PowerTest User Manual V2.3
PowerTest User Manual V2.3
PowerTest
Concept
VERSION: Concept-AE-2.30
DATE: JUNE 2017
This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of this manual
please contact PONOVO POWER CO., LTD in advance.
1
PowerTest Concept
Reminder
1. Please carefully read the PowerTest Concept before you are going to
operate the relay testing system.
Content
1. PowerTest Installation and Authorization Instruction ...............................................................6
1.1. Install PowerTest ....................................................................................................................6
1.2. Install the authorization files .............................................................................................. 12
2. Main interface .............................................................................................................................. 14
2.1. Test Modules composition ................................................................................................. 15
2.2. Basic ...................................................................................................................................... 16
2.3. Protection.............................................................................................................................. 17
2.4. Advanced .............................................................................................................................. 18
2.5. Special .................................................................................................................................. 19
2.6. IEC61850 (Valid only for PWF) ......................................................................................... 20
2.7. New Modules ....................................................................................................................... 21
3. Setup ............................................................................................................................................ 22
3.1. System & IEC....................................................................................................................... 23
3.1.1 System set ......................................................................................................................... 23
3.1.2 GOOSE Subscription ....................................................................................................... 26
3.1.3 GOOSE Publish ................................................................................................................ 28
3.2. Aux DC .................................................................................................................................. 34
3.3. Binary .................................................................................................................................... 36
3.4. License .................................................................................................................................. 39
4. Test Manager .............................................................................................................................. 40
4.1. Template ............................................................................................................................... 40
4.2. Report.................................................................................................................................... 43
4.3. Test Plan............................................................................................................................... 43
5. Calibration .................................................................................................................................... 44
6. Support ......................................................................................................................................... 45
7. Basic instruction of PowerTest ................................................................................................. 46
7.1. How to select the test module ........................................................................................... 46
7.1.1 Single choice ..................................................................................................................... 46
8. Operations ................................................................................................................................... 90
8.1. Set Voltage Output 300V ................................................................................................... 90
8.2. How to Output 600V............................................................................................................ 92
8.3. How to generate test template .......................................................................................... 95
8.4. How to user-define distance curve ................................................................................... 98
8.5. GPS Instruction.................................................................................................................. 106
8.6. Binary input configuration in QuickTest modules ......................................................... 108
8.7. How to change the IP in the PC ...................................................................................... 110
Download the setup files from the USB Disk or internet and Double click the setup program to install.
Then it pops up the License Agreement. Select the “I accept the agreement” and click “Next” to
continue.
Select the components you desire. It is suggested to install the complete components.
Select the additional tasks such as if create a desktop icon or create a quick launch icon.
Confirm all the installation information and press “Install” to finish it.
If user plans to start the PowerTest immediately, please select “Launch PowerTest” to start.
If users purchase the basic package, it is unnecessary to install the authorization file. The protection,
advanced packages, special package, and new modules could be installed in the following steps.
Extract the zip file and get the file folder, or directly open the sn folder and find the folder, named “Test
Template”.
Copy the file folder to the installation address of PowerTest such as C:\PowerTest
It will pop up the following dialog when users paste the folder.
Run the QuickTest in the basic package online, the below message pops up and please press “Yes”.
The kit information is updated in the program.
Without License
With License
2. Main interface
The start page of PowerTest is the place where we can see the software menu and its selections
showing in the following figure.
We can have access to test modules just from the start page.
The Setup, Test Manager, Calibration and support will be introduced in later chapters.
The association of the above diagram components to the software is shown bellow.
The Test Modules include Basic, Protection, Advanced, Special, IEC61850(PWF) and New Modules.
2.2. Basic
User open the software, the basic interface is displayed. Customer can select one or more modules in
“Test Modules” at the same time and click ‘OK’ button to enter into the test page.
Note: The basic package is default software that the license is included in the installation, it is not
necessary to install the license separately.
Please refer to the PowerTest Basic User Manual for more details.
2.3. Protection
Here users can open the Protection modules after authorized by PONOVO.
Please contact support@relaytest.com to get the authorization license.
Please refer to Chapter 1.2 to get the authorization installation.
The grey part in left is not authorized while the right is authorized. The other modules are the same
except Basic Modules.
Note: Please refer to the PowerTest Protection User Manual for more details.
2.4. Advanced
Note: Please refer to the PowerTest Advanced User Manual for more details.
2.5. Special
Here user can open the Special modules after authorized by PONOVO.
Not all relay tester can be used to do special modules, only the relay tester with equipped hardware are
available with the modules here.
Please contact support@relaytest.com to get the authorization license.
Please refer to Chapter 1.2 to get the authorization installation.
Note: Please refer to the PowerTest Special User Manual for more details.
Here we can open the New modules saved by customer in the place of customers selection. It requires
authorization from PONOVO.
Please contact support@relaytest.com to get the authorization license.
Please refer to Chapter 1.2 to get the authorization installation.
The user manual for each module is independent. The module and its manual can be downloaded
directly from the website, please kindly register on website first via the following
link: http://www.relaytest.com/customer_area.php
3. Setup
Voltage (LL): Here we need to give the nominal secondary voltage of PT which is connected to the
relay voltage input. If we know the L-N voltage we can get the L-L voltage with the following calculation.
V ( LN ) = V ( LL) / 3
Current: Here we need to give the nominal secondary current of CT which is connected to the relay
current input.
Debounce time: This time will be used to filter the bouncing of output contact of the relay under test.
Example:
In above example the relay contact is experiencing bouncing process. The duration of T1-T4 are all
less than 3ms. So these T1-T4 bouncing will not be sensed by our test software. The T5 sensed by the
test software because it’s duration is longer than 3ms.
By default we set 3ms here. Customer needs to make necessary modification if this setting can not
meet the test requirement.
The setting range is 0-25ms
When test is over we will consider this debounce time in our tripping time calculation So that no extra
error will be added to tripping time result.
Model: The PowerTest software can be used by different model of PONOVO relay test sets.
Run QuickTest(4V,3I), the model can be identified automatically, even if you choose incorrect model
here.
Set Com: Here we need to define the communication port of the relay test set. By default Ethernet will
be set here.
Set Type: All of PONOVO kits output analog except PWF serial digital relay testers.
PWF series digital relay tester only outputs digital signals.
Note: GOOSE Subscription and publish are optional, and should be ordered separately.
The tester has to subscribe GOOSE information when it receives the tested relays’ GOOSE signal. The
GOOSE can subscribe some information under the MAC address.
When subscribing, the following specifications have to be set: 1) GOOSE control reference; 2) GOOSE
ID; 3) Application ID;4) MAC Address, or only MAC Address is set to receive GOOSE information.
Map GOOSE data such as the data for tripping signal to the “Binary Input” on the tester. When the
tester receives GOOSE information, the change of information status will be reflected on the related
binary input. The testing software will judge the operation status according to the binary situation.
“Data SB.” means the sequence of the Dataset of the testing data. The number begins with the above
picture GOOSE Subscription includes manual setting and auto setting.
Manual setting
If there are no setting documents of the tested relays, it needs manual setting.
1) Get GOOSE configuration information by capturing tool such as MMS ETHEREAL and input it to
the related configuration frame.
2) Map by GOOSE data and binary: Input “Data SB.”, put the cursor after binary and left-click “Map”.
Automatic setting
Click “lead-in SCL document” in the GOOSE Subscription interface, open the tested relays’ SCL (SCD,
ICD, CID) setting documents. According to the software configuration interface, the substation binary
information can be subscribed, and the GOOSE information (GOOSE control reference, GOOSE ID,
Application ID, MAC Address) is set automatically. The operation is executed according to software
showing in below figures
The tester can also analog other intelligent device to publish GOOSE information. For example, if
it is going to test the reclosing time, the tester has to analog intelligent operation box to publish
GOOSE signal of circuit breaker to meet the reclosing requirements.
GOOSE information will be transmitted in substation by multicasting. When receiving GOOSE
information, it has to confirm if the GOOSE parameter is relative to the subscribed parameter.
The GOOSE parameter and GOOSE Data structures must comply with the configuration of the
relays.
GOOSE Control Reference: Goose Control Block reference (Object Reference), data NR with
maximum 65 bits.
GOOSE ID:The GOOSE Identifier (string), data NR with maximum 65 bits.
APPID:GOOSE application identifier
MAC address: range 01-0C-CD-01-00-00 To 01-0C-CD-01-01-FF
Time Allowed to Live: Unit: millisecond
DatSet: data NR with maximum 65 bits
NdsCom: boolean
Test: Boolean, Specifies the status of the GOOSE test bit (0=False, 1=True = Test Mode )
VLAN—Virtual Local Area Network
VLAN Priority
When the tester connects with switchboard, VLAN and VLAN priority need to set. The
manufacturer has to provide the values.
There are six kinds of editable data in GOOSE publication data: BOOLEAN, Unsigned Integer,
UTCTime, BitString, Float and dual-position remote signal, shown in below table.
The two ways of getting GOOSE parameter and GOOSE Dataset structure:
1) Provided by protection device manufacture or substation.
2) Getting by capturing GOOSE document (These GOOSE message are sent by other intelligent
device. The device may be other protective device or intelligent operation box.)
Automatic setting
In the GOOSE publication interface, click “lead-in SCL document” to open the configuration documents
of tested SCL (SCD, ICD, CID). Select the tested IED according to software indication. The data
system of GOOSE parameter and GOOSE Dataset are completed automatically. The configuration
process is shown in below figures.
Manual setting
Manual setting includes manual setting GOOSE parameter and GOOSE publication data. We take
reclosing time as an example.
In order to get GOOSE configuration parameter and GOOSE Dataset, MMS Ethereal tool can be used
to get GOOSE message sent by intelligent operation box. If the GOOSE interface is electricity interface
such as RJ45, the wiring diagram is the below figure.
The captured GOOSE message is shown in below figure. It clearly shows the GOOSE parameter and
data system (16 BOOLEAN style data).
Data
We take a test as an example (shown in below figure) to indicate. Click “GOOSE publication data” and
click “lead-in”, the GOOSE dataset structure will be displayed in the data edition window and the data is
separated by comma. User can edit publication data at the related position of this window.
Simulate intelligent operation box to send circuit breaker position signal (Suppose the breaker is
closed.)
It is known from the message of intelligent operation box that it sends out 16 BLOOEAN type data, and
the first data is the breaker position signal from the relay user manual (True means that the breaker is
closed. False means it is opened.) Other 15 signals also have specified meaning. To be short, all of
them are set as “False”. See the edited data in below figure.
Note:
The SMV is available only for relay tester PWF.
Please refer to the instruction for output form of SMV in User Manual-IEC61850-EN.
3.2. Aux DC
Here we can set the Auxiliary DC for driving the relay which requires DC power supply.
The auxiliary DC voltage will be generated at the moment we start the test and will remain active
when we change from test module to test module.
We can also set the auxiliary DC in the test page by selecting AuxDC in ‘Settings’ of drop-down menu
Drag the cursor to the setting position and click Set to confirm the setting.
To stop the auxiliary DC output we need to enter into the above setting page and set drag the cursor to
OFF position.
3.3. Binary
Here we can set binary input forms (dry contact or threshold and power level) and voltage.
For relay test set with adjustable threshold we need to configure the binary input characteristic and/or
threshold here.
Potential Free
For potential free contact customer needs to select the potential free box for the binary input to be used.
In that case the setting for threshold will be prohibited.
Threshold
For potential contact customer needs to set the threshold here.
The threshold is the point where potential contact changes from high status to low status or from low
status to high status.
For example, we can define the open status of dry contact as the closed status in the software, or vice
versa.
A/1 means binary close is for logic close.
B/2 means binary open is for logic close.
For potential contact customer can associate its actual status with that to be displayed in the software.
Example: we can define the high status of potential contact as the closed status in the software, or vice
versa.
A/1 means close status at low level.
B/2 means close status at high level.
Suppose the potential contact has a threshold of 90V. Bellow 90V the potential contact is to be
regarded as closed status in the software. When the contact status changes the voltage applied to the
binary input will jump to 220V. We can set any one of the 8 binary inputs. In this example we are going
to set binary input A/1.
Note: We can increase the threshold setting to avoid possible electromagnetic noise at the site. For
example we can set 110V in this example
In the example above the low status voltage is 90V, lower than the threshold setting of 110V. When
potential status changes the voltage will jump to 220V and this status will be regarded as open status in
the software.
The AC signal can be injected in the binary input, but the triggering voltage should be set based on the
peak value.
Example: when the triggered AC voltage is 220V, the required value is 110*1.4142=155.56V. Please
type in trigger voltage 115V.
Considering the error, the triggering voltage is suggested to be decreased by 10% to avoid the
mal-function. For example: in the DC 110V, the injected voltage is 108V that is normal in the protection
system, but in the kits, it does not meet the trigger voltage and not trigger.
Click “Online”
If the high power output is required, please select the high power below.
3.4. License
Example:
Step1: Press “License” in the main interface and select the modules.
4. Test Manager
4.1. Template
Test template is used to test a complete protective relay system where different relay tests are
required.
Click the Templates button in the start page and select the template file from the folder where the
template file is saved. Then we will enter into the test page automatically with test modules containing
in this template. The test parameters and relay settings in the saved template will also be uploaded
here.
In the test page drop-down menu select ‘Template’ and select open. Then we need to select template
file from the place where it’s saved.
If we have save the test report in PowerTest format with the extension of rpt we can also open the
template through opening this report in any module.
rpt format test report can be opened in the test module. At the same time the template information
contained in the report will also be opened.
4.2. Report
5. Calibration
In this part, it is optional. Users can consult with PONOVO for detailed information.
6. Support
Users press “Help” to get related documents and press “User forum” to enter into PONOVO website
seeking online support.
User can select several test items in different “Test Modules”. For example, user can choose test items
both in Basic and Protection simultaneously.
Note: User should choose the test items either authorized or unauthorized by PONOVO.
Only all the modules authorized can be multiple chosen at the same time, vice versa for the
unauthorized modules.
If choosing the unauthorized items, users only can enter into the interface for demonstration, but can’t
make tests. The software will instruct “NOT BEEN AUTHROZIED”.
○
1 E A Drop-Down Menu: Operate and set the program.
○
2
A E A Quick control buttons: Do some quick operations.
○
3
A E A Test Item: Set the test item for each test module.
○
4
A E A Parameters: Press it to set the present test item’s parameters.
○
5
A E A Assessment: Press to edit the present assessment condition.
○
6
A E A Wiring: Press to get the wiring information.
○
7
A E A Characteristic: Press to get the module setting information.
○
8
A E A Report setting: Set the items in report.
○
9
A E A GOOSE Data: Output GOOSE message.
○
10
A E A Group setting: The group settings for ○
4 ~○
A 9 .
E A A E A
○
11
A E A Relay settings: Edit relay settings
○
12
A E A Para.: Set the test parameters excluding relay settings.
○
13
A E A Binary: Set BI disable or enable, and BO open or close.
○
14
A E A Tips: Indicate the software running status.
○
15
A E A View windows: Display parameters according to selected module or item.
○
16
A E A Task list: Display and edit the module number and name.
○
17
A E A Test results: Show the present test module’s result.
○
18
A E A Test status: Show the running status.
○
19
A E A Binary input: Open or close
○
20
A E A Monitor: Show the hardware status
○
21
A E A Control test process
○
22
A E A Binary output: Open or close
Save as Template File (F): Save the present test file into template. It is not available in the module
without authorization.
Save Template File: Update the parameters into the template and save (Not valid)
Check Device List: The testers in the Lan can be checked and founded.
Select Network Card: Valid for the PC with several network cards.
Note: Please carefully change the IP address and clearly label the edited IP in case connection failure.
Please contact support@relaytest.com to get more details how to change the IP address.
.
7.3.3 Report(R)
User Defined Report (P): Concert the report into user-defined format.
Note: This shall only be used within customized templates.
7.3.4 Setting(S)
During the test process we can see the output waveform and output value from this monitoring window.
Recorder(F): This function is used to record the test process after test is over. The binary
input/output status during the test process is also recorded.
In this example we show a ramping process. The current will increase with set step value and step
duration. When relay trips the current will decrease until relay drops.
Note: The recording button will be activated only after test is over.
Recording window
The recording window provides some simple tools to better view the recording display.
The instantaneous, RMS and harmonic values for voltages and currents at the cursor place can be
displayed at the same time.
Note: To view the value display at a cursor position drags the cursor to the position.
The instantaneous, RMS and harmonic values for voltages and current
Through these settings we can set the maximum range for displaying the voltages and currents for
better view.
The time difference between two cursors and also the absolute time for each cursor position are also
being displayed.
T1: the absolute time counted from the start point to the position of cursor 1
T2: the absolute time counted from the start point to the position of cursor 2
dT: the time difference between T1 and T2
The recorded waveform and binary input/output status can be exported to COMTRADE format file.
Move mouse pointer to the waveform display area and right click the mouse button. Then we see the
following menu will appear.
Select Save As Comtrade to export the current waveform and binary input/output status display as
COMTRDE file.
Topics (T): Press to open the Help text to get help information.
About Power Test(A): Show software version and authorization information.
The same as Word Report(W) in chapter 7.3.3. It is not used at this time being.
4 control buttons are provided to switch over among different view windows.
Depending on the module these 4 control buttons may bring different view windows, such as relay
characteristic, vector diagram, wiring, relay settings, test process, etc.
Example: a view window which shows the vector diagram and output settings.
To edit the report template we need to use the bookmarks associated to settings/test parameters in the
software.
Click we can see the bookmarks for the module customer is using.
Note: To know more about the optional report editing tool please contact the manufacture
In QuickTest, there is only one test item, so there is no special area for it.
