can download these technical publications and other technical information from our website
at https://www.se.com/ww/en/download/ .

EIO0000003101 12/2019 9
Product Related Information

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires except
under the specific conditions specified in the appropriate hardware guide for this equipment.
 Always use a properly rated voltage sensing device to confirm the power is off where and when
indicated.
 Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
 Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.

DANGER
POTENTIAL FOR EXPLOSION
 Only use this equipment in non-hazardous locations, or in locations that comply with Class I,
Division 2, Groups A, B, C and D.
 Do not substitute components which would impair compliance to Class I, Division 2.
 Do not connect or disconnect equipment unless power has been removed or the location is
known to be non-hazardous.
 Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions will result in death or serious injury.

10 EIO0000003101 12/2019
WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths
and, for certain critical control functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are emergency stop and overtravel
stop, power outage and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.1
 Each implementation of this equipment must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest
edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003101 12/2019 11
Terminology Derived from Standards
The technical terms, terminology, symbols and the corresponding descriptions in this manual, or
that appear in or on the products themselves, are generally derived from the terms or definitions
of international standards.
In the area of functional safety systems, drives and general automation, this may include, but is not
limited to, terms such as safety, safety function, safe state, fault, fault reset, malfunction, failure,
error, error message, dangerous, etc.
Among others, these standards include:

Standard Description
IEC 61131-2:2007 Programmable controllers, part 2: Equipment requirements and tests.
ISO 13849-1:2015 Safety of machinery: Safety related parts of control systems.
General principles for design.
EN 61496-1:2013 Safety of machinery: Electro-sensitive protective equipment.
Part 1: General requirements and tests.
ISO 12100:2010 Safety of machinery - General principles for design - Risk assessment and risk
reduction
EN 60204-1:2006 Safety of machinery - Electrical equipment of machines - Part 1: General
requirements
ISO 14119:2013 Safety of machinery - Interlocking devices associated with guards - Principles
for design and selection
ISO 13850:2015 Safety of machinery - Emergency stop - Principles for design
IEC 62061:2015 Safety of machinery - Functional safety of safety-related electrical, electronic,
and electronic programmable control systems
IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: General requirements.
IEC 61508-2:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: Requirements for electrical/electronic/programmable
electronic safety-related systems.
IEC 61508-3:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: Software requirements.
IEC 61784-3:2016 Industrial communication networks - Profiles - Part 3: Functional safety
fieldbuses - General rules and profile definitions.
2006/42/EC Machinery Directive
2014/30/EU Electromagnetic Compatibility Directive
2014/35/EU Low Voltage Directive

12 EIO0000003101 12/2019
In addition, terms used in the present document may tangentially be used as they are derived from
other standards such as:

Standard Description
IEC 60034 series Rotating electrical machines
IEC 61800 series Adjustable speed electrical power drive systems
IEC 61158 series Digital data communications for measurement and control – Fieldbus for use in
industrial control systems

Finally, the term zone of operation may be used in conjunction with the description of specific
hazards, and is defined as it is for a hazard zone or danger zone in the Machinery Directive
(2006/42/EC) and ISO 12100:2010.
NOTE: The aforementioned standards may or may not apply to the specific products cited in the
present documentation. For more information concerning the individual standards applicable to the
products described herein, see the characteristics tables for those product references.

EIO0000003101 12/2019 13
14 EIO0000003101 12/2019
Modicon M251 Logic Controller
Modicon M251 Logic Controller Introduction
EIO0000003101 12/2019

Part I
Modicon M251 Logic Controller Introduction

Modicon M251 Logic Controller Introduction

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
1 M251 General Overview 17
2 M251 Features 43
3 M251 Installation 53

EIO0000003101 12/2019 15
Modicon M251 Logic Controller Introduction

16 EIO0000003101 12/2019
Modicon M251 Logic Controller
M251 General Overview
EIO0000003101 12/2019

Chapter 1
M251 General Overview

M251 General Overview

Overview
This chapter provides general information about the M251 Logic Controller system architecture
and its components.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
M251 Logic Controller Description 18
Maximum Hardware Configuration 20
TM2 Expansion Modules 23
TM3 Expansion Modules 27
TM3 Bus Couplers 36
TM4 Expansion Modules 37
TM5 Fieldbus Interfaces 38
TM5 CANopen Fieldbus Interfaces 39
TM7 CANopen Fieldbus Interfaces 40
Accessories 41

EIO0000003101 12/2019 17
M251 General Overview

M251 Logic Controller Description

Overview
The M251 Logic Controller has various powerful features and can service a wide range of
applications.
Software configuration, programming, and commissioning are achieved with the EcoStruxure
Machine Expert software described in the EcoStruxure Machine Expert Programming Guide
(see EcoStruxure Machine Expert, Programming Guide) and in the M251 Logic Controller
Programming Guide.

Programming Languages
The M251 Logic Controller is configured and programmed with the EcoStruxure Machine Expert
software, which supports the following IEC 61131-3 programming languages:
 IL: Instruction list
 ST: Structured text
 FBD: Function block diagram
 SFC: Sequential function chart
 LD: Ladder diagram

EcoStruxure Machine Expert software can also be used to program this controller using CFC
(continuous function chart) language.

Power Supply
The power supply of the M251 Logic Controller is 24 Vdc (see page 78).

Real Time Clock


The M251 Logic Controller includes a Real Time Clock (RTC) system (see page 44).

Run/Stop
The M251 Logic Controller can be operated externally by the following:
 a hardware Run/Stop switch (see page 48)
 an EcoStruxure Machine Expert software command

Memory
This table describes the different types of memory:

Memory Type Size Used


RAM 64 Mbytes, of which 8 Mbytes To execute the application.
available for the application
Flash 128 Mbytes To save the program and data in case of a
power interruption.

18 EIO0000003101 12/2019
M251 General Overview

Removable Storage
M251 Logic Controllers include an embedded SD card slot (see page 49).
The main uses of the SD card are:
 Initializing the controller with a new application
 Updating the controller firmware
 Applying post configuration files to the controller
 Applying recipes
 Receiving data logging files

Embedded Communication Features


The M251 Logic Controller native communication ports include (depending on the controller
reference):
 CANopen Master
 Ethernet (see page 101)
 USB Mini-B (see page 105)
 Serial Line (see page 106)

Expansion Module and Bus Coupler Compatibility


Refer to the compatibility tables in the EcoStruxure Machine Expert - Compatiblity and Migration
User Guide.

M251 Logic Controllers

Reference Digital Inputs Digital Outputs Communication Ports


TM251MESC 0 0 1 serial line port
(see page 87) 1 USB mini-B programming port
1 dual port Ethernet switch
1 CANopen port
TM251MESE 0 0 1 serial line port
(see page 91) 1 USB mini-B programming port
1 dual port Ethernet switch
1 Ethernet port for fieldbus

EIO0000003101 12/2019 19
M251 General Overview

Maximum Hardware Configuration

Introduction
The M251 Logic Controller is a control system that offers a scalable solution with optimized
configurations and an expandable architecture.

Local and Remote Configuration Principle


The following figure defines the local and remote configurations:

(1) Local configuration


(2) Remote configuration

M251 Logic Controller Local Configuration Architecture


Optimized local configuration and flexibility are provided by the association of:
 M251 Logic Controller
 TM4 expansion modules
 TM3 expansion modules
 TM2 expansion modules

Application requirements determine the architecture of your M251 Logic Controller configuration.
The following figure represents the components of a local configuration:

(A) Expansion modules (3 maximum)


(B) Expansion modules (7 maximum)

20 EIO0000003101 12/2019
M251 General Overview

NOTE: It is prohibited to mount a TM2 module before any TM3 module as indicated in the following
figure:

M251 Logic Controller Remote Configuration Architecture


Optimized remote configuration and flexibility are provided by the association of:
 M251 Logic Controller
 TM4 expansion modules
 TM3 expansion modules
 TM3 transmitter and receiver modules

Application requirements determine the architecture of your M251 Logic Controller configuration.
NOTE: You cannot use TM2 modules in configurations that include the TM3 transmitter and
receiver modules.
The following figure represents the components of a remote configuration:

(1) Logic controller and modules


(C) TM3 expansion modules (7 maximum)

EIO0000003101 12/2019 21
M251 General Overview

Maximum Number of Modules


The following table shows the maximum configuration supported:

References Maximum Type of Configuration


TM251•••• 7 TM3 / TM2 expansion Local
modules
TM251•••• 3 TM4 expansion modules Local
TM3XREC1 7 TM3 expansion modules Remote
NOTE: TM3 transmitter and receiver modules are not included in a count of the maximum number of
expansion modules.

NOTE: The configuration with its TM4, TM3, and TM2 expansion modules is validated by
EcoStruxure Machine Expert software in the Configuration window.
NOTE: In some environments, the maximum configuration populated by high consumption
modules, coupled with the maximum distance allowable between the TM3 transmitter and receiver
modules, may present bus communication issues although the EcoStruxure Machine Expert
software allows for the configuration. In such a case you will need to analyze the power
consumption of the modules chosen for your configuration, as well as the minimum cable distance
required by your application, and possibly seek to optimize your choices.

22 EIO0000003101 12/2019
M251 General Overview

TM2 Expansion Modules

Overview
You can expand the number of I/Os of your M251 Logic Controller by adding TM2 I/O expansion
modules.
The following types of electronic modules are supported:
 TM2 digital I/O expansion modules
 TM2 analog I/O expansion modules

For more information, refer to the following documents:


 TM2 Digital I/O Expansion Modules Hardware Guide
 TM2 Analog I/O Expansion Modules Hardware Guide

NOTE: TM2 modules can only be used in the local configuration, and only if there is no TM3
transmitter and receiver modules present in the configuration.
NOTE: It is prohibited to mount a TM2 module before any TM3 module. The TM2 modules must
be mounted and configured at the end of the local configuration.

TM2 Digital Input Expansion Modules


The following table shows the compatible TM2 digital input expansion modules with the
corresponding channel type, nominal voltage/current, and terminal type:

Reference Channels Channel Type Voltage Terminal Type


Current
TM2DAI8DT 8 Regular inputs 120 Vac Removable screw
7.5 mA terminal block
TM2DDI8DT 8 Regular inputs 24 Vdc Removable screw
7 mA terminal block
TM2DDI16DT 16 Regular inputs 24 Vdc Removable screw
7 mA terminal block
TM2DDI16DK 16 Regular inputs 24 Vdc HE10 (MIL 20)
5 mA connector
TM2DDI32DK 32 Regular inputs 24 Vdc HE10 (MIL 20)
5 mA connector

EIO0000003101 12/2019 23
M251 General Overview

TM2 Digital Output Expansion Modules


The following table shows the compatible TM2 digital output expansion modules with the
corresponding channel type, nominal voltage/current, and terminal type:

Reference Channels Channel type Voltage Terminal type


Current
TM2DRA8RT 8 Relay outputs 30 Vdc / 240 Vac Removable screw
2 A max terminal block
TM2DRA16RT 16 Relay outputs 30 Vdc / 240 Vac Removable screw
2 A max terminal block
TM2DDO8UT 8 Regular transistor 24 Vdc Removable screw
outputs (sink) 0.3 A max per output terminal block
TM2DDO8TT 8 Regular transistor 24 Vdc Removable screw
outputs (source) 0.5 A max per output terminal block
TM2DDO16UK 16 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (sink) 0.1 A max per output connector
TM2DDO16TK 16 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (source) 0.4 A max per output connector
TM2DDO32UK 32 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (sink) 0.1 A max per output connector
TM2DDO32TK 32 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (source) 0.4 A max per output connector

TM2 Digital Mixed Input/Output Expansion Modules


The following table shows the compatible TM2 digital mixed I/O expansion modules with the
corresponding channel type, nominal voltage/current, and terminal type:

Reference Channels Channel type Voltage Terminal type


Current
TM2DMM8DRT 4 Regular inputs 24 Vdc Removable screw
7 mA terminal block
4 Relay outputs 24 Vdc / 240 Vac
7 A maximum per
common line / 2 A
maximum per output
TM2DMM24DRF 16 Regular inputs 24 Vdc Non-removable
7 mA spring terminal
block
8 Relay outputs 24 Vdc / 240 Vac
7 A maximum per
common line / 2 A
maximum per output

24 EIO0000003101 12/2019
M251 General Overview

TM2 Analog Input Expansion Modules


The following table shows the compatible TM2 analog input expansion modules with the
corresponding channel type, nominal voltage/current, and terminal type:

Reference Channels Channel type Voltage Terminal Type


Current
TM2AMI2HT 2 High-level inputs 0...10 Vdc Removable screw
4...20 mA terminal block
TM2AMI2LT 2 Low-level inputs Thermocouple type Removable screw
J,K,T terminal block
TM2AMI4LT 4 Analog inputs 0...10 Vdc Removable screw
0...20 mA terminal block
PT100/1000
Ni100/1000
TM2AMI8HT 8 Analog inputs 0...20 mA Removable screw
0...10 Vdc terminal block
TM2ARI8HT 8 Analog inputs NTC / PTC Removable screw
terminal block
TM2ARI8LRJ 8 Analog inputs PT100/1000 RJ11 connector
TM2ARI8LT 8 Analog inputs PT100/1000 Removable screw
terminal block

TM2 Analog Output Expansion Modules


The following table shows the compatible TM2 analog output expansion modules with the
corresponding channel type, nominal voltage/current, and terminal type:

Reference Channels Channel type Voltage Terminal Type


Current
TM2AMO1HT 1 Analog outputs 0...10 Vdc Removable screw
4...20 mA terminal block
TM2AVO2HT 2 Analog outputs +/- 10 Vdc Removable screw
terminal block

EIO0000003101 12/2019 25
M251 General Overview

TM2 Analog Mixed Input/Output Expansion Modules


The following table shows the compatible TM2 analog mixed I/O expansion modules with the
corresponding channel type, nominal voltage/current, and terminal type:

Reference Channels Channel type Voltage Terminal Type


Current
TM2AMM3HT 2 Analog inputs 0...10 Vdc 4...20 mA Removable screw
terminal block
1 Analog outputs 0...10 Vdc 4...20 mA
TM2AMM6HT 4 Analog inputs 0...10 Vdc 4...20 mA Removable screw
2 Analog outputs 0...10 Vdc 4...20 mA terminal block
TM2ALM3LT 2 Low-level inputs Thermo J,K,T, Removable screw
PT100 terminal block
1 Analog outputs 0...10 Vdc 4...20 mA

26 EIO0000003101 12/2019
M251 General Overview

TM3 Expansion Modules

Introduction
The range of TM3 expansion modules includes:
 Digital modules, classified as follows:
 Input modules (see page 27)
 Output modules (see page 28)
 Mixed input/output modules (see page 30)

 Analog modules, classified as follows:


 Input modules (see page 31)
 Output modules (see page 32)
 Mixed input/output modules (see page 33)

 Expert modules (see page 34)


 Safety modules (see page 34)
 Transmitter and Receiver modules (see page 35)
For more information, refer to the following documents:
 TM3 Digital I/O Modules Hardware Guide
 TM3 Analog I/O Modules Hardware Guide
 TM3 Expert I/O Modules Hardware Guide
 TM3 Safety Modules Hardware Guide
 TM3 Transmitter and Receiver Modules Hardware Guide

TM3 Digital Input Modules


The following table shows the TM3 digital input expansion modules, with corresponding channel
type, nominal voltage/current, and terminal type:

Reference Channels Channel Type Voltage Terminal Type / Pitch


Current
TM3DI8A 8 Regular inputs 120 Vac Removable screw
7.5 mA terminal block /
5.08 mm
TM3DI8 8 Regular inputs 24 Vdc Removable screw
7 mA terminal block /
5.08 mm
TM3DI8G 8 Regular inputs 24 Vdc Removable spring
7 mA terminal block /
5.08 mm
TM3DI16 16 Regular inputs 24 Vdc Removable screw
7 mA terminal blocks /
3.81 mm

EIO0000003101 12/2019 27
M251 General Overview

Reference Channels Channel Type Voltage Terminal Type / Pitch


Current
TM3DI16G 16 Regular inputs 24 Vdc Removable spring
7 mA terminal blocks /
3.81 mm
TM3DI16K 16 Regular inputs 24 Vdc HE10 (MIL 20)
5 mA connector
TM3DI32K 32 Regular inputs 24 Vdc HE10 (MIL 20)
5 mA connector

TM3 Digital Output Modules


The following table shows the TM3 digital output expansion modules, with corresponding channel
type, nominal voltage/current, and terminal type:

Reference Channels Channel Type Voltage Terminal Type / Pitch


Current
TM3DQ8R 8 Relay outputs 24 Vdc / 240 Vac Removable screw
7 A maximum per terminal block /
common line / 2 A 5.08 mm
maximum per output
TM3DQ8RG 8 Relay outputs 24 Vdc / 240 Vac Removable spring
7 A maximum per terminal block /
common line / 2 A 5.08 mm
maximum per output
TM3DQ8T 8 Regular transistor 24 Vdc Removable screw
outputs (source) 4 A maximum per terminal block /
common line/0.5 A 5.08 mm
maximum per output
TM3DQ8TG 8 Regular transistor 24 Vdc Removable spring
outputs (source) 4 A maximum per terminal block /
common line/0.5 A 5.08 mm
maximum per output
TM3DQ8U 8 Regular transistor 24 Vdc Removable screw
outputs (sink) 4 A maximum per terminal block /
common line/0.5 A 5.08 mm
maximum per output
TM3DQ8UG 8 Regular transistor 24 Vdc Removable spring
outputs (sink) 4 A maximum per terminal block /
common line/0.5 A 5.08 mm
maximum per output
TM3DQ16R 16 Relay outputs 24 Vdc / 240 Vac Removable screw
8 A maximum per terminal blocks /
common line / 2 A 3.81 mm
maximum per output

28 EIO0000003101 12/2019
M251 General Overview

Reference Channels Channel Type Voltage Terminal Type / Pitch


Current
TM3DQ16RG 16 Relay outputs 24 Vdc / 240 Vac Removable spring
8 A maximum per terminal blocks /
common line / 2 A 3.81 mm
maximum per output
TM3DQ16T 16 Regular transistor 24 Vdc Removable screw
outputs (source) 8 A maximum per terminal blocks /
common line / 0.5 A 3.81 mm
maximum per output
TM3DQ16TG 16 Regular transistor 24 Vdc Removable spring
outputs (source) 8 A maximum per terminal blocks /
common line / 0.5 A 3.81 mm
maximum per output
TM3DQ16U 16 Regular transistor 24 Vdc Removable screw
outputs (sink) 8 A maximum per terminal blocks /
common line / 0.5 A 3.81 mm
maximum per output
TM3DQ16UG 16 Regular transistor 24 Vdc Removable spring
outputs (sink) 8 A maximum per terminal blocks /
common line / 0.5 A 3.81 mm
maximum per output
TM3DQ16TK 16 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (source) 2 A maximum per connector
common line / 0.1 A
maximum per output
TM3DQ16UK 16 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (sink) 2 A maximum per connector
common line / 0.1 A
maximum per output
TM3DQ32TK 32 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (source) 2 A maximum per connectors
common line / 0.1 A
maximum per output
TM3DQ32UK 32 Regular transistor 24 Vdc HE10 (MIL 20)
outputs (sink) 2 A maximum per connectors
common line / 0.1 A
maximum per output

EIO0000003101 12/2019 29
M251 General Overview

TM3 Digital Mixed Input/Output Modules


This following table shows the TM3 mixed I/O modules, with corresponding channel type, nominal
voltage/current, and terminal type:

Reference Channels Channel Type Voltage Terminal Type / Pitch


Current
TM3DM8R 4 Regular inputs 24 Vdc Removable screw
7 mA terminal block /
5.08 mm
4 Relay outputs 24 Vdc / 240 Vac
7 A maximum per
common line / 2 A
maximum per output
TM3DM8RG 4 Regular inputs 24 Vdc Removable spring
7 mA terminal block /5.08 mm
4 Relay outputs 24 Vdc / 240 Vac
7 A maximum per
common line / 2 A
maximum per output
TM3DM24R 16 Regular inputs 24 Vdc Removable screw
7 mA terminal
8 Relay outputs 24 Vdc / 240 Vac blocks / 3.81 mm
7 A maximum per
common line / 2 A
maximum per output
TM3DM24RG 16 Regular inputs 24 Vdc Removable spring
7 mA terminal
8 Relay outputs 24 Vdc / 240 Vac blocks / 3.81 mm
7 A maximum per
common line / 2 A
maximum per output

30 EIO0000003101 12/2019
M251 General Overview

TM3 Analog Input Modules


The following table shows the TM3 analog input expansion modules, with corresponding
resolution, channel type, nominal voltage/current, and terminal type:

Reference Resolution Channels Channel Mode Terminal Type /


Type Pitch
TM3AI2H 16 bit, or 2 inputs 0...10 Vdc Removable screw
15 bit + sign -10…+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
TM3AI2HG 16 bit, or 2 inputs 0...10 Vdc Removable spring
15 bit + sign -10…+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
TM3AI4 12 bit, or 4 inputs 0...10 Vdc Removable screw
11 bit + sign -10…+10 Vdc terminal block /
0...20 mA 3.81 mm
4...20 mA
TM3AI4G 12 bit, or 4 inputs 0...10 Vdc Removable spring
11 bit + sign -10…+10 Vdc terminal blocks /
0...20 mA 3.81 mm
4...20 mA
TM3AI8 12 bit, or 8 inputs 0...10 Vdc Removable screw
11 bit + sign -10…+10 Vdc terminal block /
0...20 mA 3.81 mm
4...20 mA
0...20 mA extended
4...20 mA extended
TM3AI8G 12 bit, or 8 inputs 0...10 Vdc Removable spring
11 bit + sign -10…+10 Vdc terminal blocks /
0...20 mA 3.81 mm
4...20 mA
0...20 mA extended
4...20 mA extended
TM3TI4 16 bit, or 4 inputs 0...10 Vdc Removable screw
15 bit + sign -10…+10 Vdc terminal block /
0...20 mA 3.81 mm
4...20 mA
Thermocouple
PT100/1000
NI100/1000

EIO0000003101 12/2019 31
M251 General Overview

Reference Resolution Channels Channel Mode Terminal Type /


Type Pitch
TM3TI4G 16 bit, or 4 inputs 0...10 Vdc Removable spring
15 bit + sign -10…+10 Vdc terminal blocks /
0...20 mA 3.81 mm
4...20 mA
Thermocouple
PT100/1000
NI100/1000
TM3TI4D 16 bit, or 4 inputs Thermocouple Removable screw
15 bit + sign terminal block /
3.81 mm
TM3TI4DG 16 bit, or 4 inputs Thermocouple Removable spring
15 bit + sign terminal blocks /
3.81 mm
TM3TI8T 16 bit, or 8 inputs Thermocouple Removable screw
15 bit + sign NTC/PTC terminal block /
Ohmmeter 3.81 mm
TM3TI8TG 16 bit, or 8 inputs Thermocouple Removable spring
15 bit + sign NTC/PTC terminal blocks /
Ohmmeter 3.81 mm

TM3 Analog Output Modules


The following table shows the TM3 analog output modules, with corresponding resolution, channel
type, nominal voltage/current, and terminal type:

Reference Resolution Channels Channel Mode Terminal Type / Pitch


Type
TM3AQ2 12 bit, or 2 outputs 0...10 Vdc Removable screw
11 bit + sign -10…+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
TM3AQ2G 12 bit, or 2 outputs 0...10 Vdc Removable spring
11 bit + sign -10…+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
TM3AQ4 12 bit, or 4 outputs 0...10 Vdc Removable screw
11 bit + sign -10…+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
TM3AQ4G 12 bit, or 4 outputs 0...10 Vdc Removable spring
11 bit + sign -10…+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA

32 EIO0000003101 12/2019
M251 General Overview

TM3 Analog Mixed Input/Output Modules


This following table shows the TM3 analog mixed I/O modules, with corresponding resolution,
channel type, nominal voltage/current, and terminal type:

Reference Resolution Channels Channel Mode Terminal Type / Pitch


Type
TM3AM6 12 bit, or 4 inputs 0...10 Vdc Removable screw
11 bit + sign -10...+10 Vdc terminal block /
2 outputs
0...20 mA 3.81 mm
4...20 mA
TM3AM6G 12 bit, or 4 inputs 0...10 Vdc Removable spring
11 bit + sign -10...+10 Vdc terminal block /
2 outputs
0...20 mA 3.81 mm
4...20 mA
TM3TM3 16 bit, or 2 inputs 0...10 Vdc Removable screw
15 bit + sign -10...+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
Thermocouple
PT100/1000
NI100/1000
12 bit, or 1 outputs 0...10 Vdc
11 bit + sign -10...+10 Vdc
0...20 mA
4...20 mA
TM3TM3G 16 bit, or 2 inputs 0...10 Vdc Removable spring
15 bit + sign -10...+10 Vdc terminal block /
0...20 mA 5.08 mm
4...20 mA
Thermocouple
PT100/1000
NI100/1000
12 bit, or 1 outputs 0...10 Vdc
11 bit + sign -10...+10 Vdc
0...20 mA
4...20 mA

EIO0000003101 12/2019 33
M251 General Overview

TM3 Expert Modules


The following table shows the TM3 expert expansion modules, with corresponding terminal types:

Reference Description Terminal Type / Pitch


TM3XTYS4 TeSys module 4 front connectors RJ-45
(see Modicon TM3, 1 removable power supply
Expert I/O Modules, connector / 5.08 mm
Hardware Guide)
TM3XHSC202 High Speed Counting (HSC) module Removable screw terminal
(see Modicon TM3, blocks / 3.81 mm
Expert I/O Modules,
Hardware Guide)
TM3XHSC202G High Speed Counting (HSC) module Removable spring terminal
(see Modicon TM3, blocks / 3.81 mm
Expert I/O Modules,
Hardware Guide)

TM3 Safety Modules


This table contains the TM3 safety modules, with the corresponding channel type, nominal
voltage/current, and terminal type:

Reference Function Channels Channel type Voltage Terminal type


Category Current
TM3SAC5R 1 function, 1 or 2 (1) Safety input 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start (2) Input
category 3 removable screw
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
TM3SAC5RG 1 function, 1 or 2 (1) Safety input 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start (2) Input
category 3 removable spring
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
TM3SAF5R 1 function, 2 (1) Safety inputs 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start Input
category 4 removable screw
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
(1) Depending on external wiring
(2)
Non-monitored start

34 EIO0000003101 12/2019
M251 General Overview

Reference Function Channels Channel type Voltage Terminal type


Category Current
TM3SAF5RG 1 function, 2 (1) Safety inputs 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start Input
category 4 removable spring
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
TM3SAFL5R 2 functions, 2 (1) Safety inputs 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start Input
category 3 removable screw
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
TM3SAFL5RG 2 functions, 2 (1) Safety inputs 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start Input
category 3 removable spring
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
TM3SAK6R 3 functions, 1 or 2 (1) Safety inputs 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start Input
category 4 removable screw
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
TM3SAK6RG 3 functions, 1 or 2 (1) Safety inputs 24 Vdc 3.81 mm (0.15 in.) and
up to 100 mA maximum 5.08 mm (0.20 in.),
Start Input
category 4 removable spring
3 in parallel Relay outputs 24 Vdc / 230 Vac terminal block
Normally open 6 A maximum per output
(1) Depending on external wiring
(2)
Non-monitored start

TM3 Transmitter and Receiver Modules


The following table shows the TM3 transmitter and receiver expansion modules:

Reference Description Terminal Type / Pitch


TM3XTRA1 Data transmitter module for remote I/O 1 front connector RJ-45
1 screw for functional ground
connection
TM3XREC1 Data receiver module for remote I/O 1 front connector RJ-45
Power supply connector /
5.08 mm

EIO0000003101 12/2019 35
M251 General Overview

TM3 Bus Couplers

Introduction
The TM3 bus coupler is a device designed to manage fieldbus communication when using TM2
and TM3 expansion modules in a distributed architecture.
For more information, refer to the Modicon TM3 Bus Coupler Hardware Guide (see Modicon TM3
Bus Coupler, Hardware Guide).

Modicon TM3 Bus Couplers


The following table shows the TM3 bus couplers, with ports and terminal types:

Reference Port Communication type Terminal type


TM3BCEIP 2 isolated switched EtherNet/IP RJ45
Ethernet ports Modbus TCP
1 USB mini-B port USB 2.0 USB mini-B
TM3BCSL 2 isolated ports Serial Line RJ45
Modbus
1 USB mini-B port USB 2.0 USB mini-B

36 EIO0000003101 12/2019
M251 General Overview

TM4 Expansion Modules

Introduction
The range of TM4 expansion modules includes communication modules.
For more information, refer to the TM4 Expansion Modules Hardware Guide.

TM4 Expansion Modules


The following table shows the TM4 expansion module features:

Module reference Type Terminal type


TM4ES4 Ethernet communication 4 RJ45 connectors
1 screw for functional ground connection
TM4PDPS1 PROFIBUS DP slave communication 1 SUB-D 9 pins female connector
1 screw for functional ground connection
NOTE: The TM4ES4 module has two applications: expansion or standalone. For more information, refer to
TM4 Compatibility.

EIO0000003101 12/2019 37
M251 General Overview

TM5 Fieldbus Interfaces

Introduction
The TM5 fieldbus interfaces are devices designed to manage EtherNet/IP communication when
using TM5 System and TM7 expansion modules with a controller in a distributed architecture.
For more information, refer to the Modicon TM5 System Interface – Hardware Guide.

TM5 Fieldbus Interfaces


The following table shows the TM5 fieldbus interfaces with ports and terminal type:

Reference Port Communication type Terminal type


TM5NEIP1 2 Ethernet switched ports EtherNet/IP RJ45

38 EIO0000003101 12/2019
M251 General Overview

TM5 CANopen Fieldbus Interfaces

Introduction
The TM5 fieldbus module is a CANopen interface with built-in power distribution and is the first
TM5 distributed I/O island.
For more information, refer to the Modicon TM5 CANopen Interface Hardware Guide.

Modicon TM5 CANopen Fieldbus Interfaces


The following table shows the TM5 CANopen fieldbus interfaces:

Reference Communication type Terminal type


TM5NCO1 CANopen 1 SUB-D 9, male

EIO0000003101 12/2019 39
M251 General Overview

TM7 CANopen Fieldbus Interfaces

Introduction
The TM7 fieldbus modules are CANopen interfaces with 24 Vdc digital configurable input or output
on 8 or 16 channels.
For more information, refer to the Modicon TM7 CANopen Interface I/O Blocks Hardware Guide.

Modicon TM7 CANopen Fieldbus Interfaces


The following table shows the TM7 CANopen fieldbus interfaces:

Reference Number of channels Voltage/Current Communication type Terminal type


TM7NCOM08B 8 inputs 24 Vdc / 4 mA CANopen M8 Connector
8 outputs 24 Vdc / 500 mA
TM7NCOM16A 16 inputs 24 Vdc / 4 mA CANopen M8 Connector
16 outputs 24 Vdc / 500 mA
TM7NCOM16B 16 inputs 24 Vdc / 4 mA CANopen M12 Connector
16 outputs 24 Vdc / 500 mA

40 EIO0000003101 12/2019
M251 General Overview

Accessories

Overview
This section describes the accessories and cables.

Accessories

Reference Description Use Quantity


TMASD1 SD Card Use to update the controller firmware, initialize a 1
(see page 49) controller with a new application or clone a
controller, manage user files, etc.,.
TMAT2PSET Set of 5 removable Connects 24 Vdc power supply. 1
screw terminal block
NSYTRAAB35 End brackets Helps secure the controller or receiver module and 1
their expansion modules on a top hat section rail
(DIN rail).
TM2XMTGB Grounding Bar Connects the cable shield and the module to the 1
functional ground.
TM200RSRCEMC Shielding take-up Mounts and connects the ground to the cable 25 pack
clip shielding.

Cables

Reference Description Details Length


TCSXCNAMUM3P Terminal port/USB From the USB mini-B port on the M251 Logic 3m
port cordset Controller to USB port on the PC terminal. (10 ft)
TCSMCN3M4F3C2 RS-232 serial link For DTE terminal (printer). 3m
cordset (9.84 ft)
1 RJ45 connector
and 1 SUB-D 9
connector
TCSMCN3M4M3S2 RS-232 serial link For DCE terminal (modem, converter). 3m
cordset (9.84 ft)
1 RJ45 connector
and 1 SUB-D 9
connector

EIO0000003101 12/2019 41
M251 General Overview

Reference Description Details Length


490NTW000•• Ethernet shielded Standard cable, equipped with RJ45 2, 5, 12, 40, or 80 m
cable for DTE connectors at each end for DTE. (6.56, 16.4, 39.37,
connections CE compliant. 131.23 or 262.47 ft)
490NTW000••U Standard cable, equipped with RJ45 2, 5, 12, 40, or 80 m
connectors at each end for DTE. (6.56, 16.4, 39.37,
UL compliant. 131.23, or 262.47 ft)
TCSECE3M3M••S4 Cable for harsh environment, equipped with 1, 2, 3, 5, or 10 m
RJ45 connectors at each end. (3.28, 6.56, 9.84, 16.4,
CE compliant. 32.81 ft)
TCSECU3M3M••S4 Cable for harsh environment, equipped with 1, 2, 3, 5, or 10 m
RJ45 connectors at each end. (3.28, 6.56, 9.84, 16.4,
UL compliant. 32.81 ft)

42 EIO0000003101 12/2019
Modicon M251 Logic Controller
M251 Features
EIO0000003101 12/2019

Chapter 2
M251 Features

M251 Features

Overview
This chapter describes the Modicon M251 Logic Controller features.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Real Time Clock (RTC) 44
Run/Stop 48
SD Card 49

EIO0000003101 12/2019 43
M251 Features

Real Time Clock (RTC)

Overview
The M251 Logic Controller includes an RTC to provide system date and time information, and to
support related functions requiring a real-time clock. To continue keeping time when power is off,
a non-rechargeable battery is required (see reference below). A battery LED on the front panel of
the controller indicates if the battery is depleted or absent.
This table shows how RTC drift is managed:

RTC Characteristics Description


RTC drift Less than 60 seconds per month without any user calibration at 25 °C
(77 °F)

Battery
The controller has one battery.
In the event of a power interruption, the backup battery maintains the RTC for the controller.
This table shows the characteristics of the battery:

Characteristics Description
Use In the event of a transient power outage, the battery powers the RTC.
Backup life At least 2 years at 25 °C maximum (77 °F). At higher temperatures, the time
is reduced.
Battery monitoring Yes
Replaceable Yes
Controller battery type Lithium carbon monofluoride, type Panasonic BR2032

44 EIO0000003101 12/2019
M251 Features

Installing and Replacing the Battery


While lithium batteries are preferred due to their slow discharge and long life, they can present
hazards to personnel, equipment and the environment and must be handled properly.

