Service: Marine Generator Sets
Service: Marine Generator Sets
Service: Marine Generator Sets
Models:
13EOZ/11EFOZ
14EOZ/11.5EFOZ
15.5EOZ/13EFOZ
20EOZ/16EFOZ
20EOZ/17.5EFOZ
23EOZ/19EFOZ
24EOZ/20EFOZ
TP-6071 3/00
Safety Precautions and Instructions . . . . . . . . . I 6.3.2 High Water Temperature (HWT) and
High Exhaust Temperature (HET)
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i Shutdown Switch . . . . . . . . . . . . . . . . . . 22
6.3.3 Overspeed Safety Shutdown (SDR) . . 23
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . ii
6.4 Controller Circuit Board . . . . . . . . . . . . . . . . . . . . . 23
Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
6.5 Troubleshooting Flow Chart . . . . . . . . . . . . . . . . . 24
Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Section 7 Generator Troubleshooting . . . . . . . . 29
Section 1 Specifications . . . . . . . . . . . . . . . . . . . . 1
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
7.2 Generator Troubleshooting . . . . . . . . . . . . . . . . . . 29
1.2 Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
7.3 Separate Excitation . . . . . . . . . . . . . . . . . . . . . . . . 29
1.3 Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7.4 PowerBoostä V Voltage Regulators . . . . . . . . . . 30
1.4 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7.5 Voltage Regulator Test . . . . . . . . . . . . . . . . . . . . . 31
1.5 Generator, 4 Lead . . . . . . . . . . . . . . . . . . . . . . . . . 4
7.6 Voltage Regulator Adjustment . . . . . . . . . . . . . . . 32
1.6 Generator, 12 Lead . . . . . . . . . . . . . . . . . . . . . . . . 4
7.7 Exciter Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1.7 Service Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.8 Exciter Armature . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Section 2 Scheduled Maintenance . . . . . . . . . . . 7 7.9 Rectifier Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.10 Rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.2 Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . 8 7.11 Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
This manual provides troubleshooting and repair Read this manual and carefully follow all procedures
instructions for 13-24EOZ and 11-20EFOZ model and safety precautions to ensure proper equipment
generator sets (4-lead and 12-lead), controllers, and operation and to avoid bodily injury. Read and follow the
accessories. Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
Refer to the engine service manual for generator set equipment for future reference.
engine service information.
x:in:001:001 The equipment service requirements are very important
This manual may be used for models not listed on the to safe and efficient operation. Inspect the parts often
front cover. and perform required service at the prescribed intervals.
Maintenance work must be performed by appropriately
Information in this publication represents data available skilled and suitably-trained maintenance personnel
at the time of print. Kohler Co. reserves the right to familiar with generator set operation and service.
change this publication and the products represented x:in:001:003
Service Side
10 11 12 13 14
5 8 9 15
3 4 6 7
2 16
1
17
18
19
20
13/20EOZ
11/16/17.5EFOZ 26 25 24 23 22 21
9 Non-Service Side
27
29
28
14/15.5/23/24EOZ
11.5/13/19/20EFOZ
1. Controller 15. Fuel return line
2. Start/stop switch 16. Fuel injection pump HX-250000
3. DC circuit breaker 17. Belt guard
4. Hourmeter 18. Oil fill
5. Optional circuit breaker location 19. Seawater pump (water inlet)
6. Customer load lead access connection (back of controller) 20. Oil pressure sender (optional)
7. Remote start/stop and meter connector 21. Oil drain valve and hose
(located on the back of the controller) 22. Governor lever
8. Mixing elbow (water outlet/exhaust outlet) 23. Lube oil filter
9. Air intake silencer 24. Oil check
10. Lifting eye 25. Fuel feed pump
11. Coolant overflow bottle 26. Fuel inlet
12. Pressure cap (coolant fill) 27. High exhaust temp. shutdown switch
13. Fuel filter/separator 28. Heat exchanger drain
14. High water temp. shutdown sender (optional) 29. Heat exchanger
Not Shown: Air intake heater (optional preheat kit required to make air intake heater functional).
starting difficulties.
°C --30 --20 --10 0 10 20 30 40 °C
°F 0 20 40 60 80 100 °F
Operating Temperature
TP-5856-1
2. Remove the element from the cover and inspect it. Inspecting the exhaust system. Carbon monoxide can
To clean the element, continue to step 3. If the cause severe nausea, fainting, or death. For the safety of
element is damaged or in poor condition, replace the craft’s occupants, install a carbon monoxide detector.
the element; skip step 3 and go to step 4. If the Consult the boat builder or dealer for approved detector
element is clean go to step 6. location and installation. Inspect the detector before each
generator set use. In addition to routine exhaust system
3 4 inspection, test the carbon monoxide detector per the
2 manufacturer’s instructions and keep the detector operational
at all times.
1
Exhaust System. Check for exhaust leaks and
blockages. Check the silencer and piping condition and
5 check for tight exhaust system connections.