For all test items/points listed in the table customer can decide which items/points will be tested. Simply
click the items/points in the column of Sel to enable or disable it.
When test is over the status for each tested item/point will be displayed
Message (E)
Click Message the following screen will appear
Here we can edit the wiring information for the selected test items/points. In the message box we can
also edit necessary notice/instructions.
The following is one example.
When this is selected the software will compare the message of this test item/point with that of the last
test item/point. If there is any difference the current popping box will appear before test starts. And test
will start after click the OK button.
With this selection and after the current test is completed a pop-up dialog box will appear. Customer
needs to click the OK button to start the next test.
Note: This facility can be used to manually observe each test item/point
With this selection and when we start test the setting page will pop-up first. And after we click OK button
the test will then start.
Add Test Item (A): Add the same test item as present one.
Delete Test Item (D): Delete the selected item.
Select All(S): Select all the items included in Sel.
Clear(C): Cancel all the selection in Sel.
Select Failed Item (F): Only the failed items are chosen to the Sel.
Select Tested Item (T): All the tested items can be included in Sel.
Select Failed and No-tested Item: The failed test and non-tested items will be chosen to Sel.
Select All Item Cursor(Y): Select all the items before the present item.
7.6. Parameters
In different test ite, the function is different, and the parameter is different too.
In parameters, user can edit the test item accordingly.
In each module, there will be instruction for parameters.
In this part, we only introduce the general part including add, remove test point and clear the results,
etc.
Click ‘Add’ and ‘Remove’ buttons in the parameter setting area to add or delete the test point in a test
item.
Add: Copy the same test point at the cursor position.
Quick Add: Add few test points within the setting range.
Remove: Remove the present test point, but if there is only one test point, it is not allowed to be
removed.
Remove N-1: Remove all the test points except the first one.
Clear: Clear the test results at the present test point.
Clear All: Clear all the test result of all the test points.
If the newly added test item/point may have different parameters, wiring, report setting, or assessment
customer can make setting just in the parameter setting area.
All test items/points share the same group of relay setting values, general parameters, binary input
configuration and relay characteristic.
For each test item/point we can set test parameters in the item parameter setting area.
For each test item/point it has its own test Parameter, Assessment, Wiring and GOOSE Data ect.
Note: The layout and content of parameter setting area may differ from module to module
For test parameters which require setting values we can put in the direct setting values according to our
test requirement.
In the above example the variable RE1 and XE1 represents the relay setting RE1 and XE1.
If RE1 setting is 3 ohm then the expression of 0.95*RE1 is equal 0.95*3=2.85 ohm
Note: For more details about variables please refer to Name for settings and variables
7.7. Assessment
7.8. Wiring
Click “Wiring” button we can view the wiring diagram. The wiring diagram is made based on the
information we put in Message.
7.9. Characteristic
It is used to import, add, delete and edit different characteristic curves. Not all modules has this part.
For different test modules the group setting page may be different.
By select “Setting” button we can view the setting names and their variables.
By select “Para.” button we can view the parameter names and their variables.
By click button we can view the setting/parameter names and their variables at the same time.
Bin
Binary input, Enable or Disable
Out
Binary Output, Open or Close
Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Note: The set binary input configuration will be applicable to all test items/points
7.15. Tips
It shows the test status, vector diagram, and characteristic curve and test parameters.
Note: This edition should be done PONOVO or experienced engineer knowing our template very well.
All Items (L): It is for reserved.
Part Items (I): It is for reserved
Periodic Item(R): It is for reserved
RUN indicator: When it flashes, there is current/ voltage output. When the test stops, it will not flash.
P/NLK indicator: When the pause button on the front panel of relay tester (such as PW636i or PW460)
is pressed, the P/NLK will be green.
7.21. Monitor
When the current output is open or distortion, it will be on, but the
current or voltage output will not be stoped.
When the voltage output is short-circuited or distortion, it will be on. The test will be
alarming and stop voltage/ current output. When the fault is excluded, the output will be
recovered.
When the tester is over hot or voltage short-circuited, it will be on. The current/ voltage
output will be stopped. When the fault is excluded, the output will be recovered.
We can use the follow 4 quick control buttons to control the test process
After test is started one message will pop-up to indicate the current test status
Button is activated
If we press this button we will stop the test and the button will become inactivated.
This button is used in some modules where we use this button to manually switch from one state to the
next one
Note: More detailed information will be provided on the use of this button in modules where this button
is used.
Note: More detailed description on is available in the module where this control button will be
used
8. Operations
8.1. Set Voltage Output 300V
Step 6: Set VA VB output same amplitude and frequency and Opposite angle.
Step 1
Select test modules to be included in the test template from the start page and enter into the test page.
In our example here we are going to generate a test template which contains ‘Ramp’ and
‘Distance(R,X)’ modules.
Step 2
In the ‘Task List’ area of test page right click the mouse button and we see the pop-up selection page
Step 3
Click the ‘Disable multi-select’ option to make it active. After this operation we will be able to select
more test modules at the same time.
Step 4
Select the two modules
Step 5
We can also change the module name. To do it we can right click the mouse button and select
‘Rename’. Then we see the pop-up dialog box.
Step 6
Enter the new name for the module.
Step 7
Make relay settings for these two modules accordingly.
Step 8
In the ‘Task List’ area right click the mouse button and select ‘Save as Template File’ and we will be
asked to select the folder where we want to save the template.
Step 9
Select the folder we want to save the template and give the name for the template.
It is possible to set all zones either with quadrilateral (polygon) characteristics, or with mho circles.
Here are some examples for further understanding.
Zx Arg1
D C
Arg4
A Arg2 Zr Arg1
R
Arg3
B
Settings:
Zr=4.8 Ohms
Zx =5.6 Ohms
Arg1=78 degree: Line Angle
Arg2=115 degree
Arg3= -15 degree
Arg4= -3 degree
There are six lines, line 1-6, and four characteristic points A(0,0); B(4.8,0); C(5.6/(tg(78/180*3.1415)),
5.6); D(0,5.6)
Zone
5 zones are available for choice.
Fault loop
Earth fault/ phase-phase fault/ All
Earth fault
Display curve only in earth fault
Phase-phase fault
Display curve only in phase-phase fault
Both earth fault and phase-phase fault are applicable for the settings with different values.
All
The settings for earth fault and phase-phase fault are the same.
Label
Type in remark information
Add
Add curve
Delete
Delete curve
Edit
Edit the curve
Import
Import RIO file
Export
Export RIO file
NR
The serial number of curve
Content
Including axis, angle, etc
Predefined
Curve type, line, arc, circle, len
Line shape
It is activated in line, arc curve type, four shapes available
Line
The characteristic points crossing line and the angle
Two ways to get the characteristic points
Cartesian(R-X) or Polar (Z-phi)
Arc
The characteristic points crossing Arc and radius, start angle, ending angle, Arc direction (clockwise or
anti-clockwise)
Two ways to get the characteristic points
Cartesian(R-X) or Polar (Z-phi)
Circle
Draw MHO, including forward impedance setting, reverse impedance setting and MHO angle.
Lens
Including forward impedance setting, reverse impedance setting and lens width, etc.
Step 1
Add 6 lines
Step 2
Edit line 1, cross A (0,0), angle: Arg3=-15 degree
Step 3
Edit line 2, cross B (4.8, 0); Angle: -90
Step 4
Edit line 3, cross B(4.8, 0), Angle: Arg1= 78 degree
Line Angle
Arg1
Z REV
GPS: Test state will be switched to the next one if GPS pulse signal is received. GPS signal trigger
condition means the end of the current state (after output 50ms) and begin of next state.
GPS is usually used in the ends of line differential protection to make online test. It requires the current
as 0 before synchronization output. If the GPS is set as the first state (before fault), there should not be
current output. If the first state has current output, it will make the first state protection trip since the
outputs of both sides is not synchronized.
Example:
The line differential protection is made by simulating phase A fault in State Sequence. The following is
the parameter setting.
It is waveform output.
From the waveform, there is a 50mS state waveform output after receiving GPS signals. The waveform
is synchronized at both ends at this time.
The binary inputs will be used to sense the relay operation during the test.
Properly configure the binary input is important for successful relay test.
The selection of binary input type, potential free or potential as while as the setting of threshold for
potential contact, can be found on 3.3
In the test module what we do is to configure the logic combination of binary input and decide which
one will be used to sense the relay operation.
We can also modify these names according to our own wish in the column of Display Name
For the selected binary inputs we can configure them as OR logic or AND logic.
OR logic
Indicating OR logic. When any of the selected binary input meets with the trigger condition the current
test process will be terminated.
In above example binary 1 and 2 are defined as OR logic. Any trigger operation of binary 1 or 2 will
terminate the current test process.
AND logic
Indicating AND logic. When all of the selected binary input meets with the trigger condition the current
test process will be terminated.
In above example binary 1 and 2 are defined as AND logic. Only when both of them meet the trigger
condition then the current test process will be terminated.
Trigger on Overload
Overcurrent for switch test
Then write the IP adress in this format: 192.168.1.xx , where xx is the number that you want,
except 133 because that is the number that PONOVO’s relay test set have by default.
PowerTest
Basic
VERSION: Basic-AE-2.30
DATE : JUNE 2017
This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of this manual
please contact PONOVO POWER CO., LTD in advance.
1
PowerTest Basic
Reminder
1. Please carefully read the PowerTest Concept before you read the
PowerTest Basic.
2
PONOVO POWER CO., LTD
PowerTest Basic
Content
1. General............................................................................................................................................6
1.1. Set group parameters ..........................................................................................................7
1.2. Set test item point/ item parameters .................................................................................8
1.3. Set binary ..............................................................................................................................9
1.4. Assessment........................................................................................................................ 10
1.5. Set wiring ............................................................................................................................ 11
1.6. GOOSE Data ..................................................................................................................... 12
1.7. Enter Results ..................................................................................................................... 13
2. QuickTest (4V, 3I)....................................................................................................................... 15
2.1. Manual test mode.............................................................................................................. 15
2.2. Test in manual mode ........................................................................................................ 19
2.3. Time test with Lock button ............................................................................................... 20
2.4. Auto test mode .................................................................................................................. 21
3. QuickTest(4V or 6V,6I) .............................................................................................................. 22
4. QuickTest (VL-L, 3I) ................................................................................................................... 24
5. QuickTest (Sequence) ............................................................................................................... 26
6. QuickTest (Power) ...................................................................................................................... 28
7. QuickTest (Z, I Const) ................................................................................................................ 30
8. QuickTest (Z, V Const) .............................................................................................................. 33
9. QuickTest (Z, Zs Const) ............................................................................................................ 34
10. Time ......................................................................................................................................... 35
10.1. Set group setting ............................................................................................................... 36
10.2. Set group parameters ....................................................................................................... 37
10.3. Set group binary ................................................................................................................ 38
10.4. Set test point/item parameters ........................................................................................ 39
10.5. Set characteristic definition .............................................................................................. 41
10.6. Set wiring ............................................................................................................................ 41
10.7. GOOSE Data ..................................................................................................................... 42
3
PONOVO POWER CO., LTD
PowerTest Basic
5
PONOVO POWER CO., LTD
PowerTest Basic
1. General
QuickTest provides several sub-modules for quick and fast test purpose.
QuickTest(VL-L,3I)
Provides L-L voltage, zero sequence voltage and 3 current sources
QuickTest(Sequence)
Provides voltage and current in sequence components mode
QuickTest(Power)
Provides the way to control three phase powers
QuickTest(Z,I Const)
Quickly test distance relay with constant current
QuickTest(Z,V Const)
Quickly test distance relay with constant voltage
QuickTest(Z,Zs Const)
Quickly test distance relay with constant system impedance
All the above modules have the same test interface, except set test point/ item parameters, and
operation process; we will introduce the general interface and operation in this part.
6
PONOVO POWER CO., LTD
PowerTest Basic
In all above mentioned modules we can select to control the output manually or automatically.
Click “Para.” button and we see the following screen.
If we change the test mode from from-to to from-to-from then we may have different ways to control
the selected variable automatically.
from-to
Check trip only.
from-to-from
Check trip and drop-off.
7
PONOVO POWER CO., LTD
PowerTest Basic
8
PONOVO POWER CO., LTD
PowerTest Basic
Input Binary
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Trigger on Overload
Overcurrent for switch test
Note:
In QuickTest (4V or 6V/ 6I), there is not pre-fault state, so the Pre-fault output binary is not available.
Either is the trigger on overload.
9
PONOVO POWER CO., LTD
PowerTest Basic
1.4. Assessment
It is reserved.
It is not valid in QuickTest (4V or 6V, 6I).
10
PONOVO POWER CO., LTD
PowerTest Basic
It is reserved.
11
PONOVO POWER CO., LTD
PowerTest Basic
12
PONOVO POWER CO., LTD
PowerTest Basic
13
PONOVO POWER CO., LTD
PowerTest Basic
Fill in the test name and test result and click “OK” to confirm the operation.
In this way we can get the test report with the test name and results we have entered.
14
PONOVO POWER CO., LTD
PowerTest Basic
In this module we have 4 voltage and 3 current sources available for test purpose.
Current sources are internally configured as 3 phase output mode.
In this mode we can manually control all sources to change with set steps.
We can control the amplitude, phase angle and frequency of voltage and current sources.
Note: In case Vdc is not used to supply auxiliary DC voltage to drive relay, we can also control it here.
15
PONOVO POWER CO., LTD
PowerTest Basic
Quantity (Channel)
Va, b, c, z
Control Va, Vb, Vc, Vz independent
Va,Vb
Control Va,Vb at same time
Vb,Vc
Control Vb,Vc at same time
Vc,Va
Control Vc,Va at same time
Va,Vb,Vc
Control Va,Vb,Vc at same time
Ia, b, c
Control Ia Ib, Ic independent
Ia,Ib
Control Ia,Ib at same time
Ib,Ic
Control Ib,Ic at same time
Ic,Ia
Control Ic,Ia at same time
Ia,Ib,Ic
Control Ia,Ib,Ic at same time
Vdc
Control auxiliary DC
Ia+Ib
Control Ia+Ib (parallel output)
Ia+Ib+Ic
Control Ia+Ib+Ic (parallel output)
Quantity
For each selected variable we can select the following quantities to control.
Amplitude
Control the amplitude
Angle
Control the phase angle
16
PONOVO POWER CO., LTD
PowerTest Basic
Frequency
Control the frequency (not valid for Vdc)
Step
Set the step variable
Time
The step time in auto mode
From
The start value in Auto mode, the start point from where the variable will ramp
To
The ending value in Auto mode, If relay does not trip during the ramping process the test will terminate
at this point
Note: the ‘from’ value must be set in the way that relay will not trip at this setting. For some type of
relay, such as low voltage relay, the ‘from’ setting is larger than ‘to’ setting
Quantity (No. 2)
Setup (No. 2)
nd
In Manual mode, set the 2 groups of variables.
st
The parameters have the same settings in the 1 groups of variables.
Note:
In manual mode, there are two groups of variables.
st
In the 1 groups of variables, the settings should be controlled by Up/Down on keyboard or
in the interface.
nd
In the 2 groups of variables, the settings should be controlled by Pg Up/ Pg Down on the keyboard.
Switching
It is used to switch the state between Prefault and fault in Auto mode and Prefault selected.
Up PreFault state
Ext. time
When this time is set here the output time will be extended even after relay trips.
Note: This time setting is normally used in the test application where we need to consider the circuit
breaker mechanism operation time.
Prefault Time
17
PONOVO POWER CO., LTD
PowerTest Basic
Auto
Auto mode
Manual mode
Prefault
No Prefault state in Auto mode
Prefault state in Auto mode
DC
Output current/ voltage frequency in AC
Output current/ voltage in DC
Lock button
This button is designed to test the relay tripping time in manual mode.
18
PONOVO POWER CO., LTD
PowerTest Basic
st nd
In this mode we can manually control all sources selected (the 1 and 2 groups) to change with set
step.
st
The 1 group: control by Up/Down on keyboard or in the interface.
nd
The 2 group: control by Pg Up/Pg Down in the keyboard.
Note:
1. In manual mode, all the tests should be controlled manually including test start and stop.
2. After the test is done, the engineer should check the relay trip or not. If there is binary input, the
PowerTest binary input will give tips, but not stop.
19
PONOVO POWER CO., LTD
PowerTest Basic
Example: test the relay tripping time with Lock button in manual mode
Step 1:
Make wiring, connecting voltage and current outputs to relay and connect relay tripping output to binary
input 1
Step 2:
Set normal voltages and currents for a health system
Step 3:
Step 4:
Step 5:
Modify voltages and currents to faulty status.
Step 6:
At the same time the internal timer will start. When relay trips the timer will stop and the tripping time will
be displayed.
20
PONOVO POWER CO., LTD
PowerTest Basic
In this mode we can select different way to control the output automatically in group para. .
from-to
Test pickup.
from-to-from
Test pickup and drop-off.
In auto test mode some more test parameters will be allowed to set
Before the testing, we have to set the quantity, step, time, from, to, and it will automatically increase/
decrease the variables in the process.
After testing, the settings and time will be recorded and saved.
21
PONOVO POWER CO., LTD
PowerTest Basic
3. QuickTest(4V or 6V,6I)
In this module we have 4 voltage or 6 voltage and 6 current sources available for test purpose.
The way to set those test parameters is exactly the same as QuickTest (4V, 3I) except the following
points.