DANGER
EXPLOSION, FIRE, OR CHEMICAL BURNS
 Replace with identical battery type.
 Follow all the instructions of the battery manufacturer.
 Remove all replaceable batteries before discarding unit.
 Recycle or properly dispose of used batteries.
 Protect battery from any potential short-circuit.
 Do not recharge, disassemble, heat above 100 °C (212 °F), or incinerate.
 Use your hands or insulated tools to remove or replace the battery.
 Maintain proper polarity when inserting and connecting a new battery.
Failure to follow these instructions will result in death or serious injury.

To install or replace the battery, follow these steps:

Step Action
1 Remove power from your controller.
2 Use an insulated screw-driver to pull out the battery holder.

3 Side out the battery holder of the controller

EIO0000003101 12/2019 45
M251 Features

Step Action
4 Remove the battery from the battery holder.

5 Insert the new battery into the battery holder in accordance with the polarity markings on the
battery.

6 Replace the battery holder on the controller and verify that the latch clicks into place.

46 EIO0000003101 12/2019
M251 Features

Step Action
7 Slide in the battery holder of the controller.

8 Power up your M251 Logic Controller.


9 Set the internal clock. For further details on the internal clock, refer to M251 Logic Controller
Programming Guide (see Modicon M251 Logic Controller, Programming Guide).

NOTE: Replacement of the battery in the controllers other than with the type specified in this
documentation may present a risk of fire or explosion.

WARNING
IMPROPER BATTERY CAN PROVOKE FIRE OR EXPLOSION
Replace battery only with identical type: Panasonic Type BR2032.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003101 12/2019 47
M251 Features

Run/Stop

Run/Stop
The M251 Logic Controller can be operated externally by the following:
 a hardware Run/Stop switch
 an EcoStruxure Machine Expert software command.

The M251 Logic Controller has a Run/Stop hardware switch, which puts the controller in a RUN or
STOP state.

48 EIO0000003101 12/2019
M251 Features

SD Card

Overview
When handling the SD card, follow the instructions below to help prevent internal data on the SD
card from being corrupted or lost or an SD card malfunction from occurring:

NOTICE
LOSS OF APPLICATION DATA
 Do not store the SD card where there is static electricity or probable electromagnetic fields.
 Do not store the SD card in direct sunlight, near a heater, or other locations where high
temperatures can occur.
 Do not bend the SD card.
 Do not drop or strike the SD card against another object.
 Keep the SD card dry.
 Do not touch the SD card connectors.
 Do not disassemble or modify the SD card.
 Use only SD cards formatted using FAT or FAT32.
Failure to follow these instructions can result in equipment damage.

The M251 Logic Controller does not recognize NTFS formatted SD cards. Format the SD card on
your computer using FAT or FAT32.
When using the M251 Logic Controller and an SD card, observe the following to avoid losing
valuable data:
 Accidental data loss can occur at any time. Once data is lost it cannot be recovered.
 If you forcibly extract the SD card, data on the SD card may become corrupted.
 Removing an SD card that is being accessed could damage the SD card, or corrupt its data.
 If the SD card is not positioned correctly when inserted into the controller, the data on the card
and the controller could become damaged.

NOTICE
LOSS OF APPLICATION DATA
 Backup SD card data regularly.
 Do not remove power or reset the controller, and do not insert or remove the SD card while it
is being accessed.
Failure to follow these instructions can result in equipment damage.

EIO0000003101 12/2019 49
M251 Features

This figure shows the SD card slot:

It is possible to set the Write-Control Tab to prevent write operations to the SD card. Push the tab
up, as shown in the example on the right-hand side, to release the lock and enable writing to the
SD card. Before using an SD card, read the manufacturer's instructions.

50 EIO0000003101 12/2019
M251 Features

Step Action
1 Insert the SD card into the SD card slot:

2 Push until you hear it “click”:

SD Card Slot Characteristics

Topic Characteristics Description


Supported type Standard Capacity SD (SDSC)
High Capacity SDHC
Global memory Size 16 GB max.

EIO0000003101 12/2019 51
M251 Features

TMASD1 Characteristics

Characteristics Description
Card removal durability Minimum 1000 times
File retention time 10 years @ 25 °C (77 °F)
Flash type SLC NAND
Memory size 256 MB
Ambient operation temperature –10 … +85°C (14...185 °F)
Storage temperature –25 … +85°C (–13...185 °F)
Relative humidity 95% max. non-condensing
Write/Erase cycles 3,000,000 (approximately)

NOTE: The TMASD1 has been rigorously tested in association with the logic controller. For other
commercially available cards, consult your local sales representative.
NOTE: The SD card can be used directly on your PC.

52 EIO0000003101 12/2019
Modicon M251 Logic Controller
M251 Installation
EIO0000003101 12/2019

Chapter 3
M251 Installation

M251 Installation

Overview
This chapter provides installation safety guidelines, device dimensions, mounting instructions, and
environmental specifications.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
3.1 M251 Logic Controller General Rules for Implementing 54
3.2 M251 Logic Controller Installation 59
3.3 M251 Electrical Requirements 74

EIO0000003101 12/2019 53
M251 Installation

Section 3.1
M251 Logic Controller General Rules for Implementing

M251 Logic Controller General Rules for Implementing

What Is in This Section?


This section contains the following topics:
Topic Page
Environmental Characteristics 55
Certifications and Standards 58

54 EIO0000003101 12/2019
M251 Installation

Environmental Characteristics

Enclosure Requirements
M251 Logic Controller system components are designed as Zone B, Class A industrial equipment
according to IEC/CISPR Publication 11. If they are used in environments other than those
described in the standard, or in environments that do not meet the specifications in this manual,
the ability to meet electromagnetic compatibility requirements in the presence of conducted and/or
radiated interference may be reduced.
All M251 Logic Controller system components meet European Community (CE) requirements for
open equipment as defined by IEC/EN 61131-2. You must install them in an enclosure designed
for the specific environmental conditions and to minimize the possibility of unintended contact with
hazardous voltages. Use metal enclosures to improve the electromagnetic immunity of your M251
Logic Controller system. Use enclosures with a keyed locking mechanism to minimize
unauthorized access.

Environmental Characteristics
All the M251 Logic Controller module components are electrically isolated between the internal
electronic circuit and the input/output channels within the limits set forth and described by these
environmental characteristics. For more information on electrical isolation, see the technical
specifications of your particular controller found later in the current document. This equipment
meets CE requirements as indicated in the table below. This equipment is intended for use in a
Pollution Degree 2 industrial environment.

WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the environmental and electrical characteristics
tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003101 12/2019 55
M251 Installation

The following table shows the general environmental characteristics:

Characteristic Minimum Tested Range


Specification
Standard compliance IEC/EN 61131-2 –
IEC/EN 61010-2-
201
Ambient operating temperature – Horizontal –10...55 °C (14...131 °F)
installation
– Vertical installation –10...35 °C (14...95 °F)
Storage temperature – –25...70 °C (- 13...158 °F)
Relative humidity – Transport and 10...95 % (non-condensing)
storage
Operation 10...95 % (non-condensing)
Degree of pollution IEC/EN 60664-1 2
Degree of protection IEC/EN 61131-2 IP20 with protective covers in place
Corrosion immunity – Atmosphere free from corrosive gases
Operating altitude – 0...2000 m (0...6560 ft)
Storage altitude – 0...3000 m (0...9843 ft)
Vibration resistance IEC/EN 61131-2 Panel mounting or 3.5 mm (0.13 in) fixed amplitude
mounted on a top from 5...8.4 Hz
hat section rail (DIN 9.8 m/s2 (32.15 ft/s2) (1 gn) fixed
rail) acceleration from 8.4...150 Hz
10 mm (0.39 in) fixed amplitude
from 5...8.7 Hz
29.4 m/s2 (96.45 ft/s2) (3 gn) fixed
acceleration from 8.7...150 Hz
Mechanical shock resistance – 147 m/s2 or 482.28 ft/s2 (15 gn) for a duration of 11 ms

NOTE: The tested ranges may indicate values beyond that of the IEC Standard. However, our internal standards
define what is necessary for industrial environments. In all cases, we uphold the minimum specification if indicated.

56 EIO0000003101 12/2019
M251 Installation

Electromagnetic Susceptibility
The M251 Logic Controller system meets electromagnetic susceptibility specifications as indicated
in the following table:

Characteristic Minimum Specification Tested Range


Electrostatic discharge IEC/EN 61000-4-2 8 kV (air discharge)
4 kV (contact discharge)
Radiated electromagnetic IEC/EN 61000-4-3 10 V/m (80...1000 MHz)
field 3 V/m (1.4...2 GHz)
1 V/m (2...3 GHz)
Fast transients burst IEC/EN 61000-4-4 24 Vdc main 2 kV (CM1 and DM2)
power lines
24 Vdc I/Os 2 kV (clamp)
Relay output 1 kV (clamp)
Digital I/Os 1 kV (clamp)
Communication 1 kV (clamp)
line
Surge immunity IEC/EN 61000-4-5 – CM1 DM2
IEC/EN 61131-2
DC Power lines 0.5 kV 0.5 kV
Relay Outputs – –
24 Vdc I/Os – –
Shielded cable 1 kV –
(between shield
and ground)
Induced electromagnetic field IEC/EN 61000-4-6 10 Vrms (0.15...80 MHz)
Conducted emission IEC 61000-6-4  10...150 kHz: 120...69 dBμV/m QP
 150...1500 kHz: 79...63 dBμV/m QP
 1.5...30 MHz: 63 dBμV/m QP

Radiated emission IEC 61000-6-4 30...230 MHz: 40 dBμV/m QP


230...1000 MHz: 47 dBμV/m QP
1 Common Mode
2 Differential Mode

NOTE: The tested ranges may indicate values beyond that of the IEC Standard. However, our internal standards
define what is necessary for industrial environments. In all cases, we uphold the minimum specification if indicated.

EIO0000003101 12/2019 57
M251 Installation

Certifications and Standards

Introduction
The M251 Logic Controllers are designed to conform to the main national and international
standards concerning electronic industrial control devices:
 IEC/EN 61131-2
 UL 508
 CSA 22.2 n° 142
 CSA E61131-2

The M251 Logic Controllers have obtained the following conformity marks:
 CE
 cULus
 CSA

For product compliance and environmental information (RoHS, REACH, PEP, EOLI, etc.), go to
www.schneider-electric.com/green-premium.

58 EIO0000003101 12/2019
M251 Installation

Section 3.2
M251 Logic Controller Installation

M251 Logic Controller Installation

What Is in This Section?


This section contains the following topics:
Topic Page
Installation and Maintenance Requirements 60
M251 Logic Controller Mounting Positions and Clearances 63
Top Hat Section Rail (DIN rail) 66
Installing and Removing the Controller with Expansions 70
Direct Mounting on a Panel Surface 73

EIO0000003101 12/2019 59
M251 Installation

Installation and Maintenance Requirements

Before Starting
Read and understand this chapter before beginning the installation of your system.
The use and application of the information contained herein require expertise in the design and
programming of automated control systems. Only you, the user, machine builder or integrator, can
be aware of all the conditions and factors present during installation and setup, operation, and
maintenance of the machine or process, and can therefore determine the automation and
associated equipment and the related safeties and interlocks which can be effectively and properly
used. When selecting automation and control equipment, and any other related equipment or
software, for a particular application, you must also consider any applicable local, regional or
national standards and/or regulations.
Pay particular attention in conforming to any safety information, different electrical requirements,
and normative standards that would apply to your machine or process in the use of this equipment.

