Franke Seminar Ipoh
Franke Seminar Ipoh
Franke Seminar Ipoh
27/09/2019 1c
Power Quality Solutions
Agenda
Introduction
Capacitor Design
Harmonics
Power factor compensation
Radio frequency interferences RFI
Motor protection
27/09/2019 2
Power Quality Solutions
Introduction
27/09/2019 3
Our History
27/09/2019 5
FRANKE Capacitor Design
27/09/2019 6
FRANKE Capacitor Design
27/09/2019 7
FRANKE Capacitor Design
27/09/2019 8
FRANKE Capacitor Design
27/09/2019 9
Power Target Areas
Harmonics
PFC Motor Protection
Voltage stabilizers
10
Harmonics
27/09/2019 11
Harmonics
• When the load is nonlinear load the current has distortion, this means
current harmonics.
• The current is not sinusoidal
|V|
I
Fourier series
V, I 40, 000
v(t)=Vm sin (2pft + F0)
I7 n from 1
10, 000
- 5, 000
- 20, 000
- 35, 000
- 50, 000
Harmonics
L1
L2 Vdc
L3
Vac
Harmonics
• Example:
– 3 phase drives means 6 diodes bridge
– p= 6
– h= (1x6)-1=5 5x50 = 250 Hz
– h= (1x6)+1=7
– h= (2x6)-1=11
– h= (2x6)+1=13
Harmonics
27/09/2019 17
Harmonics
19
Harmonics – The Problem
20
Harmonic Filters application
p= 4
h= (1x4)-1=3 3x50 = 150 Hz
h= (1x4)+1=5
h= (2x4)-1= 7
h= (2x4)+1=9
27/09/2019 21
Harmonic Filters application
L1
L2
L3
N
27/09/2019 22
Problems due to the Harmonics
• Motors:
– Vibrations and mechanical stress due to the
torque created by harmonic currents.
– Loss on iron increase so increase the temperature
and decrease the life
Problems due to the Harmonics
• Transformers:
• Harmonics :
L1
L2
L3
N
27/09/2019 29
Harmonics and RFI
• RFI:
L1
L2
L3
N
27/09/2019 30
Problems due to the Harmonics
• Standards
– EN61000-3-2 (up to 16 A)
– EN61000-3-12 (up to 75 A)
• Standards
– IEEE 519 limits
27/09/2019 32
FIN HRM
Passive Filter
Active Filter
80
180 80
180
60
60
120
120
40
40
60
20 60
20
Current (A)
Voltage (V)
0 0 V 0 0 I
-20 -20
-60 -60
-40 -40
-120 -120
-60 -60
-180 -180
-80 -80
Supply
LOAD
FIN HRMA
Harmonic Filters application
Passive filters:
normally used on the inverter, where the load is quite stable, in this
situation the passive filter is convenient
36
Harmonic Filters application
Active filter:
in this application the use of an active filter is more convenient, the load
can change with the insertion of the machine. Normally in this application
the current is big but the THD don’t exceed 30%.
For example with a current of 1000 A could be enough a filter of 300 A.
Active
Filter
37
FINHRM Passive Filter
june 2008 38
FIN HRM
FIN HRM5
27/09/2019 43
FINHRM5
380
380
310
310
360 360
155 185
115 Ø8 145 Ø8
H5R.080.060.1170 H5D.080.1170 THD reduced up to 5%
400 Vac-480 Vac (available 690 Vac)
260
260
50 or 60 Hz
5
Up to 750 A
120
135
FINC.0250.M
130 130
overload 150% for 60 s every 10
350
minutes
Reactive power less than 20% on no
load condition
27/09/2019 44
FIN HRMA
Current transformer
Supply
LOAD
FINHRMA New compact Active Filter
• modular system
• module 25 A, 50 A, 75 A, 100 A, 150 A
• Distortion correction ability: <5% TDD
• rack and wall mounting
• Operation voltage: 400 , 480 and 690 Vac
• Frequency: 50Hz and 60 Hz
• Harmonic order: 2nd~50th
• Output ability: 100%,self-limited;
• IGBT Switch frequency: 20kHz
• Full response time: 10ms
• Display/interface: LCD
• Extension: up to 10 units in parallel
• 3 phase plus neutral product with compensation
on neutral 3 times than phase compensation
FINHRMA New compact Active Filter
27/09/2019 51
PF Power Factor – The Problem
Reactive
75kvar
Power
100kW
Real power used
𝑃,𝑟𝑒𝑎𝑙 𝑝𝑜𝑤𝑒𝑟
P𝑜𝑤𝑒𝑟 𝐹𝑎𝑐𝑡𝑜𝑟 𝑐𝑜𝑠Ɵ = 𝑆,𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡 𝑝𝑜𝑤𝑒𝑟
52
PF Power Factor – The Problem
53
Static Var Generator
Reactive
Apparent power Power
Supply
LOAD
Compensate current
FINSVG
Why improve your Power factor?
• Your utility bill will be smaller. Low power factor requires an increase
in the electric utility’s generation and transmission capacity to handle the
reactive power component caused by inductive loads. Utilities usually
charge a penalty fee.