22
PONOVO POWER CO., LTD
PowerTest Basic
Va, b, c, z
Control Va, Vb, Vc, Vz independent
Va,Vb,Vc
Control Va,Vb,Vc at same time
Va,Vb
Control Va,Vb at same time
Vb,Vc
Control Vb,Vc at same time
Vc,Va
Control Vc,Va at same time
Va’, b’, c;
Control Va’, Vb’, Vc independent
Ia, b, c
Control Ia Ib, Ic independent
Ia,Ib,Ic
Control Ia,Ib,Ic at same time
Ia’, b’, c’
Control Ia’, Ib’, Ic’ independent
Ia’,Ib’,Ic’
Control Ia’,Ib’,Ic’ at same time
Frequency
Control frequency
23
PONOVO POWER CO., LTD
PowerTest Basic
In this module we have the facility to control the line-line voltage, 3V0 (zero sequence voltage) and 3
currents (in 3 current output mode).
The way to set those test parameters is exactly the same as QuickTest (4V, 3I) except the following
points.
Vab
Control Vab
3V0
Control 3V0
Ia, Ib, Ic
Control Ia, Ib, Ic independent
Ia,Ib
Control Ia,Ib at same time
Ib,Ic
Control Ib,Ic at same time
24
PONOVO POWER CO., LTD
PowerTest Basic
Ic,Ia
Control Ic,Ia at same time
Ia,Ib,Ic
Control Ia,Ib,Ic at same time
Vdc
Control auxiliary DC
25
PONOVO POWER CO., LTD
PowerTest Basic
5. QuickTest (Sequence)
In this module we have the facility to control the sequence components for voltage and current.
The way to set those test parameters is exactly the same as QuickTest (4V, 3I) except the following
points.
V1
Control positive sequence component of voltage
V2
Control negative sequence component of voltage
V0
Control zero sequence component of voltage
I1
Control positive sequence component of current
I2
Control negative sequence component of current
I0
26
PONOVO POWER CO., LTD
PowerTest Basic
Vdc
Control auxiliary DC
27
PONOVO POWER CO., LTD
PowerTest Basic
6. QuickTest (Power)
The way to set those test parameters is exactly the same as QuickTest (4V, 3I) except the following
points.
Sa (Pa,Qa)
Control phase A output power
Sb (Pb,Qb)
Control phase B output power
Sc (Pc,Qc)
Control phase C output power
S (P, Q)
Control three phase output power
28
PONOVO POWER CO., LTD
PowerTest Basic
Pa
Control active power for phase A
Pb
Control active power for phase B
Pc
Control active power for phase C
Pa, Pb, Pc
Control three phase active power
Qa
Control reactive power for phase A
Qb
Control reactive power for phase B
Qc
Control reactive power for phase C
Qa, Qb, Qc
Control three phase reactive power
29
PONOVO POWER CO., LTD
PowerTest Basic
This module provides a simple way to test impedance relay with constant current.
In this mode we can manually or automatic search the relay operation value.
Fault Type
Earth fault: A-E, B-E, C-E, A-B-E, B-C-E, C-A-E
Earth fault: A-B, B-C, C-A, A-B-C
Impedance type
Z (Z-phi)
Set impedance in Z-Phi way
R-X
Set impedance in R-X way
|Z|
The impedance and angle valid in Z-Phi way
R-X
Resistance impedance valid in R-X way
Current
Fault current
Quantity (variables)
30
PONOVO POWER CO., LTD
PowerTest Basic
Z: Impedance
R
Resistance
X
Reactance
If
Fault current (can be used to test Accurate Working Current of electromagnetic type impedance relay)
Amplitude
Can be choose in all the quantity variables
Angle
Valid only in Z
Prefault Time
The prefault time in auto mode
Step
Set the step variable
Time
The step time in auto mode
From
The start value in Auto mode, the start point from where the variable will ramp
To
The ending value in Auto mode, If relay does not trip during the ramping process the test will terminate
at this point
Note: the ‘from’ value must be set in the way that relay will not trip at this setting. For some type of
relay, such as low voltage relay, the ‘from’ setting is larger than ‘to’ setting
Ext. time
The extension time after relay trip to continue next state
Earth Compensation
There are three types of KE mode available and we need to select the one according to the relay under
test.
∣K0∣, Phi(K0)
KR, KX
∣Z0/Z1∣, Phi(Z0/Z1)
Prefault
No Prefault state in Auto mode
Prefault state in Auto mode
31
PONOVO POWER CO., LTD
PowerTest Basic
Auto
Auto mode
Manual mode
32
PONOVO POWER CO., LTD
PowerTest Basic
This module provides a simple way to test impedance relay with constant voltage
The way to set those test parameters is exactly the same as QuickTest (Z, I const) except the
following points.
Vf
Fault type
Here we set the voltage to be injected into the relay under test. And this voltage will remain constant
during the test process.
Quantity
Here we select the quantity and the variable to change.
33
PONOVO POWER CO., LTD
PowerTest Basic
This module provides a simple way to test impedance relay with constant system impedance
The way to set those test parameters is exactly the same as QuickTest (Z,I const) except the following
points.
Zs
Power System impedance
Here we set the system impedance which will remain constant during the test process.
34
PONOVO POWER CO., LTD
PowerTest Basic
10. Time
This module is used to test trip time of AC current or voltage type time relay.
35
PONOVO POWER CO., LTD
PowerTest Basic
Tset
Trip time setting
The buttons above are reserved for R&D development, not for testing purpose.
36
PONOVO POWER CO., LTD
PowerTest Basic
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
Tprefault
During this time no voltage or current is generated
Fault
Here we can select the fault to be simulated for the test.
A-E: A-E fault
B-E: B-E fault,
C-E: C-E fault
A-B: A-B fault
B-C: B-C fault
C-A: C-A fault
A-B-C: A-B-C fault
3I0: use 3I0 as the quantity to change
I2: use I2 as the quantity to change
The three buttons are reserved for R&D development, not for testing purpose.
37
PONOVO POWER CO., LTD
PowerTest Basic
Bin
Binary input, Enable or Disable
Out
Binary Output, Open or Close
Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
38
PONOVO POWER CO., LTD
PowerTest Basic
Name
Edit the test point/ item/ item name here.
Voltage
Prefault voltage
Current
Prefault current (load current)
Angle
Angle between voltage and current
Freq.
The power system frequency
Current
Current for the current test point/ item expressed in times of rated current
Anlge
Angle between voltage and current
Freq.
39
PONOVO POWER CO., LTD
PowerTest Basic
Fault type
Display the fault type we have selected in group parameter page
Add
Copy the same test point/item at the cursor position.
Quick Add
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
40
PONOVO POWER CO., LTD
PowerTest Basic
41
PONOVO POWER CO., LTD
PowerTest Basic
42
PONOVO POWER CO., LTD
PowerTest Basic
This module is used to define a series of test states for special test applications.
With this module we can generate a series of states to test the tripping time
43
PONOVO POWER CO., LTD
PowerTest Basic
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
DC offset
DC offset can be added to the output signal if we select Yes here. The magnitude of DC offset is
defined by
t
−
I dc =
− I max × e τ
Imax: related to the current value at the end of last test state
τ Time constant
tou
Refer to time constant
Ref. State
Here we define the binary input trigger condition for the current test state.
No 1: we compare the current binary input status with the one of the first test state. The trigger will
happen if they have different status.
priev: we compare the current binary input status with the one of the last test state. The trigger will
happen if they have different status.
The three buttons are reserved for R&D development, not for testing purpose.
44
PONOVO POWER CO., LTD
PowerTest Basic
Name
Edit the test item name here.
Frequency
The power system frequency
Trigger con.
There are six trigger modes can be selected here.
Time
Test state will last for the time defined here and when this time is over the current test state will be
switched to the next one.
Bin. Input
Fault status comes immediately after binary input H senses the trigger signal
Manual
45
PONOVO POWER CO., LTD
PowerTest Basic
Test state will be switched to the next one if we press button or F3 directly.
GPS
Fault status comes immediately after GPS pulse signal is received.
Note: GPS controlled test is available with optional PGPS-2 GPS Synchronization Device. Please
contact the manufacture for more information
Low Value
It is valid in dV/dt df/dt and Ramp .
When the variable reaches the trigger value, it switches into next state.
Duration
The duration time at the present state
Binary inputs
Binary A-L, logic OR/ AND
Binary outputs
Binary output 1-8
Overturn
It overturns in the same state.
Hold time
The duration time for binary output
Ext.time
The extension time after relay trip to continue next state
dV/dt
The dv/dt parameters can be set after selecting it.
Vol. Stop
Ending voltage
46
PONOVO POWER CO., LTD
PowerTest Basic
df/dt
Fre. Stop
Ending frequency
Ramp
Fault Cal
47
PONOVO POWER CO., LTD
PowerTest Basic
Based on the setting here the required voltage, current and phase angle setting will be calculated and
filled automatically in the parameters.
Idff Cal
Based on the differential relay settings the actual test currents will be calculated and filled automatically
in the parameters.
48
PONOVO POWER CO., LTD
PowerTest Basic
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Clear
Clear the test results at the present test point/item.
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
49
PONOVO POWER CO., LTD
PowerTest Basic
The absolute error limits and real error can be set here.
It indicates the results between 9.8-10.3 are acceptable, otherwise, it is not valid.
50
PONOVO POWER CO., LTD
PowerTest Basic
51
PONOVO POWER CO., LTD
PowerTest Basic
The way to set group parameters and test parameters is similar to Stat Sequence (4V, 3I).
Please refer to Chapter 11 State Sequence (4V,3I).
52
PONOVO POWER CO., LTD
PowerTest Basic
13. CB Operate
This module can be used to check different types of line protection system, including over current, line
carrier, distance and zero-sequence over-current. The whole relay system, including auto-reclosing,
tripping mechanism along with/or without circuit breaker can be checked.
Features
53
PONOVO POWER CO., LTD
PowerTest Basic
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
TPrefault
Prefault time setting.
During this time the test set will supply normal system balance voltage.
Trigger Mode
There are four trigger modes can be selected here.
Time
Manual
Bin. Input
GPS
Bin. Input: Fault status comes immediately after binary input H senses the trigger signal
GPS Fault status comes immediately after GPS pulse signal is received.
Note: GPS controlled test is available with optional PGPS-2 GPS Synchronization Device. Please
contact the manufacture for more information
PT at
Select it according to the actual PT installation position
Busbar side
Line side
CT polarity
Select it according to the actual CT polarity
Busbar polarity is toward busbar side
Line polarity is toward line side
Control Mode
Define the way to switch from one state to the next one
Bin. Input controlled by binary input
Time controlled by time
KE Mode
There are three types of KE mode available and we need to select the one according to the relay under
test.
∣K0∣, Phi(K0)
RERL, XEXL
∣Z0∣, Phi(Z0)
∣KE∣or RE(KE)
Setting for ∣K0∣, RERL or ∣Z0∣
Phi(KE) or Im(KE)
55
PONOVO POWER CO., LTD
PowerTest Basic
Test Mode
We can select the follow test modes.
IConst Constant current
VConst Constant voltage
ZsConst Constant system impedance
∣Zs∣, Phis
When Constant system impedance is selected then we need to give settings here.
CB Sim.
When optional Circuit Breaker Simulator is used we can need to select Yes here.
TOpen
Related to CB Sim.
TClose
Related to CB Sim.
fixed angle
The angle between voltage and current at the moment of fault can be set here
F Fault Angle
If we select fixed angle in Fault Inc. Mode we need to set the angle here
DC offset
Here we can define if DC offset is to be added when fault occurs
Uz Defined
Select the definition of Vz output
1.732*3Vo
-1.732*3Vo
3Vo
-3Vo
Vs
If Vs is selected we need to set the following settings accordingly
Phi(Uz)Ref.
Reference voltage for Vz
|Uz|
Amplitude of Vz
Phi(Uz)
Phase angle between Vz and reference voltage
56
PONOVO POWER CO., LTD
PowerTest Basic
Z-Phi or R-X
Select to set impedance value by Z-Phi or R-X
The three buttons are reserved for R&D development, not for testing purpose.
57
PONOVO POWER CO., LTD
PowerTest Basic
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Out 1-8
binary Output, Open or Close
Output Mode
Two modes available, Bin.In and Time
58
PONOVO POWER CO., LTD
PowerTest Basic
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Example: tripping time record with selection of TripA, TripB and TripC
In this example we can see the tripping time difference for phase A, B and C
TripABC
If we select them then test set will sense the binary inputs for TripA, TripB and TripC separately and
record the latest tripping time as the tripping time for all three phase tripping
In this example the tripping time is same for phase A, B and C output
59
PONOVO POWER CO., LTD
PowerTest Basic
Name
Edit the name for the current test point
Fault:
Select the fault type to simulate
Z, Angle, R, X
Set the impedance for the fault to simulate
Tmax
Total test time
I Test,V Test
Constant current or voltage setting
Direction
Forward fault occurs in the forward direction
Reversed fault occurs in the reversed direction
Mode:
Transient only one fault will be simulated
Permanent circuit breaker will be reclosed to a faulty system and one more tripping is expected
Dev. fault:
Select it to activate the setting for the second fault with different fault type
Developing Fault
60
PONOVO POWER CO., LTD
PowerTest Basic
61
PONOVO POWER CO., LTD
PowerTest Basic
Trip A
Criterion for phase A tripping
Trip B
Criterion for phase B tripping
Trip C
Criterion for phase C tripping
Rec
Criterion for reclosing
Sec. trip
Criterion for tripping after reclosing
Example 1:
If phase tripping time is smaller than 0.2s the test result will be regarded as Passed
Example 2:
If phase A tripping time meets the criterion of smaller than 0.2s and larger than 0.1s at the same time
(AND logic) then the test result will be regarded as Passed
Example 3:
62
PONOVO POWER CO., LTD
PowerTest Basic
Example 4:
If phase does not trip or if tripping time is larger than 5s (OR logic) then the test result will regarded as
Passed.
Above mentioned logic will happen when we test the relay with back up protection. If we set a very long
fault time the backup protection may be activated. With this criterion we can still get the test result
marked as Passed
63
PONOVO POWER CO., LTD
PowerTest Basic
64
PONOVO POWER CO., LTD
PowerTest Basic
65
PONOVO POWER CO., LTD
PowerTest Basic
Fill in the test name and test result and click “OK” to confirm the operation.
In this way we can get the test report with the test name and results we have entered.
66
PONOVO POWER CO., LTD
PowerTest Basic
67
PONOVO POWER CO., LTD
PowerTest Basic
This module is specially designed to realize RAMP for different test applications.
68
PONOVO POWER CO., LTD
PowerTest Basic
Pulse ramp
The typical pulse ramping process is as follows
t1: relay prepare time or reset time. This time will appear only once during the whole test process
t2: relay prefault time. This time will be applied each time when we give the next shot. For pulse
ramp this t2 is also known as wait time
A: Start value from where the selected variable will ramp.
B: End value at the point the test process will terminate
C: Step value
D: Step time
Linear ramp
The typical linear ramping process is as follows
t1: relay prepare time or reset time. This time will appear only once during the whole test process
A: Start value from where the selected quantity will ramp.
B: End value at that point test process will terminate
C: Step value
D: Step time
Note 1: In Pulse ramp mode if we set prefault time as zero it will become linear ramp
Note 2: In the group setting page we can set the prefault time/voltage/current, etc
69
PONOVO POWER CO., LTD
PowerTest Basic
Time
The fault time
Setting
In pick-up test, it is used as assessment.
The buttons above are reserved for R&D development, not for testing purpose.
70
PONOVO POWER CO., LTD
PowerTest Basic
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below
Tprepare
Relay prepare time or reset time
Tprefault
Prefault time or wait time
Vprefault
Prefaull voltage
Iprefault
Prefault current
Phiprefault
Prefault angle
The three buttons are reserved for R&D development, not for testing purpose.
71
PONOVO POWER CO., LTD
PowerTest Basic
In the above example we have changed the name of test item 1 as Test 1.
72
PONOVO POWER CO., LTD
PowerTest Basic
Ia
Phi(Vab,Ia)
Vbc
Vbc,Ib Ib
Phi(Vbc,Ib)
Vca
Vca,Ic Ic
Phi(Vca,Ic)
Vb
Vb,Ib Ib
Phi(Vb,Ib)
Vc
Vc,Ic Ic
Phi(Vc,Ic)
Frequency Frequency
We can make the selection according to the test requirement.
73
PONOVO POWER CO., LTD
PowerTest Basic
Vab
Ic
3V0
V2
Vab,Ic 3I0
I2
Phi(Vab,Ic)
Phi(3V0,3I0)
Phi(V2,I2)
Vbc,Ia
Vca,Ib
Vab,Ia
Vbc,Ib Same as above except the items marked in yellow
Vca,Ic
Vb,Ib
Vc,Ic
Frequency Frequency
From
The start value for quantity
To
The ending value for quantity
Tmax
The max duration time for each step
The y is used to avoid the situation where Tset is very small. In that case we use y as the step time.
Type
Pick-up, pick-up + drop-off, characteristic angle
Note: To select Characteristic Angle we need to select the record quantity as angle.
Here we have selected record quantity as Phi(Va,Ia) to enable the selection of Characteristic Angle
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear
Clear the test results at the present test point/item.
75
PONOVO POWER CO., LTD
PowerTest Basic
Input Binary
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Binary output
Define the output binary status in Pre-fault and fault.
Ext. Time
The hold time after trigger
76
PONOVO POWER CO., LTD
PowerTest Basic
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
77
PONOVO POWER CO., LTD
PowerTest Basic
78
PONOVO POWER CO., LTD
PowerTest Basic
15. Harmonic
This module is used to generate harmonics for all voltage and current outputs.
The module can be used for the following applications.
nd th
Check the 2 and 5 harmonic restraint
Check the harmonic measurement of the relay
79
PONOVO POWER CO., LTD
PowerTest Basic
Here we can switch among output channels and set the harmonic for each channel separately.
