Delta Data Sheets
Delta Data Sheets
Subindex
Features
• Very high power density 1100 W/l - 18 W/in3
• High efficiency ≥ 91%
• Hot pluggable, all connectors at the rear
• Fan cooled with air flow monitoring
• Wide input voltage range: 88 - 300 Vrms
• Power factor ~ 1.0 (sinusoidal input current)
• Constant output power characteristic
• System bus: analogue / digital
• Operating temperature range up to 75°C
Applications
• Digital subscriber line (DSL)
• Transmission
• PBX
• Wireless base stations
• Network components
Description
The rectifier DPR 1200B-48 is a single phase, hot-pluggable, fan-cooled rectifier. The outstanding
power density of this product offers the optimum 1U or 3U shelf solution for space critical
applications. The constant output power characteristic supplies the specified power over the full
output voltage range. The benefit is an optimised modular system design (fewer number of
modules) and matches the supply requirements for state-of-the-art telecom equipment. These
performances as well as the extended temperature range, wide input voltage range and advanced
technology (patented solution) are the key factors of the success of this rectifier and it offers a cost
effective and reliable solution.
The typical applications for this rectifier are both in indoor and outdoor environments, which is a
perfect solution for digital subscriber line (DSL), transmission, PBX, wireless base stations, core
network components, telecommunication networks and data networks.
The rectifier meets the requirements set by the telecommunication standards.
Output characteristic:
Uout [V]
58 1200 W
53.5
control range
43
42
Iout [A]
20.7 22.4 28
Features
• Efficiency ≥ 91%
• Compact (500 W / l) and light (4.4 kg)
• Hot pluggable, all connectors at the rear
• Fan cooled with air flow monitoring
• Wide input voltage range: 88 - 276 Vrms
• Power factor ~ 1.0 (sinusoidal input current)
• Constant output power characteristic
• System bus: analogue / with PSC 3: digital
• Operating temperature range up to 70°C
Applications
• Indoor and outdoor
• Medium to large power systems
• Shelf power solutions
• Telecom, wireless, datacom
Description
The rectifier FR 48 V - 2000 W - E is a single phase, hot-pluggable, fan-cooled rectifier. The
constant output power characteristic supplies the specified power over the full output voltage
range. The benefit is an optimised modular system design (fewer number of modules) and
matches the supply requirements for state-of-the-art telecom equipment. This performance as well
as the extended temperature range, wide input voltage range, high power density and advanced
technology are the key factors of the success of this rectifier and it offers a cost effective and
reliable solution.
The typical applications for this rectifier are both in indoor and outdoor environments, which is a
perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The rectifier meets the requirements set by the telecommunications standards.
Output characteristic:
Uout [V]
58 2000 W
53.5
control range
43
42
Iout [A]
34.5 37.4 46.5
Features
• 3 Phase, 380/480 Vrms input
• Efficiency 90 %
• Low THD <5%
• Hot swappable, no system shutdown for maintenance
• Wide input voltage range: 264 - 530 Vrms
• Power factor correction (0.99)
• Constant output power characteristic
• User friendly LCD Display
• Intelligent micro-processor controlled
Applications
• Bulk power system
• Telecom, wireless, datacom
Description
The rectifier ESR 48 V - 7200 W - A is a three phase, hot-pluggable, fan-cooled rectifier. The constant output power
characteristic supplies the specified power over the full output voltage range. The rectifier employs the
state-of-the-art technology and provides excellent performance in the extended temperature range, wide input
voltage range, and low THD. The advanced technology is the key factor of the success of this rectifier and it offers a
cost effective and reliable solution.
The typical application for this rectifier is indoor environments, which is a perfect solution for core network
components, telecommunications networks and data networks.
Leaflet_esr48_7200waa/rev. 1.0/26.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex
Output
Voltage, nominal 54 Vdc
Voltage adjust range 40 ... 60 Vdc
Load regulation < ± 0.5 %
Line regulation < ± 0.1 %
Overvoltage protection 60 Vdc
Ripple + spikes ≤ 100 mVp-p
Psophometric noise ≤ 2.0 mVrms (weighted)
Current limit, nominal 150 Adc
Load sharing < ± 2%
Power limit 7200 W, fixed
Output connector Rear side
Output protection Internal fuse 180 A x 1
Output characteristic:
Uout [V]
60 7200 W
54
48
40
Iout [A]
120 133 150
Leaflet_esr48_7200waa/rev. 1.0/26.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex
Energy Systems
Features
• Modular structure
• 19’’ rectifier shelf / 5 U
• Easy to stack shelves
• Up to 12 kW installed power
• Fan cooled rectifiers FR 48 V – 2000 W – E
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
• Integrated 3 phase AC terminal (3L+N+PE)
Applications
• Indoor and outdoor
• Medium to large power systems
• Shelf power solutions
• Telecom, wireless, datacom
Description
The AMS 48/2000-6 19’’ is a very compact 19’’ / 5U shelf for the rectifier FR 48 V - 2000 W – E.
The modular design allows flexible power system solutions in 19’’ standard cabinets and is the key
factor of the success of this power system and it offers a cost effective and reliable solution.
The typical applications for this rectifier shelf are both in indoor and outdoor environments, which is
a perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
Energy Systems
AMS 48/2000-6 19'': Technical specifications
General Mechanics
Efficiency ≥ 91 % Construction steel frame
Losses, max. 1200 W (6 rectifiers) Cabinet standard 19’’
Safety IEC/EN 60 950 Height, overall 225 mm / 5 U
EMC EN 300 386-2 Width, body 432 mm
Cooling Fan cooled Depth, overall 437 mm
Weight, shelf 10 kg
Input Weight, rectifiers 6 x 4.4 kg
AC connection 3L + N + PE
Nominal voltage 3 x 230 Vrms (L-N) Environment
Range, full power 184 ... 276 Vrms Ambient temperature -25 ... + 70 °C
Range, reduced power 88 ... 184 Vrms Reduced power 60 ... + 70 °C
Frequency range 45 ... 66 Hz Relative humidity 95 % max, non cond.
