SIPROTEC 5 Application Note Distancia
SIPROTEC 5 Application Note Distancia
SIPROTEC 5 Application Note Distancia
com/protection
SIPROTEC 5 - Application:
SIP5-APN-016
Distance protection with tele-protection (pilot
protection) on an OHL feeder
Content
SIP5-APN-016 2
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
1.2 Overview
Every protection engineer has his own preference when calculating settings. Some prefer calculations in
primary, others secondary and some in per unit quantities. The finer details of distance protection setting co-
ordination are also not addressed here as this is typically obtained with special software tools. The zone
reaches are therefore predefined in Table 1 without further calculation.
Single pole tripping will be permitted for faults cleared by the under-reaching zone 1 and the tele-protection.
For the tele-protection the forward over-reaching time delayed Zone 2 will be applied with a POTT scheme.
Bus1
Bus3
LS1 VT1
Line 2
CT1
ISO1
Line 1
VT2 Line3
CT2
LS2
ISO2
Feeder 2
CT3 VT3
LS3
Bus2
VT4
3 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
The distance protection is applied to protect Line1 in Figure 1 above with the zone reaches defined in Table 1
below.
The values given in the table below are typically obtained by protection co-ordination studies using software
tools (e.g. PSS®SINCAL). For this application example the zone reaches as defined below will be used:
Zone number Function Reach Time delay
Zone 1 Fast underreach protection for Line 1 80% Line 1 0.00 sec
Zone 2 Forward time delay backup, overreach 20% less than Z1 1 time step
reach on Line 3
Zone 3 Reverse time delay backup 50% Z Line 1 2 time steps
Zone 5 Non-directional 120% Line 2 3 time steps
Table 1
Although the configuration in Figure 1 shows a breaker-and-a-half application, this has no significant impact
on the general application of distance protection as explained in this example. For this general case it is
assumed that the two CT’s are identical so that they may be replaced by a single CT which is equivalent to the
double busbar application with only one CT. The allocation of the CT’s and VT’s to the various measuring
points as well as the circuit breakers to the relevant function groups is covered in a separate application
description.
SIP5-APN-016 4
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
Parameter Value
System data Nominal system voltage phase-phase 400 kV
Power system frequency 50 Hz
Maximum positive sequence source impedance 10 + j100
Maximum zero sequence source impedance 25 + j200
Minimum positive sequence source impedance 1 + j10
Minimum zero sequence source impedance 2.5 + j20
Maximum ratio remote infeed / local infeed (IRem/ILoc) 3
Instrument Voltage transformer ratio (LINE) (VT2) 380 kV / 100 V
transformers
Voltage transformer ratio (BUS) (VT1) 400 kV / 110 V
CT1 and CT2: Current transformer ratio 1000 A / 1 A
CT1 and CT2: Current transformer data 5P20 20VA Pi=3VA
CT1 and CT2 secondary connection cable 2.5 mm2 50m
CT ratio / VT ratio for impedance conversion 0.2632
Line 1 - length 80 km
Maximum load current 250% of full load
Line data Minimum operating voltage 85% nominal voltage
Sign convention for power flow Export = negative
Full load apparent power (S) 600 MVA
Line 1 – positive seq. impedance per km Z1 0.025 + j0.21 Ω/km
Line 1 – zero seq. impedance per km Z0 0.13 + j0.81 Ω/km
Line 2 – total positive seq. impedance 3.5 + j39.5 Ω
Line 2 – total zero seq. impedance 6.8 + j148 Ω
Line 3 – total positive seq. impedance 1.5 + j17.5 Ω
Line 3 – total zero seq. impedance 7.5 + j86.5 Ω
Maximum fault resistance, Ph-E 250 Ω
Average tower footing resistance 15 Ω
Earth Wire 60 mm2 steel
Tower data Distance: Conductor to tower (ground) 5m
Distance: Conductor to conductor (phase-phase) 12 m
Circuit breaker 1 Trip operating time 60 ms
and 2
Close operating time 70 ms
Table 2: Power system and line parameters
5 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
Based on the source and line impedance, the following minimum fault current levels can be calculated for
faults on Line 1:
U source
I fault = with Usource = 400 kV
3 ⋅ Z tot
If fault resistance is neglected for 3 phase faults:
Ztot = sum of positive sequence source and line impedance (as only current magnitudes are being calculated,
only the magnitude of the impedance is relevant)
400kV
I 3 phmin =
3 ⋅ 117.4
I 3 phmin = 1967 A
400kV
I1 phmin =
3 ⋅ 167.3
I1 phmin = 1380 A
Z tot _ R = RF + Z tot
Z tot = 250 + 19.8 + j166.1
Z tot = 316.8
The minimum single phase fault current with high resistance is therefore:
SIP5-APN-016 6
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
400kV
I1 phmin_ R =
3 ⋅ 316.8
I1 phmin_ R = 729 A
7 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
SIP5-APN-016 8
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
For the distance protection the residual compensation factors “Kr and Kx” must be set for the ground loop
measurement. The default setting format “Kr, Kx” is used in this application note. Alternatively the complex
“K0” factor may also be used.
