PacDrive LMC400c
PacDrive LMC400c
PacDrive LMC400c
EIO0000001503 04/2018
04/2018
EIO0000001503.04
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2018 Schneider Electric. All Rights Reserved.
2 EIO0000001503 04/2018
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 1 Specific Safety Information . . . . . . . . . . . . . . . . . . . . . . . 15
Product Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Proper Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 2 System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
System Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Logic Motion Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Lexium 62 Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Lexium 52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Lexium 62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Lexium SH3 Servo Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Type Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Nameplate Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 3 Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.1 Electromagnetic Compatibility, EMC . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electromagnetic Compatibility, EMC . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.2 Control Cabinet Planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Degree of Protection (IP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Mechanical and Climatic Environmental Conditions in the Control
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Using Cooling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.3 Information about Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
General Information about Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Cable Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Configuring and Coding the Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . 48
ESD Protection Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Chapter 4 Installation and Maintenance . . . . . . . . . . . . . . . . . . . . . 51
4.1 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Prerequisites for Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Preparing Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Preparing the Control Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Mechanical Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Completion of Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
EIO0000001503 04/2018 3
4.2 Maintenance, Repair, Cleaning, Replacement Equipment Inventory. . 64
Prerequisites for Maintenance, Repair, and Cleaning . . . . . . . . . . . . . 65
Battery Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Maintenance - Uninterruptible Power Supply. . . . . . . . . . . . . . . . . . . . 69
Machine Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Replacement Equipment Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4.3 Replacing Components and Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Prerequisites for Replacing Components and Cables . . . . . . . . . . . . . 72
Device Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fast Device Replacement (FDR) - Introduction . . . . . . . . . . . . . . . . . . 76
Fast Device Replacement - Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Fast Device Replacement - Controller Display . . . . . . . . . . . . . . . . . . 79
Fast Device Replacement - Application . . . . . . . . . . . . . . . . . . . . . . . . 82
Cable Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Chapter 5 Indicators and Control Elements . . . . . . . . . . . . . . . . . . . 89
Indicators of the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
CompactFlash Card Slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Chapter 6 Integrated Communication Ports . . . . . . . . . . . . . . . . . . . 103
Electrical Connections Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Connection Details Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Chapter 7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Ambient Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Standards and Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Mechanical and Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Chapter 8 Uninterruptible Power Supply UPS. . . . . . . . . . . . . . . . . . 133
Retrofitting Installation of UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Chapter 9 Optional Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
9.1 Communication Module OM-NE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Initial Installation of the Optional Module . . . . . . . . . . . . . . . . . . . . . . . 140
Removal of the Optional Module (No Replacement) . . . . . . . . . . . . . . 142
Replacement of the Optional Module. . . . . . . . . . . . . . . . . . . . . . . . . . 143
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
4 EIO0000001503 04/2018
9.2 Communication Module OM-P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Initial Installation of the Optional Module . . . . . . . . . . . . . . . . . . . . . . . 149
Removal of the Optional Module (No Replacement) . . . . . . . . . . . . . . 151
Replacement of the Optional Module . . . . . . . . . . . . . . . . . . . . . . . . . 152
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
9.3 Communication Module OM-C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Initial Installation of the Optional Module . . . . . . . . . . . . . . . . . . . . . . . 156
Removal of the Optional Module (No Replacement) . . . . . . . . . . . . . . 158
Replacement of the Optional Module . . . . . . . . . . . . . . . . . . . . . . . . . 159
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Appendices ......................................... 161
Appendix A Further Information on the Manufacturer . . . . . . . . . . . . 163
Contact Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Product Training Courses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Appendix B Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Appendix C Units and Conversion Tables . . . . . . . . . . . . . . . . . . . . . 167
Units and Conversion Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Index ......................................... 171
EIO0000001503 04/2018 5
6 EIO0000001503 04/2018
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.
EIO0000001503 04/2018 7
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.
QUALIFICATION OF PERSONNEL
Only appropriately trained persons who are familiar with and understand the contents of this
manual and all other pertinent product documentation are authorized to work on and with this
product.
The qualified person must be able to detect possible hazards that may arise from parameterization,
modifying parameter values and generally from mechanical, electrical, or electronic equipment.
The qualified person must be familiar with the standards, provisions, and regulations for the
prevention of industrial accidents, which they must observe when designing and implementing the
system.
INTENDED USE
The products described or affected by this document, together with software, accessories, and
options, are programmable logic controllers (referred to herein as “logic controllers”), intended for
industrial use according to the instructions, directions, examples, and safety information contained
in the present document and other supporting documentation.
The product may only be used in compliance with all applicable safety regulations and directives,
the specified requirements, and the technical data.
Prior to using the product, you must perform a risk assessment in view of the planned application.
Based on the results, the appropriate safety-related measures must be implemented.
Since the product is used as a component in an overall machine or process, you must ensure the
safety of persons by means of the design of this overall system.
Operate the product only with the specified cables and accessories. Use only genuine accessories
and spare parts.
Any use other than the use explicitly permitted is prohibited and can result in unanticipated
hazards.
8 EIO0000001503 04/2018
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have
point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on
factors such as the control function required, degree of protection required, production methods,
unusual conditions, government regulations, etc. In some applications, more than one processor
may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and
factors present during setup, operation, and maintenance of the machine and, therefore, can
determine the automation equipment and the related safeties and interlocks which can be properly
used. When selecting automation and control equipment and related software for a particular
application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States
of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as point-
of-operation guarding must be provided. This is necessary if the operator's hands and other parts
of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software
cannot be substituted for or take the place of point-of-operation protection.
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation
protection have been installed and are operational before placing the equipment into service. All
interlocks and safeties related to point-of-operation protection must be coordinated with the related
automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation
protection is outside the scope of the Function Block Library, System User Guide, or other
implementation referenced in this documentation.
EIO0000001503 04/2018 9
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means
used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment
documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not
installed according to local regulations (according to the National Electrical Code in the U.S.A, for
instance). If high-potential voltage testing is necessary, follow recommendations in equipment
documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
10 EIO0000001503 04/2018
About the Book
At a Glance
Document Scope
Read and understand the material contained in this manual before you work on the controller for
the first time. Take particular note of the chapter Specific Safety Information (see page 15). Only
those persons who meet the criteria described in Qualification of Personnel (see page 8) are
allowed to work with the controller.
A copy of this manual must be available for personnel who work with the controller.
This manual is to help you use the capabilities of the controller safely and properly.
Follow the instructions within this manual to help:
Reduce risks
Reduce repair costs and downtime of the controller
Increase the service life of the controller
Increase reliability of the controller
Validity Note
This document has been updated for the release of SoMachine Motion V4.4 SP1.
The technical characteristics of the devices described in the present document also appear online.
To access the information online:
Step Action
1 Go to the Schneider Electric home page www.schneider-electric.com.
2 In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks (*).
3 If you entered a reference, go to the Product Datasheets search results and click on the
reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click
on the product range that interests you.
4 If more than one reference appears in the Products search results, click on the reference that
interests you.
5 Depending on the size of your screen, you may need to scroll down to see the data sheet.
6 To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
EIO0000001503 04/2018 11
The characteristics that are presented in the present document should be the same as those
characteristics that appear online. In line with our policy of constant improvement, we may revise
content over time to improve clarity and accuracy. If you see a difference between the document
and online information, use the online information as your reference.
For product compliance and environmental information (RoHS, REACH, PEP, EOLI, etc.), go to
www.schneider-electric.com/green-premium.
Related Documents
You can download these technical publications and other technical information from our website
at www.schneider-electric.com/en/download.
Standard Description
EN 61131-2:2007 Programmable controllers, part 2: Equipment requirements and tests.
ISO 13849-1:2008 Safety of machinery: Safety related parts of control systems.
General principles for design.
EN 61496-1:2013 Safety of machinery: Electro-sensitive protective equipment.
Part 1: General requirements and tests.
12 EIO0000001503 04/2018
Standard Description
ISO 12100:2010 Safety of machinery - General principles for design - Risk assessment and risk
reduction
EN 60204-1:2006 Safety of machinery - Electrical equipment of machines - Part 1: General
requirements
EN 1088:2008 Safety of machinery - Interlocking devices associated with guards - Principles
ISO 14119:2013 for design and selection
ISO 13850:2006 Safety of machinery - Emergency stop - Principles for design
EN/IEC 62061:2005 Safety of machinery - Functional safety of safety-related electrical, electronic,
and electronic programmable control systems
IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: General requirements.
IEC 61508-2:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: Requirements for electrical/electronic/programmable
electronic safety-related systems.
IEC 61508-3:2010 Functional safety of electrical/electronic/programmable electronic safety-
related systems: Software requirements.
IEC 61784-3:2008 Digital data communication for measurement and control: Functional safety
field buses.
2006/42/EC Machinery Directive
2014/30/EU Electromagnetic Compatibility Directive
2014/35/EU Low Voltage Directive
In addition, terms used in the present document may tangentially be used as they are derived from
other standards such as:
Standard Description
IEC 60034 series Rotating electrical machines
IEC 61800 series Adjustable speed electrical power drive systems
IEC 61158 series Digital data communications for measurement and control – Fieldbus for use in
industrial control systems
Finally, the term zone of operation may be used in conjunction with the description of specific
hazards, and is defined as it is for a hazard zone or danger zone in the Machinery Directive
(2006/42/EC) and ISO 12100:2010.