Current nominal 3 x 19 Arms @ 12kW Protection IP 20
Current maximum 3 x 24 Arms @ 12kW
Inrush current < 30 Apeak per phase Options
Line current Meets IEC 1000-3-2 Number of rectifiers 1 ... 6
Harmonic distort. THD <5% AC connection 3L+N+PE
Mains terminal AC cord 5 x 6mm2 / 5 m 3L+PE (220/240Vrms L-L)*
Input protection, recomm. MCB 3 x 25 A / C-curve
Main switch External Accessories
Distribution DFU 300-DC 19’’
Output
*
Voltage, nominal 53.5 Vdc on request
Voltage adjust range 42 ... 58 Vdc
Voltage error, static ± 250 mVdc Subject to change due to technical progress
Overvoltage protection 59 V ± 1 V
Ripple + spikes ≤ 200 mVp-p
Psophometric noise ≤ 1.0 mVrms (weighted)
Nominal current 224 Adc @ 12kW, 53.5V
Current limit, maximum 279 Adc @ 12kW, 43V
Power, nominal 12 kW
Power, redundant 10 kW
Power, reduced min. 4800 W
Output terminal Copper bar, rear side
Output protection Internal fuse each rect.
Energy Systems
Features
• Modular structure
• 19’’ rectifier shelf / 1 U
• Short depth
• Easy to stack shelves
• Up to 3.6 kW installed power
• Fan cooled rectifiers DPR 1200B-48
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
Applications
• Indoor and outdoor
• Digital subscriber line (DSL)
• Transmission, PBX
• Telecom, wireless, datacom
Description
The DPS 1200B-48-3RS 19IN is a very compact and short 19’’ / 1U shelf for three DPR 1200B-48
rectifiers. The modular design allows flexible power system solutions in 19’’ standard cabinets,
offering a cost effective and reliable solution. The DPS 1200B-48-3RS 19IN can be applied with
various types of standard or customised distribution units with PSC 1000 or PSC 3 power system
controllers.
The typical applications for this rectifier shelf are both in indoor and outdoor environments, which is
a perfect solution for digital subscriber line (DSL), transmission, PBX, wireless base stations, core
network components, telecommunications networks and data networks.
Energy Systems
DPS 1200B-48-3RS 19IN: Technical specifications
General Mechanics
Efficiency ≥ 91 % Construction Steel frame
Losses, max. 405 W (3 rectifiers) Cabinet standard 19’’
Safety IEC/EN 60 950 Height, overall 44.45 mm / 1 U
EMC EN 300 386-2 Width, body 444 mm / 19’’
Cooling Fan cooled Depth, overall 280 mm
Weight, shelf TBD
Input Weight, rectifiers 3 x 1.25 kg
AC connection 3 / 400 V / N / PE
Nominal voltage 230 Vrms (L-N) Environment
Voltage range 88 ... 300 Vrms Ambient temperature - 25 ... + 75 °C
Range, reduced power 88 ... 184 Vrms Reduced power + 65 ... + 75 °C
Volt. range, no PFC 276 … 300 Vrms Relative humidity 95 % max, non cond.
Frequency range 45 ... 66 Hz Protection IP 20
Current nominal 5.8 Arms @ 1.2kW / phase
Current maximum 7.5 Arms @ 1.2kW / phase Options
Inrush current < 10.6 Apeak per phase Number of rectifiers 1 ... 3
Line current Meets IEC 1000-3-2 Alternative AC connect. 3 / 120 V / PE
Harmonic distort. THD <5%
Mains terminal max. 5 x 2.5 mm2 Accessories
Input protection, recomm. Internal fuse in each rect. Distribution DPD 200 19IN-3U
DPD 250 19IN-5U
Output
Voltage, nominal 53.5 Vdc Subject to change due to technical progress.
Voltage adjust range 42 ... 58 Vdc
Voltage error, static ± 250 mVdc
Overvoltage protection 59 V ± 1 V
Ripple + spikes ≤ 200 mVp-p
Psophometric noise ≤ 1.0 mVrms (weighted)
Nominal current 67 Adc @ 3.6 kW, 53.5 V
Current limit, maximum 84 Adc @ 3.6 kW, 43.0 V
Power, nominal 3.6 kW
Power, redundant 2.4 kW
Output terminal Varies
- Direct copper busbar or
- Cable connection points
Output protection Internal fuse in each rect.
Energy Systems
Typical applications
• Medium power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks
Description
The AMS 48/2000-8 GFE is a compact medium power system for power up to 16 kW. The stable
construction is based on a sheet metal design. The system contains a rectifier shelf for up to 8
rectifiers FR 48 V – 2000 W – E and one distribution unit with configurable elements for AC-, DC
distribution, LVD, LVLD and a power system controller. The power system can be mounted on top
of the battery cabinet or to the wall.
The typical applications for this power system are wireless base stations, core network
components, telecommunications and data networks.
This compact, high power density power system is the perfect choice for space-critical solutions.
Energy Systems
AMS 48/2000-8 GFE: Technical specifications
General Battery connection
Efficiency ≥ 91 % MCB 1 ... 6 x 125 A
Losses, max. 1600 W (8 rectifiers) LVD Option
Safety IEC/EN 60 950
EMC EN 300 386-2 Mechanics
Cooling Fan cooled Construction sheet metal
Cabinet standard GFE
Input Width, body 600 mm
AC connection 3L + N + PE Depth, overall 480 mm
8 x L+N+PE Height, overall 680 mm
Nominal voltage 3 x 230 Vrms (L-N) Weight, system 80 kg
Range, full power 184 ... 276 Vrms Weight, rectifiers 8 x 4.4 kg
Range, reduced power 88 ... 184 Vrms
Frequency range 45 ... 66 Hz Environment
Current nominal 3 x 28,5 Arms @ 16kW Ambient temperature -25 ... + 70 °C
Current maximum 3 x 36 Arms @ 16kW Reduced power 60 ... + 70 °C
Inrush current < 90 Apeak per phase Relative humidity 95 % max, non cond.
Line current Meets IEC 1000-3-2 Protection IP 20
Harmonic distort. THD <5%
Mains terminal Terminal blocks Control and monitoring
Input protection, recomm. 3 x 40 A Power system controller PSC 1000
8 x 16 A (8 x 1~) PSC 3*
Main switch External See leaflet for power system controller.