Disconnecting Power
All options and modules should be assembled and installed before installing the control system on
a mounting rail, onto a mounting plate or in a panel. Remove the control system from its mounting
rail, mounting plate or panel before disassembling the equipment.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires except
under the specific conditions specified in the appropriate hardware guide for this equipment.
 Always use a properly rated voltage sensing device to confirm the power is off where and when
indicated.
 Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
 Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.

60 EIO0000003101 12/2019
M251 Installation

Programming Considerations

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Operating Environment
In addition to the Environmental Characteristics, refer to Product Related Information in the
beginning of the present document for important information regarding installation in hazardous
locations for this specific equipment.

WARNING
UNINTENDED EQUIPMENT OPERATION
Install and operate this equipment according to the conditions described in the Environmental
Characteristics.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003101 12/2019 61
M251 Installation

Installation Considerations

WARNING
UNINTENDED EQUIPMENT OPERATION
 Use appropriate safety interlocks where personnel and/or equipment hazards exist.
 Install and operate this equipment in an enclosure appropriately rated for its intended
environment and secured by a keyed or tooled locking mechanism.
 Use the sensor and actuator power supplies only for supplying power to the sensors or
actuators connected to the module.
 Power line and output circuits must be wired and fused in compliance with local and national
regulatory requirements for the rated current and voltage of the particular equipment.
 Do not use this equipment in safety-critical machine functions unless the equipment is
otherwise designated as functional safety equipment and conforming to applicable regulations
and standards.
 Do not disassemble, repair, or modify this equipment.
 Do not connect any wiring to reserved, unused connections, or to connections designated as
No Connection (N.C.).
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: JDYX2 or JDYX8 fuse types are UL-recognized and CSA approved.

62 EIO0000003101 12/2019
M251 Installation

M251 Logic Controller Mounting Positions and Clearances

Introduction
This section describes the correct mounting positions for the M251 Logic Controller.
NOTE: Keep adequate spacing for proper ventilation and to maintain the operating temperature
specified in the Environmental Characteristics (see page 55).

Correct Mounting Position


To obtain optimal operating characteristics, the M251 Logic Controller should be mounted
horizontally on a vertical plane as shown in the figure below:

Acceptable Mounting Positions


The M251 Logic Controller can also be mounted vertically on a vertical plane as shown below.

NOTE: Expansion modules must be mounted above the controller.

EIO0000003101 12/2019 63
M251 Installation

Incorrect Mounting Position


The M251 Logic Controller should only be positioned as shown in the Correct Mounting Position
figure. The figures below show the incorrect mounting positions.

Minimum Clearances

WARNING
UNINTENDED EQUIPMENT OPERATION
 Place devices dissipating the most heat at the top of the cabinet and ensure adequate
ventilation.
 Avoid placing this equipment next to or above devices that might cause overheating.
 Install the equipment in a location providing the minimum clearances from all adjacent
structures and equipment as directed in this document.
 Install all equipment in accordance with the specifications in the related documentation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The M251 Logic Controller has been designed as an IP20 product and must be installed in an
enclosure. Clearances must be respected when installing the product.
There are 3 types of clearances to consider:
 The M251 Logic Controller and all sides of the cabinet (including the panel door).
 The M251 Logic Controller terminal blocks and the wiring ducts to help reduce potential
electromagnetic interference between the controller and the duct wiring.
 The M251 Logic Controller and other heat generating devices installed in the same cabinet.

64 EIO0000003101 12/2019
M251 Installation

The following figure shows the minimum clearances that apply to all M251 Logic Controller
references:

EIO0000003101 12/2019 65
M251 Installation

Top Hat Section Rail (DIN rail)

Dimensions of Top Hat Section Rail DIN Rail


You can mount the controller or receiver and their expansions on a 35 mm (1.38 in.) top hat section
rail (DIN rail). The DIN rail can be attached to a smooth mounting surface or suspended from a EIA
rack or mounted in a NEMA cabinet.

Symmetric Top Hat Section Rails (DIN Rail)


The following illustration and table indicate the references of the top hat section rails (DIN rail) for
the wall-mounting range:

Reference Type Rail Length (B)


NSYSDR50A A 450 mm (17.71 in.)
NSYSDR60A A 550 mm (21.65 in.)
NSYSDR80A A 750 mm (29.52 in.)
NSYSDR100A A 950 mm (37.40 in.)

66 EIO0000003101 12/2019
M251 Installation

The following illustration and table indicate the references of the symmetric top hat section rails
(DIN rail) for the metal enclosure range:

Reference Type Rail Length (B-12 mm)


NSYSDR60 A 588 mm (23.15 in.)
NSYSDR80 A 788 mm (31.02 in.)
NSYSDR100 A 988 mm (38.89 in.)
NSYSDR120 A 1188 mm (46.77 in.)

The following illustration and table indicate the references of the symmetric top hat section rails
(DIN rail) of 2000 mm (78.74 in.):

Reference Type Rail Length


NSYSDR2001 A 2000 mm (78.74 in.)

NSYSDR200D2 A
1 Unperforated galvanized steel
2 Perforated galvanized steel

EIO0000003101 12/2019 67
M251 Installation

Double-Profile Top Hat Section Rails (DIN rail)


The following illustration and table indicate the references of the double-profile top hat section rails
(DIN rails) for the wall-mounting range:

Reference Type Rail Length (B)


NSYDPR25 W 250 mm (9.84 in.)
NSYDPR35 W 350 mm (13.77 in.)
NSYDPR45 W 450 mm (17.71 in.)
NSYDPR55 W 550 mm (21.65 in.)
NSYDPR65 W 650 mm (25.60 in.)
NSYDPR75 W 750 mm (29.52 in.)

68 EIO0000003101 12/2019
M251 Installation

The following illustration and table indicate the references of the double-profile top hat section rails
(DIN rail) for the floor-standing range:

Reference Type Rail Length (B)


NSYDPR60 F 588 mm (23.15 in.)
NSYDPR80 F 788 mm (31.02 in.)
NSYDPR100 F 988 mm (38.89 in.)
NSYDPR120 F 1188 mm (46.77 in.)

EIO0000003101 12/2019 69
M251 Installation

Installing and Removing the Controller with Expansions

Overview
This section describes how to install and remove the controller with its expansion modules from a
top hat section rail (DIN rail).
To assemble expansion modules to a controller or receiver module, or to other modules, refer to
the respective expansion modules hardware guide(s).

Installing a Controller with its Expansions on a DIN Rail


The following procedure describes how to install a controller with its expansion modules on a top
hat section rail (DIN rail):

Step Action
1 Fasten the top hat section rail (DIN rail) to a panel surface using screws.
2 Position the top groove of the controller and its expansion modules on the top
edge of the DIN rail and press the assembly against the top hat section rail
(DIN rail) until you hear the top hat section rail (DIN rail) clip snap into place.

70 EIO0000003101 12/2019
M251 Installation

Step Action
3 Place 2 terminal block end clamps on both sides of the controller and
expansion module assembly.

AB1AB8P35

NOTE: Type ABB8P35 or equivalent terminal block end clamps help


minimize sideways movement and improve the shock and vibration
characteristics of the controller and expansion module assembly.

EIO0000003101 12/2019 71
M251 Installation

Removing a Controller with its Expansions from a Top Hat Section Rail (DIN Rail)
The following procedure describes how to remove a controller with its expansion modules from a
top hat section rail (DIN rail):

Step Action
1 Remove all power from your controller and expansion modules.
2 Insert a flat screwdriver into the slot of the top hat section rail (DIN rail) clip.

3 Pull down the DIN rail clip.


4 Pull the controller and its expansion modules from the top hat section rail (DIN rail)
from the bottom.

72 EIO0000003101 12/2019
M251 Installation

Direct Mounting on a Panel Surface

Overview
This section shows how to install M251 Logic Controller on a panel surface using the mounting
holes.

Mounting Hole Layout


This diagram shows the mounting hole layout for M251 Logic Controller:

EIO0000003101 12/2019 73
M251 Installation

Section 3.3
M251 Electrical Requirements

M251 Electrical Requirements

What Is in This Section?


This section contains the following topics:
Topic Page
Wiring Best Practices 75
DC Power Supply Characteristics and Wiring 78
Grounding the M251 System 82

74 EIO0000003101 12/2019
M251 Installation

Wiring Best Practices

Overview
This section describes the wiring guidelines and associated best practices to be respected when
using the M251 Logic Controller system.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires except
under the specific conditions specified in the appropriate hardware guide for this equipment.
 Always use a properly rated voltage sensing device to confirm the power is off where and when
indicated.
 Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
 Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths
and, for certain critical control functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are emergency stop and overtravel
stop, power outage and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.1
 Each implementation of this equipment must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1
For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest
edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.

EIO0000003101 12/2019 75
M251 Installation

Wiring Guidelines
This rules must be applied when wiring a M251 Logic Controller system:
 Communication wiring must be kept separate from the power wiring. Route these 2 types of
wiring in separate cable ducting.
 Verify that the operating conditions and environment are within the specification values.
 Use proper wire sizes to meet voltage and current requirements.
 Use copper conductors (required).
 Use twisted pair, shielded cables for networks, and fieldbus.

Use shielded, properly grounded cables for all communication connections. If you do not use
shielded cable for these connections, electromagnetic interference can cause signal degradation.
Degraded signals can cause the controller or attached modules and equipment to perform in an
unintended manner.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Use shielded cables for all communication signals.
 Ground cable shields for all communication signals at a single point1.
 Route communication separately from power cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1Multipoint
grounding is permissible if connections are made to an equipotential ground plane
dimensioned to help avoid cable shield damage in the event of power system short-circuit currents.
For more details, refer to Grounding Shielded Cables (see page 83).
NOTE: Surface temperatures may exceed 60 °C (140 °F).
To conform to IEC 61010 standards, route primary wiring (wires connected to power mains)
separately and apart from secondary wiring (extra low voltage wiring coming from intervening
power sources). If that is not possible, double insulation is required such as conduit or cable gains.

76 EIO0000003101 12/2019
M251 Installation

Rules for Removable Screw Terminal Block


The following tables show the cable types and wire sizes for a 5.08 pitch removable screw terminal
block (power supply):

The use of copper conductors is required.

DANGER
LOOSE WIRING CAUSES ELECTRIC SHOCK
Tighten connections in conformance with the torque specifications.
Failure to follow these instructions will result in death or serious injury.

DANGER
FIRE HAZARD
Use only the correct wire sizes for the maximum current capacity of the power supplies.
Failure to follow these instructions will result in death or serious injury.

EIO0000003101 12/2019 77
M251 Installation

DC Power Supply Characteristics and Wiring

Overview
This section provides the characteristics and the wiring diagrams of the DC power supply.

DC Power Supply Voltage Range


If the specified voltage range is not maintained, outputs may not switch as expected. Use
appropriate safety interlocks and voltage monitoring circuits.

DANGER
FIRE HAZARD
 Use only the correct wire sizes for the maximum current capacity of the I/O channels and
power supplies.
 For relay output (2 A) wiring, use conductors of at least 0.5 mm2 (AWG 20) with a temperature
rating of at least 80 °C (176 °F).
 For common conductors of relay output wiring (7 A), or relay output wiring greater than 2 A,
use conductors of at least 1.0 mm2 (AWG 16) with a temperature rating of at least 80 °C
(176 °F).
Failure to follow these instructions will result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the environmental and electrical characteristics
tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

78 EIO0000003101 12/2019
M251 Installation

DC Power Supply Requirements


The M251 Logic Controllerand associated I/O (TM2, TM3, with a nominal voltage of 24 Vdc. The
24 Vdc power supplies must be rated Safety Extra Low Voltage (SELV) or Protective Extra Low
Voltage (PELV) according to IEC 61140. These power supplies are isolated between the electrical
input and output circuits of the power supply.