NOTE: The aforementioned standards may or may not apply to the specific products cited in the
present documentation. For more information concerning the individual standards applicable to the
products described herein, see the characteristics tables for those product references.
EIO0000001503 04/2018 13
14 EIO0000001503 04/2018
PacDrive Logic Motion Controller
Specific Safety Information
EIO0000001503 04/2018
Chapter 1
Specific Safety Information
Overview
This chapter contains important safety information regarding working with the controller. The
controller conforms to recognized technical safety regulations.
EIO0000001503 04/2018 15
Specific Safety Information
Overview
Health and safety risks arising from the controller have been reduced. However a residual risk
remains, since the controller works with electrical voltage and electrical currents.
If activities involve residual risks, a safety message is made at the appropriate points. This includes
potential hazard(s) that may arise, their possible consequences, and describes preventive
measures to avoid the hazard(s).
Electrical Parts
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires except
under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when
indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Operate electrical components only with a connected protective ground (earth) cable.
After the installation, verify the secure connection of the protective ground (earth) cable to all
electrical devices to ensure that connection complies with the connection diagram.
Before enabling the device, safely cover the live components to prevent contact.
Do not touch the electrical connection points of the components when the module is
energized.
Provide protection against indirect contact (EN 50178).
Connect and disconnect cables and terminals only after you have verified that the power has
been removed from the system.
Failure to follow these instructions will result in death or serious injury.
16 EIO0000001503 04/2018
Specific Safety Information
DANGER
INSUFFICIENT GROUNDING
Use a protective ground conductor with at least 10 mm2 (AWG 6) or two protective ground
conductors with the same or larger cross section of the conductors supplying the power
terminals.
Verify compliance with all local and national electrical code requirements as well as all other
applicable regulations with respect to grounding of all equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
CRUSHING, SHEARING, CUTTING AND HITTING DURING HANDLING
Observe the general construction and safety regulations for handling and assembly.
Use appropriate mounting and transport equipment and use appropriate tools.
Prevent clamping and crushing by taking appropriate precautions.
Cover edges and angles to protect against cutting damage.
Wear appropriate protective clothing (for example, protective goggles, protective boots,
protective gloves).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Hazardous Movements
There can be different sources of hazardous movements:
No, or incorrect, homing of the drive
Wiring or cabling errors
Errors in the application program
Component errors
Error in the measured value and signal transmitter
NOTE: Provide for personal safety by primary equipment monitoring or measures. Do not rely only
on the internal monitoring of the drive components. Adapt the monitoring or other arrangements
and measures to the specific conditions of the installation in accordance with a risk and error
analysis.
EIO0000001503 04/2018 17
Specific Safety Information
DANGER
UNAVAILABLE OR INADEQUATE PROTECTION DEVICE(S)
Prevent entry to a zone of operation with, for example, protective fencing, mesh guards,
protective coverings, or light barriers.
Dimension the protective devices properly and do not remove them.
Do not make any modifications that can degrade, incapacitate, or in any way invalidate
protection devices.
Before accessing the drives or entering the zone of operation, bring the drives and the motors
they control to a stop.
Protect existing workstations and operating terminals against unauthorized operation.
Position EMERGENCY STOP switches so that they are easily accessible and can be reached
quickly.
Validate the functionality of EMERGENCY STOP equipment before start-up and during
maintenance periods.
Prevent unintentional start-up by disconnecting the power connection of the drive using the
EMERGENCY STOP circuit or using an appropriate lock-out tag-out sequence.
Validate the system and installation before the initial start-up.
Avoid operating high-frequency, remote control, and radio devices close to the system
electronics and their feed lines, and perform, if necessary, an EMC validation of the system.
Failure to follow these instructions will result in death or serious injury.
Drive systems may perform unanticipated movements because of incorrect wiring, incorrect
settings, incorrect data or other errors.
WARNING
UNINTENDED MOVEMENT OR MACHINE OPERATION
Carefully install the wiring in accordance with the EMC requirements.
Do not operate the product with undetermined settings and data.
Perform comprehensive commissioning tests that include verification of configuration settings
and data that determine position and movement.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
PELV Circuits
The signal voltage and the control voltage of the devices are less than 30 Vdc and have to be
designed as PELV (Protective Extra Low Voltage) circuits. In this range, the specification as PELV
system, according to IEC 61800-5-1 requires a protective measure against direct and indirect
contact with hazardous voltage through an implemented separation in the system/machine of the
primary and the secondary side. Separate high and low voltage wiring and respect the standard
IEC 61800-5-1, Adjustable speed electrical power drive systems - safety requirements.
18 EIO0000001503 04/2018
Specific Safety Information
DANGER
ELECTRIC SHOCK BY INADEQUATE PROTECTIVE SEPARATION
Only connect devices, electrical components, or lines to the signal voltage connectors of these
products that feature a sufficient, protective separation from the connected circuits in accordance
with the standards (IEC 61800-5-1: Adjustable speed electrical power drive systems - safety
requirements).
Failure to follow these instructions will result in death or serious injury.
Cyber Security
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED MACHINE
OPERATION
Evaluate whether your environment or your machines are connected to your critical
infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-
Depth, before connecting the automation system to any network.
Limit the number of devices connected to a network to the minimum necessary.
Isolate your industrial network from other networks inside your company.
Protect any network against unintended access by using firewalls, VPN, or other, proven
security measures.
Monitor activities within your systems.
Prevent subject devices from direct access or direct link by unauthorized parties or unauthen-
ticated actions.
Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001503 04/2018 19
Specific Safety Information
Proper Use
Installation
Install and operate this equipment in an enclosure appropriately rated for its intended environment
and secured by a keyed or tooled locking mechanism..
WARNING
UNINTENDED EQUIPMENT OPERATION
Ensure that a risk assessment is conducted and respected according to EN/ISO 12100 during
the design of your machine.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
If circumstances occur that affect the safety or cause changes to the operating behavior of the
controllers, then immediately shut down the controllers and contact your Schneider Electric
representative.
20 EIO0000001503 04/2018
Specific Safety Information
WARNING
UNINTENDED EQUIPMENT OPERATION
Only use software and hardware components approved by Schneider Electric for use with this
equipment.
Do not attempt to service this equipment outside of authorized Schneider Electric service
centers.
Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Environment Restrictions
The components must not be used in the following environments:
In hazardous (explosive) atmospheres
In mobile, movable, or floating systems
In life support systems
In domestic appliances
Underground
This equipment has been designed to operate outside of any hazardous location. Only install this
equipment in zones known to be free of a hazardous atmosphere.
DANGER
POTENTIAL FOR EXPLOSION
Install and use this equipment in non-hazardous locations only.
Failure to follow these instructions will result in death or serious injury.
EIO0000001503 04/2018 21
Specific Safety Information
22 EIO0000001503 04/2018
PacDrive Logic Motion Controller
System Overview
EIO0000001503 04/2018
Chapter 2
System Overview
System Overview
EIO0000001503 04/2018 23
System Overview
System Overview
System Overview
The control system consists of several components, depending on its application.
PacDrive 3 system overview
24 EIO0000001503 04/2018
System Overview
Overview
Product Description
The PacDrive LMC (Logic Motion Controller), with a VxWorks real-time
operating system, centrally implements the Logic Controller and motion
functions. A PacDrive LMC synchronizes, coordinates, and creates the
motion functions of a machine for a maximum of:
0 Sercos servo drives for the controller PacDrive LMC100
4 Sercos servo drives for the controller PacDrive LMC101
6 Sercos servo drives for the controller PacDrive LMC106
8 Sercos servo drives for the controller PacDrive LMC201
12 Sercos servo drives for the controller PacDrive LMC212
16 Sercos servo drives for the controller PacDrive LMC216
8 Sercos servo drives for the controller PacDrive LMC300
16 Sercos servo drives for the controller PacDrive LMC400
16 Sercos servo drives for the controller PacDrive LMC402
99 Sercos servo drives for the controller PacDrive LMC600
130 Sercos servo drives for the controller PacDrive LMC802
EIO0000001503 04/2018 25
System Overview
Overview
The modular servo drive system Lexium 62 Drive System is designed for the operation of servo
drives in a multi-axes system.
The power electronic components of the Lexium 62 Drive System are fitted inside the control
cabinet.
Using a common DC bus, the central power supply unit Lexium 62 Power
Supply supplies the connected servo converters with the power required.
The central Lexium 62 Power Supply, using a common DC bus, supplies the
connected Lexium 62 Cabinet Drives with the power required.
The Lexium 62 Drive System helps simplify the wiring of the devices in relation to the initial start-
up and in service cases. This also applies to the cable connection of the enclosed devices to the
field. All the connectors that can be connected from the outside (power input, DC bus, 24 Vdc
supply, Sercos, Ready, and Inverter Enable) are designed such, that a fast and simple
configuration without tools can be realized on the device.