Transient OVP Option
Options
Output Number of rectifiers 1 ... 8
Voltage, nominal 53.5 Vdc AC connection 3L+N+PE
Voltage adjust range 42 ... 58 Vdc 2 x (3L+N+PE)
Voltage error, static ± 250 mVdc L+N+PE (single AC
Overvoltage protection 59 V ± 1 V feed for each rect)
Ripple + spikes ≤ 200 mVp-p 3L+PE (220/240VrmsL-L)*
Psophometric noise ≤ 1.0 mVrms (weighted) Power system controller PSC 1000
Nominal current 299 Adc @ 16kW, 53.5V PSC 3*
Current limit, maximum 372 Adc @ 16kW, 43V LVD 350 A
Power, nominal 16 kW LVLD 350 A
Power, redundant 14 kW Transient OVP
Power, reduced min. 6400 W
Accessories
Load distribution Rectifier front cover
MCB 1 ... 24 pcs / 1 ... 63 A Battery cabinets
LVLD Option See leaflet for battery cabinets
* on request
Energy Systems
Typical applications
• Medium power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks
Description
The AMS 48/2000-8 ETS is a modular large power
system for power up to 16 kW. The stable construction
is based on a frame cabinet design. The system
contains one rectifier shelf for up to 8 FR 48 V – 2000 W
– E rectifiers and a distribution unit with configurable
elements for AC-, DC distribution, LVD, LVLD and a
power system controller.
The modular design allows flexible power system
solutions in the ETS cabinet line and is the key factor of
the success of this power system and it offers a cost
effective and reliable solution.
The typical applications for this power system are
wireless base stations, core network components,
telecommunications and data networks.
Energy Systems
Energy Systems
Typical applications
• Large power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks
Description
The AMS 48/2000-16 ETS is a modular large power
system for power up to 32 kW. The stable
construction is based on a frame cabinet design. The
system contains two rectifier shelves for up to 16
rectifiers FR 48 V – 2000 W – E and different
distribution units with configurable elements for AC-,
DC distribution, LVD, LVLD and a power system
controller.
The modular design allows flexible power system
solutions in the ETS cabinet line and is the key factor
of the success of this power system and it offers a
cost effective and reliable solution. This power
system is expandable with a 2nd cabinet.
The typical applications for this power system are
wireless base stations, core network components,
telecommunications and data networks.
This compact, high power density power system is
the perfect choice for space-critical solutions.
Energy Systems
Output Options
Voltage, nominal 53.5 Vdc Number of rectifiers 1 ... 16
Voltage adjust range 42 ... 58 Vdc AC connection 3L+N+PE (AC feed/shelf)
Voltage error, static ± 250 mVdc L+N+PE (single AC
Overvoltage protection 59 V ± 1 V feed for each rect)
Ripple + spikes ≤ 200 mVp-p 3L+PE (220/240Vrms L-L)*
Psophometric noise ≤ 1.0 mVrms (weighted) Power system controller PSC 1000
Nominal current 598 Adc @ 32kW, 53.5V PSC 3*
Current limit, maximum 744 Adc @ 32kW, 43V LVD 600 A / battery fuse
Power, nominal 32 kW LVLD 600 A / distribution unit
Power, redundant 30 kW Transient OVP
Power, reduced min. 12.8 kW
Accessories
Load distribution Rectifier front cover
Three/four rows DFU 29xMCB Cable channel
DFU 12x00
*
DFU 7x01 on request
DFU 7x02
DFU 5x03
Subject to change due to technical progress.
LVLD Option
See leaflet for distribution units.
Energy Systems
Typical applications
• Large power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks
Description
The AMS 48/2000-24 ETS is a modular large power
system for power up to 48 kW. The stable
construction is based on a frame cabinet design. The
system contains three rectifier shelves for up to 16
rectifiers FR 48 V – 2000 W – E and different
distribution units with configurable elements for AC-,
DC distribution, LVD, LVLD and a power system
controller.
The modular design allows flexible power system
solutions in the ETS cabinet line and is the key factor
of the success of this power system and it offers a
cost effective and reliable solution. This power
system is expandable with a 2nd cabinet.
The typical applications for this power system are
wireless base stations, core network components,
telecommunications and data networks.
This compact, high power density power system is
the perfect choice for space-critical solutions.
Energy Systems
Features
• Reliable and user-friendly smart controller
• Parameter entry via key-pad
• User configurable alarms and settings
• Programmable DC output voltage
• Temperature compensated float charge
• Smart battery management
• Essential functions protected by password
• Remote monitoring (option)
Applications
• Medium power systems
Description
The power system controller PSC 1000 is a powerful microprocessor unit intended to supervise
and control modular power systems. The product complies to all important requirements and
standards of the telecommunication market. The superior features make this controller a prime
choice for your telecom power systems.
The PSC 1000 provides a full set of control and supervision functions. This means user
configurable alarms and settings which are well readable on the liquid crystal display with plain text
indication. The smart battery management with regularly accomplished capacity tests is one of the
key factors for the availability of a power system. The controller allows alarming by means of
potential-free relay contacts and remote supervision with modem and the PC based power system
manager PSM magic.
General Mechanics
System voltages 24 / 36 / 48 / 60 Vdc Width 116 mm
Accuracy of system voltage measurement Height 180 mm
0.2 % Depth 30 mm
Nominal system current 0 ... 2000 Adc Weight 0.4 kg
Accuracy of system current measurement
2% Environment
User definable alarms and thresholds Ambient temperature 0 ... + 50 °C (operation)
yes - 40 ... + 70°C (storage)
Power supply 18 ... 75 Vdc / 50 mA Relative humidity 95 % max, non cond.
Remote monitoring Option Protection IP 20
System reliability in case All rectifiers operate at
of controller failure their preset default values Operation
Display (LCD) 2 lines of 16 char each
Connections Local alarms (LEDs) Urgent alarm
Load 3 independent strings Non-urgent alarm
Battery 2 independent strings Alarm stop
Mains failure
Rectifier modules 24 maximum Service not automatic
Alarm relays 4, with potential free Mode of operation Menu controlled
contacts
Menu languages English, Swedish,
Low battery disconnect. 1, with potential free German, Chinese,
changeover contact Spanish, Finnish, Polish,
Italian, Hungarian,
Battery control French, Catalan
Accuracy of battery voltage measurement
0.5 %
Temperature compensated float charging voltage
0 ... - 200 mV / °C
Automatic boost charging Option
Low battery disconnect Option
Periodic battery test Option
Separate charging Option
Features
• Modular power system controller
• Flexible system configuration
• Easy system expansion
• Digital system bus IMBUS
• Different add on functions
• Different front end modules
• Smart battery management
• Remote monitoring with modem or LAN
Applications
• Medium to large power systems
• Decentralised data acquisition
Description
The PSC 3 is a 3rd generation of power system controller. This product is an optimum solution for
medium to very large and complex power systems. It consists of a central unit, which provides
basic I/O periphery and a very robust and reliable CAN standard based communication bus. This
concept provides easy expansion by means of different front end modules as user interface with
LCD, rectifiers, inverters, different sensors, I/O modules, customised gateways etc.