4. Lightly coat the foam element with oil. D Check that the exhaust outlet is unobstructed.
5. Squeeze out any excess oil. D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
6. Wipe the cover and base with a clean rag to remove Carbon and soot residue indicates an exhaust leak.
any dirt. Replace the base if it is damaged. Seal leaks as needed.
7. Reassemble the element and cover assembly to D Ensure that the carbon monoxide detector is (1) in the
the intake silencer base. Make sure the sealing craft, (2) functional. and (3) energized whenever the
surfaces fit properly. generator set operates.
x:op:001:002:a
8. Direct the air intake silencer duct down and away
from engine.
In most installations, both the generator set and the 1. Close the fuel valve.
propulsion engine operate from a common fuel tank with
2. Remove the fuel filter.
a dual dip tube arrangement. The generator set’s dip
tube is shorter than the propulsion engine’s dip tube. 3. Clean the contact surface of the fuel oil filter
With this arrangement fuel may not be available to the adapter.
generator set when the fuel supply is low. See
Figure 4-1 for a fuel system schematic. 4. Lightly lubricate the gasket surface of the new fuel
filter with fresh fuel oil. Thread the filter on the
adapter until the gasket makes contact; hand
To fuel
tighten the filter an additional one-half turn.
injectors
5. Open the fuel valve.
4.3 Bleeding
Generator
set If the generator set engine runs out of fuel, if air leaks
develop in the suction side of the fuel system, or if the
fuel filter is replaced, it will be necessary to bleed the
1 entire system to prevent starting failures and/or erratic
operation.
607141
607142
1. Vent screw B
2. Vent screw A
3. Fuel filter
4. Vent screw C
5. Fuel injection pump
4
4.4 Fuel Pump 1
5.1 General Checking the coolant level. Hot coolant can cause severe
injury or death. Allow the engine to cool. Release pressure
Heat exchanger cooling consists of a heat exchanger from the cooling system before removing the pressure cap. To
with coolant recovery tank, thermostat, rubber impeller release pressure, cover the pressure cap with a thick cloth and
then slowly turn the cap counterclockwise to the first stop.
seawater pump, centrifugal-type engine circulating
Remove the cap after pressure has been completely released
pump, water-cooled exhaust manifold, and an exhaust
and the engine has cooled. Check the coolant level at the tank
mixer. See Figure 5-1 for cooling system components. if the generator set has a coolant recovery tank.
WARNING NOTICE
Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
remove salt deposits from metal surfaces.
1
2
3
5
6
12
9
Seawater
10 Coolant/antifreeze
11
607151
1. Engine block 7. Heat exchanger
2. Exhaust manifold 8. Engine seawater pump
3. Exhaust mixer elbow 9. Seawater strainer
4. Outlet flapper 10. Seacock
5. Silencer 11. Intake strainer
6. Thermostat 12. Engine-driven water pump
7 8
9
1
20
18 4
Waterline
19
14 10
17
13
15
11
16
12 TP-5586-3
5 1
AC--CIRCUIT
START
DC--CIRCUIT BREAKER
2
BREAKER
HOUR
METER
3
6 STOP/
PREHEAT 8
4
7
5
4
6
A-359146
The normally open K25 contacts close to energize the 6.2.3 Stop
fuel solenoid and the battery charging alternator (BCA).
Close the start/stop switch between N and 43 (local or
As the engine builds oil pressure during cranking, the remote).
normally closed LOP contacts open.
The K4 relay energizes (LED4 lights).
Note: The bridge rectifier (BR1) and the voltage As the generator set shuts down, the K1 relay
regulator (VR1) provide 12 volts DC to the K1 and deenergizes (LED1 goes out). The normally open K1
K5 relays. contacts open to deenergize the K2 relay (LED2 goes
out). The normally closed K2 contacts close to ground
The stator winding V1-V4 provides a voltage sensing the circuit to the K4 relay until the generator set comes to
source to the voltage regulator. a complete stop.
The normally open K1 contacts close to maintain
voltage to the K2 relay (LED2 remains lit).
The normally closed K4 contacts open to deenergize the The normally open K4 contacts close to maintain a
K25 relay. The closed (normally open) K25 contacts ground to the K4 relay.
open to deenergize the fuel solenoid.
As the generator set shuts down, the K1 relay
The normally open K4 contacts close to maintain a deenergizes (LED1 goes out). The normally open K1
ground to the K4 relay. contacts open to deenergize the K2 relay (LED2 goes
out). The normally closed K2 contacts close to ground
As the generator set shuts down, the K1 relay the circuit to the K4 relay until the generator set comes to
deenergizes (LED1 goes out). The normally open K1 a complete stop.
TP-6071
No
A
No Yes
Is the K3 relay
functioning?
No Yes
No
No Yes
No Yes
No Generator set
No checks out okay.
Replace the
Yes inoperative
start/stop
switch.
Replace the
circuit board Is the K25 relay functioning?
(inoperative No
K4 relay).
Yes Replace
the K25
relay.
No
Yes Replace the fuse.
Is there 12VDC at
Yes Yes
the exciter field?