26 EIO0000001503 04/2018
System Overview
The highlights:
1...4 connections for Lexium 62 ILMs or daisy chain lines or further Lexium 62 Distribution Box
Easy wiring using pre-assembled hybrid cables or power cables (daisy chain wiring)
Easy to expand
Lexium 62 ILM
The innovative Lexium 62 ILM combines motor, power stage, and digital
servo controller for an axis in a space-saving housing. Due to its compact
construction with the integrated controller, it is perfectly suitable for peripheral
setup. It is available with individual or multi-turn encoders and configures itself
with the aid of the electronic nameplate in the Lexium 62 ILM.
The highlights:
Compact type of construction
3.5 times peak torque
Integrated Sercos interface
High-resolution single or multi-turn encoder
Degree of protection IP65
Simple wiring
EIO0000001503 04/2018 27
System Overview
28 EIO0000001503 04/2018
System Overview
The following Lexium 62 ILMs can be equipped with the Daisy Chain Connector Box in order to
implement a daisy chain wiring:
ILM070••
ILM100••
ILM140••
EIO0000001503 04/2018 29
System Overview
Lexium 52
Overview
Product Description
The stand-alone Lexium 52 Sercos servo amplifier is designed for servo drive
solutions with independent single axes, or other applications involving
asynchronous motors.
The power electronic components of the Lexium 52 are fitted inside the
control cabinet.
The drive provides the phase currents required for the position control of the
connected motors. According to the different requirements in relation to the
individual servo axes of the application, the Lexium 52 is available in different
current classes.
The Lexium 52 helps simplify the wiring in relation to the initial start-up and
service cases. This also applies to the cable connection of the enclosed
devices to the field. All the connectors that can be connected from the outside
(power input, DC bus, 24 Vdc supply, Sercos, motor, encoder, I/Os,
I/O supply, Ready and Inverter Enable (STO)) are designed so that a fast,
simple configuration on the device can be realized.
30 EIO0000001503 04/2018
System Overview
Lexium 62
Overview
The modular servo drive system Lexium 62 is designed for the operation of servo drives in a multi-
axis group.
The power electronic components of the Lexium 62 are fitted inside the control cabinet.
Product Description
The central Lexium 62 Power Supply, using a common DC bus, supplies the
connected Lexium 62 Cabinet Drives with the power required.
EIO0000001503 04/2018 31
System Overview
Overview
Product Description
The servo motors meet rigorous requirements of dynamics and precision.
Five flange sizes with different torque outputs offer the correct drive solution
for your application.
The highlights:
Developed for high dynamics and precision
Single tooth winding
Compact size
High-power density
Low internal moment of inertia
High overload capability
Low detent torque
32 EIO0000001503 04/2018
System Overview
Type Code
Overview
The graphic shows the type code PacDrive LMC Pro/Pro2:
EIO0000001503 04/2018 33
System Overview
Nameplate Descriptions
Overview
The Logic Motion Controller (LMC) nameplate is located on the side of the housing:
Label Description
LMC400Cxxxxxx Device type and Unicode
Input d.c Digital inputs / input voltage and input current (per input)
Output d.c. Digital outputs / output voltage and rated current (per input)
IP20 Degree of protection
CE (symbol) CE mark
Label Description
LMC400CCABA00 Device type and Unicode
907156.0010 Serial number
RS:02 Hardware revision (1)
DOM Date of manufacture
(1) When replacing the controller (see page 74), the hardware revision for the previous and the new device
should be identical to help avoid potential compatibility issues with the equipment. The hardware revision
can also be read from the hardware code in the device (see page 99). For more information on the
compatibility of different hardware revisions, contact your local Schneider Electric representative.
34 EIO0000001503 04/2018
PacDrive Logic Motion Controller
Planning
EIO0000001503 04/2018
Chapter 3
Planning
Planning
EIO0000001503 04/2018 35
Planning
Section 3.1
Electromagnetic Compatibility, EMC
WARNING
ELECTROMAGNETIC DISTURBANCES OF SIGNALS AND DEVICES
Use proper EMC shielding techniques to help prevent unintended device operation in accordance
with the standard IEC 61131-2.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
These types of devices are not intended to be used on a low-voltage public network which supplies
domestic premises. Radio frequency interference is expected if used in such a network.
WARNING
RADIO INTERFERENCE
Do not use these products in domestic electrical networks.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Enclosure Layout
The prerequisite for compliance with the specified limit values is an EMC compatible layout.
Depending on the application, the following measures can improve the EMC-dependent values:
36 EIO0000001503 04/2018
Planning
Shielded Cables
Cable Routing
Use fine wire potential equalization conductor. Discharging of high frequency interference currents.
EIO0000001503 04/2018 37
Planning
Voltage Supply
38 EIO0000001503 04/2018
Planning
EIO0000001503 04/2018 39
Planning
Section 3.2
Control Cabinet Planning
40 EIO0000001503 04/2018
Planning
Overview
Install components such that a degree of protection corresponding to the actual operational
environment is set up.
For more information on the degree of protection of the component, refer to Ambient Conditions
(see page 122).
The following ambient conditions may damage the components:
Oil
Moisture
Electromagnetic interference
Ambient temperature
Metal dust deposits
WARNING
UNINTENDED EQUIPMENT OPERATION
Observe and conform to ambient temperatures, storage temperatures and transport
temperatures of the individual components as specified in the operating manuals of the
components.
Prevent the formation of moisture during the operation, storage and transport of individual
components.
Conform to the vibration and shock requirements specified in the operating manuals for the
components when operating, storing and transporting system components.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001503 04/2018 41
Planning
Overview
Step Action
1 Observe the climatic and mechanical ambient conditions.
For more information on the general climatic and mechanical environmental conditions
according to IEC/EN 60721, refer to Ambient Conditions (see page 122).
2 Verify the technical data of the device whether the permitted deviations (for example, higher
shock load or higher temperature) are specified.
42 EIO0000001503 04/2018
Planning
Step Action
1 Position the cooling units so that no condensate drips out of the cooling unit onto electronic
components or is sprayed by the cooling air flow.
2 Provide specially designed control cabinets for cooling units on the top of the control cabinet.
3 Design the control cabinet so that the cooling unit fan cannot spray any accumulated condensate
onto the electronic components when it restarts after a pause.
4 When using cooling units, use only well-sealed control cabinets so that warm, humid outside air,
which causes condensation, does not enter the cabinet.
5 When operating control cabinets with open doors during commissioning or maintenance, ensure
that the electronic components are at no time cooler than the air in the control cabinet after the
doors are shut, in order to avoid any condensation.
6 Continue to operate the cooling unit even when the system is switched off, so that the
temperature of the air in the control cabinet and the air in the electronic components remains the
same.
7 Set cooling unit to a fixed temperature of 40 °C (104 °F).
8 For cooling units with temperature monitoring, set the temperature limit to 40 °C (104 °F) so that
the internal temperature of the control cabinet does not fall below the external air temperature.
WARNING
UNINTENDED EQUIPMENT OPERATION
Follow the installation instructions such that the condensation from the cooling unit can not enter
electronic components.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001503 04/2018 43
Planning
44 EIO0000001503 04/2018
Planning
Section 3.3
Information about Wiring
EIO0000001503 04/2018 45
Planning
Overview
Use only Schneider Electric approved devices in your application, and especially Schneider
Electric pre-fabricated cables wherever and whenever possible.
Use an appropriate torque indication or screwdriver for tightening connections.
For information on the tightening torques and cable cross-sections, refer to Integrated
Communication Ports (see page 103).
Observe the following points when wiring:
1. Observe the minimum cross-sections of the cables necessary for the load carrying capacity of
the equipment being connected.
2. Verify the integrity of cable shields to ensure continuity to ground.
3. Ensure that there is a proper connection to ground for all interconnected equipment.
4. Eliminate any ground loops.
5. Do not disconnect cable connections terminals when under power.
6. Ensure that all ground connections have sufficient surface area continuity.
7. Do not interchange encoder connections.
8. Do not interchange the EMERGENCY STOP circuits.
Example
If, for example, two parallel conductors are shown as coming from one point, you may not run just
one conductor and then branch it off at a later point. If it is wired this way, induction loops
(interference emitters and antennas) as well as interfering potential shifts may occur.
DANGER
INCORRECT OR UNAVAILABLE GROUNDING
Remove paint across a large surface at the installation points before installing the devices (bare
metal connection).
Failure to follow these instructions will result in death or serious injury.
46 EIO0000001503 04/2018
Planning
Cable Characteristics
Characteristics
Cable characteristics of the Sercos cable (see the Schneider Electric catalog for the various cables
available):
Property Value
Voltage isolation (jacket) 300 Vdc
Temperature range -20... +60 °C / -4...+140 °F
Cable diameter 5.8 ± 0.2 mm (0.23 ± 0.008 in.)