The front end modules are located close to the elements to be monitored like shunts or fuses. The
benefit is an easy wiring instead of a large cable harness, which is perfect for expandable medium
power systems or high power solutions with decentralised distributions (BDFB) and monitoring
batteries in separate rooms.
The smart battery management with regularly accomplished capacity tests is one of the key factors
for the availability of a power system.
The PSC 3 allows alarming by means of potential-free relay contacts and remote supervision with
a standard web browser via modem or LAN / Ethernet.
Energy Systems
Description
The battery cabinet is compatible with the GFE system
cabinet line. Depending on the cabinet height and
amount of shelves there is space for two to four battery
strings in the cabinet.
The modular design offers a complete solution together
with a power system from the GFE product line which
can be mounted onto this battery cabinet family.
For separate installation an optional roof is available.
The battery cabinet will be delivered as a kit and it is
easy to assemble on a site.
Energy Systems
Battery cabinet: Technical specifications
Battery cabinet IFE (depth 480 mm) and IFF (depth 600 mm)
Front view 3 shelves Front view 2 shelves Side view, depth 480/600
41,5
8
282,33
432
900 282,33
558 432
Battery cabinet LFE (depth 480 mm) and LFF (depth 600 mm)
Front view 4 shelves Front view 3 shelves Side view, depth 480/600
39,5
282,5
382,33
282,5
1200 382,33
558
Options: roof
All measurements in millimeters.
Energy Systems
Features
• Modular structure
• 19’’ distribution unit / 3 U
• Easy to install,
all user connections on the front
• LVD and PLD option
• Controller PSC 3
• 3-phase AC-terminal
• AC and DC-connections for rectifier shelves
Applications
• Indoor and outdoor
• Medium to large power systems
• Shelf power solutions
• Telecom, wireless, datacom
Description
The DPD 200 19IN-3U is a very compact 19’’ / 3U distribution unit applicable with various rectifier
shelves. The stable construction is based on sheet metal design. The system contains connections
for up to 4 rectifier shelves of the DP 1200B Series, AC- and DC-connections, battery connection and
power system controller PSC 3. The modular design allows flexible power system solutions in 19’’
standard cabinets, offering a cost effective and reliable solution.
The typical applications for this distribution unit are both in indoor and outdoor environments, which is
a perfect solution for wireless base stations, core network components, telecommunications networks
and data networks.
Energy Systems
DPD 200 19IN-3U: Technical specifications
General Battery connection
Safety IEC/EN 60 950 MCB 4 x C120 series
EMC EN 300 386-2 LVD Optional 200 A
Cooling Convection cooled Cable size, max. 35 mm2
AC connection Mechanics
Input 3 / 400 V / N / PE Construction Steel rack
Mains terminal Terminal block Height, overall 131 mm (3 U)
Max. current 36A / phase Width, body 444 mm (19'')
Cable size, max. 6 mm2 Depth, overall 275 mm
Mains switch External Protection IP 20
Lightning protection External
Environment
Output Optimized connection Ambient temperature - 25... + 67 °C
board for Reduced power + 65 ... + 67 °C
DPS 1200B-48-3RS 19IN Relative humidity 95 % max, non cond.
Connector 4 x Phoenix GICV
2,5/5-G-7,62 Control & alarms
Max. current 12 A Power system controller PSC 3
Cable size, max. 2,5 mm2 PSC 200*
DC connection Accessories
Voltage, nominal 53.5 Vdc Rectifier shelf DPS 1200B-48-9RS 19IN
Current, maximum 200 A DPS 1200B-48-3RS 19IN
Input connection AMS 48/2000-6 19''
- Copper bars DPS 1200B-48-3RS 19IN AMS 48/540-9 19’’
- Cables Others
* on request
Load distribution
MCB 12 x 1...63 A (C60 series)
PLD Optional 125 A Subject to change due to technical progress.
- disconnects 3 / 6 / 9 MCBs
Cable size, max.
- MCB 1 A ... 32 A 16 mm2
- MCB 40 A ... 63 A 35 mm2
Energy Systems
Description
The distribution fuse units (DFU) are designed for 19’’ rack or wall mounting. The modular
structure allows flexible configurations according to the customer needs. Partial load disconnection
LVLD is an option.
The DFU can be equipped with 18 magnetic circuit breakers (MCB) or 12 MCB with LVLD, which
disconnects 6 MCBs.
The fuse fault alarm is detected by the power system controller.
Energy Systems
External DFUs: Technical specifications
Load distribution
DFU DFU 12 x MCB + LVLD 200A 19’’ (W/R)
1 A, 2 A, 3 A, 4 A, 6 A,
10 A, 16 A, 20 A, 25 A,
32 A, 40 A, 50 A, 63 A,
100 A (2p), 150 A (3p)
LVLD 200 A
Max current per DFU 200 A
Feeding cable 70 mm2
Load distribution
DFU DFU 18 x MCB 19’’ (W/R)
MCB 1 A, 2 A, 3 A, 4 A, 6 A,
0 A, 16 A, 20 A, 25 A,
32 A, 40 A, 50 A, 63 A,
100 A (2p), 150 A (3p)
LVLD -
Max current per DFU 200 A
Feeding cable 70 mm2
Energy Systems
Main features
• Applicable in ETS cabinet line
• Breaker (MCB) or fuse (00, 01 , 02, 03)
• Flexible, configurable power system distribution
• LVLD option per distribution unit
Description
The distribution fuse unit (DFU) is compatible with Delta
Energy Systems ETS system cabinet line. The modular
structure allows flexible configurations according to the
customer needs. LVLD for each distribution row is an
option.
The DFU can be equipped with magnetic circuit
breakers (MCB) or fuses (00, 01, 02, and 03).
The fuse fault alarm is detected by the power system
controller.