Based on those setting we can then view the calculated output waveform on the display window
Clear
Trip time
80
PONOVO POWER CO., LTD
PowerTest Basic
Quantity
Source and number of harmonic
Step size: step value
From: from where the quantity starts to change
To: test will terminate at this value
Step time: time duration for each step
Frequency: nominal frequency
Auto: Automatically test
Harmonic showing way
Amplitude
nd
It shows the 2 harmonic at 0.25V.
Percentage
nd
It shows the 2 harmonic at 10%, it equals to 10%*2.5V=0.25V.
It is different ways to show the same value.
81
PONOVO POWER CO., LTD
PowerTest Basic
HR
The percentage of harmonic value with reference to basic value
THD
Total harmonic distortion
TMS
Peak current
82
PONOVO POWER CO., LTD
PowerTest Basic
Input Binary
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Output binary
Define the output binary status
83
PONOVO POWER CO., LTD
PowerTest Basic
84
PONOVO POWER CO., LTD
PowerTest Basic
85
PONOVO POWER CO., LTD
PowerTest Basic
Fill in the test name and test result and click “OK” to confirm the operation.
In this way we can get the test report with the test name and results we have entered.
86
PONOVO POWER CO., LTD
PowerTest Basic
87
PONOVO POWER CO., LTD
PowerTest Basic
This module neither has any output value nor judge the binary input. It only generates a complete
report for project check from appearance and safety.
Add: Add check items while editing check items including Name and Test Method Requires
After adding the result name and test method, press F2 to start the test.
It pops up the diagram with the name added; we can type in the test result manually and end the test.
88
PONOVO POWER CO., LTD
PowerTest Basic
89
PONOVO POWER CO., LTD
PowerTest Basic
The standard COMTRADE format includes normally the following two parts.
CFG describe the recording channels, including signal names, sampling frequencies, etc
DAT contain the sampling values for each channels
For more information about COMTRADE files, please refer to IEC_IEEE 60255-24 COMTRADE for
power systems
90
PONOVO POWER CO., LTD
PowerTest Basic
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
91
PONOVO POWER CO., LTD
PowerTest Basic
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Note:
All the binary time is calculated from the test start, rather than the fault start time.
92
PONOVO POWER CO., LTD
PowerTest Basic
Configure channels
In Channel A drop-down selection box we can view all voltage channels from the COMTRADE file and
we need to assign one voltage from the list to the Va output of our test set.
93
PONOVO POWER CO., LTD
PowerTest Basic
Two channels can be combined together to get a new output. This happens when we need to get the
voltage which is the vector summation from two voltage channels.
Example
• • •
I a ' = ( I a − I b) / 3
• • •
I b' = ( I b − I c ) / 3
• • •
I c' = ( I c − I a ) / 3
In case the recorded data is for the primary side we need to set the ratio for PT and CT.
Here we can see the maximum voltage and current for this COMTRADE file. Proper setting of PT and
CT ratio will avoid them exceeding the available output range of the test set in use.
94
PONOVO POWER CO., LTD
PowerTest Basic
T1 and t2 indicate the peak values at the position for cursor 1 and cursor 2. dt indicates the time
difference between t1 and t2.
95
PONOVO POWER CO., LTD
PowerTest Basic
Insert Points
96
PONOVO POWER CO., LTD
PowerTest Basic
Note:
The maximum sampling rate should not exceed 10kHz
The maximum allowed playback time determined by the current sampling rate is displayed here.
97
PONOVO POWER CO., LTD
PowerTest Basic
17.5. Edit
98
PONOVO POWER CO., LTD
PowerTest Basic
Out 1, 2, 3, 4
It is based on the comtrade file. If there is binary output in COMTRADE file, there will be option
available, vice versa.
The binary in COMTRADE file is mapped to the binary output 1-4 of the tester.
Maximum 4 binary output are supported..
Location
It is for reserved.
99
PONOVO POWER CO., LTD
PowerTest Basic
Note:
1. When a new test point is added, a COMTRADE should be imported to this new test point.
2. Between the two test point/items, the waveform is not continuous.
100
PONOVO POWER CO., LTD
PowerTest Protection
PowerTest
Protection
VERSION: Protection-AE-2.30
DATE : JUNE 2017
This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of this manual
please contact PONOVO POWER CO., LTD in advance.
1
PowerTest Protection
Reminder
1. Please carefully read the PowerTest Concept before you read the
PowerTest Protection.
Content
1. Distance (Z-Phi) .............................................................................................................................9
1.1. Set group settings ........................................................................................................ 10
1.2. Set group parameters ................................................................................................. 11
1.3. Set group binary........................................................................................................... 15
1.4. Set test point/ item/ item parameters ........................................................................ 17
1.5. Set assessment criterion ............................................................................................ 19
1.6. Set wiring ...................................................................................................................... 21
1.7. Set characteristic ......................................................................................................... 22
1.8. Report setting ............................................................................................................... 24
1.9. GOOSE Data ................................................................................................................ 25
1.10. Add test point/ item/ item ............................................................................................ 26
1.11. Z-T diagram .................................................................................................................. 29
1.12. Test report example .................................................................................................... 30
2. Distance (R-X)............................................................................................................................. 32
2.1. Set group settings ........................................................................................................ 33
2.2. Set group parameters ................................................................................................. 34
2.3. Set group binary........................................................................................................... 38
2.4. Set test point/ item parameters.................................................................................. 40
2.5. Set assessment criterion ............................................................................................ 42
2.6. Set wiring ...................................................................................................................... 44
2.7. Set characteristic ......................................................................................................... 45
2.8. Report setting ............................................................................................................... 47
2.9. GOOSE Data ................................................................................................................ 48
2.10. Add test point/ item/ item ............................................................................................ 49
2.11. Z-T diagram .................................................................................................................. 52
2.12. Test report example .................................................................................................... 53
3. Differential (6I)............................................................................................................................. 55
3.1. Set group settings ........................................................................................................ 56
1. Distance (Z-Phi)
This module is used to test impedance relay with Z-Phi setting in different ways, including
Here we can set the values based on actual relay settings under test.
LN Zone n
Impedance for zone n setting in earth fault
LL Zone n
Impedance for zone n setting in phase-phase fault
LL Tn
Trip time for zone n setting in phase-phase fault
LN Tn
Trip time for zone n setting in earth fault
Phi
Line angle
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
TPrefault
Prefault time setting.
During this time the test set will supply normal system balance voltage.
Tpostfault
Post fault time setting
Trigger Mode
There are four trigger modes can be selected here.
Time
Manual
Bin. Input
GPS
Bin. Input: Fault status comes immediately after binary input H senses the trigger signal
GPS: Fault status comes immediately after GPS pulse signal is received.
Note: GPS controlled test is available with optional PGPS-2 GPS Synchronization Device. Please
contact the manufacture for more information.
PT at
Select it according to the actual PT installation position
Busbar side
Line side
CT polarity
Select it according to the actual CT polarity
CB Sim.
When optional Circuit Breaker Simulator is used we can need to select Yes here.
Open Time
CB trip delay, related to CB Sim.
Close Time
CB close delay, related to CB Sim.
Note: Please contact the manufacture for more information about the optional Circuit Breaker
Simulator and its application
Test Mode
We can select the follow test modes.
K0 Number
It is used to set the same KE value or independent value for each zone.
1, the same KE value
>1, independent KE value
KE Given as
There are three types of KE mode available and we need to select the one according to the relay under
test.
∣K0∣, Phi(K0)
KR, KX
∣Z0/Z1∣, Phi(Z0/Z1)
Vz Define
Set Vz output method.
1.732*3V0: 1.732*(VA+VB+VC)
-1.732*3V0: -1.732*(VA+VB+VC)
3V0: (VA+VB+VC)
-3V0: (VA+VB+VC)
Vs: Synchronization voltage
Phi(Vz) Ref.
Set Vz reference phase
Note: It is valid when Vz Define is selected as Vs.
Phi(Va)
Phi(Vb)
Phi(Vc)
Phi(Vab)
Phi(Vbc)
Phi(Vca)
ILOAD
It is the load current.
ILOADPH
It is the angle of load current.
ERRORRANGE
It is the impedance error range (%).
ABSERROR
It is the absolute impedance error range.
Note: The software will choose the maximum error between ERRORRANGE and ABSERROR.
Example 1
Z=5ohm, ERRORRANGE=5%, ABSERROR=0.5ohm, 0.5ohm>5*5%(0.25ohm), the final error range
will be 0.5ohm
Example 2
Z=5ohm, ERRORRANGE=5%, ABSERROR=0.1ohm, 0.1ohm<5*5% (0.25ohm), the final error range
will be 0.25ohm
LINEANGLE
The line is showing as below picture.
Click “Binary” button to enter into binary input and output configuration page
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Out 1-8
binary Output, Open or Close
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Example: tripping time record with selection of TripA, TripB and TripC
In this example we can see the tripping time difference for phase A, B and C
TripABC
If we select them then test set will sense the binary inputs for TripA, TripB and TripC separately and
record the latest tripping time as the tripping time for all three phase tripping
In this example the tripping time is same for phase A, B and C output
Name
Edit the test item/ point here
Fault type
|Z|
Impedance
Phi
The impedance phase
R, X
R is the resistance.
X is the reactance.
Note:
R= |Z| * cos (Phi)
X= |Z| * sin (Phi)
Current
The fault current
It is enabled when IConst is selected in Test Mode in Para, showing in below.
Voltage
The fault voltage
It is enabled when IConst is selected in Test Mode in Para, showing in below.
Direction
Reverse, or forward
Fault mode
Transient: circuit breaker will be reclosed to a health system
Permanent: circuit breaker will be reclosed to a faulty system and one more tripping is expected
Fault time
The fault time should be longer than the relay setting time.
Add
Copy the same test point/item at the cursor position.
Quick Add
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
Trip A
Criterion for phase A tripping
Trip B
Criterion for phase B tripping
Trip C
Criterion for phase C tripping
Rec
Criterion for reclosing
Sec. trip
Criterion for tripping after reclosing
Example 1:
If phase tripping time is smaller than 0.2s the test result will be regarded as Passed
Example 2:
If phase A tripping time meets the criterion of smaller than 0.2s and larger than 0.1s at the same time
(AND logic) then the test result will be regarded as Passed
Example 3:
Example 4:
If phase does not trip or if tripping time is larger than 5s (OR logic) then the test result will regarded as
Passed.
Above mentioned logic will happen when we test the relay with back up protection. If we set a very long
fault time the backup protection may be activated. With this criterion we can still get the test result
marked as Passed
Click Import.
Then we will be asked to select the folder where RIO files are saved.
Under the installation directory we can see Test Objects_RIO
Select RIO
Select the manufacture and double click the mouse button to enter into that folder. Select the RIO file
we need and confirm the operation.
For this module we provide the facility to edit the results to be included in the test report
On Z plain
Move mouse pointer to Z plain area and right click the mouse button, select Add Test point/ item
Move mouse pointer to the position where we want to set and double click the mouse button to confirm
this operation
After this operation the corresponding test point/ item in test list will be assigned to the value associated
to that point on Z plain
Add
In the parameter page click Add to add a new test point/ item/ item.
Quick Add
Here we can select the test point/ item by giving the percentage of the relay setting.
Example:
Note: The other settings and selections here are related to the test parameters.
The principle Z-T diagram can be got based on relay settings (impedance setting and time setting) in
group setting page.
From the above example we can see that the tripping occurs in zone 4 with a tripping time of 2.003s
2. Distance (R-X)
This module is used to test impedance relay with R-X setting in different ways, including
Here we can set the values based on actual relay settings under test.
LN Rn
Resistance for zone n setting in earth fault
LN Xn
Reactance for zone n setting in earth fault
LL Rn
Resistance for zone n setting in phase-phase fault
LL Xn
Reactance for zone n setting in phase-phase fault
LL Tn
Trip time for zone n setting in phase-phase fault
LN Tn
Trip time for zone n setting in earth fault
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
TPrefault
Prefault time setting.
During this time the test set will supply normal system balance voltage.
Tpostfault
Post fault time setting
Trigger Mode
There are four trigger modes can be selected here.
Time
Manual
Bin. Input
GPS
Bin. Input: Fault status comes immediately after binary input H senses the trigger signal
GPS: Fault status comes immediately after GPS pulse signal is received.
Note: GPS controlled test is available with optional PGPS-2 GPS Synchronization Device. Please
contact the manufacture for more information.
PT at
Select it according to the actual PT installation position
Busbar side
Line side
CT polarity
Select it according to the actual CT polarity
CB Sim.
When optional Circuit Breaker Simulator is used we can need to select Yes here.
Open Time
CB trip delay, related to CB Sim.
Close Time
CB close delay, related to CB Sim.
Note: Please contact the manufacture for more information about the optional Circuit Breaker
Simulator and its application
Test Mode
We can select the follow test modes.
K0 Number
It is used to set the same KE value or independent value for each zone.
1, the same KE value
>1, independent KE value
KE Given as
There are three types of KE mode available and we need to select the one according to the relay under
test.
∣K0∣, Phi(K0)
KR, KX
∣Z0/Z1∣, Phi(Z0/Z1)
Vz Define
Set Vz output method.
1.732*3V0: 1.732*(VA+VB+VC)
-1.732*3V0: -1.732*(VA+VB+VC)
3V0: (VA+VB+VC)
-3V0: (VA+VB+VC)
Vs: Synchronization voltage
Phi(Vz) Ref.
Set Vz reference phase
Note: It is valid when Vz Define is selected as Vs.
Phi(Va)
Phi(Vb)
Phi(Vc)
Phi(Vab)
Phi(Vbc)
Phi(Vca)
ILOAD
It is the load current.
ILOADPH
It is the angle of load current.
ERRORRANGE
It is the impedance error range (%).
ABSERROR
It is the absolute impedance error range.
Note: The software will choose the maximum error between ERRORRANGE and ABSERROR.
Example 1
Z=5ohm, ERRORRANGE=5%, ABSERROR=0.5ohm, 0.5ohm>5*5%(0.25ohm), the final error range
will be 0.5ohm
Example 2
Z=5ohm, ERRORRANGE=5%, ABSERROR=0.1ohm, 0.1ohm<5*5% (0.25ohm), the final error range
will be 0.25ohm
LINEANGLE
The line is showing as below picture.
Click “Binary” button to enter into binary input and output configuration page
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Out 1-8
binary Output, Open or Close
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Example: tripping time record with selection of TripA, TripB and TripC
In this example we can see the tripping time difference for phase A, B and C
TripABC
If we select them then test set will sense the binary inputs for TripA, TripB and TripC separately and
record the latest tripping time as the tripping time for all three phase tripping
In this example the tripping time is same for phase A, B and C output
Name
Edit the test item/ point here
Fault type
|Z|
Impedance
Phi
The impedance phase
R, X
R is the resistance.
X is the reactance.
Note:
R= |Z| * cos (Phi)
X= |Z| * sin (Phi)
Current
The fault current
It is enabled when IConst is selected in Test Mode in Para, showing in below.
Voltage
The fault voltage
It is enabled when IConst is selected in Test Mode in Para, showing in below.
Direction
Reverse, or forward
Fault mode
Transient: circuit breaker will be reclosed to a health system
Permanent: circuit breaker will be reclosed to a faulty system and one more tripping is expected
Fault time
The fault time should be longer than the relay setting time.
Add
Copy the same test point/item at the cursor position.
Quick Add
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
Trip A
Criterion for phase A tripping
Trip B
Criterion for phase B tripping
Trip C
Criterion for phase C tripping
Rec
Criterion for reclosing
Sec. trip
Criterion for tripping after reclosing
Example 1:
If phase tripping time is smaller than 0.2s the test result will be regarded as Passed
Example 2:
If phase A tripping time meets the criterion of smaller than 0.2s and larger than 0.1s at the same time
(AND logic) then the test result will be regarded as Passed
Example 3:
Example 4:
If phase does not trip or if tripping time is larger than 5s (OR logic) then the test result will regarded as
Passed.
Above mentioned logic will happen when we test the relay with back up protection. If we set a very long
fault time the backup protection may be activated. With this criterion we can still get the test result
marked as Passed
Click Import.
Then we will be asked to select the folder where RIO files are saved.
Under the installation directory we can see Test Objects_RIO
Select RIO
Select the manufacture and double click the mouse button to enter into that folder. Select the RIO file
we need and confirm the operation.
For this module we provide the facility to edit the results to be included in the test report
On Z plain
Move mouse pointer to Z plain area and right click the mouse button, select Add Test point/ item
Move mouse pointer to the position where we want to set and double click the mouse button to confirm
this operation
After this operation the corresponding test point/ item in test list will be assigned to the value associated
to that point on Z plain
Add
In the parameter page click Add to add a new test point/ item/ item.
Quick Add
Here we can select the test point/ item by giving the percentage of the relay setting.
Example:
Note: The other settings and selections here are related to the test parameters.
The principle Z-T diagram can be got based on relay settings (impedance setting and time setting) in
group setting page.
From the above example we can see that the tripping occurs in zone 4 with a tripping time of 2.003s
3. Differential (6I)
Ih/Iref (HV)
Balance coefficient (Side1): Balance coefficient in Side1
Ih/Iref (MV)
Balance coefficient (Side2): Balance coefficient in Side2
Ih/Iref (LV)
Balance coefficient (Side3): Balance coefficient in Side3
Id>>
It is instant trip current
Id>
It is pickup value.
Limp Number
1 or 2 limp number can be chosen.
When limp number 2 is chosen, the slop2 will be activated.
Limp1
It is the limp point 1.
Limp2
It is the limp point 2.
Slop0
It is the Initial slop.
Slop1, Slop 2
The curve will be changed according to the slop value setting here.