Bending radius 8 x diameter (fixed routing)
Sheath PVC, flame-retardant
Cable type and shielding CAT6 with S/FTP (Sercos III)
EIO0000001503 04/2018 47
Planning
Overview
For configuring and coding the cables, use the appropriate connector kit supplied with the device.
48 EIO0000001503 04/2018
Planning
General
Observe the following instructions to help avoid damages due to electrostatic discharge:
NOTICE
ELECTROSTATIC DISCHARGE
Do not touch any of the electrical connections or components.
Prevent electrostatic charges, for example, by wearing appropriate clothing.
If you must touch circuit boards, do so only on the edges.
Move the circuit boards as little as possible.
Remove existing static charge by touching a grounded, metallic surface.
Failure to follow these instructions can result in equipment damage.
EIO0000001503 04/2018 49
Planning
50 EIO0000001503 04/2018
PacDrive Logic Motion Controller
Installation and Maintenance
EIO0000001503 04/2018
Chapter 4
Installation and Maintenance
General Information
Proceed with care during the following steps in order to help to avoid the following points:
Injuries and material damage
Incorrect installation and programming of components
incorrect operation of components
use of non-authorized cables or modified components
EIO0000001503 04/2018 51
Installation and Maintenance
Section 4.1
Commissioning
Commissioning
52 EIO0000001503 04/2018
Installation and Maintenance
Prerequisites
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires except
under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when
indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Operate electrical components only with a connected protective ground (earth) cable.
After the installation, verify the secure connection of the protective ground (earth) cable to all
electrical devices to ensure that connection complies with the connection diagram.
Before enabling the device, safely cover the live components to prevent contact.
Do not touch the electrical connection points of the components when the module is
energized.
Provide protection against indirect contact (EN 50178).
Connect and disconnect cables and terminals only after you have verified that the power has
been removed from the system.
Failure to follow these instructions will result in death or serious injury.
EIO0000001503 04/2018 53
Installation and Maintenance
Preparing Commissioning
Prerequisite
Verify safety-related circuits for proper function, if applicable.
ESD Protection
Observe the following instructions to help avoid damages due to electrostatic discharge:
NOTICE
ELECTROSTATIC DISCHARGE
Do not touch any of the electrical connections or components.
Prevent electrostatic charges, for example, by wearing appropriate clothing.
If you must touch circuit boards, do so only on the edges.
Move the circuit boards as little as possible.
Remove existing static charge by touching a grounded, metallic surface.
Failure to follow these instructions can result in equipment damage.
Unpacking
How to unpack the device:
Step Action
1 Remove packaging
2 Dispose of the packaging material in accordance with the relevant local regulations.
Verifying
How to verify the device:
Step Action
1 Verify that the delivery is complete on the basis of the delivery slip.
2 Closely inspect the device for any signs of damage.
3 Verify the data with the help of the nameplates.
4 Observe requirements for the installation location.
5 In addition to the following instructions, also note the information in the chapter Planning
(see page 35).
6 If you intend to install optional modules, refer also to the information in the chapter Optional
Modules (see page 137).
7 If you intend to install the UPS battery pack, refer also to the information in the chapter
Uninterruptible Power Supply UPS (see page 133).
54 EIO0000001503 04/2018
Installation and Maintenance
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not mount or commission damaged drive systems.
Do not modify the drive systems.
Send back inoperative devices.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001503 04/2018 55
Installation and Maintenance
Overview
DANGER
INCORRECT OR UNAVAILABLE GROUNDING
Remove paint across a large surface at the installation points before installing the devices (bare
metal connection).
Failure to follow these instructions will result in death or serious injury.
Step Action
1 If necessary to maintain and respect the maximum ambient operating temperature, install
additional fan in the control cabinet.
2 Do not block the fan air inlet of the product.
3 Drill mounting holes in the control cabinet according to the mounting-grid pattern.
4 Keep a distance of at least 100 mm (3.94 in) above and below the products.
56 EIO0000001503 04/2018
Installation and Maintenance
EIO0000001503 04/2018 57
Installation and Maintenance
Required Distances
Required distances in the control cabinet for the PacDrive LMC Pro/Pro2, Lexium 62 Power
Supply, Lexium 62 Cabinet Drive:
– mm in Thread
(1) 100 (± 0.2) 3.94 (± 0.01) M6
(2) 296 (+ 0.5 / -0) 11.65 (± 0.02 / -0) M6
(3) 35 (± 0.2) 1.38 (± 0.01) M6
(4) 90 (± 0.2) 3.54 (± 0.01) M6
(5) 45 (± 0.2) 1.77 (± 0.01) M6
NOTE: For the shield plates (external shield connections), additional holes are required.
58 EIO0000001503 04/2018
Installation and Maintenance
Mechanical Mounting
Procedure
Step Action
1 Screw the pan-head screws M6 (socket head cap screws) into the prepared mounting holes.
2 Keep a distance of 10 mm (0.39 in) between the screw head and the mounting plate.
3 Hook in device and verify the vertical mounting arrangement.
4 Tighten the mounting screws (torque: 4.6 Nm (41 lbf in)).
EIO0000001503 04/2018 59
Installation and Maintenance
Wiring
Step Action
1 Connect the protective conductor with the ring cable lug and the M5 screw to the shield
connection of the controller (tightening torque: 1 Nm (8.85 lbf in))
2 Follow the assembly based on the shield connection:
lock washer
ring cable lug
lock washer
washer
screw
3 Connect the plug-in connector CN1 ”24 V supply” to the controller. For important safety
information, follow the instructions in the second safety message after this table.
4 Connect the Sercos cable CN12 (CN13) to the power supply
60 EIO0000001503 04/2018
Installation and Maintenance
Step Action
5 Insert the other end of the Sercos cable to CN2 (CN3) into the Lexium 62 Power Supply or
Lexium 62 Cabinet Drive.
NOTE: Depending on the device combination choose the appropriate Sercos cable length.
NOTE: If possible, establish a Sercos connection via the ring topology (2).
NOTE:
If Sercos devices are assigned via the topological addresses (IdentificationMode =
TopologyAddress) to the PacDrive LMC Pro/Pro2, then consider the following:
Connect your Sercos device to the PacDrive LMC Pro/Pro2 either completely via Sercos
port 1 (CN12) in line topology or in ring topology using Sercos port 1 and 2 (CN12/CN13).
Do not connect the Sercos devices to the PacDrive LMC Pro/Pro2 via double line topology
(CN12/CN13).
Do not connect the Sercos devices to the PacDrive LMC Pro/Pro2 only via Sercos port 2
(CN13).
Line topology and ring topology
1 Line topology
2 Ring topology
6 Optionally, connect the plug-in connector CN2 / CN3 "Digital I/Os" to the controller.
7 Optionally, connect the plug-in connector CN4 "TP / fast digital inputs" to the controller
8 Optionally, connect the plug-in connector CN5 "Analog I/Os" to the controller.
9 Optionally, connect a Ethernet cable to CN8 "Ethernet connection" of the controller.
10 Optionally, connect a PacNet cable to CN9 "PacNet" of the PacDrive LMC Pro/Pro2. Provide an
unused connection CN9 with a PacNet terminating plug.
11 Optionally, connect a RT-Ethernet cable to CN10 (CN11) "RT Ethernet port1 (port2)" of the
controller.
12 Optionally, connect serial interface cable to CN15 "COM1 (RS-232)" of the controller.
EIO0000001503 04/2018 61
Installation and Maintenance
Step Action
13 Optionally, connect serial interface cable to CN16 "COM2 (RS-485))" of the controller.
14 Optionally, connect CAN bus cable to CN17 "CAN" of the controller.
15 Optionally, connect PROFIBUS DP bus cable to CN18 "PROFIBUS" of the controller.
16 Optionally, if optional modules are available then insert the respective cables with the
corresponding connections of the optional modules.
DANGER
ELECTRIC SHOCK CAUSED BY HIGH LEAKAGE (TOUCH) VOLTAGE
Attach the shock protector covers on the extremities of the Bus Bar Module combination
(see page 59).
Apply power to the device only if the shock protector covers have been attached to the
extremities of the Bus Bar Module combination.
Failure to follow these instructions will result in death or serious injury.
DANGER
INSUFFICIENT GROUNDING
Use a protective ground conductor with at least 10 mm2 (AWG 6) or two protective ground
conductors with the same or larger cross section of the conductors supplying the power
terminals.
Verify compliance with all local and national electrical code requirements as well as all other
applicable regulations with respect to grounding of all equipment.
Failure to follow these instructions will result in death or serious injury.
62 EIO0000001503 04/2018
Installation and Maintenance
Completion of Commissioning
EIO0000001503 04/2018 63
Installation and Maintenance
Section 4.2
Maintenance, Repair, Cleaning, Replacement Equipment Inventory
64 EIO0000001503 04/2018
Installation and Maintenance
Introduction
Observe the following instructions before carrying out maintenance on the controller.
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Wait 15 minutes to allow the residual energy of the DC bus capacitors to discharge.
Measure the voltage on the DC bus with a properly rated voltage sensing device and verify
that the voltage is less than 42.4 Vdc.
Do not assume that the DC bus is voltage-free when the DC bus LED is off.