Energy Systems
DFUs for ETS: Technical specifications
Load distribution
DFU DFU 30xMCB ETS
MCB 1 A, 2 A, 3 A, 4 A, 6 A,
10 A, 16 A, 20 A, 25 A,
32 A, 40 A, 50 A, 63 A,
100 A (2p), 150 A (3p)
LVLD Option 600 A
max current per DFU 600 A
Features
• Module design for scaleable, cost effective expansion
• High efficiency
• EMC Class B
Applications
• 3G Co-station requirement
Description
Delta DD 48 V - 480 W - A is a hot-pluggable, fan-cooled converter which converts typical 24 Vdc input into -48
Vdc for various telecommunication applications. The high power density DD module employs the start-of-the-art
technology and provides high performance in efficiency, power density and extended operation temperature
range. Up to 4 DD power modules can be equipped into one 23” width power shelf and parallel up to 3 shelves.
The maximum capability can provide more than 5.5kW output power.
The typical application for this converter is 3G co-station environments, which is a perfect solution for core
network components, telecommunications networks and data networks.
.
Leaflet_dd48_480waa/rev. 1.0/03.11.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex
Input
Voltage range 20 ... 30 Vdc
Inrush current < 200 A
Current maximum 75 A
EMI, conducted EN55022, class B
Compliant with
Mains connector Rear side
Input protection Breaker 60 A x 1
Input switch Yes
Polarity protection Yes
Output
Voltage, nominal 48 Vdc,
Voltage adjust range 42 ... 57.5 Vdc
Load regulation <±1V
Line regulation < ± 0.2 %
Overvoltage protection 59 ± 1V
Ripple ≤ 100 mVp-p
Current limit, nominal 20 Adc ± 5%
Load sharing < ± 5%
Power limit 480 W
Output connector Rear side
Short circuit protection Yes
User Interface
Status indication LED «DC O.K.»
LED «50% LOAD»
LED «100% LOAD»
LED «Converter Fail Alarm»
LED «Fan Fail»
O/P Voltage Adjustment Variable Resistor
Mechanics
Width, overall 5.1” / 130 mm
Depth, overall 11.7” / 297 mm
Height, overall 3.1” / 80 mm
Weight 2.22 lb / 1 kg
Leaflet_dd48_480waa/rev. 1.0/03.11.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex
Features
• Compact size (9.1W/in3) and light weight
• High efficiency 88 %
• Hot swappable, no system shutdown for maintenance
• Wide operation temperature: -10~60 °C
• Reverse polarity protection design
• EMC Class B
• UL/cUL, TUV/CE Certificated
Applications
• 3G Co-station requirement
Description
Delta DD 55 V - 1300 W - A is a hot-pluggable, fan-cooled converter which converts typical 24 Vdc input into –55
Vdc for various telecommunication applications. The high power density DD module employs the start-of-the-art
technology and provides high performance in efficiency, power density and extended operation temperature range.
Up to 6 DD power modules can be equipped into one 19” width power shelf and can provide total 7.8KW output
power.
The typical application for this converter is 3G co-station environments, which is a perfect solution for core network
components, telecommunications networks and data networks.
.
Leaflet_dd55_1300wac/rev. 1.0/30.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex
Input
Voltage range 20 ... 31 Vdc
Inrush current < 200 A
Current maximum 75 A
EMI, conducted CISPR 14
Compliant with
Mains connector Rear side
Input protection Internal fuse 160 A x 1
Input switch No
Polarity protection Yes
Output
Voltage, nominal 55 Vdc, fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8V
Ripple ≤ 150 mVp-p
Current limit, nominal 26 Adc ± 5%
Load sharing < ± 5%
Power limit 1300 W, fixed
Output connector Rear side
Short circuit protection Yes
User Interface
Status indication LED «Input OK»
LED «Output Fail»
LED «Fan Fail»
Mechanics
Width, overall 2.6” / 65 mm
Depth, overall 9.8” / 250 mm
Height, overall 6.7” / 170 mm
Weight 6.67 lb / 3 kg
Leaflet_dd55_1300wac/rev. 1.0/30.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex
Features
• 20 – 31 Vdc input; at 7.8 kW / 55 Vdc output
• High Efficiency 88%
• 4U high in 19" and ETSI rack standard format
• Hot swappable 1.3 kW DC/DC power modules
• EMC Class B
• UL/CUL, TUV approvals, CE mark and CB report
Applications
• 3G Co-station requirement
Description
The DD 55/1300W-6 KBA Power system combines a
compact modular design with intelligent power features
and state-of-the-art technology. The DD 55/1300W-6 KBA
is capable of providing power up to 7.8 kW. It contains up
to 6 converters DD 55 V - 1300 W - A, as well as different
distribution units with configurable elements for DC.
Output
Voltage, nominal 55 Vdc ,fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8 V
Maximum power 7800 W, max.
Current limit 138 A ± 5%
Load sharing < ± 5%
Options
Aux. Breaker Module 20A
Features
• 20 - 31 Vdc input; at 7.8 kW / 55Vdc output
• High Efficiency 88%
• 8U high in 19" and ETSI rack standard format
• Hot swappable 1.3 kW DC/DC power modules
• UL/CUL, TUV approvals, CE mark and CB report
Applications
• 3G Co-station requirement
Description
The DD 55/1300W-6 KDA01 Power system combines a
compact modular design with intelligent power features
and state-of-the-art technology. The DD 55/1300W-6
KDA01 is capable of providing power up to 7.8 kW. It
contains up to 6 converters DD 55 V - 1300 W - A, as well
as different distribution units with configurable elements
for DC.
Input
DC connection Single/Multi-Feeder(s)
Voltage range 20 ... 31 Vdc
Current maximum 6 x 75 A
EMI, conducted FCC Part 14,
Compliant with EN 55022, class A
DC terminal Screw terminal
DC switch None
Output
Voltage, nominal 55 Vdc ,fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8 V
Maximum power 7800 W, max.
Current limit 138 A ± 5%
Load sharing < ± 5%
Options
PDU Box 10 ... 100 A, 16 positions
400 A maximum
Mechanics
Construction Shelf
Width, overall 18.3” / 465 mm
Depth, overall 14.3” / 365 mm
Height, overall 13.6” / 347 mm
Weight, system (empty) 35.6 lb / 16 kg
Weight, converter 6.67 lb / 3 kg per converter
Environment
Operating temperature - 5 ... + 50 °C
Relative humidity 95 % max, non condensing
Altitude - 500 ~ 10000 feet
Features
• 20 – 31 Vdc input; at 7.8 kW / 55 Vdc output
• High Efficiency 88%
• 4U high in 19" and ETSI rack standard format
• Hot swappable 1.3 kW DC/DC power modules
• EMC Class B
• UL/CUL, TUV approvals, CE mark and CB report
Applications
• 3G Co-station requirement
Description
The DD 55/1300-6 KDA06 Power system combines a
compact modular design with intelligent power features
and state-of-the-art technology. The DD 55/1300-6 KDA06
is capable of providing power up to 7.8 kW. It contains up
to 6 converters DD 55 V - 1300 W - A, as well as different
distribution units with configurable elements for DC.