The setting of “Block monitoring dir.” should remain “off”. It can be changed to “on” during testing and
commissioning to avoid a flood of test related signals arriving in the control centre. This blocking can also be
activated via binary input.
9 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
sampling frequency so that a fixed number of samples per cycle are available. Although the distance
protection does not use re-sampling the tracking is set to “active” for the line current measurement because
other functions in the device may use frequency tracking.
The rated primary and secondary current are set according to the application data given in Table 2.
The Current range setting for distance protection is fixed at 100 x IR.
The CT polarity is selected by correct application of the star point. This is done with the selection of the CT
neutral point direction which may be towards the protected object (line) or not. The correct setting must be
checked during commissioning or with “on-load” direction check.
The setting “Inverted phases” is only relevant when a there is the possibility of reversed phase rotation. For
example the phase sequence in the generator bay of a pumped storage plant has a phase sequence change
when it switches from pumping to generating. In this application the phase sequence is fixed so that this
parameter is set to “none”
The other settings such as e.g. CT error are not applicable to this application. For Line Differential protection
these have significance.
The settings for the 2nd CT, Meas.point I-3ph 2, are exactly the same as the CT’s are identical.
Meas. Pont VT Settings
For the VT the mask for applying the settings is as follows:
SIP5-APN-016 10
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
1.4.3 Recording
The fault recording in SIPROTEC 5 is in the first place provided by the fault log. In the Information Routing the
selection for the fault log can be applied. The oscillographic recording (records) also contain bimary traces
that are selectable in the Information Routing matrix. The following settings cn be applied for the Fault
recorder:
11 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
Z1 = 0.025 + j0.21
⎛X ⎞
Line _ angle = arctan⎜⎜ L ⎟⎟
⎝ RL ⎠
SIP5-APN-016 12
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
Although the residual compensation factors can be set for each zone separately, the setting based on the line
data should be set here.
R E 1 ⎛ R0 ⎞ XE 1 ⎛ X0 ⎞
= ⋅ ⎜⎜ − 1⎟⎟ = ⋅ ⎜⎜ − 1⎟⎟
RL 3 ⎝ R1 ⎠ X L 3 ⎝ X1 ⎠
RE 1 ⎛ 0.13 ⎞ X E 1 ⎛ 0.81 ⎞
= ⋅⎜ − 1⎟ = ⋅⎜ − 1⎟
RL 3 ⎝ 0.025 ⎠ X L 3 ⎝ 0.21 ⎠
RE XE
= 1.4 = 0.95
1116
RL XL
If the fault current (with transients) can cause CT saturation, the setting for CT saturation detection should be
set to yes. This ensures that appropriate stabilization measures are applied to prevent mal-operation due to
CT saturation during faults. When this setting is “yes” the CT saturation threshold must be set. This current
level can be calculated with the given CT data:
n'
CT _ Saturation _ Threshold = ⋅ I nom
5
PN + Pi
with: n' = n ⋅ = actual _ overcurrent _ factor
P'+ Pi
In this example only the 7SA87 relay is connected to the CT, so that the relay burden is 0.05 VA per phase.