Block the motor shaft to prevent rotation prior to performing any type of work on the drive
system.
Do not create a short-circuit across the DC bus terminals or the DC bus capacitors.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 In the case of any drives, servos or other equipment with high capacity capacitors, wait at least
15 minutes after removing power (switching off) to allow the DC bus capacitors to discharge.
4 Verify whether the DC-BUS LED indicator has turned off on all components located in the axis
group.
5 Verify with an appropriate measuring instrument that the voltages between DC+ to PE
(Protective Earth/ground), DC- to PE and DC+ to DC- are all less than 42.4 Vdc.
EIO0000001503 04/2018 65
Installation and Maintenance
DANGER
ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Verify with a correctly calibrated measuring instrument that the DC bus is de-energized (less than
42.4 Vdc) before replacing, maintaining or cleaning machine components.
Failure to follow these instructions will result in death or serious injury.
For more information on the DC Bus LED indicator, refer to Bus Bar Module LED Indicators on the
Lexium 62 Power Supply and Lexium 62 Cabinet Drive (see Lexium 62, Hardware Guide).
66 EIO0000001503 04/2018
Installation and Maintenance
Battery Compartment
Overview
The battery compartment is located under the operating cover of the controller. The controller
battery buffers controller data (BIOS cmos, NVRAM, RTC).
Maintenance Interval
The maintenance interval for replacing the battery is 5 years. After this period of time, the battery
must be replaced. If the device (with battery installed) is not used for an extended period of time,
you should verify/replace the battery.
Step Action
1 Remove battery and then make the manual measurement.
2 Or observe the diagnostic message 037 Battery low in the IEC program and display it on an HMI
(panel), if necessary.
3 Replace battery three days after the first diagnostic message at the latest.
EIO0000001503 04/2018 67
Installation and Maintenance
DANGER
EXPLOSION, FIRE, OR CHEMICAL BURNS
Replace with identical battery type.
Follow all the instructions of the battery manufacturer.
Remove all replaceable batteries before discarding unit.
Recycle or properly dispose of used batteries.
Protect battery from any potential short-circuit.
Do not recharge, disassemble, heat above 100 °C (212 °F), or incinerate.
Use your hands or insulated tools to remove or replace the battery.
Maintain proper polarity when inserting and connecting a new battery.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 You can change the battery while the controller is on or off. There is no loss of data when it is
performed with the controller on. When the controller is switched off, the time period of the data
buffering without a battery is approximately 30 seconds.
2 Use pliers with insulated tips to lightly pull the battery out of its slot.
3 Carefully place the battery on the guide and lightly push it into the device.
NOTE: Replacement of the battery in the controllers other than with the type specified in this
documentation may present a risk of fire or explosion.
WARNING
IMPROPER BATTERY CAN PROVOKE FIRE OR EXPLOSION
Replace battery only with identical type: 3 V Lithium Renata Type CR2450N.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
68 EIO0000001503 04/2018
Installation and Maintenance
Overview
The maintenance interval for replacing the battery pack is 3 years. For more information, refer to
Uninterruptible Power Supply - UPS (see page 133).
Machine Repair
Presentation
When replacing controllers, be sure to observe the important safety information in the sections of
the present document concerning mounting and dismounting components.
With exception of batteries, there are no other user-serviceable parts within the controllers. Either
replace the controller or contact Schneider Electric (see page 164).
WARNING
UNINTENDED EQUIPMENT OPERATION
Only use software and hardware components approved by Schneider Electric for use with this
equipment.
Do not attempt to service this equipment outside of authorized Schneider Electric service
centers.
Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Use only the accessories and mounting parts specified in the documentation and no third-party
devices or components that have not been expressly approved by Schneider Electric. Do not
modify the equipment.
In case machine repair includes the replacement of the drive components, observe the following
instructions for ESD protection in order to avoid any damage due to electrostatic discharge:
NOTICE
ELECTROSTATIC DISCHARGE
Do not touch any of the electrical connections or components.
Prevent electrostatic charges, for example, by wearing appropriate clothing.
If you must touch circuit boards, do so only on the edges.
Move the circuit boards as little as possible.
Remove existing static charge by touching a grounded, metallic surface.
Failure to follow these instructions can result in equipment damage.
EIO0000001503 04/2018 69
Installation and Maintenance
Cleaning
NOTICE
CORROSION CAUSED BY CLEANING AGENTS
Before using a cleaning agent, carry out a compatibility test in relation to the cleaning agent
and the component affected.
Do not use alkaline detergent.
Do not use any chlorid-containing cleaning agents.
Failure to follow these instructions can result in equipment damage.
For more information on the material properties of your component, refer to Mechanical and
Electrical Data (see page 126).
Replacement Equipment Inventory
Presentation
Keep a stock of the most important components to make certain your machine is functioning and
ready for operation.
Replace devices with the same hardware configuration to help ensure compatibility.
Indicate the following information on the replacement equipment order:
Unicode: for example, LMC400CAABA00
Hardware revision: for example, RS:02
This information can be found on the logistic nameplate (see page 34).
For more information concerning the replacement of components, refer to Replacing Components
and Cables (see page 71).
70 EIO0000001503 04/2018
Installation and Maintenance
Section 4.3
Replacing Components and Cables
EIO0000001503 04/2018 71
Installation and Maintenance
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Wait 15 minutes to allow the residual energy of the DC bus capacitors to discharge.
Measure the voltage on the DC bus with a properly rated voltage sensing device and verify
that the voltage is less than 42.4 Vdc.
Do not assume that the DC bus is voltage-free when the DC bus LED is off.
Block the motor shaft to prevent rotation prior to performing any type of work on the drive
system.
Do not create a short-circuit across the DC bus terminals or the DC bus capacitors.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 In the case of any drives, servos or other equipment with high capacity capacitors, wait at least
15 minutes after removing power (switching off) to allow the DC bus capacitors to discharge.
4 Verify whether the DC-BUS LED indicator has turned off on all components located in the axis
group.
5 Verify with an appropriate measuring instrument that the voltages between DC+ to PE
(Protective Earth/ground), DC- to PE and DC+ to DC- are all less than 42.4 Vdc.
72 EIO0000001503 04/2018
Installation and Maintenance
DANGER
ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Verify with a correctly calibrated measuring instrument that the DC bus is de-energized (less than
42.4 Vdc) before replacing, maintaining or cleaning machine components.
Failure to follow these instructions will result in death or serious injury.
For more information on the DC Bus LED indicator, refer to Bus Bar Module LED Indicators on the
Lexium 62 Power Supply and Lexium 62 Cabinet Drive (see Lexium 62, Hardware Guide).
Other Prerequisites
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Operate electrical components only with a connected protective ground (earth) cable.
After the installation, verify the secure connection of the protective ground (earth) cable to all
electrical devices to ensure that connection complies with the connection diagram.
Before enabling the device, safely cover the live components to prevent contact.
Do not touch the electrical connection points of the components when the module is
energized.
Provide protection against indirect contact (EN 50178).
Connect and disconnect cables and terminals only after you have verified that the power has
been removed from the system.
Failure to follow these instructions will result in death or serious injury.
With exception of batteries, there are no other user-serviceable parts within the controllers. Either
replace the component or contact Schneider Electric (see page 164).
WARNING
UNINTENDED EQUIPMENT OPERATION
Only use software and hardware components approved by Schneider Electric for use with this
equipment.
Do not attempt to service this equipment outside of authorized Schneider Electric service
centers.
Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001503 04/2018 73
Installation and Maintenance
Device Replacement
DANGER
INOPERABLE SAFETY FUNCTION
Test the proper functioning of the safety functions after every device replacement and every
change of the wiring.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 In order to maintain compatibility with your application and machine, replace the existing
controller with that of the same hardware revision (for example, RS:02 on the logistical
nameplate (see page 34) or 02 in the hardware code (see page 91).
2 Contact your Schneider Electric representative if the replacement controller is of a different
hardware revision.
3 When replacing the controller, in addition to the following instructions, the specifications of the
original machine manufacturer must also be observed.
4 Disconnect cables from the controller.
5 Loosen the mounting screws from the top and bottom of the housing brackets.
6 Remove the controller and replace the complete unit.
7 Install the new controller and tighten the mounting screws.
8 Connect the controller according to the circuit diagram of the machine.
9 Following replacement of the controller, proceed as for the initial start-up.
NOTICE
IMPROPER REPLACEMENT / COMMISSIONING
Do not open the controller for commissioning or replacement.
Failure to follow these instructions can result in equipment damage.
74 EIO0000001503 04/2018
Installation and Maintenance
DANGER
INCORRECT ASSIGNMENT OF CABLES
Verify that the assignment of the cables conforms to their previous connector assignments.
Failure to follow these instructions will result in death or serious injury.
CAUTION
FALLING HEAVY OBJECT
Do not fully remove the screw connections of the device mounting suspension and prevent the
device from falling out and down.
Failure to follow these instructions can result in injury or equipment damage.
How to Start-Up
Proceed as follows to start up:
Step Action
1 Import the user project again using a PC on which the automation toolkit SoMachine Motion
Logic Builder is installed.
