Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

NYTRO® LIBRA (English) PDS

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PRODUCT DATA SHEET

NYTRO® LIBRA
Property Unit Test Method Specification Limits Typical Data
Min Max
1 - Function
Viscosity, 40°C mm²/s (cSt) ISO 3104 12 9.3
Viscosity, -30°C mm²/s (cSt) ISO 3104 1800 1050
Pour point °C ISO 3016 -40 -51
Water content mg/kg IEC 60814 30 < 20
Breakdown voltage kV IEC 60156
- Before treatment kV IEC 60156 30 40-60
- After treatment kV IEC 60296 70 > 70
Density, 20°C kg/dm³ ISO 12185 0.895 0.875
DDF at 90°C IEC 60247 0.005 < 0.001
2 - Refining/stability
Colour ISO 2049 1.5 < 0.5
Appearance at 15°C IEC 60296 Clear, Free from Clear, Free from
Sediment Sediment
Acidity mg KOH/g IEC 62021 0.01 < 0.01
Interfacial tension at 25°C mN/m IEC 62961 40 47
Corrosive sulphur DIN 51353 Non-Corrosive Non-Corrosive
Potentially corrosive sulphur IEC 62535 Non-Corrosive Non-Corrosive
Corrosive sulphur ASTM D1275 Non-Corrosive Non-Corrosive
DBDS mg/kg IEC 62697-1 Not Detectable Not Detectable
Antioxidants wt % IEC 60666 Not Detectable Not Detectable
Metal passivator additives mg/kg IEC 60666 Not Detectable Not Detectable
Other additives * None None
2-Furfural and related compounds mg/kg IEC 61198 < 0.05 < 0.05
content
Aromatic content % IEC 60590 9
3 - Performance
Oxidation stability at 120°C, 164 h IEC 61125
- Total acidity mg KOH/g IEC 61125 1.2 0.7
- Sludge wt % IEC 61125 0.8 0.17
- DDF at 90°C IEC 61125 0.500 0.041
4 - Health, safety and environment (HSE)
Flash Point, PM °C ISO 2719 135 150
PCA wt % IP 346 < 3.0 < 3.0
PCB mg/kg IEC 61619 Not Detectable Not Detectable
*this product contains no undeclared additives Severely hydrotreated insulating oil
NYTRO LIBRA is an uninhibited insulating oil meeting IEC 60296 Ed. 5 (2020) and is Issuing date: 09-23-2020
Type B, TVBU. Breakdown voltage after treatment as per definition in IEC 60296,
section 6,4

You might also like