Due to the Holmgreen connection, the maximum burden for earth currents is therefore twice 0.05VA =0.1VA.
2 ⋅ l cable ⋅ ρ CU
Rcable =
a cable
lcable = 50 m
ρcu = 0,0179 Ωmm2/m
acable = 2,5 mm2
13 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
therefore:
2 ⋅ 50 ⋅ 0.0179
Rcable =
2 .5
Rcable = 0.72
2
P ' = Rcable ⋅ InomCT + Prelay
P ' = 0.72 ⋅ 12 + 0.1
P ' = 0.82VA
20 + 3
n' = 20 ⋅
0.82 + 3
n' = 120
SIP5-APN-016 14
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
Process monitor
15 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
SIP5-APN-016 16
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
X Z2 Z4
I2
R I1 R
nceda
mpe
Z1
line i
weak I1 I2
strong
source
relay Fault source
resistance
Figure 12: Example, sequential tripping with back-up stage during remote faults
Although the fault is in the Zone 2 range (according to reach co-ordination) it is initially not seen in zone 2
due to the fault resistance and strong remote infeed. The remote end with strong infeed will trip according to
its setting (reach and time delay). When the remote infeed is open the current (I2) resets so that the fault
impedance is seen in Zone 2. With the applied setting, the zone 2 timer was already started on distance
pickup, and zone 2 will trip in the desired time although the fault was initially outside zone 2.
The Line Angle setting must be calculated from the positive sequence line parameters:
Z1 = 0.025 + j0.21
⎛X ⎞
Line _ angle = arctan⎜⎜ L ⎟⎟
⎝ RL ⎠
The remaining settings in Figure 10 can remain on the default values. For details refer to the manual or online
help function.
17 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
For the distance protection a minimum current is required for operation. It is typically left unchanged on the
default value corresponding to 10% of secondary nominal current. As this setting is not relevant for the reach
grading and is generally much smaller than typical load current it is not based on a fault current calculation. If
however weak in-feed conditions exist which may result in internal faults having fault current flow below this
threshold, a special “Weak In-Feed” protection may have to be applied.
The load cut-out is typically only required on long lines where the set zone reaches may include load
impedances. If this is the case the load cut-out should be activated – not the case in this example.
X
Z poly
Maximum Zphi
Load Load
area area R
Minimum Zload
SIP5-APN-016 18
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
19 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
This is converted to a secondary value by multiplying with the conversion factor in Table 2:
A separate resistance reach setting is available for ph-ph measured loops and ph-g measured loops. With the
“Distance characteristic angle” under General above the angle of inclination of the distance characteristic is
set equal to the line angle. The resistance settings of the individual zones therefore only have to cover the
fault resistance at the fault location (faults on the protected line). For the Z1 setting only arc faults will be
SIP5-APN-016 20
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
considered. For this purpose the arc resistance will be calculated with the following equation.
U arc
Rarc =
IF
The arc voltage (Uarc) will be calculated using the following rule of thumb which provides a very conservative
estimate (estimated Rarc is larger than actual value):
The length of the arc is greater than the spacing between the conductors (ph-ph) because the arc is blown
into a curve due to thermal and magnetic forces. For estimation purposes it is assumed that larc is 1.5 times
the conductor spacing. To obtain the largest value of Rarc , which is required for the setting, the smallest value
of fault current must be used (calculated earlier):
For the earth fault, not only the arc voltage must be considered, but also the tower footing resistance. From
the graph in Figure 20 it is apparent that although the individual tower footing resistance is 15 Ω (Table 2)
the resultant value due to the parallel connection of multiple tower footing resistances is less than 1.5 Ω.
⎛ I2⎞
RTF = ⎜1 + ⎟ ⋅ effective _ tower _ footing _ R
⎝ I1 ⎠
RTF = (1 + 3) ⋅ 1.5
RTF = 6Ω( prim)
21 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
SIP5-APN-016 22
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
To obtain the largest value of Rarc , which is required for the setting, the smallest value of fault current must
be used (calculated earlier):
18.75kV
Rarc =
1380 A
Rarc = 13.6Ω
The total resistance that must be covered during earth faults is the sum of Rarc and RTF . A safety factor of 20%
is included and the result is converted to secondary values (division by factor (1 + RE/RL) because Rarc and RTF
appear in the loop measurement while the setting is done as phase impedance or positive sequence
impedance). :
The phase to phase fault resistance reach is calculated along the same lines as the setting for ph-ph resistance.