I2f/Idiff
It is the 2nd harmonic restraint
I5f/Idff
It is the 5th harmonic restraint
The buttons above are reserved for R&D development, not for testing purpose.
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
TPrefault
Prefault time setting
Tfault
Fault time setting
Tested Winding
Select windings to be tested.
Side 1-Side 3 test HV-LV winding
Side 1-Side 2 test HV-MV winding
Side 2-Side 3 test MV-LV winding
Conversion
Here we define from where we normalize the current to the reference side. It is based on the relay
setting and vector group.
Phase shifting
This refers to vector group number with winding 1 as the reference side.
Example:
For Y-D-11 connection we need to select 11 here
AxisDef
Name or Pu (Per unit)
Inom
It is activated when Pu is selected in AxisDef. It is the reference value.
Search Mode
Here we define the search mode for getting Id tripping point under each Ir setting.
CT starpoint
Here we define the direction of CT.
Normally we can determine the direction by looking at the bias equation in relay instruction manual
Example:
Equation Id=IA+IB indicates that CT direction is toward the protective device. Thus we need to select
tow.prot.obj
Example:
Equation Id=IA-IB indicates that CT direction is toward the transmission line. Thus we need to select
tow.line
Bias. Equ.
Here we select the equation which defines Ir/Id characteristic. This equation is available from relay
instruction manual.
Ir=|I2|
K1, K2
They are bias quantities in the bias equation and can be found in relay instruction manual
Test Phase
Here we can define to test only one phase or to test three phases at the same time.
A, B, C only one phase will be tested
ABC 6 currents will be injected into the relay under test. And the tripping time for all three phase will
be got
Resolution
This setting is related to Search Mode selection.
For dichotomic mode this resolution setting will be used to assess the current tripping point. If the
difference between the output value of the current tripping point and the value of the last un-tripping
point is less than this setting then the current tripping point will be determined.
For linear mode this resolution indicates the minimum step can be set.
Note:
We can set a bigger resolution to reduce the test time. But this may bring bigger error in the test result.
The three buttons are reserved for R&D development, not for testing purpose.
In
Binary input, Enable or disable
Out
Binary Output, Open or Close
Logic
The logic for binary input, Or and And options available.
Output Mode
Two modes available, Bin.In and Time
OutputHoldTime
Output hold time delay
Example: OR logic
In this example any tripping from A, B, or C will terminate the test process.
In this example when tripping for A, B, or C all comes then test process will be terminated and the
tripping time for all three phased will be recorded.
For each test point/ item/item we can set its test parameters on the parameter setting area as below.
Name
Here we modify the name for the current test point/ item/item/point
Test Phase
This is the selected winding we set in group parameter. ABC means phase ABC will be tested.
IR
Here we see the Ir setting for the current test point/ item/item. We can edit this setting according to our
test requirement.
Type
Here we define the way to test the current test point/ item/item.
Verify curve
The curve can be user-defined.
Slope 1
To do this test we need to set two points on slop 1. And the test process will check the Id tripping
values according to Ir settings of these two slop 1 points. At the same time the gradient for slop 1
will also be calculated.
Slope 2
To do this test we need to set two points on slop 2. And the test process will check the Id tripping
values according to Ir settings of these two slop 2 points. At the same time the gradient for slop 2
will also be calculated.
Slope 3
To do this test we need to set two points on slop 3. And the test process will check the Id tripping
values according to Ir settings of these two slop 3 points. At the same time the gradient for slop 3
will also be calculated.
Id>
Check the pickup value
Id>>
Check the rapid tripping value
Resolution
Display the resolution setting from group parameter page.
Frequency
It is the rated power system frequency.
Manual
By selecting manual here, the differential current can be controlled manually by up and down keys.
Clear
Clear the present test point/ item/ item result
Clear All
Clear all the test point/ item/ items results
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
Common wiring
Note:
The wiring connection is fixed, for example, Side 1-Side 2 or Side 1-Side 3 or Side 2-Side 3, and the
software will output for each phase automatically according to the settings.
4. Differential (3I)
Ih/Iref (HV)
Balance coefficient (Side1): Balance coefficient in Side1
Ih/Iref (MV)
Balance coefficient (Side2): Balance coefficient in Side2
Ih/Iref (LV)
Balance coefficient (Side3): Balance coefficient in Side3
Id>>
It is instant trip current
Id>
It is pickup value.
Limp Number
1 or 2 limp number can be chosen.
When limp number 2 is chosen, the slop2 will be activated.
Limp1
It is the limp point 1.
Limp2
It is the limp point 2.
Slop0
It is the Initial slop.
Slop1, Slop 2
The curve will be changed according to the slop value setting here.
I2f/Idiff
It is the 2nd harmonic restraint
I5f/Idff
It is the 5th harmonic restraint
The buttons above are reserved for R&D development, not for testing purpose.
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
TPrefault
Prefault time setting
Tfault
Fault time setting
CB Sim.
When optional Circuit Breaker Simulator is used we need to select “Yes” here.
Topen Tclose
Related to CB Sim.
Note:
Please contact the manufacture for more information about the optional Circuit Breaker Simulator
and its application
Tested Winding
PONOVO POWER CO., LTD 71
PowerTest Protection
Conversion
Here we define from where we normalize the current to the reference side. It is based on the relay
setting and vector group.
No
Wye-winding
Delta-winding
Example:
For Y-D-11 connection we need to select 11 here
AxisDef
Name or Pu (Per unit)
Inom
It is activated when Pu is selected in AxisDef. It is the reference value.
Search Mode
Here we define the search mode for getting Id tripping point under each Ir setting.
CT starpoint
Here we define the direction of CT.
Normally we can determine the direction by looking at the bias equation in relay instruction manual
Example:
Equation Id=IA+IB indicates that CT direction is toward the protective device. Thus we need to select
tow.prot.obj
Example:
Equation Id=IA-IB indicates that CT direction is toward the transmission line. Thus we need to select
tow.line
Bias. Equ.
Here we select the equation which defines Ir/Id characteristic. This equation is available from relay
instruction manual.
K1, K2
They are bias quantities in the bias equation and can be found in relay instruction manual
Test Phase
Here we can define to test only one phase or to test three phases at the same time.
A, B, C only one phase will be tested
ABC 6 currents will be injected into the relay under test. And the tripping time for all three phase will
be got
Test Method
Resolution
This setting is related to Search Mode selection.
For dichotomic mode this resolution setting will be used to assess the current tripping point. If the
difference between the output value of the current tripping point and the value of the last un-tripping
point is less than this setting then the current tripping point will be determined.
For linear mode this resolution indicates the minimum step can be set.
Note:
We can set a bigger resolution to reduce the test time. But this may bring bigger error in the test result.
Va,Vb,Vc
In module Differential (3I), there is voltage output with setting voltage amplitude.
The three buttons are reserved for R&D development, not for testing purpose.
In
Binary input, Enable or disable
Out
Binary Output, Open or Close
Logic
The logic for binary input, Or and And options available.
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
For each test point/ item/item we can set its test parameters on the parameter setting area as below.
Name
Here we modify the name for the current test point/ item/item/point
Test Phase
This is the selected winding we set in group parameter. A means only phase A will be tested.
IR
Here we see the Ir setting for the current test point/ item/item. We can edit this setting according to our
test requirement.
Type
Here we define the way to test the current test point/ item/item
None
Test process will check the Id tripping value based on the current Ir setting.
Slope 1
To do this test we need to set two points on slop 1. And the test process will check the Id tripping
values according to Ir settings of these two slop 1 points. At the same time the gradient for slop 1
will also be calculated.
Slope 2
To do this test we need to set two points on slop 2. And the test process will check the Id tripping
values according to Ir settings of these two slop 2 points. At the same time the gradient for slop 2
will also be calculated.
Slope 3
To do this test we need to set two points on slop 3. And the test process will check the Id tripping
values according to Ir settings of these two slop 3 points. At the same time the gradient for slop 3
will also be calculated.
PkUp
Check the pickup value
Id>>
Resolution
Display the resolution setting from group parameter page.
Frequency
It is the rated power system frequency.
Manual
By selecting manual here, the differential current can be controlled manually by up and down keys.
Add
Copy the same test point/item at the cursor position.
Add Sweep
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
Common wiring
Make the settings in Para. as below.
Add
In the parameter page click Add to add a new test point/ item/item.
Quick Add
Press OK, 5 more test point/ item/items will be added in the test list. See below
The relay mentioned above can be time definite and with time delay
Inom
Indicate the rated current of the relay under test.
Td
Delay time, dmt or idmt
Ipickup
The pickup current
The buttons above are reserved for R&D development, not for testing purpose.
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below
TPrefault
Prefault time setting.
During this time the test set will supply normal system balance voltage.
Fault
Here we can select the fault to be simulated for the test.
CT polarity
Select it according to the actual CT polarity
Vz Define
Set Vz output method.
1.732*3V0: 1.732*(VA+VB+VC)
-1.732*3V0: -1.732*(VA+VB+VC)
3V0: (VA+VB+VC)
-3V0: (VA+VB+VC)
Vs: Synchronization voltage
Phi(Vz) Ref.
Set Vz reference phase
Note: It is valid when Vz Define is selected as Vs.
Phi(Va)
Phi(Vb)
Phi(Vc)
Phi(Vab)
Phi(Vbc)
Phi(Vca)
|Vz|
Vz output value
Note: It is valid when Vz Define is selected as Vs.
Phi(Vz)
Phi (Vz) value is based on the Phi (Vz) Ref.
Note: It is valid when Vz Define is selected as Vs.
The three buttons are reserved for R&D development, not for testing purpose.
Bin
Binary input, Enable or Disable
Out
Binary Output, Open or Close
Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Name
Edit the test point/ item/ item name here.
Voltage
Prefault voltage
Current
Prefault current (load current)
Angle
Angle between voltage and current
Freq.
The power system frequency
Current
Current for the current test point/ item expressed in times of rated current
Anlge
Angle between voltage and current
Freq.
The power system frequency
Fault type
Display the fault type we have selected in group parameter page
Add
Copy the same test point/item at the cursor position.
Quick Add
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
In case we want to test time inversed current relay with our own defined curve we need first import and
define the tripping characteristic from our library.
In the parameter page click Add to add a new test point/ item
In the parameter page click Quick Add to add a new test point/ item
Quick Add
Here current setting is expressed as the times of the rated current we set in group setting page.
Example:
After we confirm this setting we can see new test point/ items are added in the test list.
On the characteristic curve we can also see the test point/ items
97
PowerTest Protection
The relay mentioned above can be time definite and with time delay
The buttons above are reserved for R&D development, not for testing purpose.
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below
TPrefault
Prefault time setting
During this time the test set will supply normal system balance voltage.
CT polarity
Select it according to the actual CT polarity
Fault Phase
Here we can select the fault to be simulated for the test.
Bin
Binary input, Enable or Disable
Out
Binary Output, Open or Close
Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Name
Edit the test point/ item/ item name here.
Pre-Fault
V (L-N)
Prefault voltage
Current
Pre-fault current (load current)
Angle
Pre-fault angle between voltage and current
Freq.
The power system frequency
Fault
V(L-L)/ Vf/ V(L-N)
Fault voltage in phase-phase or in earth fault
Note:
V (L-L): fault voltage in phase-phase
Vf: earth fault voltage
V (L-N): fault voltage in 3-phase
Current
Current for the current test point/ item expressed in times of rated current
Anlge
Angle between voltage and current
PONOVO POWER CO., LTD 102
PowerTest Protection
Freq.
The power system frequency
Vf Define
It is valid only in 3-phase.
Add
Copy the same test point/item at the cursor position.
Quick Add
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
In case we want to test time inversed voltage relay with our own defined curve we need first select the
item Under Voltage or Over Voltage.
Add
In the parameter page click Add to add a new test point/ item
Quick Add
Here current setting is expressed as the times of the rated current we set in group setting page.
7. Directional
This module is used to test maximum trip angle and two boundary angles (Lead and lag angles).
MTA
Maximum Torque Angle
Leadangle
Boundary angle 1 (Lead angle)
Lagangle
Boundary angle 2 (Lag angle)
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
Tprepare
During this time, Vn and Iprefault are output. The phase angle is phiprefault for once.,
Tprefault
During this time, Vn and Iprefault are output. The phase angle is phiprefault.
Iprefault
The output current before fault and within preparation time
Phiprefault
The phasae angle between the output current before fault and within preparation time and voltage
Angle Define
The reference of phase
Vz Define
Set Vz output method.
1.732*3V0: 1.732*(VA+VB+VC)
-1.732*3V0: -1.732*(VA+VB+VC)
3V0: (VA+VB+VC)
-3V0: (VA+VB+VC)
Vs: Synchronization voltage
Phi(Vz) Ref.
Set Vz reference phase
Note: It is valid when Vz Define is selected as Vs.
Phi(Va)
Phi(Vb)
Phi(Vc)
Phi(Vab)
Phi(Vbc)
Phi(Vca)
PONOVO POWER CO., LTD 109
PowerTest Protection
Name
Edit the test point/ item/ item name here.
Phase
The recorded current and voltage phase during test including phase A voltage and current, phase B
voltage and current, phase C voltage and negative sequence and zero sequence voltage and current.
Fault type
Set fault type according to different phase.
Voltage
Can be set according to the test requirement
Current
Should be set large enough to make relay trip
Frequency
The phase angle of output current and voltage (Can’t be changed. The fixed value is the system
voltage Fn.)
From
the start variable phase
To
the end variable phase
Step Size
the phase step size
Tmax
Should be set larger than tripping time setting
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear
Clear the test results at the present test point/item.
Input Binary
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Output Binary
Define the output binary status in Pre-fault and fault.
Hold Time
The hold time after trigger
Assessment
The error could be set here to compare between the actual testing value and reference value.
Act (Results)
Here it only shows the results that can’t be edited.
8. Frequency relay
Trip freq
Here we set the tripping value of frequency we will get from tripping test
Trip time
Tripping time setting
df/dt blocking
df/dt blocking setting
Blocking voltage
Bblocking voltage setting
Blocking current
Blocking current setting
Blocking voltage
Vpp: L-L voltage
Vpc: L-N voltage
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
F Change Mode
Here we define the way for frequency to change during the test.
Continuous
In this mode the frequency will change according to the df/dt setting with the minimum dt step.
Sudden
In this mode the frequency will change according to the df/dt setting and also the setting of dt (see
below)
dt
For a given df/dt setting we can define the step of dt. At the minimum setting of dt the frequency will
change almost linearly. This setting will become active when sudden is selected in F Change Mode.
Tprefault
prefault time. During this time, Vn and Iprefault are output. The phase angle is phiprefault.
Bin
Binary input, Enable or Disable
Out
Binary Output, Open or Close
Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
df/dt
This setting should be lower than the actual relay df/dt setting in order to make relay trip
Fre. Start
When test starts the frequency will decrease/ increase from nominal system frequency and when it
reaches the value set here it will return to the nominal value
Fre. Stop
Test will terminate when frequency reaches this value
Note: When the normal frequency is higher than Fre. Stop value, it is under-frequency, the frequency
will decrease, or vice versa over-frequency, it will increase.
Hold time
Step duration which should be longer than the actual relay tripping time setting
Nominal Frequency
The phase angle of output current and voltage (Can’t be changed. The fixed value is the system
voltage Fn.)
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear Results
Clear the test results at the present test point/item.
The following diagram indicates this test process (Especially for under-frequency)
Df/dt
This setting should be lower than the actual relay df/dt setting in order to make relay trip.
Fre. Stop
This value should be lower/ higher than the Trip freq. setting in group setting page.
Note: When the normal frequency is higher than Fre. Stop value, it is under-frequency, the frequency
will decrease, or vice versa over-frequency, it will increase.
Hold time
Step duration which should be longer than the actual relay tripping time setting.
Frequency will start to decrease/ increase from the Trip freq. value
Since df/dt we set here is lower than relay df/dt setting relay the relay tripping is allowed
When frequency reaches the under-frequency tripping value the internal timer in the relay will be
activated
Since the hold time is longer than the actual relay tripping time we can get the relay tripping time
after delay time is over
This tripping time will then be recorded in the test result
Fre. Stop
This value should be lower than the Trip freq. setting in group setting page.
Note: When the normal frequency is higher than Fre. Stop value, it is under-frequency, the frequency
will decrease, or vice versa over-frequency, it will increase.
df/dt start
From where the df/dt will change by step
df/dt stop
Test will terminate when df/dt reaches this value.
df/dt step
For each cycle of test the df/dt will decrease with this step setting
Hold time
Step duration which should be longer than the actual relay tripping time setting
Frequency will start to decrease/ increase from the nominal frequency with the df/dt value set by
df/dt start. Normally the df/dt start is higher than the actual df/dt setting so the relay will not trip
for this first cycle of test.
When frequency reaches the end frequency defined by Fre. Stop the frequency will return to
nominal frequency and a new cycle of test will start.
In the new test cycle the frequency will decrease with a new df/dt value which is one step (df/dt
step) lower than the df/dt used in last test cycle
Test will be terminated in the cycle where relay trips and the df/dt value used in this cycle will be
recorded in the test result
Df/dt
This value should be lower than the Trip freq. setting in group setting page so the df/dt blocking
function will be disabled.
Fre. Stop
This value should be lower/ higher than the Trip freq. setting in group setting page.
Note: When the normal frequency is higher than Fre. Stop value, it is under-frequency, the frequency
will decrease, or vice versa over-frequency, it will increase.
I Start
From where the current starts to decrease. This star current should be smaller than the current
blocking setting to enable the blocking.
I Stop
Test will terminate when current reaches this value.