Input
DC connection Multi-Feeders
Voltage range 20 ... 31 Vdc
Current maximum 6 x 75 A
EMI, conducted FCC Part 22,
Compliant with EN 55022, class B
Mains terminal Screw terminal
Main switch None
Output
Voltage, nominal 55 Vdc ,fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8 V
Maximum power 7800 W, max.
Current limit 138 A ± 5%
Load sharing < ± 5%
Options
Aux. Breaker Module 20A
Mechanics
Construction Shelf
Width, overall 18.3” / 465 mm
Depth, overall 14.3” / 365 mm
Height, overall 6.9” / 176 mm
Weight, system (empty) 8.9 lb / 4 kg
Weight, converter 6.67 lb / 3 kg per converter
Environment
Operating temperature - 5 ... + 50 °C
Relative humidity 95 % max, non condensing
Altitude - 500 ~ 10000 feet
Features
• High efficiency (88 %)
• Compact (153 VA/l) and light (6 kg)
• All connectors on front panel
• Fan cooled with air flow monitoring
• Universal input for 48 V and 60 V systems
• Overload capability and protections
• Wide cosϕ range
• Outstanding dynamic performance
• Parallel operation up to 15 inverter modules
• Operating temperature range up to 60°C
Applications
• Indoor and outdoor
• Small to medium AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom
Description
The inverter FI 48 / 230 V - 1000 VA is a single phase, fan-cooled inverter. It converts all direct
voltages from 48 and 60 V battery systems to an uninterruptible, stabilised AC voltage of 230 V / 50
Hz. The outstanding dynamic performance matches the supply requirements for state-of-the-art
telecom equipment. This performance as well as the advanced technology are the key factors of
the success of this inverter and it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup and static switch products.
The typical applications for this inverter are both in indoor and outdoor environments, which is a
perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The inverter meets the requirements set by the telecommunications standards.
Input Mechanics
Voltage range 40 ... 72 Vdc Width, overall 70 mm
Current maximum (60s) 26 Adc Depth, overall 350 mm
Current maximum (3s) 47 Adc Height, body 266 mm
EMI, conducted EN 55 022, class B Height, front panel 311 mm
Input connector D SUB, front side Weight 6 kg
Input protection External protection 32 A
Input switch None Environment
Ambient temperature 0 ... + 60 °C
Output Red. peak current limit + 50 ... + 60 °C
Voltage, nominal 230 Vrms ± 1% (1/2 load) Relative humidity 95 % max, non cond.
Frequency, nominal 50 Hz ± 0.05 Hz
THD, linear load < 1% Accessories
Voltage error, static ± 2.5 % INVBUSD P/N: D0005980
Current, nominal 4.4 Arms
Peak current limit 12.2 Apeak Static switch products
Crest factor, maximum 2.8 SSW 230 V – 6 kVA P/N: D0006119
Power, nominal 1000 VA / 800 W SSW 230 V – 20 kVA P/N: D0100400
Power, maximum (60s) 1100 VA / 880 W
Power, maximum (3s) 2000 VA / 1600 W
cos ϕ, range 0 .. 1 ind. and cap.
EMI, conducted EN 55 022, class B
Output connector 3 pole (L+N+PE), front
Output protection Internal fuse 6.3 A (L)
Internal relay (L+N)
Output characteristic:
Pout
1600 W
880 W
800 W
3s 60 s
Features
• High efficiency (88 %)
• Compact (238 VA/l) and light (12 kg)
• All connectors on front panel
• Fan cooled with air flow monitoring
• Universal input for 48 V and 60 V systems
• Overload capability and protections
• Wide cosϕ range
• Outstanding dynamic performance
• Parallel operation up to 15 inverter modules
• Operating temperature range up to 55°C
Applications
• Indoor and outdoor
• Medium to large AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom
Description
The inverter FI 48 / 230 V - 3000 VA is a single phase, fan-cooled inverter. It converts all direct
voltages from 48 and 60 V battery systems to an uninterruptible, stabilised AC voltage of 230 V / 50
Hz. The outstanding dynamic performance matches the supply requirements for state-of-the-art
telecom equipment. This performance as well as the advanced technology are the key factors of
the success of this inverter and it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup and static switch products.
The typical applications for this inverter are both in indoor and outdoor environments, which is a
perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The inverter meets the requirements set by the telecommunications standards.
Input Mechanics
Voltage range 40 ... 72 Vdc Width, overall 135 mm
Current maximum (60s) 78 Adc Depth, overall 385 mm
Current maximum (3s) 125 Adc Height, body 266 mm
EMI, conducted EN 55 022, class B Height, front panel 311 mm
Input connector D SUB, front side Weight 12 kg
Input protection Ext. fuse / MCB 80 A
Input switch None Environment
Ambient temperature 0 ... + 55 °C
Output Red. peak current limit + 50 ... + 55 °C
Voltage, nominal 230 Vrms ± 1% (1/2 load) Relative humidity 95 % max, non cond.
Frequency, nominal 50 Hz ± 0.05 Hz
THD, linear load < 1% Accessories
Voltage error, static ± 2.5 % INVBUSD P/N: D0005980
Current, nominal 13.3 Arms
Peak current limit 36.6 Apeak Static switch products
Crest factor, maximum 2.8 SSW 230 V – 6 kVA P/N: D0006119
Power, nominal 3000 VA / 2400 W SSW 230 V – 20 kVA P/N: D0100400
Power, maximum (60s) 3300 VA / 2640 W
Power, maximum (3s) 6000 VA / 4800 W
cos ϕ, range 0 .. 1 ind. and cap.