Initially calculate the ph-ph arc resistance
By addition of a 20% safety margin and conversion to secondary impedance (factor from Table2) the
following minimum setting is calculated (division by 2 because Rarc appears in the loop measurement while
the setting is done as phase impedance or positive sequence impedance):
1.2 * 23 * 0.2632
R ( Z1) =
2
R ( Z1) = 3.63Ω(sec)
23 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
X reach Calculation
Definition Calculation Result
Ohm (sec)
Z1 0.8 x Xline1 0.8 x 80 x 0,21 x 0,2632 3,537
Z2 0.8 x (Xline1 + 0.8 x Xline3) 0.8 x( 80 x 0,21 + 0.8 x 4.606) x 0.2632 6,485
Z3 0.5 x XLine1 0.5 x 80 x 0,21 x 0,2632 2,211
Z5 1.2 x (XLine1 + XLine2) 0.8 x 80 x 0,21 x 0,2632 17,78
The resistance reaches are simply increased proportional to the resistance reaches calculated for Zone Z1:
For the Z2 zone specific residual compensation factors will be used. If the parameter is selected for this
purpose, the required settings are accessible:
SIP5-APN-016 24
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
( X 21 − X Line1 )
R 21 = RLine1 + ⋅ RLine 3
X Line 3
24.64 − 80 ⋅ 0.21
R 21 = 80 ⋅ 0.025 + ⋅ 1 .5
17.5
R 21 = 2.672
25 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
( X 2 − X Line1 ) ( X 2 − X Line1 )
X 2 0 = X 0 Line1 + ⋅ X 0 Line 3 R 2 0 = R 0 Line1 + ⋅ R0 Line 3
X Line 3 X Line 3
24.64 − 80 ⋅ 0.21 24.64 − 80 ⋅ 0.21
X 2 0 = 80 ⋅ 0.81 + ⋅ 86.5 R 2 0 = 80 ⋅ 0.13 + ⋅ 7.5
17.5 17.5
X 2 0 = 103.4 R 2 0 = 13.76
Figure 20: Graphic illustration of positive and zero sequence impedance for Z2
The Kr and Kx factors for Z2 can then be directly calculated using the above results:
1 ⎛ R0 ⎞ 1 ⎛ X0 ⎞
Kr = ⋅ ⎜⎜ − 1⎟⎟ Kx = ⋅ ⎜⎜ − 1⎟⎟
3 ⎝ R1 ⎠ 3 ⎝ X1 ⎠
1 ⎛ 13.76 ⎞ 1 ⎛ 103.4 ⎞
= ⋅⎜ − 1⎟ = ⋅⎜ − 1⎟
3 ⎝ 2.672 ⎠ 3 ⎝ 24.64 ⎠
= 1.38 = 1.07
SIP5-APN-016 26
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
27 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
SIP5-APN-016 28
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
29 SIP5-APN-016
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
The Leader will reset the Flip-Flop when the leader Cycle is successful. This is indicated with the Remote Close
Command from CB1 which is issued when there is no further protection operation within a set time after the
re-close of CB1.
In the Follower the “Max. dead time extension” must be set longer than the release delay from the leader as
set above.
SIP5-APN-016 30
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
1.9 Conclusion
The breaker-and-a-half application with SIPROTEC5 can be achieved with flexible combination of the available
functions. A logical grouping of protection and control functions is possible to cover the special requirements
of all users.
31 SIP5-APN-016
SIPROTEC 5 Application
Fehler! Verweisquelle konnte nicht gefunden werden.
Published by and copyright © 2013:
Siemens AG
Humboldtstr. 59
Siemens AG
Energy Automation
Humboldtstr. 59
www.siemens.com/protection
SIP5-APN-016 32