I step
Step for current to increase in the new test cycle,
Hold time
Step duration which should be longer than the actual relay tripping time setting
Phase
We can select the current source here depending on the requirement of relay
df/dt
This value should be lower than the Trip freq. setting in group setting page so the df/dt blocking
function will be disabled.
Fre. Stop
This value should be lower/ higher than the Trip freq. setting in group setting page.
Note: When the normal frequency is higher than Fre. Stop value, it is under-frequency, the frequency
will decrease, or vice versa over-frequency, it will increase.
V Start
From where the voltage starts to decrease. This star voltage should be smaller than the voltage
blocking setting to enable the blocking.
V Stop
Test will terminate when voltage reaches this value.
V Step
Step for voltage to increase in the new test cycle.
Hold time
Step duration which should be longer than the actual relay tripping time setting.
Phase
We can select the voltage source here depending on the requirement of relay
Assessment
The error could be set here to compare between the actual testing value and reference value.
Act (Results)
Here it only shows the results that can’t be edited.
9. Voltage relay
Under-voltage blocking
Under-voltage setting
Trip time
Tripping time setting
dv/dt blocking
dv/dt blocking setting
Current
Current to be injected into the relay
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
V Change Mode
Here we define the way for voltage to change during the test.
Continuous
In this mode the voltage will change according to the dv/dt setting with the minimum dt step.
Sudden
In this mode the voltage will change according to the dv/dt setting and also the setting of dt (see bellow)
dt
For a given dv/dt setting we can define the step of dt. At the minimum setting of dt the voltage will
change almost linearly. This setting will become active when sudden is selected in V Change Mode.
Tprefault
prefault time. During this time, Vn and Iprefault are output. The phase angle is phiprefault.
Bin
Binary input, Enable or Disable
Out
Binary Output, Open or Close
Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
dv/dt
This setting should be lower than the actual relay dv/dt setting
Note: When the Vpp or Vpn. Stop value is higher than normal voltage, it is under-voltage, the voltage
will decrease, or vice versa over- voltage, it will increase.
V. Step
Each time when voltage starts again to decrease/ increase this step frequency will be added to the end
frequency of last cycle of frequency change
Hold time
Step duration which should be longer than the actual relay tripping time setting
Variable
Select Blocking Voltage Vpn
Va
Vb
Vc
Vabc
Select Blocking Voltage Vpp
Vab
PONOVO POWER CO., LTD 132
PowerTest Protection
Vbc
Vca
Vabc
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear
Clear the test results at the present test point/item.
Note:
The Add, Remove and Clear Results functions are the same in next three parts
dv/dt
This setting should be lower than the actual relay dv/dt setting in order to make relay trip.
Note: When the Vpp or Vpn. Stop value is higher than normal voltage, it is under-voltage, the voltage
will decrease, or vice versa over- voltage, it will increase.
Hold time
Step duration which should be longer than the actual relay tripping time setting
Nominal voltage will be applied for the time defined by prefault time setting to reset the relay
After prefault time is over the voltage will drop to V.Stop value (lower/ higher than the voltage
setting) defined here with the speed of dv/dt (lower than dv/dt blocking setting) for a time
defined by Hold time (longer than the trip time setting)
The trip time will then be recorded in the test result
Note: When the Vpp or Vpn. Stop value is higher than normal voltage, it is under-voltage, the voltage
will decrease, or vice versa over- voltage, it will increase.
dv/dt start
From where the dv/dt will change by step
dv/dt stop
Test will terminate when dv/dt reaches this value.
dv/dt step
For each cycle of test the dv/dt will decrease with this step.
Hold time
Step duration which should be larger than the actual relay tripping time setting.
Voltage will start to decrease/ increase from the nominal frequency with the dv/dt defined by dv/dt
start. Normally the dv/dt start is higher/ lower than the actual dv/dt setting so the relay will not trip
for this first cycle of test.
When voltage reaches the end voltage defined by V. Stop the voltage will return to nominal
voltage and a new test cycle will start.
In the new test cycle the voltage will decrease/ increase with a new dv/dt value which is one step
(dv/dt step) lower than the dv/dt used in last test cycle
Test will be terminated in the cycle where relay trips and the dv/dt value for this cycle will be
recorded in the test result
Assessment
The error could be set here to compare between the actual testing value and reference value.
Act (Results)
Here it only shows the results that can’t be edited.
137
PowerTest Protection
Test Object
Substation:Ponovo Bay:Testing Laboratory
Device:PSL 612C Type:Line
Manufacture:NARI SN:P0408389
Tested by: Lee Date:05/07/2008 11:27
1.V Act
NR Setting Act Assessment
1 40.000V 39.600V Passed
2.dv/dt Time
NR Setting Act Assessment
1 1.000s 1.058s Passed
3.dv/dt Act
NR Setting Act Assessment
1 10.000V/s 9.800V/s Passed
This module can be used to test AC type auxiliary/intermediate relay and AC type time relay
This module is used to test pick-up and drop-off of AC voltage type auxiliary relay.
Vset
Rated voltage setting
Tset
Trip time setting
The buttons above are reserved for R&D development, not for testing purpose.
Treset
Prepare time used for relay to reset; no voltage or current is generated during this time
Tprefault
This time will appear before each test cycle; no voltage or current is generated during this time
The three buttons are reserved for R&D development, not for testing purpose.
Name
Edit the test item name here.
Quantity
Indicates the quantities to change during the test
From
From where the voltage will start to change
To
Test will terminate at this voltage value
Step Size
Step for voltage to change
Tmax
Step time and it should be larger than tripping time setting
Type
select the test mode
Pick-up
Pickup+drop-off
Characteristic angle (No use)
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear Results
Clear the test results at the present test point/item.
Note:
The Add, Remove and Clear Results functions are the same in next three parts
Binary Inputs
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Binary Output
Define the output binary status in Pre-fault and fault.
Ext.Time
The hold time after trigger
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
This module is used to test pick-up and drop-off of AC current type auxiliary relay.
Iset
Rated current setting
Tset
Trip time setting
Treset
Prepare time used for relay to reset; no voltage or current is generated during this time
Tprefault
This time will appear before each test cycle; no voltage or current is generated during this time
Quantity
Indicates the quantities to change during the test
From
From where the current will start to change
To
Test will terminate at this current value
Step Size
Step for current to change
Tmax
Step time and it should be larger than tripping time setting
Type
Select the test mode
Pick-up
Pickup+drop-off
Characteristic angle (No use)
Binary Inputs
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Binary Output
Define the output binary status in Pre-fault and fault.
Ext.Time
The hold time after trigger
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
This module is used to test trip time of AC voltage type time relay.
Vset
Rated voltage setting
Time
Trip time setting
Tprefault
During this time no voltage or current is generated
Input A-H
Binary input, Enable or Disable
Out 1-8
Binary Output, Open or Close
Trigger Logic
Binary input, AND or OR
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
Pre-Fault parameters
Voltage
Can be set according the test requirement
Current
Can be set according to the test requirement
Angle
Can be set according to the test requirement
Fault parameters
Vf
The fault voltage can be set according to the test requirement
Current
Can be set according to the test requirement
Angle
Can be set according to the test requirement
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
PONOVO POWER CO., LTD 156
PowerTest Protection
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
Assessment
The error could be set here to compare between the actual testing value and reference value.
Characteristic
It is not activated.
This module is used to test trip time of AC current type time relay.
Iset
Rated current setting
Tset
Trip time setting
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
Tprefault
Prault time. During this time no voltage or current is generated
Pre-Fault parameters
Voltage
can be set according the test requirement
Current
can be set according to the test requirement
Angle
can be set according to the test requirement
Fault parameters
Vf
The fault voltage can be set according to the test requirement
Current
should be set large enough to make relay trip
Angle
can be set according to the test requirement
Assessment
The error could be set here to compare between the actual testing value and reference value.
Characteristic
It is not activated.
This module is used to test DC type voltage relay. Auxiliary DC source Vdc is used for this test. Ia is
used to generate DC current for some relays which requires DC current during the test.
Iset
The current to be injected to the relay if required
Vset
Voltage setting
Time
Trip time setting
The buttons above are reserved for R&D development, not for testing purpose.
Tprepare
Prepare time used for relay to reset; no voltage or current is generated during this time
Tprefault
This time will appear before each test cycle; no voltage or current is generated during this time
Vprefault
The voltage here is the value at the pre-fault time.
The three buttons are reserved for R&D development, not for testing purpose.
Ia
if current is required for testing the relay we need to set the current value here
From
From where the voltage will start to change
To
Test will terminate at this voltage value
Step Size
Step for voltage to change
Tmax
Step time and it should be larger than tripping time setting
Type
Select the test mode
Pick-up
Pickup+drop-off
Characteristic angle (No use)
Binary Inputs
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Binary Output
Define the output binary status in Pre-fault and fault.
Ext.Time
The hold time after trigger
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
This module is used to test DC type current relay. Current source Ia is used for this test. Vdc is used to
generate DC current for some relays which requires DC voltage during the test.
Iset
Current setting
Vset
The voltage to be applied to the relay if required
Time
Trip time setting
The buttons above are reserved for R&D development, not for testing purpose.
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
Tprepare
Used for relay to reset; no voltage or current is generated during this time
Tprefault
This time will appear before each test cycle; no voltage or current is generated during this time
Vprefault
The voltage here is the value at the pre-fault time.
The three buttons are reserved for R&D development, not for testing purpose.
Vdc
If voltage is required for testing the relay we need to set the voltage value here
From
From where the current will start to change
To
Test will terminate at this current value
Step Size
Step for current to change
Tmax
Step time and it should be larger than tripping time setting
Type
Select the test mode
Pick-up
Pickup+drop-off
Characteristic angle (No use)
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear
Clear the test results at the present test point/item
Binary Inputs
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
Binary Output
Define the output binary status in Pre-fault and fault.
Ext.Time
The hold time after trigger
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
12. Auto-Reclosing
Angle
Fault angle
|Z|
Fault value
Trecloser
Dead time
Ref. Phase
Reference Phase
Vset
voltage block setting
Syn. Angle
Angle block setting
KE Mode
There are three types of KE mode available and we need to select the one according to the relay under
test.
∣K0∣, Phi(K0)
RERL, XEXL
∣Z0∣, Phi(Z0)
∣KE∣or RE(KE)
Setting for ∣K0∣, RERL or ∣Z0∣
Phi(KE) or Im(KE)
Setting for Phi(K0), XEXL or Phi(Z0)
The buttons above are reserved for R&D development, not for testing purpose.
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below
Tprefault:
Prefault time setting.
During this time the test set will supply normal system balance voltage.
Tpostfault:
Postfault time setting.
During this time the test set will supply normal system balance voltage.
Trigger Con.
There are four trigger modes can be selected here.
Time
Manual
Bin. Input
GPS
Bin. Input: Fault status comes immediately after binary input H senses the trigger signal
GPS: Fault status comes immediately after GPS pulse signal is received.
Note: GPS controlled test is available with optional PGPS-2 GPS Synchronization Device. Please
contact the manufacture for more information
Main PT at
Select it according to the actual PT installation position
Busbar side
Line side
CT polarity
Select it according to the actual CT polarity
CB Simu.
When optional Circuit Breaker Simulator is used we can need to select Yes here.
Topen
Related to CB Simu.
Tclose
Related to CB Simu..
Note: Please contact the manufacture for more information about the optional Circuit Breaker
Simulator and its application
ILOAD
The load current
ILOADPH
The angle of load current
The three buttons are reserved for R&D development, not for testing purpose.
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Out 1-8
binary Output, Open or Close
Output Mode
Two modes available, Bin.In and Time
OutputTime
PONOVO POWER CO., LTD 184
PowerTest Protection
OutputHoldTime
Output hold time delay
Example: tripping time record with selection of TripA, TripB and TripC
In this example we can see the tripping time difference for phase A, B and C
TripABC
If we select them then test set will sense the binary inputs for TripA, TripB and TripC separately and
record the latest tripping time as the tripping time for all three phase tripping
In this example the tripping time is same for phase A, B and C output
Fault
|Z|
Impedance
Angle
The impedance angle
ITest
Current during fault condition
After-Reclosing
|Z|
Impedance
Angle
The impedance angle
ITest
Current during fault condition
Fault type
Fault mode
Transient
Successful auto-reclosing process is expected
Permanent
Unsuccessful auto-reclosing process is expected. The Afer Reclosing enable after in permanent mode.
V(Syn PT)
It is the power system voltage.
Phi(Syn PT)
It is the power system voltage angle.
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test results of all the test point/items.
Example 1:
If phase tripping time is smaller than 0.2s the test result will be regarded as Passed
Example 2:
If phase A tripping time meets the criterion of smaller than 0.2s and larger than 0.1s at the same time
(AND logic) then the test result will be regarded as Passed
188
PowerTest Protection
Example 3:
Example 4:
If phase does not trip or if tripping time is larger than 5s (OR logic) then the test result will regarded as
Passed.
Above mentioned logic will happen when we test the relay with back up protection. If we set a very long
fault time the back up protection may be activated. With this criterion we can still get the test result
marked as Passed
Test Object
Substation:Ponovo Bay:Testing Laboratory
Device:PSL 612C Type:Line
Manufacture:China SN:P0408389
Tested by:XXX Date:05/07/2008 10:50
PowerTest
Advanced
VERSION: BASIC-AE-2.30
DATE : JUNE 2017
This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of this manual
please contact PONOVO POWER CO., LTD in advance.
1
PowerTest Advanced
Reminder
1. Please carefully read the PowerTest Concept before you read the
PowerTest Advanced.
2
PONOVO POWER CO., LTD
PowerTest Advanced
Content
1. Advanced Differential (6I) ............................................................................................... 5
1.1. Set group settings .................................................................................................... 6
1.2. Set group parameters .............................................................................................. 8
1.3. Set group binary......................................................................................................12
1.4. Set test point/item parameters..............................................................................13
1.5. Set assessment criterion .......................................................................................15
1.6. Set wiring .................................................................................................................16
1.7. GOOSE Data ..........................................................................................................17
1.8. Add test point/item .................................................................................................18
2. Advanced Differential (3I) .............................................................................................21
2.1. Set group settings ..................................................................................................22
2.2. Set group parameters ............................................................................................24
2.3. Set group binary .....................................................................................................28
2.4. Set test point/item parameters .............................................................................29
2.5. Set assessment criterion .......................................................................................31
2.6. Set wiring .................................................................................................................32
2.7. Add test point/item .................................................................................................34
3. Advanced TransPlay (4V, 3I) .......................................................................................37
3.1. Import COMTRADE file .........................................................................................38
3.2. Set group binary .....................................................................................................39
3.3. Channel select ........................................................................................................40
3.4. Set sampling rate ...................................................................................................43
3.5. Edit............................................................................................................................45
3.6. Set wiring .................................................................................................................48
3.7. Set output binary ....................................................................................................49
3.8. Add test point/item .................................................................................................50
4. RX Characteristic Sweep .............................................................................................51
4.1. Set group parameters ............................................................................................52
3
PONOVO POWER CO., LTD
PowerTest Advanced
4
PONOVO POWER CO., LTD
PowerTest Advanced
5
PONOVO POWER CO., LTD
PowerTest Advanced
Setting Mode
Per-unit Value/Actual Value
Id>>
It is instant trip current
Id>
It is pickup value.
Limp Number
1 or 2 limp number can be chosen.
When limp number 2 is chosen, the slop2 will be activated.
Limp1
It is the limp point 1.
Limp2
It is the limp point 2.
6
PONOVO POWER CO., LTD
PowerTest Advanced
Slop0
It is the Initial slop.
Slop1, Slop 2
The curve will be changed according to the slop value setting here.
I2f/Idiff
It is the 2nd harmonic restraint
I5f/Idff
It is the 5th harmonic restraint
The buttons above are reserved for R&D development, not for testing purpose.
7
PONOVO POWER CO., LTD
PowerTest Advanced
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown bellow
TPrefault
Prefault time setting
Tfault
Fault time setting
Balance Coefficient
Automatic Calculation: Make calculation automatically
Manual and Input : Manual input
Conversion
Here we define from where we normalize the current to the reference side. It is based on the relay
setting and vector group.
Tested Winding
Select windings to be tested.
Side 1-Side 3 test HV-LV winding
Side 1-Side 2 test HV-MV winding
Side 2-Side 3 test MV-LV winding
Phase shifting
This refers to vector group number with winding 1 as the reference side.
Example:
For Y-D-11 connection we need to select 11 here
Search Mode
Here we define the search mode for getting Id tripping point under each Ir setting.
9
PONOVO POWER CO., LTD
PowerTest Advanced
CT starpoint
Here we define the direction of CT.
Normally we can determine the direction by looking at the bias equation in relay instruction manual
Example:
Equation Id=IA+IB indicates that CT direction is toward the protective device. Thus we need to select
tow.prot.obj
Example:
Equation Id=IA-IB indicates that CT direction is toward the transmission line. Thus we need to select
tow.line
Bias. Equ.
Here we select the equation which defines Ir/Id characteristic. This equation is available from relay
instruction manual.
K1, K2
They are bias quantities in the bias equation and can be found in relay instruction manual
Test Phase
Here we can define to test only one phase or to test three phases at the same time.
A, B, C only one phase will be tested
ABC 6 currents will be injected into the relay under test. And the tripping time for all three phase will
be got
Resolution
This setting is related to Search Mode selection.
For dichotomic mode this resolution setting will be used to assess the current tripping point. If the
difference between the output value of the current tripping point and the value of the last un-tripping
point is less than this setting then the current tripping point will be determined.
For linear mode this resolution indicates the minimum step can be set.
Note:
We can set a bigger resolution to reduce the test time. But this may bring bigger error in the test result.
10
PONOVO POWER CO., LTD
PowerTest Advanced
The three buttons are reserved for R&D development, not for testing purpose.