EMI, conducted EN 55 022, class B
Output connector 3 pole (L+N+PE), front
Output protection Internal fuses 20 A (L+N)
Internal relay (L only)
Output characteristic:
Pout
4800 W
2640 W
2400 W
3s 60 s
Features
• Standard 19”, 23”and 25” rack
• 1 kVA/800 W, 2 kVA/1600 W
• Selectable 208/220/230/240 V system output
• High efficiency
• Pure sine wave output
• Compact, lightweight modular design
• Bypass function
• RS-232 communication
• User friendly LED and LCD display
Applications
• Indoor and outdoor
• Telecom, wireless, datacom
Description
The inverter ESI 48 / 230 V inverters are single phase, fan-cooled inverters. They convert all direct voltages from 48
V battery systems to an uninterruptible, stabilized AC voltage. The outstanding dynamic performance matches the
supply requirements for state-of-the-art telecom equipment. This performance as well as the advanced technology
is the key factors of the success of this inverter and it offers a cost effective and reliable solution.
The typical applications for this inverter are both in indoor and outdoor environments, which is a perfect solution for
wireless base stations, core network components, telecommunications networks and data networks.
Leaflet_esi48_230_1000_2000va/rev. 1.0/01.10.2003/LChen
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314;http://www.deltaww.com
Back to
Subindex
Output
Output voltage 208 / 220 / 230 / 240 Vrms
Voltage regulation <±2%
Frequency 50 / 60 Hz ± 0.2 Hz
THD 3 %: 100% linear load
5 %: 100% SPS load
Current, nominal 5 Arms (1k VA)
10 Arms (2k VA)
Crest factor 3:1
Power, nominal 1000 VA / 800 W
2000 VA / 1600 W
Receptacles IEC-320 x 4
Overload protection:
Pout [VA]
1500
1490
1250
1000
t [s]
1 30 180
Leaflet_esi48_230_1000_2000va/rev. 1.0/01.10.2003/LChen
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314;http://www.deltaww.com
Back to
Subindex
Features
• 230 Vrms / 50 Hz / 6000 VA single phase
• ON LINE or OFF LINE mode selection
• High performance AC line quality monitoring
• Quick detection of AC faults
• Configurable switching criteria
• Load transfer of up to 6 kVA
• Synchronisation of the Delta inverter group
• Convection cooled
• Compact and light
• Power connectors on the rear
Applications
• Indoor and outdoor container
• Small to medium AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom
Description
The static switch SSW 230 V - 6 KVA is a microcontroller driven state of the art switch between the AC
mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a
mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A
communication and synchronisation bus is responsible for the system performance and the Delta
inverters are synchronised to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE mode can be realised in combination with
Delta inverters and DC power systems with battery backup.
The typical applications for this static switch are both in indoor and outdoor containers, which is a
perfect solution for UPS, wireless base stations, core network components, telecommunications
networks and data networks.
The static switch meets the requirements set by the telecommunications standards.
Product versions:
Static switch SSW 230 V - 20 kVA
Features
• 230 Vrms / 50 Hz / 20 kVA single phase
• ON LINE or OFF LINE mode selection
• High performance AC line quality monitoring
• Quick detection of AC faults
• Configurable switching criteria
• Load transfer of up to 20 kVA
• Synchronisation of the Delta inverter group
• Convection cooled
• Compact and light
• Power connectors on the rear
Applications
• Indoor and outdoor container
• Medium to large AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom
Description
Static switch SSW 230 V - 20 kVA is a microcontroller driven state of the art switch between the AC
mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a
mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A
communication and synchronisation bus is responsible for the system performance and the Delta
inverters are synchronised to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE mode can be realised in combination with
Delta inverters and DC power systems with battery backup.
The typical applications for this static switch are both in indoor and outdoor containers, which is a
perfect solution for UPS, wireless base stations, core network components, telecommunications
networks and data networks.
The static switch meets the requirements set by the telecommunications standards.
Product versions:
Static switch SSW 230 V - 6 kVA
Energy Systems
Features
• Complete 1 kVA power supply system
• Fan cooled inverter FI 48 / 230 V – 1000 VA
• Sinusoidal output voltage with low THD
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 130 x 485 x 395 mm
(19'', 3 U)
Applications
• Stand alone inverter system
• Indoor and outdoor container
• Telecom, wireless, datacom
Description
The AMS 230/1000-1 19’’ is a single phase, fan-cooled, stand alone inverter system. The stable
construction is based on a sheet metal design with one FI 48 / 230 V – 1000 VA inverter and DC-
and AC-distribution and provides an easy installation into 19‘‘ standard cabinets. The outstanding
dynamic performance matches the supply requirements for state-of-the-art telecom equipment. This
feature, as well as the advanced technology, are the key factors of the success of this inverter
system and it offers a cost effective and reliable solution.
The typical applications for this inverter system are both in indoor and outdoor containers, which is
a perfect solution for wireless base stations, core network components, telecommunications
networks and data networks. The inverter system meets the requirements set by the
telecommunications standards.
Energy Systems
Load distribution
Residual current
circuit breaker 2 x 16 A/ 30 mA
Service socket 1 (L + N + PE)
Connections 2.5 mm2 (L + N + PE)
Energy Systems
Features
• Complete 3 kVA power supply system
with static switch
• Manual bypass switch
• Sinusoidal output voltage with low THD
• Fan cooled inverters FI 48 / 230 V – 1000 VA
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 311 x 483 x 430 mm
(19'', 7 U)
Applications
• Modular UPS configurations
• Indoor and outdoor container
• Telecom, wireless, datacom
Description
The AMS 230/1000-3 19’’ is a single phase, fan-cooled inverter system with an integrated static
switch. The stable construction is based on a sheet metal design with a maximum of 3 parallel
connected FI 48 / 230 V – 1000 VA inverters, a static switch and DC- and AC-distribution and
provides an easy installation into 19‘‘ standard cabinets or to a wall. The outstanding dynamic
performance matches the supply requirements for state-of-the-art telecom equipment. This feature,
as well as the advanced technology, are the key factors of the success of this inverter system and
it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup.
The typical applications for this inverter system are both in indoor and outdoor containers, which is
a perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The inverter system meets the requirements set by the telecommunications standards.