• modular system
• module 25 A, 50 A, 75 A, 100 A, 150 A
• Distortion correction ability: <5% TDD
• rack and wall mounting
• Operation voltage: 400 , 480 and 690 Vac
• Frequency: 50Hz and 60 Hz
• Harmonic order: 2nd~50th
• Output ability: 100%,self-limited;
• IGBT Switch frequency: 20kHz
• Full response time: 10ms
• Display/interface: LCD
• Extension: up to 10 units in parallel
Capacitor bank VS Active Var Generator
Capacitor banks are typically grouped by switch. Output current Active VAR generator is controlled by a current transformer (CT)
is step style, which often leads to over/under compensation. thus obtaining compensation effect with the level of PF 0.99
Conventional compensation is 20ms Dynamic response time is less than 50uS – Total response time is
less than 15ms.
Reactive power is compensated mainly by SCR and capacitors. Filter does not require installation of a filter bank resulting in no
This system may be affected by harmonic resonance which concerns with resonant amplification
causes challenges and prematurely failure.
Only compensates inductive reactive power Compensates both inductive reactive power and capacitive
reactive power
Capacitors provide capacitive reactive power. The output of System is active; Voltage from the grid has little influence on the
reactive power is subject to the voltage of the grid. Reactive compensation capacity
compensation will be low if voltage is low; This causes
inadequate compensation
To have a better compensation, conventional capacitor banks The compensation capacity is the same as the installed capacity
require an installed capacity larger than required
EMC
RFI NOISE
RFI FILTERS
27/09/2019 58
Interferences
Example
59
Noise vs Frequency
61
Power drive system full concept scheme
L1 L2 L3
PWM
1500 V
500 V
200 ns
CE Compliance
89/336/CEE Directive
Mandatory since January 1st 1996
2004/108/EC Directive
Mandatory since July 1st 2007
2014/30/EU Directive
Mandatory since July 20th 2016
CE Compliance
DIRECTIVE 2014/30/EU
Minimum requirements
EMISSIONS IMMUNITY
Standards
Conducted Emission
Required Instrumentation:
Receiver
Reference impedance: Line Impedance
Stabilization Network (L.I.S.N.)
Voltage probe (High current)
Emission (set up)
Network
E.U.T. L.I.S.N. Line
Network
E.U.T.
Line
Probe
Voltage between
phase and the Receiver
reference (ground)
in the frequency
band from 150 KHz
up to 30 MHz
What does this disturbance look like?
Filters attenuation
71
What does this disturbance look like?
73
Filters application
74
CE Has More Than One Limit
What works for VFDs may not work for the panel!
RBW 9 kHz
MT 100 ms
Att 10 dB PREAMP OFF
110
SGL
1 PK 618003QP
100
CLRWR
90
55011QP
80
70
PRN
60
6DB
50
40
30
20
10
L1
L2
L3
Filter
Measure here
Inverter
Motor Motor
settembre 2010
Filters
77
Filters
Advantages of Enerdoor
5 Year Warranty
UL/CSA up to 600Vac for three-phase filter and three-phase
plus neutral
Only manufacturer with parallel filter for low frequency
attenuation.
Complies with UL508A.
25 years of experience dealing with EMC interference.
Can provide EMC and FCC testing of customers machine on-
site.
78
Filter Applications
79
Grounding - Filter
Panel Layout
Test Results
80
Grounding - Filter
Panel Layout
Test Results
81
Filter Installation
L1
L2
L3
YES Filter
Filter
0.5 – 0.6 m
Drive
Drive
NO
82
Filter Installation
Motor Motor
83
Filters application
Main switch
3 phase
series filter
PLC
Servodrives / VDF
Filters application
Main switch
3-phase
parallel filter
3 phase
series filter
Servodrives
Servodrives
PLC
Servomotors Servomotors
Filters application
Main switch
3-phase parallel
filter
Servodrives 30Amps
PLC
3 phase
series
filter
Main switch
3-phase
parallel filter Servomotors
EMI Solution
FIN538S1
FIN230SP FIN1500 FIN3755
FIN730 FIN1900 FIN1740ESM
FIN1240
Three Phase Filter – Parallel Filter
Application
L1
L2 Filter
L3
june 2008 89
Three Phase Filter – Parallel Filter
90
Three Phase Filter – Parallel Filter
Motor
100A
Motor Motor Motor
91
Single Phase Filter
june 2008 92
Three Phase Filter (FIN538S1)
93
Three Phase + Neutral Filter (FIN1740ESM)
94
EMC
RFI NOISE
MOTOR PROTECTION
27/09/2019 95
Power Target Areas
Harmonics
PFC Motor Protection
Voltage
stabilizeers
96
Motor Protection
Downtime Production
Loss of Precision
97
Solutions
• Output reactor
• Sine wave filter
• Snubber
• High frequency inductance
Output reactors
Without choke
100
Sinus filter
Motor
Motor Protection – How Does it Work
102
Sinus filters
103
Motor protection Solution
Snubber reduces dV/dt spikes, improving motor life and reducing stress to
the components.
2500
2000
Voltage
1500
Drive Motor
1000
No snubber
Snubber 500 Enerdoor snubber
0
0 400 800 800
(L-PE) (L-PE) (L-PE) (N-PE)
Speed
Solutions - Snubber
No snubber filter
Max: 1104 V
Min: -480 V
dv/dt: ~ 3.04 kV/us
105
Motor protection
Initial condition
108
Solutions - Snubber
109
High frequency reactors
110
High frequency reactors
Setup
2ft 20ft
Load
Reactor
PRODUCT A PRODUCT B
3-phase high frequency
3-phase load reactor load reactor
V = 480Vac V = 480Vac
L = 2.4mH L = 2.4mH
I = 25 A I = 25 A
Core Material: Core Material:
Iron laminate high frequency material
LABORATORY TEST
Temperature Testing
• Wire Temperature
• Laminate Temperature
27/09/2019 113