11
PONOVO POWER CO., LTD
PowerTest Advanced
Example: OR logic
In this example any tripping from A, B, or C will terminate the test process.
In this example when tripping for A, B, or C all comes then test process will be terminated and the
tripping time for all three phased will be recorded.
12
PONOVO POWER CO., LTD
PowerTest Advanced
For each test point/item we can set its test parameters on the parameter setting area as below.
Name
Here we modify the name for the current test point/item/point
Test Phase
This is the selected winding we set in group parameter. A means only phase A will be tested.
IR
Here we see the Ir setting for the current test point/item. We can edit this setting according to our test
requirement.
Type
Here we define the way to test the current test point/item
None
Test process will check the Id tripping value based on the current Ir setting.
Slope 1
To do this test we need to set two points on slop 1. And the test process will check the Id tripping
values according to Ir settings of these two slop 1 points. At the same time the gradient for slop 1
will also be calculated.
Slope 2
To do this test we need to set two points on slop 2. And the test process will check the Id tripping
values according to Ir settings of these two slop 2 points. At the same time the gradient for slop 2
will also be calculated.
PkUp
Check the pick up value
Id>>
Check the rapid tripping value
Resolution
Display the resolution setting from group parameter page.
13
PONOVO POWER CO., LTD
PowerTest Advanced
Frequency
It is the rated power system frequency.
Manual
By selecting manual here, the differential current can be controlled manually by up and down keys.
Click ‘Add’ and ‘Remove’ buttons in the parameter setting area to add or delete the test point/item.
Add
Copy the same test point/item at the cursor position.
Quick Add
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
14
PONOVO POWER CO., LTD
PowerTest Advanced
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
15
PONOVO POWER CO., LTD
PowerTest Advanced
Common wiring
Note:
The wiring connection is fixed, for example, Side 1-Side 2 or Side 1-Side 3 or Side 2-Side 3, and the
software will output for each phase automatically according to the settings.
16
PONOVO POWER CO., LTD
PowerTest Advanced
17
PONOVO POWER CO., LTD
PowerTest Advanced
When we open the module a group of default test point/items/points will appear in the test list
Direct Add
In the parameter page click Add to add a new test point/item.
18
PONOVO POWER CO., LTD
PowerTest Advanced
Quick Add
Press OK, 5 more test point/items will be added in the test list. See below
Example:
Move cursor at the test point/item where we want to add a same.
19
PONOVO POWER CO., LTD
PowerTest Advanced
After we add one new point we can see it in the test list.
At this time the newly added test point/item has the same name and parameters as the last one
We can edit the parameters for the newly added test point/item.
20
PONOVO POWER CO., LTD
PowerTest Advanced
21
PONOVO POWER CO., LTD
PowerTest Advanced
Setting Mode
Per-unit Value/Actual Value
Id>>
It is instant trip current
Id>
It is pickup value.
Limp Number
1 or 2 limp number can be chosen.
When limp number 2 is chosen, the slop2 will be activated.
Limp1
It is the limp point 1.
Limp2
It is the limp point 2.
Slop0
It is the Initial slop.
22
PONOVO POWER CO., LTD
PowerTest Advanced
Slop1, Slop 2
The curve will be changed according to the slop value setting here.
I2f/Idiff
It is the 2nd harmonic restraint
I5f/Idff
It is the 5th harmonic restraint
The buttons above are reserved for R&D development, not for testing purpose.
23
PONOVO POWER CO., LTD
PowerTest Advanced
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
TPrefault
Prefault time setting
Tfault
Fault time setting
Balance Coefficient
Automatic Calculation: Make calculation automatically
Manual and Input : Manual input
CB Sim.
When optional Circuit Breaker Simulator is used we need to select “Yes” here.
Topen Tclose
Related to CB Sim.
Note:
Please contact the manufacture for more information about the optional Circuit Breaker Simulator
and its application
Conversion
Here we define from where we normalize the current to the reference side. It is based on the relay
setting and vector group.
No
Wye-winding
Delta-winding
Tested Winding
Select windings to be tested.
Side 1-Side 3 test HV-LV winding
Side 1-Side 2 test HV-MV winding
Side 2-Side 3 test MV-LV winding
Phase shifting
This refers to vector group number with winding 1 as the reference side.
Example:
For Y-D-11 connection we need to select 11 here
25
PONOVO POWER CO., LTD
PowerTest Advanced
Search Mode
Here we define the search mode for getting Id tripping point under each Ir setting.
There are two methods available
Dichotomic
Linear
CT starpoint
Here we define the direction of CT.
Normally we can determine the direction by looking at the bias equation in relay instruction manual
Example:
Equation Id=IA+IB indicates that CT direction is toward the protective device. Thus we need to select
tow.prot.obj
Example:
Equation Id=IA-IB indicates that CT direction is toward the transmission line. Thus we need to select
tow.line
Bias. Equ.
Here we select the equation which defines Ir/Id characteristic. This equation is available from relay
instruction manual.
K1, K2
They are bias quantities in the bias equation and can be found in relay instruction manual
Test Phase
Here we can define to test only one phase or to test three phases at the same time.
A, B, C only one phase will be tested
ABC 6 currents will be injected into the relay under test. And the tripping time for all three phase will
be got
Test Method
Compensation: Output phase A, phase B and phase C. Phase C is used as compensation phase.
Note:
Different test methods will affect the wiring connections.
Resolution
This setting is related to Search Mode selection.
For dichotomic mode this resolution setting will be used to assess the current tripping point. If the
difference between the output value of the current tripping point and the value of the last un-tripping
point is less than this setting then the current tripping point will be determined.
For linear mode this resolution indicates the minimum step can be set.
Note:
We can set a bigger resolution to reduce the test time. But this may bring bigger error in the test result.
Va,Vb,Vc
In module Differential (3I), there is voltage output with setting voltage amplitude.
The three buttons are reserved for R&D development, not for testing purpose.
27
PONOVO POWER CO., LTD
PowerTest Advanced
In
Binary input, Enable or disable
Out
Binary Output, Open or Close
Logic
The logic for binary input, Or and And options available.
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
28
PONOVO POWER CO., LTD
PowerTest Advanced
For each test point/item we can set its test parameters on the parameter setting area as below.
Name
Here we modify the name for the current test point/item/point
Test Phase
This is the selected winding we set in group parameter. A means only phase A will be tested.
IR
Here we see the Ir setting for the current test point/item. We can edit this setting according to our test
requirement.
Type
Here we define the way to test the current test point/item
None
Test process will check the Id tripping value based on the current Ir setting.
Slope 1
To do this test we need to set two points on slop 1. And the test process will check the Id tripping
values according to Ir settings of these two slop 1 points. At the same time the gradient for slop 1
will also be calculated.
Slope 2
To do this test we need to set two points on slop 2. And the test process will check the Id tripping
values according to Ir settings of these two slop 2 points. At the same time the gradient for slop 2
will also be calculated.
PkUp
Check the pick up value
Id>>
Check the rapid tripping value
Resolution
Display the resolution setting from group parameter page.
29
PONOVO POWER CO., LTD
PowerTest Advanced
Frequency
It is the rated power system frequency.
Manual
By selecting manual here, the differential current can be controlled manually by up and down keys.
Click ‘Add’ and ‘Remove’ buttons in the parameter setting area to add or delete the test point/item.
Add
Copy the same test point/item at the cursor position.
Add Sweep
Add few test point/items within the setting range.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Remove N-1
Remove all the test point/items except the first one.
Clear
Clear the test results at the present test point/item.
Clear All
Clear all the test result of all the test point/items.
30
PONOVO POWER CO., LTD
PowerTest Advanced
Assessment
The error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
31
PONOVO POWER CO., LTD
PowerTest Advanced
Common wiring
Make the settings in Para. as below.
32
PONOVO POWER CO., LTD
PowerTest Advanced
33
PONOVO POWER CO., LTD
PowerTest Advanced
When we open the module a group of default test point/items/points will appear in the test list
Direct Add
In the parameter page click Add to add a new test point/item.
34
PONOVO POWER CO., LTD
PowerTest Advanced
Quick Add
Press OK, 5 more test point/items will be added in the test list. See below
Example:
Move cursor at the test point/item where we want to add a same test point/item and press “Add”.
35
PONOVO POWER CO., LTD
PowerTest Advanced
After we add one new point we can see it in the test list.
At this time the newly added test point/item has the same name and parameters as the last one
We can edit the parameters for the newly added test point/item.
36
PONOVO POWER CO., LTD
PowerTest Advanced
37
PONOVO POWER CO., LTD
PowerTest Advanced
38
PONOVO POWER CO., LTD
PowerTest Advanced
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Note:
All the binary time is calculated from the test start, rather than the fault start time.
39
PONOVO POWER CO., LTD
PowerTest Advanced
Configure channels
In Channel A drop-down selection box we can view all voltage channels from the COMTRADE file and
we need to assign one voltage from the list to the Va output of our test set.
40
PONOVO POWER CO., LTD
PowerTest Advanced
Two channels can be combined together to get a new output. This happens when we need to get the
voltage which is the vector summation from two voltage channels.
Example
• • •
I a ' = ( I a − I b) / 3
• • •
I b' = ( I b − I c ) / 3
• • •
I c' = ( I c − I a ) / 3
In case the recorded data is for the primary side we need to set the ratio for PT and CT.
Here we can see the maximum voltage and current for this COMTRADE file. Proper setting of PT and
CT ratio will avoid them exceeding the available output range of the test set in use.
41
PONOVO POWER CO., LTD
PowerTest Advanced
T1 and t2 indicate the peak values at the position for cursor 1 and cursor 2. dt indicates the time
difference between t1 and t2.
42
PONOVO POWER CO., LTD
PowerTest Advanced
Insert Points
43
PONOVO POWER CO., LTD
PowerTest Advanced
Note:
The maximum sampling rate should not exceed 10kHz
The maximum allowed playback time determined by the current sampling rate is displayed here.
44
PONOVO POWER CO., LTD
PowerTest Advanced
3.5. Edit
Trigger condition
Manual prefault data will be played first and when is pressed the data for the fault will be
played
GPS prefault data will be played first and when GPS control pulse is sensed by the test set the
data for the fault will then be played
Binary Input H prefault data will be played first and when Binary Input H control pulse is sensed by
the test set the data for the fault will then be played
Note:
Optional PGPS-02 GPS Synchronization Device should be used for this application
The pre-fault data is defined by the first section of repetition.
Data repetition
45
PONOVO POWER CO., LTD
PowerTest Advanced
Note:
In Manual and GPS control mode the first repetition section will be used as prefault data.
Similarly we can also define to cut the data section from the COMTRADE data.
Begin define the start time of the section to be cut
End define the end time of the section to be cut
We can select to cut three different sections of data
46
PONOVO POWER CO., LTD
PowerTest Advanced
47
PONOVO POWER CO., LTD
PowerTest Advanced
48
PONOVO POWER CO., LTD
PowerTest Advanced
Out 1, 2, 3, 4
It is based on the comtrade file. If there is binary output in COMTRADE file, there will be option
available, vice versa.
The binary in COMTRADE file is mapped to the binary output 1-4 of the tester.
Maximum 4 binary output are supported..
Location
It is for reserved.
49
PONOVO POWER CO., LTD
PowerTest Advanced
Note:
1. When a new test point is added, a COMTRADE should be imported to this new test point.
2. Between the two test point/items, the waveform is not continuous.
50
PONOVO POWER CO., LTD
PowerTest Advanced
4. RX Characteristic Sweep
This module is used to map out the characteristic boundary of the impedance relay.
During the test process a series of shots will be generated to search out the boundary along this shot
line. Then next shot at a different angle will be generated. In this way we can then find out the boundary
at different angles.
51
PONOVO POWER CO., LTD
PowerTest Advanced
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
TPrepare
Time for relay to reset at the first test cycle.
TPrefault
Prefault time setting for each test cycle
During this time the test set will supply normal system balance voltage.
PT
Select it according to the actual PT installation position
Busbar side
Line side
CT polarity
Select it according to the actual CT polarity
Busbar: polarity is toward busbar side
Line: polarity is toward line side
CB Sim.
When optional Circuit Breaker Simulator is used we can need to select Yes here.
52
PONOVO POWER CO., LTD
PowerTest Advanced
Open Time
Related to CB Sim.
Close Time
Related to CB Sim.
Note:
Please contact the manufacture for more information about the optional Circuit Breaker Simulator
and its application.
Fault Angle
If we select fixed angle in Fault Inc. Mode we need to set the angle here
DC offset
Here we can define if DC offset is to be added when fault occurs
Test Mode
We can select the follow test modes.
IConst: Constant current
VConst: Constant voltage
ZsConst: Constant system impedance
KE(∣K0/KR∣Z0/Z1∣)
Setting for ∣K0∣, RERL or ∣Z0∣
KE(Phi(K0) KX Phi(Z0/Z1)
Setting for Phi(K0), XEXL or Phi(Z0)
KE given as
There are three types of KE mode available and we need to select the one according to the relay under
test.
∣K0∣, Phi(K0)
RERL, XEXL
∣Z0∣, Phi(Z0)
Search Mode
Here we define the search mode for searching the boundary along one shot line.
There are two methods available
Dichotomic
53
PONOVO POWER CO., LTD
PowerTest Advanced
Linear
Vz Define
0 Output zero
1.732*3Vo 1.732 times of zero sequence voltage
-1.732*3Vo -1732 times of zero sequence voltage
3Vo Zero sequence voltage
-3Vo Reverse output zero sequence voltage
Vs System voltage
Phi(Vz) Ref.
The reference phase at 3V0
Phi(Va) The same phase as Va
Phi(Vb) The same phase as Vb
Phi(Vc) The same phase as Vc
Phi(Vab) The same phase as Vab
Phi(Vbc) The same phase as Vbc
Phi(Vca) The same phase as Vca
|Vz|
The output voltage VS
Phi(Vz)
The phase of VS
ERRORRANGE
The error range when there is distance characteristic figure.
ABSERROR
Absolute error range
LINEANGLE
Line angel
The three buttons are reserved for R&D development, not for testing purpose.
54
PONOVO POWER CO., LTD
PowerTest Advanced
Bin.In1, 5
Trip A
Trip ABC
Bin.In2, 6
Trip B
Trip ABC
Bin.In3, 7
Trip C
Trip ABC
Bin.In4, 8
Reclose
Input Sel
Select to use binary 1234, or 5678.
Out 1-8
binary Output, Open or Close
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
55
PONOVO POWER CO., LTD
PowerTest Advanced
OutputHoldTime
Output hold time delay
56
PONOVO POWER CO., LTD
PowerTest Advanced
Name
Edit test point/item name here.
Fault type
Z End
The impedance value at the end search point
Angle End
The angle at the end search point
Z Start
The impedance value at the start search point
Phi Start
The angle at the start search point
Z Step
The search frequency step
Z End
The end search point can be changed after selecting it.
57
PONOVO POWER CO., LTD
PowerTest Advanced
Current
The fault current
It is enabled when IConst is selected in Test Mode in Para, showing in below.
Voltage
The fault voltage
It is enabled when IConst is selected in Test Mode in Para, showing in below.
Tmax
The fault output time
I Load
The load current
Power Angle
The load power angle
Frequency
The power system frequency
58
PONOVO POWER CO., LTD
PowerTest Advanced
Assessment
The trip time error could be set here to compare between the actual testing value and reference value.
Results
Here it only shows the results that can’t be edited.
59
PONOVO POWER CO., LTD
PowerTest Advanced
60
PONOVO POWER CO., LTD
PowerTest Advanced
Click Import.
Then we will be asked to select the folder where RIO files are saved.
Under the installation directory we can see Test Objects_RIO
61
PONOVO POWER CO., LTD
PowerTest Advanced
Select RIO
Select the manufacture and double click the mouse button to enter into that folder. Select the RIO file
we need and confirm the operation.
62
PONOVO POWER CO., LTD
PowerTest Advanced
63
PONOVO POWER CO., LTD
PowerTest Advanced
When we open the module a group of default test point/items/points will appear in the test list
Direct Add
In the parameter page click Add to add a new test point/item.
64
PONOVO POWER CO., LTD
PowerTest Advanced
Quick Add
Z Center
The impedance at the search center point
Phi Center
The impedance angle at the search center point
Radius
The search radius based on the search center point
Phi Start
The angle at the start search point
Phi Stop
The angle at the stop search point
Phi Step
The search angle step
Search Step
65
PONOVO POWER CO., LTD
PowerTest Advanced
I Load
The load current
Power Angle
The load power angle
Fault type
Different fault types are available.
Criterion
The criterion for valid search point
Note:
If we only search a certain distance, generally we will set t>0.001S.
If we search the fixed time, for example, Tz1<Tz2<Tz3, if we test Zone 2, the criterion should be set as
below.
66
PONOVO POWER CO., LTD
PowerTest Advanced
67
PONOVO POWER CO., LTD
PowerTest Advanced
5. Synchronizer
This module is used to check synchronizing relay.
The following test functions are included
68
PONOVO POWER CO., LTD
PowerTest Advanced
Purpose of synchronizer
Synchronizing relay is used for the following purpose
Synchronize the generator to the system
Synchronize the two parts of power network
Manually close the circuit breaker
Check the synchronization status
Principle of synchronizer
The synchronizing relay will measure the voltages, phase angle and frequencies of the two system.
When voltage, phase angle and frequency difference between the two system meet the pre-defined
condition the command will be sent by synchronizing relay to close the circuit breaker.
T1 pulse width
T2 pulse cycle
The pulse width and pulse cycle settings are associated to the response time of the generator’s voltage
and frequency regulating system.
For some relays these settings are internally build and for some other relays these settings should be
set separately.