Energy Systems
AMS 230/1000-3 19'': Technical specifications
General Configuration
Efficiency ≥ 88% Operating mode On line mode
Losses, max. 400 W Off line mode
Safety IEC/EN 60 950
EMC EN 300 386-2 Load distribution
Cooling Fan cooled inverter Manual bypass 7 position switch
Convection cooled SSW MCB (DPN) 3 pcs / 1 ... 16 A
Connections 2.5 mm2 (L + N + PE)
DC Input
Voltage, nominal 53.5 VDC Mechanics
Voltage range 40 ... 72 VDC Material EN 10142 DX51D +
Maximum current (60s) 3 x 26 ADC Z275MAC
Maximum current (3s) 3 x 47 Apeak Height, overall 311 mm (7U)
Connection plus pole Terminal 35 mm2 Width, overall 483 mm (19'')
Connection minus pole Terminal 35 mm2 Depth, overall 430 mm
Fuse 3 x 32 A (MCB) Weight, system 19 kg
Weight, inverter 3 x 6 kg
AC Input Weight, static switch 3.5 kg
Voltage, nominal 230 Vrms
Frequency, nominal 50 Hz Environment
Power, maximum (60s) 3300 VA Ambient temperature 0 ... + 60 °C
Power, maximum (3s) 6000 VA Red. peak current limit + 50 ... + 60 °C
Connections L + N + PE Relative humidity 95 % max, non cond.
Fuse 16 A (MCB) Protection class IP 20
Energy Systems
Features
• Complete 6 kVA power supply system
with static switch
• Manual bypass switch
• Sinusoidal output voltage with low THD
• Fan cooled inverters FI 48 / 230 V – 1000 VA
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 680 x 600 x 480 mm
Applications
• Modular UPS configurations
• indoor and outdoor container
• Telecom, wireless, datacom
Description
The AMS 230/1000-6 GFE is a single phase, fan-cooled inverter system with an integrated static
switch. The stable construction is based on a sheet metal design. The system can be mounted on
top of the battery cabinet or to the wall.
The outstanding dynamic performance matches the supply requirements for state-of-the-art telecom
equipment. This feature, as well as the advanced technology, are the key factors of the success of
this inverter system and it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup.
The typical applications for this inverter system are in indoor environment, which is a perfect
solution for wireless base stations, core network components, telecommunications networks and
data networks.
The inverter system meets the requirements set by the telecommunications standards.
Energy Systems
AMS 230/1000-6 GFE: Technical specifications
General Output, off line mode
Efficiency ≥ 88% Voltage range ETS 300 132-1
Losses, max. 760 W Frequency range ETS 300 132-1
Safety IEC/EN 60 950 See static switch leaflet SSW 230 V – 6 kVA
EMC EN 300 386-2
Cooling Fan cooled inverter Configuration
Convection cooled SSW Operating mode On line mode
Off line mode
DC Input
Voltage, nominal 53.5 VDC Load distribution
Voltage range 40 ... 72 VDC Manual bypass 7 position switch
Maximum current (60s) 6 x 26 ADC MCB 20 pcs / 1 ... 63 A
Maximum current (3s) 6 x 47 Apeak Connections 2.5 mm2 (L + N + PE)
Connection plus pole Terminal 1 x 70 mm2 /
6x16 mm2 Mechanics
Connection minus pole Terminal 70 mm2 / Material EN 10142 DX51D +
6x16 mm2 Z275MAC
Fuse 6 x 32 A (MCB) Height, overall 680 mm
Width, overall 600 mm
AC Input Depth, overall 480 mm
Voltage, nominal 230 Vrms Weight, system 40 kg
Frequency, nominal 50 Hz Weight, inverter 6 x 6 kg
Power, maximum (60s) 6600 VA Weight, static switch 3.5 kg
Power, maximum (3s) 8000 VA
Connections L + N + PE Environment
Fuse 35 A Ambient temperature 0 ... + 60 °C
Red. peak current limit + 50 ... + 60 °C
Output, on line mode Relative humidity 95 % max, non cond.
Voltage, nominal 230 Vrms ± 1 % Protection class IP 20
Frequency, nominal 50 Hz ± 0.05 Hz
Current, nominal 26.4 Arms User interface
Current, peak limit 73.2 A Signalling LED
Crest factor 2.8 See inverter leaflet FI 48 / 230 V – 1000 VA
Power, nominal 6000 VA / 4800 W See static switch leaflet SSW 230 V – 6 kVA
With redundancy 5000 VA / 4000 W
Power, maximum (60s) 6600 VA / 5280 W Control and monitoring
Power, maximum (3s) 8000 VA / 6400 W Remote alarm Potential free contact
Power factor 0 .. 1 ind. and cap.
THD, at linear load <1%
Energy Systems
Applications
• Modular UPS configurations
• indoor and outdoor container
• Telecom, wireless, datacom
Energy Systems
AMS 230/3000-7 ETS: Technical specifications
General Configuration
Efficiency ≥ 88% Operating mode On line mode
Losses, max. 2640 W Off line mode
Safety IEC/EN 60 950
EMC EN 300 386-2 Load distribution
Cooling Fan cooled inverter Manual bypass 7 position switch
Convection cooled SSW MCB 18 pcs / 2 ... 6 A
Connections 2.5 mm2 (L + N + PE)
DC Input
Voltage, nominal 53.5 VDC Mechanics
Voltage range 40 ... 72 VDC Material EN 10142 DX51D +
Maximum current (60s) 7 x 78 ADC Z275MAC
Maximum current (3s) 7 x 125 Apeak Height, overall 2200 mm
Connection plus pole Terminal 7 x 35 mm2 Width, overall 600 mm
Connection minus pole Terminal 7 x 35 mm2 Depth, overall 600 mm
Fuse 7 x 100 A (MCB) Weight, system 150 kg
Weight, inverter 7 x 12 kg
AC Input Weight, static switch 8.6 kg
Voltage, nominal 230 Vrms
Frequency, nominal 50 Hz Environment
Power, maximum (60s) 22000 VA Ambient temperature 0 ... + 55 °C
Power, maximum (3s) 40000 VA Red. peak current limit + 50 ... + 55 °C
Connections L + N + PE Relative humidity 95 % max, non cond.
Fuse 100 A (MCB) Protection class IP 20
Energy Systems
Applications
• Large inverter system
• Indoor and outdoor container
• Telecom, wireless, datacom
Description
The AMS 230/3000-15 ETS is a single phase, fan-
cooled inverter system. The stable construction is based
on a frame cabinet design. The outstanding dynamic
performance matches the supply requirements for state-
of-the-art telecom equipment. This feature, as well as
the advanced technology, are the key factors of the
success of this inverter system and it offers a cost
effective and reliable solution.
The typical applications for this inverter system are in
indoor container, which is a perfect solution for wireless
base stations, core network components,
telecommunications networks and data networks.
The inverter system meets the requirements set by the
telecommunications standards.
Energy Systems