Or
Retrieve the CompactFlash card from the controller to be replaced and insert it into the new
controller.
2 Ensure that the CompactFlash card is functional.
3 Store the PacDrive controller in a suitable transport packaging.
4 Put the system back in operation.
EIO0000001503 04/2018 75
Installation and Maintenance
Introduction
With the help of the fast device replacement, the Lexium 62, Lexium 52 and ILM devices that are
in the configuration of a SoMachine Motion project on the controller can be replaced.
There are certain parameters that have to be set in SoMachine Motion first. Information on this can
be found in the online help of SoMachine Motion.
Subsequently, certain settings on the display of the controller have to be made which are described
in the following.
The controller interface for FDR gives the possibility to manually access the assignment between
logical devices in the controller configuration (SoMachine Motion Logic Builder) and the physical
connected devices.
76 EIO0000001503 04/2018
Installation and Maintenance
WARNING
UNINTENDED OPERATING STATE OF THE DEVICE
Make sure that the assignment of the logical devices to the physical connected devices is
exactly the same as the device assignment before the device replacement.
Before putting the machine back into service, you have to verify that the application is
addressing the physical drives correctly.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Device Replacement
If the requirements are fulfilled (see chapter Fast Device Replacement in the SoMachine Motion
online help) and you are replacing a device, then the controller display automatically shows the
start picture of the controller interface for FDR.
EIO0000001503 04/2018 77
Installation and Maintenance
Confirmation or Cancel
Action Result
You can exit the controller interface for FDR with the The controller interface for FDR is ended.
Enter key (if the arrow pointing right is on No).
You can also switch to Yes with the arrow pointing Now you can navigate through the menu like
down key (arrow pointing right on Yes), and then described in the chapter Controller Display
confirm the Yes with Enter. (see page 79). For more information, refer to the
chapter Application (see page 82).
Timeout (5 Minutes)
If no button is pressed at the display for 5 minutes, the controller interface for FDR is terminated
(timeout = 5 minutes). The system then behaves as if you have terminated the FDR mechanism
as described above. If you press a display button within the 5 minutes, the time for the timeout is
reset.
78 EIO0000001503 04/2018
Installation and Maintenance
Overview
When the controller interface for FDR is active, the controller display shows the corresponding
menu.
The following describes the menu in general. For more information, refer to the section Application
(see page 82).
– The command that is in the line that is marked with the arrow pointing right can be
confirmed/executed with the Enter key.
In the following example, FDR SNRC stands for addressing a device via the device serial number.
Instead of FDR SNRC, the FDR ATYP (for application type) or FDR SADR (for Sercos address) can
also be used.
EIO0000001503 04/2018 79
Installation and Maintenance
Placeholders Description
[x/y] Number of the logic device (x) which currently has to be processed and the total number of
the assigned devices (y). If, for example, 20 devices cannot be assigned by default
addressing and you have already assigned 11 devices via the controller interface for FDR,
then 12/20 is displayed.
If this line (for example, FDR SNRC[x/y] [TA]) contains more than 18 characters, then the
first 16 characters are displayed, followed by ....
Via the menu item Details, you can switch to a display mode that displays the complete line
(see below).
[TA] Topological address of the physical device that is currently displayed.
[log.device] Name of the logical device in the controller configuration (SoMachine Motion Logic Builder)
that shall be assigned to the physical device at the topological address [TA].
If the device name consists of more than 18 characters, the first 16 characters of the device
name are displayed, followed by ...
Via the menu item Details, you can switch to a display mode that displays the complete
logical device name (see below).
[SNRC] Serial number of the currently displayed physical device on the topological address [TA]
If the serial number has more than 18 characters, then the first 16 characters of the serial
number are displayed, followed by ...
Via the menu item Details, you can switch to a display mode that displays the complete serial
number (see below).
NOTE: Devices that were assigned via the menu item/command Assign device (see below) cannot
be removed again via a menu item/command.
80 EIO0000001503 04/2018
Installation and Maintenance
Further information on the parameters can be found under Fast Device Replacement in the online
help of SoMachine Motion.
EIO0000001503 04/2018 81
Installation and Maintenance
Starting Conditions
The following example shows a typical application for the controller interface for FDR. For the
displayed example, the following applies:
All the devices are operational.
The Sercos bus is started up.
For all the devices, the Device addressing via the Identification mode → Device serial number
was made (parameter SerialNumberController / 0).
The parameter FDRConfirmationMode of the controller was set to the value
by Display / 0.
Further information on the parameters can be found under Fast Device Replacement in the online
help of SoMachine Motion.
82 EIO0000001503 04/2018
Installation and Maintenance
Device Replacement
The following devices have to be replaced because of maintenance:
The device at the topology address 2 (TA:2) with the logical device name DEV_02 and the serial
number SNRC phy: xxx-02 has to be replaced by the new device that has the serial number
SNRC phy: xxx-15.
The device at the topology address 5 (TA:5) with the logical device name DEV_05 and the serial
number SNRC phy xxx-05 has to be replaced by the new device that has the serial number
SNRC phy xxx-16.
After the physical replacement of the devices the machine has to be restarted again. In order for
the controller interface for FDR to be started, the parameter FDRStartMode has to be set to
Start/1 or Phase start-up/2 and the parameter FDRConfirmationMode to
by display / 0.
Now the controller interface for FDR has to find the correct assignment of the two logical devices
DEV_02 and DEV_05 to the new physically connected devices at topology address 2 and 5.
EIO0000001503 04/2018 83
Installation and Maintenance
Further information on the parameters can be found under Fast Device Replacement in the online
help of SoMachine Motion.
Process
The controller interface for FDR verifies all the logical devices one after another which would trigger
the diagnostic message 8501 Sercos slave not found during the Sercos phase start-up.
Afterwards, to the respective logical device all the physical devices are checked until one device
is acknowledged.
Due to space constraints, the sequence for device 1 and device 2 is displayed one beneath the
other.
84 EIO0000001503 04/2018
Installation and Maintenance
EIO0000001503 04/2018 85
Installation and Maintenance
86 EIO0000001503 04/2018
Installation and Maintenance
Cable Replacement
Introduction
NOTE: In addition to the following instructions, you must observe the specifications of the machine
manufacturer when replacing the cables.
DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power from all equipment including connected devices prior to removing any
covers or doors, or installing or removing any accessories, hardware, cables, or wires.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Wait 15 minutes to allow the residual energy of the DC bus capacitors to discharge.
Measure the voltage on the DC bus with a properly rated voltage sensing device and verify
that the voltage is less than 42.4 Vdc.
Do not assume that the DC bus is voltage-free when the DC bus LED is off.
Block the motor shaft to prevent rotation prior to performing any type of work on the drive
system.
Do not create a short-circuit across the DC bus terminals or the DC bus capacitors.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a
proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 In the case of any drives, servos or other equipment with high capacity capacitors, wait at least
15 minutes after removing power (switching off) to allow the DC bus capacitors to discharge.
4 Verify whether the DC-BUS LED indicator has turned off on all components located in the axis
group.
5 Verify with an appropriate measuring instrument that the voltages between DC+ to PE
(Protective Earth/ground), DC- to PE and DC+ to DC- are all less than 42.4 Vdc.
EIO0000001503 04/2018 87
Installation and Maintenance
DANGER
ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Verify with a correctly calibrated measuring instrument that the DC bus is de-energized (less than
42.4 Vdc) before replacing, maintaining or cleaning machine components.
Failure to follow these instructions will result in death or serious injury.
For more information on the DC Bus LED indicator, refer to Bus Bar Module LED Indicators on the
Lexium 62 Power Supply and Lexium 62 Cabinet Drive (see Lexium 62, Hardware Guide).
Procedure
Proceed as follows for cable replacement:
Be sure that the cables clearly indicate their connections before disconnecting.
Replace cables with an identical type and length.
Refer to any documentation from the original machine manufacturer before replacing cables.
Disconnect/Attach the cable from the equipment components involved.
DANGER
INCORRECT ASSIGNMENT OF CABLES
Verify that the assignment of the cables conforms to their previous connector assignments.
Failure to follow these instructions will result in death or serious injury.
88 EIO0000001503 04/2018
PacDrive Logic Motion Controller
Indicators and Control Elements
EIO0000001503 04/2018
Chapter 5
Indicators and Control Elements
EIO0000001503 04/2018 89
Indicators and Control Elements
Overview
90 EIO0000001503 04/2018
Indicators and Control Elements
If the cover of the controller is closed, you see 3 vertically arranged LED indicators, which signify
various operating states or detected errors:
Power
WD (watchdog indicator)
Error (error display)
In addition to the LED indicators, further information about the operating status of the controller is
given on the 4-line Liquid Crystal Display (LCD).
EIO0000001503 04/2018 91
Indicators and Control Elements
The Error LED indicator is flashing on after BIOS is started. Once the operating system, user
configuration, user parameters, and the IEC program have been loaded and the IEC program has
been started successfully, the Error LED indicator is switched off again. The boot procedure is now
complete.