WARNING
POTENTIAL OF OVERHEATING AND FIRE
 Do not connect the equipment directly to line voltage.
 Use only isolating PELV power supplies and circuits to supply power to the equipment1.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1
For compliance to UL (Underwriters Laboratories) requirements, the power supply must also
conform to the various criteria of NEC Class 2, and be inherently current limited to a maximum
power output availability of less than 100 VA (approximately 4 A at nominal voltage), or not
inherently limited but with an additional protection device such as a circuit breaker or fuse meeting
the requirements of clause 9.4 Limited-energy circuit of UL 61010-1. In all cases, the current limit
should never exceed that of the electric characteristics and wiring diagrams for the equipment
described in the present documentation. In all cases, the power supply must be grounded, and you
must separate Class 2 circuits from other circuits. If the indicated rating of the electrical character-
istics or wiring diagrams are greater than the specified current limit, multiple Class 2 power
supplies may be used.

Controller DC Characteristics
This table shows the characteristics of the DC power supply required for the controller:

Characteristic Value
Rated voltage 24 Vdc
Power supply voltage range 19.2...28.8 Vdc
Power interruption time 10 ms at 24 Vdc
Maximum inrush current 50 A
Power consumption 32.6 W, max. 40.4 W(1)
Isolation between DC power supply and internal Not isolated
logic
between DC power supply and protective 500 Vac
earth ground (PE)
(1) Controller + 7 TM3 expansion modules

EIO0000003101 12/2019 79
M251 Installation

Power Interruption
The duration of power interruptions where the M251 Logic Controller is able to continue normal
operation varies depending upon the load to the power supply of the controller, but a minimum of
10 ms is maintained as specified by IEC standards.
When planning the management of the power supplied to the controller, you must consider the
power interruption duration due to the fast cycle time of the controller.
There could potentially be many scans of the logic and consequential updates to the I/O image
table during the power interruption, while there is no external power supplied to the inputs, the
outputs or both depending on the power system architecture and power interruption
circumstances.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Individually monitor each source of power used in the controller system including input power
supplies, output power supplies and the power supply to the controller to allow appropriate
system shutdown during power system interruptions.
 The inputs monitoring each of the power supply sources must be unfiltered inputs.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

DC Power Supply Wiring Diagram


This figure shows the power supply terminal block removal procedure:

80 EIO0000003101 12/2019
M251 Installation

The following figure shows the wiring of the DC power supply:

* Type T fuse

For more information, refer to the 5.08 pitch Rules for Removable Screw Terminal block
(see page 77).

EIO0000003101 12/2019 81
M251 Installation

Grounding the M251 System

Overview
To help minimize the effects of electromagnetic interference, cables carrying fieldbus
communication signals must be shielded.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Use shielded cables for communication signals.
 Ground cable shields for communication signals at a single point 1.
 Always comply with local wiring requirements regarding grounding of cable shields.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1Multipoint
grounding is permissible if connections are made to an equipotential ground plane
dimensioned to help avoid cable shield damage in the event of power system short-circuit currents.
The use of shielded cables requires compliance with the following wiring rules:
 For protective ground connections (PE), metal conduit or ducting can be used for part of the
shielding length, provided there is no break in the continuity of the ground connections. For
functional ground (FE), the shielding is intended to attenuate electromagnetic interference and
the shielding must be continuous for the length of the cable. If the purpose is both functional and
protective, as is often the case for communication cables, the cable must have continuous
shielding.
 Wherever possible, keep cables carrying one type of signal separate from the cables carrying
other types of signals or power.

Protective Ground (PE) on the Backplane


The protective ground (PE) should be connected to the conductive backplane by a heavy-duty
wire, usually a braided copper cable with the maximum allowable cable section.

82 EIO0000003101 12/2019
M251 Installation

Shielded Cables Connections


Cables carrying fieldbus communication signals must be shielded. The shielding must be securely
connected to ground. The fieldbus communication cable shields must be connected to the
protective ground (PE) with a connecting clamp secured to the conductive backplane of your
installation.
The shielding of the Modbus cable must be connected to the protective ground (PE).

DANGER
HAZARD OF ELECTRIC SHOCK
 The grounding terminal connection (PE) must be used to provide a protective ground at all
times.
 Make sure that an appropriate, braided ground cable is attached to the PE/PG ground terminal
before connecting or disconnecting the network cable to the equipment.
Failure to follow these instructions will result in death or serious injury.

WARNING
ACCIDENTAL DISCONNECTION FROM PROTECTIVE GROUND (PE)
 Do not use the TM2XMTGB Grounding Plate to provide a protective ground (PE).
 Use the TM2XMTGB Grounding Plate only to provide a functional ground (FE).
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003101 12/2019 83
M251 Installation

84 EIO0000003101 12/2019
Modicon M251 Logic Controller
Modicon M251 Logic Controller
EIO0000003101 12/2019

Part II
Modicon M251 Logic Controller

Modicon M251 Logic Controller

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
4 TM251MESC 87
5 TM251MESE 91

EIO0000003101 12/2019 85
Modicon M251 Logic Controller

86 EIO0000003101 12/2019
Modicon M251 Logic Controller
TM251MESC
EIO0000003101 12/2019

Chapter 4
TM251MESC

TM251MESC

TM251MESC Presentation

Description
This figure shows the different components of the TM251MESC logic controller:

N° Description Refer to
1 Dual port Ethernet switch Ethernet port (see page 101)
2 CANopen port CANopen port
3 Serial line port / Type RJ45 (RS-232 or RS-485) Serial Line (see page 106)
4 Run/Stop switch Run/Stop (see page 48)
5 Status LEDs –
6 TM4 bus connector TM4 Expansion Modules (see page 37)
7 TM3/TM2 bus connector TM3 Expansion Modules (see page 27)
8 SD card slot SD Card (see page 49)
9 USB mini-B programming port / For terminal connection to a USB Mini-B Programming Port
programming PC (EcoStruxure Machine Expert) (see page 105)

EIO0000003101 12/2019 87
TM251MESC

N° Description Refer to
10 Surface mounting lugs –
11 Clip-on lock for 35 mm (1.38 in.) top hat section rail (DIN-rail) Top Hat Section Rail (see page 66)
12 24 Vdc power supply DC Power supply Characteristics and
Wiring (see page 78)
13 Protective cover (SD card slot and USB mini-B programming –
port)
14 Locking hook (Hook not included) –
15 Battery holder Real Time Clock (RTC) (see page 44)

Status LEDs
This figure shows the status LEDs:

The following table describes the system status LEDs:

Label Function Color Status Description


Type
PWR Power Green On Indicates that power is applied.
Off Indicates that power is removed.
RUN Machine Green On Indicates that the controller is running a valid application.
status
Flashing Indicates that the controller has a valid application that is
stopped.
1 flash Indicates that the controller has paused at BREAKPOINT.
Off Indicates that the controller is not programmed

88 EIO0000003101 12/2019
TM251MESC

Label Function Color Status Description


Type
ERR Internal Error Red On Indicates that an operating system error has been detected
Fast flashing Indicates that the controller has detected an internal error
Slow flashing Indicates either that a minor error has been detected if RUN
is ON or that no application has been detected
I/O I/O error Red On Indicates device errors on the serial line, SD card, TM4 bus,
TM3 bus, Ethernet port(s) or CANopen port.
SD SD card Green On Indicates that the SD card is being accessed
access
BAT Battery Red On Indicates that the battery needs to be replaced.
Flashing Indicates that the battery charge is low.
ETH Ethernet port Green On Indicates that the ethernet port is connected and the IP
status address is defined.
3 flashes Indicates that the ethernet port is not connected.
4 flashes Indicates that the IP address is already in used.
5 flashes Indicates that the module is waiting for BOOTP or DHCP
sequence.
6 flashes Indicates that the configured IP address is not valid.
SL Serial line Green On Indicates the status of serial line (see page 108)
Off Indicates no serial communication
TM4 Error on TM4 Red On Indicates that an error has been detected on the TM4 bus
bus
Off Indicates that no error has been detected on the TM4 bus
CAN-R CANopen Green On Indicates that the CANopen bus is operational.
running
Off Indicates that the CANopen master is configured.
status
Flashing Indicates that the CANopen bus is being initialized.
1 flash per Indicates that the CANopen bus is stopped.
second
CAN-E CANopen Red On Indicates that the CANopen bus is stopped (BUS OFF).
error Off Indicates no CANopen detected error.
Flashing Indicates that the CANopen bus is not valid.
1 flash per Indicates that the controller has detected that the maximum
second number of error frames has been reached or exceeded.
2 flashes per Indicates that the controller has detected either a Node
second Guarding or a Heartbeat event.

NOTE: All the LEDs flash when the logic controller is being identified. For more details, refer to the
EcoStruxure Machine Expert Programming Guide.

EIO0000003101 12/2019 89
TM251MESC

Dimensions
This figures shows the external dimensions of the logic controller:

90 EIO0000003101 12/2019
Modicon M251 Logic Controller
TM251MESE
EIO0000003101 12/2019

Chapter 5
TM251MESE

TM251MESE

TM251MESE Presentation

Description
This figure shows the different components of the TM251MESE logic controller:

N° Description Refer to
1 Dual port Ethernet switch Ethernet port (see page 101)
2 Ethernet port 2 Ethernet ports (see page 103)
3 Serial line port / Type RJ45 (RS-232 or RS-485) Serial Line (see page 106)
4 Run/Stop switch Run/Stop (see page 48)
5 Status LEDs –
6 TM4 bus connector TM4 Expansion Modules (see page 37)
7 TM3/TM2 bus connector TM3 Expansion Modules (see page 27)
8 SD card slot SD Card (see page 49)
9 USB mini-B programming port / For terminal connection to a USB Mini-B Programming Port
programming PC (EcoStruxure Machine Expert) (see page 105)

EIO0000003101 12/2019 91
TM251MESE

N° Description Refer to
10 Surface mounting lugs –
11 Clip-on lock for 35 mm (1.38 in.) top hat section rail (DIN-rail) Top Hat Section Rail (see page 66)
12 24 Vdc power supply DC Power supply Characteristics and
Wiring (see page 78)
13 Protective cover (SD card slot and USB mini-B programming –
port)
14 Locking hook (Hook not included) –
15 Battery holder Real Time Clock (RTC) (see page 44)

Status LEDs
This figure shows the status LEDs:

The following table describes the system status LEDs:

Label Function Color Status Description


Type
PWR Power Green On Indicates that power is applied.
Off Indicates that power is removed.
RUN Machine Green On Indicates that the controller is running a valid application.
status
Flashing Indicates that the controller has a valid application that is
stopped.
1 flash Indicates that the controller has paused at BREAKPOINT.
Off Indicates that the controller is not programmed

92 EIO0000003101 12/2019
TM251MESE

Label Function Color Status Description


Type
ERR Internal Error Red On Indicates that an operating system error has been detected
Fast flashing Indicates that the controller has detected an internal error
Slow flashing Indicates either that a minor error has been detected if RUN
is ON or that no application has been detected
I/O I/O error Red On Indicates device errors on the serial line, SD card, TM4 bus,
TM3 bus, Ethernet port(s) or CANopen port.
SD SD card Green On Indicates that the SD card is being accessed
access
BAT Battery Red On Indicates that the battery needs to be replaced.
Flashing Indicates that the battery charge is low.
ETH.1 Ethernet port Green On Indicates that the Ethernet port is connected and the IP
ETH.2 status address is defined.
3 flashes Indicates that the Ethernet port is not connected.
4 flashes Indicates that the IP address is already in use.
5 flashes Indicates that the module is waiting for BOOTP or DHCP
sequence.
6 flashes Indicates that the configured IP address is not valid.
SL Serial line Green On Indicates the status of serial line (see page 108)
Off Indicates no serial communication
TM4 Error on TM4 Red On Indicates that an error has been detected on the TM4 bus
bus
Off Indicates that no error has been detected on the TM4 bus

NOTE: All the LEDs flash when the logic controller is being identified. For more details, refer to the
EcoStruxure Machine Expert Programming Guide.