69
PONOVO POWER CO., LTD
PowerTest Advanced
Leading Angle
Some relays may need to set this setting here.
Leading Time
We can set the time here for our assessment use
dv
Permissible voltage difference setting
dF
Permissible frequency difference setting
Vadj.Cycle
Voltage adjustment cycle setting
Fadj.Cycle
Frequency adjustment cycle setting
The buttons above are reserved for R&D development, not for testing purpose.
70
PONOVO POWER CO., LTD
PowerTest Advanced
Vsnom
Nominal voltage for system side
Fsnom
Nominal frequency for system side
Vgnom
Nominal voltage for generator side
Sel Vg
Nominal frequency for generator side
Ref. Phase
Here we define the reference phase for generator side voltage when we select Vs->Vabc,Vg->Vz
mode.
For example, if Vz is connected to the synchronizing relay as Vab then we need to select Vab here.
Trans. Connect
The PT (potential transformer) use for system side and generator side may have different vector group.
And the phase shift caused by this vector group difference must be considered. We need to select the
vector group based on the actual situation.
Tsynmax
Here we define the maximum allowed time duration for synchronizing process.
The three buttons are reserved for R&D development, not for testing purpose.
71
PONOVO POWER CO., LTD
PowerTest Advanced
72
PONOVO POWER CO., LTD
PowerTest Advanced
Name
The name can’t be edited here. The name is based on the test point/item chosen.
V-Value check voltage difference
F-Value check frequency difference
Leading Time test leading time
Auto auto-check
Vadj-PulseWidth test pulse width for voltage adjustment
Fadj-PulseWidth test pulse width for frequency adjustment
Vg
The setting here should ensure that Vs-Vg is larger than allowed voltage difference setting so
synchronizing relay will not send CB close command when test starts
Fg
The setting here should ensure that Fs-Fg is smaller than the frequency difference setting.
Vg Step
Step for voltage to change
dv/dt dv/dt for controlling voltage to change when receiving the voltage control command from
synchronizing relay.
df/dt df/dt for controlling frequency to change when receiving the frequency control command from
synchronizing relay.
Example 1:V-Value
Test process:
Since the frequency difference is set within the allowed setting the voltage difference will be the only
factor to influence the synchronizing action.
73
PONOVO POWER CO., LTD
PowerTest Advanced
The voltage will change one step for each cycle (0-360 deg). The test will terminate when circuit
breaker close command from synchronizing relay is sensed by test set.
Note:
The Fg must be set in the way that Fs-Fg is not equal to zero.
Example 2:F-Value
Test process:
Since the voltage difference is set within the allowed setting the frequency difference will be the only
factor to influence the synchronizing action.
The frequency will change one step for each cycle (0-360 deg). The test will terminate when circuit
breaker close command from synchronizing relay is sensed by test set.
Test process:
Since the voltage difference is set within the allowed setting the frequency difference will be the only
factor to influence the synchronizing action.
The frequency will change with a speed set by df/dt when receiving the frequency control command
from synchronizing relay. The duration for frequency to change is determined by the frequency control
pulse width.
The test will terminate when circuit breaker close command from synchronizing relay is sensed by test
set
Example 4: Auto
Test process:
The voltage and frequency will change with a speed set by dv/dt and df/dt when receiving voltage and
frequency control command from synchronizing relay. The duration for voltage and frequency to
change will be determined by the voltage and frequency pulse width
The test will terminate when circuit breaker close command from synchronizing relay is sensed by test
set.
Example 5: Vadj.-PulseWidth
Test process:
Since voltage difference is larger than allowed setting the synchronizing relay will send voltage
adjustment pulse to test set.
Test set will measure the pulse width and cycle accordingly and record them in the result.
Note:
The Fg must be set in the way that Fs-Fg is not equal to zero.
Example 6: Fadj.-PulseWidth
Test process:
Since frequency difference is larger than allowed setting the synchronizing relay will send frequency
adjustment pulse to test set.
74
PONOVO POWER CO., LTD
PowerTest Advanced
Test set will measure the pulse width and cycle accordingly and record them in the result.
75
PONOVO POWER CO., LTD
PowerTest Advanced
Assessment
The error could be set here to compare between the actual testing value and reference value.
Act (Results)
Here it only shows the results that can’t be edited.
76
PONOVO POWER CO., LTD
PowerTest Advanced
Common wiring
Click button to view the wiring diagram under different Sel Vg selections.
77
PONOVO POWER CO., LTD
PowerTest Advanced
Note:
The above diagrams are for generator. If there are two grid interconnection, the voltage wiring
connection keeps the same, it is required another reclosing connection. The frequency and voltage
connections are not changed. See below.
78
PONOVO POWER CO., LTD
PowerTest Advanced
79
PONOVO POWER CO., LTD
PowerTest Advanced
Test Object
Substation:Ponovo Bay:Testing Laboratory
Device:XXX Type:cccc
Manufacture:China SN:P0408389
Tested by:XXX Date:05/06/2008 17:44
1.Synchronizer
Leading Angle=0.500Deg dF=0.200Hz
Leading Time=0.500S Vadj. Cycle=10.000S
dV=2.000V Fadj. Cycle=15.000S
Vsnom=100.000V Fsnom=50.000Hz
Vgnom=100.000V Sel Vg:Vs->Va,Vg->Ub
Ref. Phase:Ua Trans. Connect:Y/Y-12
Tsynmax=400S
80
PONOVO POWER CO., LTD
PowerTest Special
PowerTest
Special
VERSION: Special-AE-2.30
DATE: JUNE 2017
This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of this manual
please contact PONOVO POWER CO., LTD in advance.
1
PowerTest Special
Reminder
1. Please carefully read the PowerTest Concept before you read the
PowerTest Speical.
2
PONOVO POWER CO., LTD
PowerTest Special
Content
1. Energy Meter ..................................................................................................................................5
1.1 Set group parameters ................................................................................................................6
1.2 Set test parameters ....................................................................................................................8
1.3 Set assessment criterion ........................................................................................................ 11
1.4 Set wiring................................................................................................................................... 11
2. High Burden Relay ..................................................................................................................... 12
2.1. Set group settings ............................................................................................................... 13
2.2. Set group parameters ......................................................................................................... 13
2.3. Set test point/ item parameters ......................................................................................... 14
2.4. Set binary.............................................................................................................................. 16
2.5. Set wiring .............................................................................................................................. 17
2.6. Enter results ......................................................................................................................... 17
2.7. Test process......................................................................................................................... 18
2.7.1 Preparations ...................................................................................................................... 18
2.7.2 Trip current and time test ................................................................................................ 18
2.7.3 Angle test ........................................................................................................................... 20
3. Power Swing Simulation ............................................................................................................ 21
3.1. Principle of power swing..................................................................................................... 22
3.2. Simulation principle ............................................................................................................. 22
3.3. Set group setting ................................................................................................................. 23
3.4. Set group parameters ......................................................................................................... 24
3.5. Set group binary .................................................................................................................. 25
3.6. View power swing parameters .......................................................................................... 26
3.7. Set test point/ item parameters ......................................................................................... 27
3.8. Set Results ........................................................................................................................... 30
3.9. Set wiring .............................................................................................................................. 30
3.10. Set characteristic ............................................................................................................. 31
3.11. Set GOOSE Data ............................................................................................................ 31
3
PONOVO POWER CO., LTD
PowerTest Special
4
PONOVO POWER CO., LTD
PowerTest Special
1. Energy Meter
This module is designed to check the functionality and accuracy of energy meter.
Note: To check some type energy meters the optional scanning head is required to turn the LED flash
on energy meter into electrical pulse which can be sensed by the test set. Please
contact support@relaytest.com for more details regarding the scanning head
5
PONOVO POWER CO., LTD
PowerTest Special
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below
Meter type
Select
Pulse / Unit
Select pulse unit as pulse per kVARh((kWh, kVAh)
Unit / Pulse
Select pulse unit as kVARh((kWh, kVAh) per pulse
Constant
Example
Side
Secondary It means the meter for secondary
Primary It means the meter for primary
6
PONOVO POWER CO., LTD
PowerTest Special
IPri
It is the primary current for CT.
ISec
It is the secondary current for CT.
VPri
It is the primary voltage for CT.
VSec
It is the secondary voltage for CT.
Input Sel
Normal Binary input 1-8
Ext.(High Speed) Binary input 9-12
7
PONOVO POWER CO., LTD
PowerTest Special
Name
Edit here the name for the current test point
Phase
Indicate the wiring type for the energy meter.
8
PONOVO POWER CO., LTD
PowerTest Special
Note: Pulse output from energy meter or scanning head must be connected to binary input 1
Current
Percent of rate current
Voltage
Percent of rate voltage
Stab. time
Stabilization time required for energy meter to enter into stable working condtion
Pulses
Pulses numbers to be sensed for testing.
Est. time
Time required for the test and this time is calculated based on the Pulses number setting and the
voltage and current settings.
Waveform
We can select to add harmonic to the voltage or current output.
9
PONOVO POWER CO., LTD
PowerTest Special
Example
nd
In this example we have set to add 5% of 2 harmonic to the current to be supplied to the energy
meter.
10
PONOVO POWER CO., LTD
PowerTest Special
We can set the value based on the accuracy of the meter under test
The results column here is only to show the test results can’t be edited.
11
PONOVO POWER CO., LTD
PowerTest Special
Connected to the main test set the Phpc-01 Current Booster will provide one channel current source
and will be controlled by this module.
Necessary voltage sources can also be provided to make relay in proper working condition.
This module is used to test trip current, time and direction of high burden relay.
Both manual and auto methods can be applied.
Note: There are special relay tester type supporting this function.
12
PONOVO POWER CO., LTD
PowerTest Special
MTA
Maximum Torque Angle
Leadangle
Boundary angle 1 (Lead angle)
Lagangle
Boundary angle 2 (Lag angle)
Click “Para.” button to enter into group parameter page. Group test parameter page along with default
settings is shown below.
If we change the test mode from “to – from” to “to-from-to”, then we may have different ways to control
the selected variable automatically.
Type
to – from
Check trip only.
to-from-to
Check trip and drop-off.
Angle Define
The reference phase: V Lead I or I lead V
13
PONOVO POWER CO., LTD
PowerTest Special
I
The high burden current impedance and phase
Va,Vb,Vc
Output voltage
Current
Amplitude or Angle
Step
The step for current
Time
In auto mode, it is the step time.
From
The start value in auto mode
To
The ending value in auto mode
Transformer Ratio
Show PHPC01 ratio gear
Frequency
The power system frequency
Out1 ~ Out4
Control binary output
14
PONOVO POWER CO., LTD
PowerTest Special
Example
In this test, Binary output 1 and 2 are close, Binary output 3 and 4 are open.
Auto
Auto test mode
Manual test mode
Note: Please set this factor carefully, otherwise the current accuracy will be affected.
Trip time
Show the trip time
This control button is designed to test the relay tripping time in manual mode.
15
PONOVO POWER CO., LTD
PowerTest Special
Input Binary
Input signal
Not used, Start, Trip, Trip LA/B/C, Sig. 1-8
Display name
The display name can be user-defined.
Trigger logic
OR, AND
16
PONOVO POWER CO., LTD
PowerTest Special
17
PONOVO POWER CO., LTD
PowerTest Special
2.7.1 Preparations
Step 1: Get wiring connection well according to PHPC01 manual.
Step 2: Set proper ratio gear on PHPC01 according to the current range of the test relay
Step 3: Set factor according to the PHPC01 calibration factor list.
Set the step and control the current by up/down buttons until the relay trips and drop-off.
Step 1
Set normal voltages and currents for a health system
Step 2
Start output and the lock button become green.
Step 3
Press Lock button
Step 4
Modify current to faulty status.
Step 5
Press Lock button to release the lock.
18
PONOVO POWER CO., LTD
PowerTest Special
At the same time the internal timer will start. When relay trips the timer will stop and the tripping time will
be displayed.
Step 1
Set initial current/voltage impedance and phase
Step 2
Select type in Para.
Step 3
Set current step, time, from and to parameters
Step 4
Run the test
Step 5
Save the report
19
PONOVO POWER CO., LTD
PowerTest Special
Step 2
Manually control the up/down buttons to make the relay trip or the binary input changes.
Record the angle between IA showing in the interface and reference voltage, this angle is boundary
angle 1.
Step 3
Manually control the up/down buttons in opposite direction to make the relay drop-off or the binary input
is recovered to the initial status. And continue to control the current angle until the relay trip again or the
binary input changes. Record the angle between the present current and reference voltage, this angle
is boundary angle 2.
Step 4
Calculate MTA with boundary angle 1 and 2.
Step 2
Select type in Para.
Step 3
Set current step, time, from and to parameters
Step 4
Run the test to search the boundary angle 1 and 2 automatically. After search, calculate the MTA.
Step 5
Save the report.
20
PONOVO POWER CO., LTD
PowerTest Special
This module is used to simulate the power swing. This can be a tool for relay test engineer to observe
the relay behavior during dynamic power swing process.
21
PONOVO POWER CO., LTD
PowerTest Special
The typical system model used for simulating the power swing is as follows
We can easily simulate the power swing by defining the following settings:
Internally the swing voltage and current will be calculated by taking account of the above parameters
and other parameters in our power swing module.
22
PONOVO POWER CO., LTD
PowerTest Special
Swing Number
It is the power swing number repeated.
Time
It is setting fault time.
The buttons above are reserved for R&D development, not for testing purpose.
23
PONOVO POWER CO., LTD
PowerTest Special
Tprefault
Prefault time will be used when simulating the power swing with fault.
CT Polarity
Select the installation position of CT.
Line: The CT primary is connected in line.
Busbar: The CT primary is connected in busbar.
The three buttons are reserved for R&D development, not for testing purpose.
24
PONOVO POWER CO., LTD
PowerTest Special
Out
Binary Output, Open or Close
Output Mode
Two modes available, Bin.In and Time
OutputTime
The output time delay
OutputHoldTime
Output hold time delay
25
PONOVO POWER CO., LTD
PowerTest Special
The power swing center is calculated by taking account of system settings set in group parameters.
The position of power swing center can be changed by changing the system settings
26
PONOVO POWER CO., LTD
PowerTest Special
Name
Edit here the name for the current test point
Swing Cycle
The time is used to complete on cycle of power swing (normally set range: 2-5s)
Swing Number
It is the number of power swing cycle to simulate
|Em|/|En|
It is the ratio of Em/En
The ratio of Em/En will influence the position of power swing center.
27
PONOVO POWER CO., LTD
PowerTest Special
from-to-from
Swing angle will change from angle start to angle end and then from angle end to angle start
Increase speed
Swing angle will change from angle start to angle end
Decrease speed
Swing angle will change from angle end to angle start
Trip Contact
Assign the binary input for sensing the tripping signal from the relay
Available binary inputs are A, B, E, F, G,H
28
PONOVO POWER CO., LTD
PowerTest Special
Fault type
|Zf|
Fault impedance
If
Fault current
KE given as
Type
There are three types of KE mode available and we need to select the one according to the relay under
test.
KE
Module: It is the value of KE
Anlge: It is the angle of KE.
RE/RL & XE/XL
Kr: It is the resistance factor
Kx: It is the reactive factor.
ZE/Z1
Module: It is the value of ZE/Z1
Anlge: It is the angle of ZE/Z1
dz/dt
Impedance change rate per second
The dz/dt will be activated after the dz/dt column is selected. When the dz/dt is chosen, the Swing
Cycle will be disabled.
Add
Copy the same test point/item at the cursor position.
Remove
Remove the present test point/item, but if there is only one test point/item, it is not allowed to be
removed.
Clear
Clear the test results at the present test point/item.
29
PONOVO POWER CO., LTD
PowerTest Special
Click “Results” to enter into the assessment setting and result display page.
Note: The result area only displays the values of Trip. Acc. Signal and Dec. Signal that can’t be edited.
30
PONOVO POWER CO., LTD
PowerTest Special
31
PONOVO POWER CO., LTD
PowerTest Special
32
PONOVO POWER CO., LTD
PowerTest Special
4. Transducer
This module is used to check the accuracy of transducer
Transducer parameters
33
PONOVO POWER CO., LTD
PowerTest Special
Test connection
Name
Edit the name here for the current test point.
Vnom (L-N)
It is the nominal L-N voltage of transducer input
Current
It is the output current to be injected into transducer.
Angle
It is the angle between output voltage and current based on power.
34
PONOVO POWER CO., LTD
PowerTest Special
Frequency
It is the fixed frequency at 50Hz.
Class
The accuracy class of transducer and this setting will be used as the assessment criterion.
Stablizing time
The average measuring values during this time will be used to reflect the actual accuracy of the
transducer under test.
Transducer settings
Type
Select Reactive power test, based on our test requirement.
Input range
It is the measuring range of transducer.
Output range
It is the output range of transducer.
Output Unit
It is the output type of transducer.
Input Value
It is the value with accordance of the current or voltage.
Primary Side
Set the primary side rating in case transducer input reflects the primary side value.
The CT and PT ratio part will be activated after selecting primary side.
35
PONOVO POWER CO., LTD
PowerTest Special
Start
Start value of the test points.
Stop
Stop value of the test points.
Step
Step value.
Confirm the setting and we see new test points added in the test list
36
PONOVO POWER CO., LTD
PowerTest Special
The operation is the same with module Time Inversed Current in Protection. Please refer to Chapter 5
Time inversed current in PowerTest Protection.
Here we invite you to focus on the wiring connection especially for the following reasons:
For the two reasons, we adapt different wiring connection showing in below picture.
Wiring connection
37
PONOVO POWER CO., LTD
PowerTest Special
38
PONOVO POWER CO., LTD
Professional Solution Provider For Protection Relay Test