92 EIO0000001503 04/2018
Indicators and Control Elements
The Ethernet connector of PacDrive LMC Pro2 has two LED indicators. One LED indicator is green
(above), the other is yellow/green (below).
EIO0000001503 04/2018 93
Indicators and Control Elements
94 EIO0000001503 04/2018
Indicators and Control Elements
EIO0000001503 04/2018 95
Indicators and Control Elements
96 EIO0000001503 04/2018
Indicators and Control Elements
Menu Navigation
Menu Buttons
Three menu buttons are located on the front side of the controller. With these menu buttons, the
user can open and navigate through the menu.
1 Up arrow button
2 Enter button
3 Down arrow button
Buttons Function
Access of the menu
Cursor down
EIO0000001503 04/2018 97
Indicators and Control Elements
If an up or down arrow is displayed on the right display edge, this indicates that the current menu
has more lines than can be shown on the display. In this case, you can use the arrow buttons
Menu Navigation
98 EIO0000001503 04/2018
Indicators and Control Elements
Item Description
FW Currently used firmware version.
PFPGA Version of the PacDrive FPGA software
PIC Version of PIC firmware
BIOS BIOS version
In the submenu HCode/SerialNo. a serial number and the hardware code are displayed. The serial
number is a unique number which is used to identify the controller. The hardware code indicates
the hardware revision.
Item Description
Serial number Controller serial number
Hardware code Hardware code of the controller(1)
(1) The first two digits of the hardware code indicate the hardware revision (for example, 02). The hardware
revision is also indicated on the logistical nameplate (see page 34) (for example, RS:02). In order to
maintain compatibility with your application and machine, replace the existing controller with that of the
same hardware code.
In the submenu IP address, the IP address, the subnet mask, and the gateway are displayed.
Item Description
IP IP address of the controller
MASK Subnet mask
GW Gateway
The MAC address is specified in the submenu MAC address. The MAC address is a clear address
of the device to identify the device in the network.
Item Description
MAC address MAC address
EIO0000001503 04/2018 99
Indicators and Control Elements
In the submenu Inputs, the user can prompt the logic state of each input. The digital inputs
correspond to the standard IEC61131-2 type 1. Touchprobes and fast inputs have a resolution of
10 µs. Fast inputs can be used to trigger an interrupt.
Item Description
DI Digital input
FI Fast input
TP Touchprobe
In the submenu Outputs, the user can prompt the logic state of each output.
Item Description
DQ Outputs
In the submenu DiagMessage, the diagnostic class, the diagnostic code, and the diagnostic text
are displayed. The system assigns each diagnostic message a specific diagnostic class when
enabled. The diagnostic code is a code that encrypts a certain diagnostic. In the diagnostic text, a
diagnostic is described in detail.
Item Description
A: A: Diagnostic class
BBB: BBBB: Diagnostic code
C...C C...C: Diagnostic text
In the submenu Select language, the user can choose the display language.
Item Description
Select language:
German Display language is German.
English Display language is English.
Overview
The CompactFlash card slot is located on the operating cover of the controller.
The CompactFlash card slot is the receptacle for the permanent data storage (CF card) of the
controller.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Hold the CompactFlash card with your thumb and forefinger and pull it out of the slot.
4 To insert, carefully place the CompactFlash card on the guide rail and push it into the device.
5 Push lightly until the CompactFlash card clicks in.
Buttons
on / off Button
The on / off buttons are located under the operating cover of the controller.
Precondition: Place the system in a secure position before switching it off.
Step Action
1 Press this button to energize the controller when the controller is completely wired and
connected to the power supply system.
2 Press this button to de-energize the controller when the system is running.
reset Button
The reset button is located under the operating cover of the controller.
Precondition: Place the system in a secure position before resetting.
Step Action
1 Press the button to reset and reboot the controller.
Chapter 6
Integrated Communication Ports
Front Panel
Connection overview of the PacDrive LMC Pro/Pro2:
Front view of the PacDrive LMC Pro/Pro2: Bottom view of the PacDrive LMC Pro/Pro2:
Connection Meaning Connection cross-section [mm2] / [AWG] Tightening torque [Nm] / [lbf in]
CN1 Control voltage / watchdog 1...1.5 17...16 –
CN2 Digital outputs 1...1.5 17...16 –
CN3 Digital inputs 0.5...1.5 20...16 –
CN4 TP / fast digital inputs 0.5...1.5 20...16 –
CN5 Analog inputs / outputs 0.5...1.5 20...16 –
CN7 USB host (USB-A) – – –
CN8 Ethernet connection – – –
CN9 PacNet – – –
CN10 RT Ethernet, port 1 – – –
CN11 RT Ethernet, port 2 – – –
CN12 Sercos, port 1 – – –
Connection Meaning Connection cross-section [mm2] / [AWG] Tightening torque [Nm] / [lbf in]
CN13 Sercos, port 2 – – –
CN14 Master encoder (Hiperface) – – 0.4 / 3.54
CN14 Master encoder – – 0.4 / 3.54
(incremental)
CN15 COM 1 (RS-232) – – 0.4 / 3.54
CN16 COM 2 (RS-485) – – 0.4 / 3.54
CN17 CAN – – 0.4 / 3.54
CN18 PROFIBUS DP – – 0.4 / 3.54
CN20 Option slot 1 – – 0.5 / 4.42
CN21 Option slot 2 – – 0.5 / 4.42
Shield connection 4 11 1 / 8.85
Connection CN1
Input connection
Connection CN2
Connection CN3
Connection CN4
Connection CN5
Input connection
Connection CN7
CN8 - Ethernet
CN9 - PacNet
Connection CN9
CN10/CN11 - RT Ethernet
Connection CN10/11
NOTE: When using the PacDrive LMC Pro/Pro2 as EtherCAT slave, the connection CN10
represents the input port and the connection CN11 the output port. The input port and output port
are predetermined by the firmware and cannot be configured.
For further information on the functions of the LED indicators, refer to the description of the
Indicators and Control elements (see page 89).
CN12/CN13 - Sercos
Connection CN12/CN13
NOTE:
If Sercos devices are assigned via the topological addresses (IdentificationMode =
TopologyAddress) to the PacDrive LMC Pro/Pro2, then consider the following:
Connect your Sercos device to the PacDrive LMC Pro/Pro2 either completely via Sercos port 1
(CN12) in line topology or in ring topology using Sercos port 1 and 2 (CN12/CN13).
Do not connect the Sercos devices to the PacDrive LMC Pro/Pro2 via double line topology
(CN12/CN13).
Do not connect the Sercos devices to the PacDrive LMC Pro/Pro2 only via Sercos port 2
(CN13).
Connection CN15
Connection CN16
CN17 - CAN
Connection CN17
NOTE: The connection of the TM5 System to the PacDrive controller can only occur via a Sercos
bus interface TM5NS31. A connection of TM5 System via CAN bus and a CANopen interface
module is not supported.
CN18 - PROFIBUS
Connection CN18
Connectors
NOTE: For the connection plugs, use a PROFIBUS connector to connect to the 9 pole PROFIBUS
outlet because the bus terminal resistors are in this connector.
Note for the bus terminal resistors:
Step Action
1 Verify for the first and last bus nodes if the terminal resistors are switched on. Otherwise data
transmission will not function properly.
2 Verify if the shielding is applied extensively and on both sides.
Chapter 7
Technical Data
Technical Data
Ambient Conditions
Overview
Standards and regulations
China RoHS Marking for the Restricted Use of Hazardous Substances in Electronic and
Electrical Products
SJ/T 11364
Dimensions
Dimensions
Dimensions of the PacDrive LMC Pro/Pro2:
Chapter 8
Uninterruptible Power Supply UPS
Overview
The controllers PacDrive LMC Pro and PacDrive LMC Pro2 can be equipped with an internal
battery pack for an uninterruptible power supply. The internal battery pack is continually being
charged via the power supply of the controller while in operation.
The function of the battery pack is to maintain the power supply to the controller in the event of a
power outage long enough to shut down the controller properly without losing any data. The preset
time of shutdown can be up to 5 minutes.
If necessary, the battery pack can also be installed or replaced afterwards, as described below.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent the main switch from being switched back on.
3 Open the operating cover of the PacDrive controller.
4 Loosen the two fastening screws on the front of the controller (1).
NOTICE
ELECTROSTATIC DISCHARGE
Do not touch any of the electrical connections or components.
Prevent electrostatic charges, for example, by wearing appropriate clothing.
If you must touch circuit boards, do so only on the edges.
Move the circuit boards as little as possible.
Remove existing static charge by touching a grounded, metallic surface.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Adjust the battery pack and attach with two cable ties (1).
2 Connect the battery cable (2).
Improperly secured equipment and accessories can cause mechanical damage of PacDrive
controller.
CAUTION
BATTERY PACK NOT PROPERLY SECURED
Use only the supplied cable ties to secure the battery pack (item number VW3E6006).
Verify that the battery pack is properly secured.
Failure to follow these instructions can result in injury or equipment damage.