EIO0000003101 12/2019 93
TM251MESE

Dimensions
This figure shows the external dimensions of the logic controller:

94 EIO0000003101 12/2019
Modicon M251 Logic Controller
Modicon M251 Logic Controller Communication
EIO0000003101 12/2019

Part III
Modicon M251 Logic Controller Communication

Modicon M251 Logic Controller Communication

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
6 Integrated Communication Ports 97
7 Connecting the M251 Logic Controller to a PC 109

EIO0000003101 12/2019 95
Modicon M251 Logic Controller Communication

96 EIO0000003101 12/2019
Modicon M251 Logic Controller
Integrated Communication Ports
EIO0000003101 12/2019

Chapter 6
Integrated Communication Ports

Integrated Communication Ports

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
CAN Port 98
Ethernet Port 101
TM251MESE Specific Considerations 103
USB Mini-B Programming Port 105
Serial Line 106

EIO0000003101 12/2019 97
Integrated Communication Ports

CAN Port

CANopen Capabilities
The Modicon M251 Logic Controller CANopen master has the following features:

Feature Description
Maximum number of slaves on the bus 63 CANopen slave devices
Maximum length of CANopen fieldbus cables According to the CAN specification (see Transmission
Speed and Cable Length (see page 100)).
Maximum number of PDOs managed by the master 252 TPDOs + 252 RPDOs

For each additional CANopen slave:


 the application size increases by an average of 10 kbytes, which conceivably could result in
exceeding memory limits.
 the configuration initialization time at the startup increases, which conceivably could result in
watchdog timeout.
Although EcoStruxure Machine Expert does not restrict you from doing so, do not exceed more
than 63 CANopen slave modules (and/or 252 TPDOs and 252 RPDOs) in order to have a sufficient
performance tolerance and avoid any performance degradation.

WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect more than 63 CANopen slave devices to the controller to avoid system overload
watchdog condition.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICE
DEGRADATION OF PERFORMANCE
Do not exceed more than 252 TPDOs and 252 RPDOs for the Modicon M251 Logic Controller.
Failure to follow these instructions can result in equipment damage.

98 EIO0000003101 12/2019
Integrated Communication Ports

J1939 Capabilities
The Modicon M251 Logic Controller J1939 master has the following features:

Feature Description
Maximum number of ECUs (slaves) on the Limited only by the address range of 0...253 for Electronic
bus Control Units (ECUs).
Maximum length of J1939 fieldbus cables According to the CAN specification (see Transmission Speed
and Cable Length (see page 100)). For J1939, the CAN bus
must be configured to run at 250 Kbps.
Maximum number of PGNs managed by the Given implicitly by the maximum number of input bits (%I) and
master output bits (%Q) available on the Modicon M251 Logic
Controller: 4096 input bits and 4096 output bits. This results in
a maximum of 512 single-packet PGNs (most PGNs are
single-packet, containing 8 bytes of data).

For each additional ECU with approximately 10 configured (single frame) Parameter Group
Numbers (PGNs):
 the application size increases by an average of 15 Kbytes. This figure includes the memory
consumed by implicitly-generated variables for configured Suspected Parameter Numbers
(SPNs). This application size increase could result in exceeding memory limits.
 the number of input bits (%I) used on the logic controller increases in proportion to the number
and size of PGNs configured as "TX Signals" in a non-local ECU or "RX Signals" in a local ECU.
 the number of output bits (%Q) used on the logic controller increases in proportion to the number
and size of PGNs configured as "TX Signals" in a local ECU.
NOTE: Thoroughly test your application regarding the number of configured J1939 ECUs
connected to the controller, and the number of PGNs configured on each ECU, to avoid a system
overload watchdog condition or performance degradation.
For more information, refer to J1939 Interface Configuration (see Modicon M251 Logic Controller,
Programming Guide).

CAN Wiring Diagram


The CAN plug is a male sub-D9 terminal block:

* To be connected externally to the protective earth

EIO0000003101 12/2019 99
Integrated Communication Ports

Pin Signal Description


1 – Reserved
2 CAN_L CAN_L bus line
3 CAN_GND CAN ground
4 – Reserved
5 (CAN_SHLD) Optional CAN shield
6 GND Ground
7 CAN_H CAN_H bus line
8 – Reserved
9 (CAN_V+) Optional CAN external positive supply

WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect wires to unused terminals and/or terminals indicated as “No Connection (N.C.)”.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Transmission Speed and Cable Length


Transmission speed is limited by the bus length and the type of cable used.
The following table describes the relationship between the maximum transmission speed and the
bus length (on a single CAN segment without a repeater):

Maximum transmission baud rate Bus length


1000 Kbps 20 m (65 ft)
800 Kbps 40 m (131 ft)
500 Kbps 100 m (328 ft)
250 Kbps 250 m (820 ft)
125 Kbps 500 m (1,640 ft)
50 Kbps 1000 m (3280 ft)
20 Kbps 2500 m (16,400 ft)

NOTE: The CAN cable must be shielded.

100 EIO0000003101 12/2019


Integrated Communication Ports

Ethernet Port

Overview
The M251 Logic Controller is equipped with Ethernet communications ports:

Reference Number of Ports Port Name


TM251MESC 2 (one dual Ethernet port switch) Ethernet
TM251MESE 2 (one dual Ethernet port switch) Ethernet 1
1 Ethernet 2

Characteristics
This table describes the different Ethernet characteristics:

Characteristic Description
Function Modbus TCP/IP, Machine Expert protocol, EtherNet I/P
Connector type RJ45
Auto negotiation from 10 M half duplex to 100 M full duplex
Cable type Shielded
Automatic cross-over detection Yes

Pin Assignment
This figure shows the RJ45 Ethernet connector pin assignment:

This table describes the RJ45 Ethernet connector pins:

Pin N° Signal
1 TD+
2 TD-
3 RD+
4 -
5 -
6 RD-
7 -
8 -

EIO0000003101 12/2019 101


Integrated Communication Ports

NOTE: The controller supports the MDI/MDIX auto-crossover cable function. It is not necessary to
use special Ethernet crossover cables to connect devices directly to this port (connections without
an Ethernet hub or switch).
NOTE: Ethernet cable disconnection is detected every second. In case of disconnection of a short
duration (< 1 second), the network status may not indicate the disconnection.

Status LED
This figure shows RJ45 connectors status LED:

This table describes the Ethernet status LEDs:

Label Description LED


Color Status Description
1 Ethernet link Green/Yellow Off No link
Solid yellow Link at 10 Mbit/s
Solid green Activity at 100 Mbit/s
2 Ethernet activity Green Off No activity
On Transmitting or receiving data

102 EIO0000003101 12/2019


Integrated Communication Ports

TM251MESE Specific Considerations

Ethernet Ports
The TM251MESE has two different Ethernet networks. Each has its own unique IP and MAC
addresses.
The two Ethernet networks are called Ethernet 1 and Ethernet 2:
 Ethernet 1 is made of two switched Ethernet ports dedicated to communication between
machines or with the control network.
 Ethernet 2 is made of one Ethernet port dedicated to the device network and supporting
industrial Ethernet connections.

Industrial Ethernet Architecture


This figure presents a typical industrial Ethernet architecture:

A Control network
B Device network
1 Logic controller (see EcoStruxure Machine Expert Industrial Ethernet, User Guide)
2 Daisy-chained slaves
3 Ethernet switch
4 I/O island (Modbus TCP)
5 Vision sensor (EtherNet/IP)
6 PC and HMI (TCP/UDP)
2, 4, and 5 Industrial Ethernet slave devices (EtherNet/IP / Modbus TCP)

EIO0000003101 12/2019 103


Integrated Communication Ports

Industrial Ethernet Connections with Modbus TCP IOScanner Architecture


For example, you can:
 Connect your PC to Ethernet 1.
 Use a Modbus TCP IOScanner or EtherNet/IP Scanner with the Ethernet 2.

This figure is an example of an industrial Ethernet architecture with the TM251MESE.

104 EIO0000003101 12/2019


Integrated Communication Ports

USB Mini-B Programming Port

Overview
The USB Mini-B Port is the programming port you can use to connect a PC with a USB host port
using EcoStruxure Machine Expert software. Using a typical USB cable, this connection is suitable
for quick updates of the program or short duration connections to perform maintenance and inspect
data values. It is not suitable for long-term connections such as commissioning or monitoring
without the use of specially adapted cables to help minimize electromagnetic interference.

WARNING
UNINTENDED EQUIPMENT OPERATION OR INOPERABLE EQUIPMENT
 You must use a shielded USB cable such as a BMX XCAUSBH0•• secured to the functional
ground (FE) of the system for any long-term connection.
 Do not connect more than one controller or bus coupler at a time using USB connections.
 Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Characteristics
This table describes the characteristics of the USB Mini-B programming port:

Parameter USB Programming Port


Function Compatible with USB 2.0
Connector type Mini-B
Isolation None
Cable type Shielded

EIO0000003101 12/2019 105


Integrated Communication Ports

Serial Line

Overview
The serial line:
 Can be used to communicate with devices supporting the Modbus protocol as either master or
slave, ASCII protocol (printer, modem...) and Machine Expert Protocol (HMI,...).
 provides a 5 Vdc power distribution.

Characteristics

Characteristic Description
Function RS485 or RS232 software configured
Connector type RJ45
Isolation Non-isolated
Maximum baud rate 1200 up to 115 200 bps
Cable Type Shielded
Maximum length (between the controller 15 m (49 ft) for RS485
and an isolated junction box) 3 m (9.84 ft) for RS232
Polarization Software configuration is used to connect when
the node is configured as a master.
560 Ω resistors are optional.
5 Vdc power supply for RS485 Yes

106 EIO0000003101 12/2019


Integrated Communication Ports

NOTE: Some devices provide voltage on RS485 serial connections. Do not connect these voltage
lines to your controller as they may damage the controller serial port electronics and render the
serial port inoperable.

NOTICE
INOPERABLE EQUIPMENT
Use only the VW3A8306R•• serial cable to connect RS485 devices to your controller.
Failure to follow these instructions can result in equipment damage.

Pin Assignment
The following figure shows the pins of the RJ45 connector:

This table describes the pin assignment of the RJ45 connector:

Pin RS232 RS485


1 RxD N.C.
2 TxD N.C.
3 N.C. N.C.
4 N.C. D1
5 N.C. D0
6 N.C. N.C.
7 N.C. * 5 Vdc
8 Common Common

*: 5 Vdc delivered by the controller, do not connect.


N.C.: No connection
RxD: Received data
TxD: Transmitted data

EIO0000003101 12/2019 107


Integrated Communication Ports

WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect wires to unused terminals and/or terminals indicated as “No Connection (N.C.)”.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Status LED
This table describes the serial line status LED:

Label Description LED


Color Status Description
SL Serial line Green On Indicates the activity of the serial line.
Off Indicates no serial communication.

108 EIO0000003101 12/2019


Modicon M251 Logic Controller
Connecting the M251 Logic Controller to a PC
EIO0000003101 12/2019

Chapter 7
Connecting the M251 Logic Controller to a PC

Connecting the M251 Logic Controller to a PC

Connecting the Controller to a PC

Overview
To transfer, run, and monitor the applications, connect the controller to a computer, that has
EcoStruxure Machine Expert installed, using either a USB cable or an Ethernet connection (for
those references that support an Ethernet port).

