Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Hoja de Datos - Válvulas de Control (ISBL) : RLP-HTNCB-HDD-J-YD-3CILP17.14-0020-H1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1 TAG FV 560202

2 Service CONTROL CAUDAL DE DESCARGA DE BOMBAS DE CARGA J-5601A/B


GENERAL 3 Location Area Classification 6"-P-56-0-02021-D1-NI ZONE 2, IIC, T3
4 P&ID RLP-HTNCB-PID-A-YD-3CILP17.14-0002-H3 4035-10-0100-IG-PR-PI-
5 Line Size Schedule 6 in 80 001
6 Type Steam Jacket Globe No
7 End Connection In End Connection Out NPS ___ / 600# NPS ___ / 600# RF - 125-250 RMS
8 Body/Bonnet Material Body Liner Material ASTM A216-WCB -
VALVE BODY
9 Liner Material Flow Direction - By Vendor
10 Bonnet Type Packing Material Standard - Integral or screwed "V" shape Teflon rings
11 Bellow Seal No
12 Type Size API 553 _____ inch (1)
13 Guide Plug Single seat cage-guided Balanced
14 Rated Cv Characteristic 136 (1) =%
TRIM
15 Leakage Class Noise (dB) ANSI / FCI 70.2 Class IV <85 (dB)
16 Guide Material Stem Material AISI 316 SS AISI 316 SS
17 Plug Material Seat Material Stellite 6 Stellite 6
18 Service Type Modulating Spring and Diaphragm
19 Air Failure Valve Máx. dP Close (1)
ACTUATOR
20 Air Supply / Range Handwheel 2,5 (min) / 3,7 (norm) kgf/cm²-g No
21 Limit Switch XLOCK System - -
22 Type Smart Electropneumatic Yes, HART
23 PST / Regulation Eex Protection Regulation EEx-i (IEC-60079-11)
POSITIONER
24 Electrical Connection Pneumatic Connection 1/2" NPT-F 1/4" NPT-F
ACCESORIES

25 Filter / Gauges Degree of Protection (2) IP 65


26 Type Power Supply - -
SOLENOID 27 Reset Type Eex Protection - -
VALVE 28 Electrical Connection Pneumatic Connection - -
29 SIL Requirement Degree of Protection - -
30 Type Service - -
SWITCH
31 Electrical Connection Eex Protection -- -
32 Fluid Phase Nafta dulce Liquid
33 Cp/Cv Z
34 Density / Specific Grav. Viscosity 720,6 kg/m³ 0,39 cP
35 Critical Pressure Critical Temperature 30,3 kgf/cm²-a °C
36 Leakage Class Fire-Safe design ANSI / FCI 70.2 Class IV No
37 Other Fluid Data Benzene content > 0,5% wt
38 DATA Units Min. Flow Norm. Flow Max. Flow (3)
39 Flow Rate kg/h 59516 99193 109112
PROCESS
40 Delta-P kgf/cm² 14,1 4,4 4,4
DATA
41 Inlet Pressure kgf/cm²-g 70,8 61,2 61,20
42 Oper. Temperature °C 40 40 40
43 Vapor Pressure kgf/cm²-a 0,4 0,4 0,4
44 Travel %
45 Noise dBA
46 Calculated Cv -
47 Required Cv -
48 Shut off Pressure 73.3 kgf/cm²-g
49 Requisition
50 Valve Positioner Solenoid
PURCHASE 51 Manufacturer
52 Model
53 Suministrator
Notes:
(1) To be confirmed by Vendor.
(2) Filter and gauge to be provided assembled with valve by Vendor.
(3) Non-dimensionating case.

Hoja de datos - Válvulas de control


(ISBL)

RA DAG 25/7/2019 FOR COMMENTS 4035-10-0100-IG-IN-HD-015 Page 4 de 68