The maintenance interval for replacing the battery pack is 3 years. Once this period has expired,
you must replace the battery pack.
CAUTION
POSSIBLE DATA LOSS BY POWER OUTAGE
Replace the battery pack at regular maintenance intervals not to exceed 3 years.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
DAMAGE TO DISPLAY SUPPLY CABLE POSSIBLE
Do not force the electronic module into the housing.
Ensure that during installation of the electronic module the display supply cable does not get
caught or torn.
Failure to follow these instructions can result in injury or equipment damage.
1 Cable ties
2 Battery cable
3 Display supply cable
Step Action
1 Carefully push the electronic module of the controller back into the housing.
2 Tighten the two fastening screws on the front of the controller.
3 Close the operating cover.
Chapter 9
Optional Modules
Optional Modules
Section 9.1
Communication Module OM-NE
Overview
Initial Installation
Initial installation of the optional module should only be done by Schneider Electric personnel.
General Information
The OM-NE module is a general communication module which features two Ethernet connectors
to realize Ethernet based field bus protocols.
OM-NE module with slot assignment
After installing the optional module, the controller will automatically detect the module. Then
configure it by using the controller configuration in SoMachine Motion Logic Builder.
NOTE: Only use OM-NE modules from hardware code 0008 for PacDrive LMC Pro/Pro2
controllers.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Open the operating cover of the PacDrive controller upwards.
4 Undo the two fastening screws on the front of the controller.
5 Then remove the electronic module from housing.
NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Insert the backplane on the rear of the module shaft into the controller circuit board.
2 Screw the backplane to the three holes provided.
Step Action
1 Select one of the two module slots on the controller.
2 Remove module slot blanking plate.
3 Insert module into open slot.
4 Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).
Result: The module is now installed.
Step Action
1 Carefully push the electronic module of the controller back into the housing.
2 Tighten the two fastening screws on the front of the controller.
3 Close operating cover.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Undo the two M3x6 screws on the module shaft.
4 Withdraw the module from the cartridge.
Result: The module is deinstalled now and the module shaft is empty.
5 Screw the blanking plate onto the empty module shaft.
Result: The empty module shaft is closed by the blanking plate.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Undo the two M3x6 screws on the module shaft.
4 Withdraw the module from the cartridge.
Result: The module is deinstalled now and the module shaft is empty.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Insert module into open slot.
4 Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).
Result: The module is now installed.
NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Electrical Connections
NOTE: Operate the EtherNet/IP scanner only by using the connection CN30 (RT Eth P1). The
connection CN31 (RT Eth P2) is reserved.
NOTE: When using them as EtherCAT slave, the connection CN30 (RT Eth P1) represents the
input port and the connection CN31 (RT Eth P2) the output port. The input port and output port are
predetermined by the firmware and cannot be configured.
Section 9.2
Communication Module OM-P
Overview
Initial Installation
Initial installation of the optional module should only be done by Schneider Electric personnel.
General Information
Another PROFIBUS interface is made available via the OM-P module.
After installing the optional module, the controller will automatically detect the module. Then
configure it by using the controller configuration in SoMachine Motion Logic Builder.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Open the operating cover of the PacDrive controller upwards.
4 Undo the two fastening screws on the front of the controller.
5 Then remove the electronic module from housing.
NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Insert the backplane on the rear of the module shaft into the controller circuit board.
2 Screw the backplane to the three holes provided.
Step Action
1 Select one of the two module slots on the controller.
2 Remove module slot blanking plate.
3 Insert module into open slot.
4 Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).
Result: The module is now installed.
Step Action
1 Carefully push the electronic module of the controller back into the housing.
2 Tighten the two fastening screws on the front of the controller.
3 Close operating cover.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Undo the two M3x6 screws on the module shaft.
4 Withdraw the module from the cartridge.
Result: The module is deinstalled now and the module shaft is empty.
5 Screw the blanking plate onto the empty module shaft.
Result: The empty module shaft is closed by the blanking plate.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Undo the two M3x6 screws on the module shaft.
4 Withdraw the module from the cartridge.
Result: The module is deinstalled now and the module shaft is empty.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Insert module into open slot.
4 Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).
Result: The module is now installed.
NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Electrical Connections
Section 9.3
Communication Module OM-C
Overview
Initial Installation
Initial installation of the optional module should only be done by Schneider Electric personnel.
General Information
Another CANBUS interface is made available via the OM-C module.
After installing the optional module, the controller will automatically detect the module. Then
configure it by using the controller configuration in SoMachine Motion Logic Builder.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Open the operating cover of the PacDrive controller upwards.
4 Undo the two fastening screws on the front of the controller.
5 Then remove the electronic module from housing.
NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Insert the backplane on the rear of the module shaft into the controller circuit board.
2 Screw the backplane to the three holes provided.
Step Action
1 Select one of the two module slots on the controller.
2 Remove module slot blanking plate.
3 Insert module into open slot.
4 Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).
Result: The module is now installed.
Step Action
1 Carefully push the electronic module of the controller back into the housing.
2 Tighten the two fastening screws on the front of the controller.
3 Close operating cover.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Undo the two M3x6 screws on the module shaft.
4 Withdraw the module from the cartridge.
Result: The module is deinstalled now and the module shaft is empty.
5 Screw the blanking plate onto the empty module shaft.
Result: The empty module shaft is closed by the blanking plate.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Undo the two M3x6 screws on the module shaft.
4 Withdraw the module from the cartridge.
Result: The module is deinstalled now and the module shaft is empty.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Step Action
1 Set main switch to OFF position, or otherwise disconnect all power to the system.
2 Prevent main switch from being switched back on.
3 Insert module into open slot.
4 Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).
Result: The module is now installed.
NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.
Electrical Connections
NOTE: The connection of the TM5 System to the PacDrive controller can only occur via a Sercos
bus interface TM5NS31. A connection of TM5 System via CAN bus and a CANopen interface
module is not supported.
EIO0000001503 04/2018
Appendices
Appendix A
Further Information on the Manufacturer
Contact Addresses
Appendix B
Disposal
Disposal
Disposal
Step Action
1 Dispose of the packaging in accordance with the relevant national regulations.
2 Dispose of the packaging at the disposal sites provided for this purpose.
3 Dispose of controller in accordance with the applicable national regulations.
Appendix C
Units and Conversion Tables
Length
– in ft yd m cm mm
in – / 12 / 36 * 0.0254 * 2.54 * 25.4
ft * 12 – /3 * 0.30479 * 30.479 * 304.79
yd * 36 *3 – * 0.9144 * 91.44 * 914.4
m / 0.0254 / 0.30479 / 0.9144 – *100 *1000
cm / 2.54 / 30.479 / 91.44 / 100 – * 10
mm / 25.4 / 304.79 / 914.4 / 1000 / 10 –
Mass
– lb oz slug 0.22 kg g
lb – * 16 * 0.03108095 * 0.4535924 * 453.5924
oz / 16 – * 1.942559*10-3 * 0.02834952 * 28.34952
slug / 0.03108095 / 1.942559*10-3 – * 14.5939 * 14593.9
0.22 kg / 0.45359237 / 0.02834952 / 14.5939 – *1000
g / 453.59237 / 28.34952 / 14593.9 / 1000 –
Force
– lb oz p dyne N
lb – * 16 * 453.55358 * 444822.2 * 4.448222
oz / 16 – * 28.349524 * 27801 * 0.27801
p / 453.55358 / 28.349524 – * 980.7 * 9.807*10-3
dyne / 444822.2 / 27801 / 980.7 – / 100*103
N / 4.448222 / 0.27801 / 9.807*10-3 * 100*103 –
Power
– HP W
HP – * 746
W / 746 –
Rotation
min-1(rpm) – * π / 30 *6
rad/s * 30 / π – * 57.295
deg./s /6 / 57.295 –
Torque
Moment of Inertia
Temperature
– °F max K
°F – (°F - 32) * 5/9 (°F - 32) * 5/9 + 273.15
max °C * 9/5 + 32 – °C + 273.15
K (K - 273.15) * 9/5 + 32 K - 273.15 –
Conductor Cross-section
AWG 1 2 3 4 5 6 7 8 9 10 11 12 13
mm 2 42.4 33.6 26.7 21.2 16.8 13.3 10.5 8.4 6.6 5.3 4.2 3.3 2.6
AWG 14 15 16 17 18 19 20 21 22 23 24 25 26
mm2 2.1 1.7 1.3 1.0 0.82 0.65 0.52 0.41 0.33 0.26 0.20 0.16 0.13
Index
C P
certifications, 125
portable systems, 21
climatic, 42
product related information, 16
condensate, 43
contact addresses, 164
cooling units, 43 Q
qualification of personnel, 8
D
daisy chain connector box, 28
daisy chain wiring, 28
S
seminars, 164
degree of protection, 41
service addresses, 164
domestic appliances, 20
F T
temperature limit, 43
floating systems, 20
training courses, 164
H U
hazardous, explosive atmospheres, 20
underground, 20
homepage, 164
I W
wiring, 46
intended use, 8
IP, 41
L
life support system, 20
M
machine grounding, 46
mechanical, 42