NOTICE
INOPERABLE EQUIPMENT
Always connect the communication cable to the PC before connecting it to the controller.
Failure to follow these instructions can result in equipment damage.

USB Powered Download


In order to execute limited operations, the M251 Logic Controller has the capability to be powered
through the USB Mini-B port. A diode mechanism avoids having the logic controller both powered
by USB and by the normal power supply, or to supply voltage on the USB port.
When powered only by USB, the logic controller executes the firmware and the boot project (if any)
and the I/O board is not powered during boot (same duration as a normal boot). USB powered
download initializes the internal flash memory with some firmware or some application and
parameters when the controller is powered by USB. The preferred tool to connect to the controller
is the Controller Assistant. Refer to the EcoStruxure Machine Expert Controller Assistant User
Guide.
The controller packaging allows easy access to USB Mini-B port with minimum opening of the
packaging. You can connect the controller to the PC with a USB cable. Long cables are not suitable
for the USB powered download.

WARNING
INSUFFICENT POWER FOR USB DOWNLOAD
Do not use a USB cable longer than 3m (9.8 ft) for USB powered download.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000003101 12/2019 109


Connecting the M251 Logic Controller to a PC

NOTE: It is not intended that you use the USB Powered Download on an installed controller.
Depending on the number of I/O expansion modules in the physical configuration of the installed
controller, there may be insufficient power from your PC USB port to accomplish the download.

USB Mini-B Port Connection


TCSXCNAMUM3P: This USB cable is suitable for short duration connections such as quick
updates or retrieving data values.
BMXXCAUSBH018: Grounded and shielded, this USB cable is suitable for long duration
connections.
NOTE: You can only connect 1 controller or any other device associated with EcoStruxure Machine
Expert and its component to the PC at any one time.
The USB Mini-B Port is the programming port you can use to connect a PC with a USB host port
using EcoStruxure Machine Expert software. Using a typical USB cable, this connection is suitable
for quick updates of the program or short duration connections to perform maintenance and inspect
data values. It is not suitable for long-term connections such as commissioning or monitoring
without the use of specially adapted cables to help minimize electromagnetic interference.

WARNING
UNINTENDED EQUIPMENT OPERATION OR INOPERABLE EQUIPMENT
 You must use a shielded USB cable such as a BMX XCAUSBH0•• secured to the functional
ground (FE) of the system for any long-term connection.
 Do not connect more than one controller or bus coupler at a time using USB connections.
 Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The communication cable should be connected to the PC first to minimize the possibility of
electrostatic discharge affecting the controller.

110 EIO0000003101 12/2019


Connecting the M251 Logic Controller to a PC

To connect the USB cable to your controller, follow the steps below:

Step Action
1 1a If making a long-term connection using the cable BMXXCAUSBH018, or other cable with a
ground shield connection, be sure to securely connect the shield connector to the functional
ground (FE) or protective ground (PE) of your system before connecting the cable to your
controller and your PC.
1b If making a short-term connection using the cable TCSXCNAMUM3P or other non-grounded
USB cable, proceed to step 2.
2 Connect your USB cable to the computer.
3 Open the hinged access cover.
4 Connect the Mini connector of your USB cable to the controller USB connector.

Ethernet Port Connection


You can also connect the controller to a PC using an Ethernet cable.

To connect the controller to the PC, do the following:

Step Action
1 Connect the Ethernet cable to the PC.
2 Connect the Ethernet cable to either of the Ethernet 1 ports on the controller.

EIO0000003101 12/2019 111


Connecting the M251 Logic Controller to a PC

112 EIO0000003101 12/2019


Modicon M251 Logic Controller
Glossary
EIO0000003101 12/2019

Glossary

A
application
A program including configuration data, symbols, and documentation.
ASCII
(American standard code for Information Interchange) A protocol for representing alphanumeric
characters (letters, numbers, certain graphics, and control characters).

B
bps
(bit per second) A definition of transmission rate, also given in conjunction with multiplicator kilo
(kbps) and mega (mbps).

C
CANopen
An open industry-standard communication protocol and device profile specification (EN 50325-4).
CFC
(continuous function chart) A graphical programming language (an extension of the IEC 61131-3
standard) based on the function block diagram language that works like a flowchart. However, no
networks are used and free positioning of graphic elements is possible, which allows feedback
loops. For each block, the inputs are on the left and the outputs on the right. You can link the block
outputs to the inputs of other blocks to create complex expressions.
configuration
The arrangement and interconnection of hardware components within a system and the hardware
and software parameters that determine the operating characteristics of the system.
continuous function chart language
A graphical programming language (an extension of the IEC61131-3 standard) based on the
function block diagram language that works like a flowchart. However, no networks are used and
free positioning of graphic elements is possible, which allows feedback loops. For each block, the
inputs are on the left and the outputs on the right. You can link the block outputs to inputs of other
blocks to create complex expressions.
controller
Automates industrial processes (also known as programmable logic controller or programmable
controller).

EIO0000003101 12/2019 113


Glossary

D
DIN
(Deutsches Institut für Normung) A German institution that sets engineering and dimensional
standards.

E
EIA rack
(electronic industries alliance rack) A standardized (EIA 310-D, IEC 60297, and DIN 41494
SC48D) system for mounting various electronic modules in a stack or rack that is 19 inches
(482.6 mm) wide.
EN
EN identifies one of many European standards maintained by CEN (European Committee for
Standardization), CENELEC (European Committee for Electrotechnical Standardization), or ETSI
(European Telecommunications Standards Institute).

F
FBD
(function block diagram) One of 5 languages for logic or control supported by the standard IEC
61131-3 for control systems. Function block diagram is a graphically oriented programming
language. It works with a list of networks, where each network contains a graphical structure of
boxes and connection lines, which represents either a logical or arithmetic expression, the call of
a function block, a jump, or a return instruction.
FE
(functional Earth) A common grounding connection to enhance or otherwise allow normal
operation of electrically sensitive equipment (also referred to as functional ground in North
America).
In contrast to a protective Earth (protective ground), a functional earth connection serves a purpose
other than shock protection, and may normally carry current. Examples of devices that use
functional earth connections include surge suppressors and electromagnetic interference filters,
certain antennas, and measurement instruments.

H
HE10
Rectangular connector for electrical signals with frequencies below 3 MHz, complying with IEC
60807-2.

114 EIO0000003101 12/2019


Glossary

I
I/O
(input/output)
IEC
(international electrotechnical commission) A non-profit and non-governmental international
standards organization that prepares and publishes international standards for electrical,
electronic, and related technologies.
IEC 61131-3
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with
controller programming languages and defines 2 graphical and 2 textual programming language
standards. The graphical programming languages are ladder diagram and function block diagram.
The textual programming languages include structured text and instruction list.
IL
(instruction list) A program written in the language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (refer to IEC 61131-3).
instruction list language
A program written in the instruction list language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (see IEC 61131-3).
IP 20
(ingress protection) The protection classification according to IEC 60529 offered by an enclosure,
shown by the letter IP and 2 digits. The first digit indicates 2 factors: helping protect persons and
for equipment. The second digit indicates helping protect against water. IP 20 devices help protect
against electric contact of objects larger than 12.5 mm, but not against water.

L
ladder diagram language
A graphical representation of the instructions of a controller program with symbols for contacts,
coils, and blocks in a series of rungs executed sequentially by a controller (see IEC 61131-3).
LD
(ladder diagram) A graphical representation of the instructions of a controller program with symbols
for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to
IEC 61131-3).

M
master/slave
The single direction of control in a network that implements the master/slave mode.

EIO0000003101 12/2019 115


Glossary

Modbus
The protocol that allows communications between many devices connected to the same network.

N
NEMA
(national electrical manufacturers association) The standard for the performance of various
classes of electrical enclosures. The NEMA standards cover corrosion resistance, ability to help
protect from rain, submersion, and so on. For IEC member countries, the IEC 60529 standard
classifies the ingress protection rating for enclosures.

P
PDO
(process data object) An unconfirmed broadcast message or sent from a producer device to a
consumer device in a CAN-based network. The transmit PDO from the producer device has a
specific identifier that corresponds to the receive PDO of the consumer devices.
PE
(Protective Earth) A common grounding connection to help avoid the hazard of electric shock by
keeping any exposed conductive surface of a device at earth potential. To avoid possible voltage
drop, no current is allowed to flow in this conductor (also referred to as protective ground in North
America or as an equipment grounding conductor in the US national electrical code).
program
The component of an application that consists of compiled source code capable of being installed
in the memory of a logic controller.

R
RJ45
A standard type of 8-pin connector for network cables defined for Ethernet.
RPDO
(receive process data object) An unconfirmed broadcast message or sent from a producer device
to a consumer device in a CAN-based network. The transmit PDO from the producer device has a
specific identifier that corresponds to the receive PDO of the consumer devices.
RS-485
A standard type of serial communication bus, based on 2 wires (also known as EIA RS-485).
RxD
The line that receives data from one source to another.

116 EIO0000003101 12/2019


Glossary

S
SFC
(sequential function chart) A language that is composed of steps with associated actions,
transitions with associated logic condition, and directed links between steps and transitions. (The
SFC standard is defined in IEC 848. It is IEC 61131-3 compliant.)
ST
(structured text) A language that includes complex statements and nested instructions (such as
iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.

T
terminal block
(terminal block) The component that mounts in an electronic module and provides electrical
connections between the controller and the field devices.
TPDO
(transmit process data object) An unconfirmed broadcast message or sent from a producer device
to a consumer device in a CAN-based network. The transmit PDO from the producer device has a
specific identifier that corresponds to the receive PDO of the consumer devices.
TxD
The line that sends data from one source to another.

EIO0000003101 12/2019 117


Glossary

118 EIO0000003101 12/2019


Modicon M251 Logic Controller
Index
EIO0000003101 12/2019

Index

A Electromagnetic Susceptibility, 57
Environmental Characteristics, 55
accessories, 41
analog input modules
specifications, 31 F
analog mixed I/O modules
features
specifications, 33
key features, 18
analog output modules
fieldbus interface
specifications, 32
specifications, 38

B G
bus coupler
Grounding, 82
specifications, 36

C I
Installation, 53
CANopen communication, 98
Electrical Requirements, 74
certifications and standards, 58
installation
communication
logic/motion controller installation, 59
CANopen, 98
intended use, 6
Communication Ports, 97
Ethernet Port, 101
Serial Line 1, 106
USB Programming Port, 105
J
connections J1939
to CANopen slaves, 98 capabilities, 99
to J1939 ECUs, 99
L
D logic/motion controller installation, 59
digital I/O modules
specifications, 23, 24, 27, 28, 30
Digital I/O modules
M
Specifications, 24 M251
TM251MESC, 87
TM251MESE, 91
E mounting positions, 63
ECUs, max. number of J1939, 99
Electrical Requirements
Installation, 74

EIO0000003101 12/2019 119


Index

N T
notice Tesys modules
loss of application data, 49 specifications, 34
transmitter and receiver modules
specifications, 35
P
PGNs, max. number of J1939, 99
Power Supply, 78 U
presentation USB Programming Port
TM251MESC, 87 Communication Ports, 105
TM251MESE, 91
programming languages
IL, LD, grafcet, 18 W
wiring, 75

Q
qualification of personnel, 6

R
real time clock, 44
regular inputs, 27, 28, 30
regular transistor outputs, 27, 28, 30
relay outputs, 27, 28, 30
Run/Stop, 48

S
SD Card, 49
Serial Line 1
Communication Ports, 106
specifications
analog input modules, 31
analog mixed I/O modules, 33
analog output modules, 32
digital I/O modules, 23, 27, 28, 30
Specifications
Digital I/O modules, 24, 24
specifications
modules, 34
transmitter and receiver modules, 35

120 EIO0000003101 12/2019