Test the voltage
No regulator. Refer to
Test the stator Section 7.
and main field.
Check the wiring
and connectors.
Go to B at the beginning
of the preceding page. No Yes
Go to E
Next page
(OPTIONAL)
Separately excite
the generator set to
determine if other
components are
inoperative.
Yes
Yes
Yes
Do the temperature Replace the
Yes safety shutdown Yes circuit board
Use a mechanical gauge to switches function? (inoperative K4
verify oil pressure. Does the relay).
engine have proper oil
pressure?
Replace the inoperative
Check the oil level. No
No temperature switch(es).
Repair/replace oil pump.
7.1 General
Generator has no or
Before beginning the troubleshooting procedures, read
low output
all the safety precautions at the beginning of this
manual. The following tests include additional safety
precautions; OBSERVE THESE PRECAUTIONS!
Separately Generator has
WARNING excite the generator output
Output
Input
8
Red
7
Green
2
Yellow 1
tV
PowerBoostt
TP-5983-7
D 1-amp fuse 11. Turn power supply off and disconnect power cord.
D 1 single-pole single-throw (SPST) switch, 1 amp 12. See Voltage Regulator Adjustment Procedure.
(minimum)
2
Hazardous voltage. Moving rotor. “YELLOW” 1
Can cause severe injury or death. V8
11 3
Operate the generator set only when V7
5. Plug the power cord into outlet. Figure 7-4 PowerBoostt V Voltage
Regulator Test
6. Turn the power variac on. The AC voltmeter should
indicate a power supply voltage of zero volts. The
lamp should be off.
8
tampered with, or if voltage/frequency reconnection has Red
7
Green
been done, readjust the voltage regulator according to STAB V/HZ VOLTS 6
F1 F2
reading indicates an internal short and a high
reading indicates an open winding. Repair or 3
replace the exciter field if the ohmmeter readings
indicate a inoperative exciter field (refer to
Section 9 for removal). If the resistance test is 4
TP-5983-7
inconclusive, perform a megohmmeter test on the
exciter field as described in the next step. 1. Voltage regulator
2. Megohmmeter
3. Frame connection
4. Exciter armature
5. Exciter field
resistance across the exciter armature leads. See 1. Main field (rotor) 4. Ohmmeter
Figure 7-9. See Section 1, Specifications for the 2. Stator windings 5. Armature
3. Rectifier module 6. Exciter field
armature resistance. No continuity indicates an
open armature winding. If the resistance test is Figure 7-9 Exciter Armature Ohmmeter Test
inconclusive, perform a megohmmeter test on the
exciter armature as described in the next step.
7 1
Note: Most ohmmeters will not accurately
AC F+
measure less than one ohm. Consider the AC
AC F--
exciter armature functional if the resistance
reading (continuity) is low and there is no
6 3
evidence of a shorted winding (heat
discoloration). 2
4
4. Check the exciter armature winding for a
short-to-ground condition. Use a megohmmeter to
apply 500 volts DC to either armature lead and the 5
armature frame. Follow the megohmmeter TP-5983-7
manufacturer’s instructions for using the
1. Main field rotor 5. Shaft connection
megohmmeter. See Figure 7-10. A reading of 2. Stator windings 6. Armature
approximately 1.5 MOhms and higher indicates the 3. Rectifier module 7. Exciter field
exciter armature is functional. A reading of less 4. Megohmmeter
than approximately 1.5 MOhms indicates Figure 7-10 Megohmmeter Connections on
deterioration of the winding insulation and possible Exciter Armature
current flow to ground; If so, replace the exciter
armature.
6 1
AC F+
3 C AC
AC F--
2 5 3
(AC) 2
4
(AC)
B
B1 TP-5983-7
A1 C1 -- +
1. Main field (rotor) 4. Ohmmeter
2. Stator windings 5. Armature
C (AC) 3. Rectifier module 6. Exciter field
TP-5983-7
1. Diode terminal
Figure 7-12 Ohmmeter Connections on
2. Diode terminal
3. Ohmmeter Main Field
Figure 7-11 Rectifier Module Test 3. Check the main field for a short-to-ground
condition by using a megohmmeter. Apply
500-volts DC to either field lead and the main field
frame. Follow the megohmmeter manufacturers
instructions for using the megohmmeter. See
Figure 7-13. A reading of 1.5 MOhms and higher
indicates the main field is functional. A reading of
less than 1.5 MOhms indicates deterioration of the
winding insulation and possible current flow to
ground; If so, replace the main field.
TP-5983-7 TP-5588-7
Leads 1, 2, 3, and 4 are the generator output leads. Figure 7-15 Stator Continuity 1-Phase
Leads 55 and 66 are the voltage regulator supply and
sensing leads. The output of leads B1 and B2 is rectified
by BR1 to supply the control voltage. BR1 is located on
the controller circuit board. Refer to the schematic in
Figure 7-14 when performing the following tests.
7 and 10 Yes V1 2
8 and 11 Yes F1 F2 V4
3 4
9 and 12 Yes 66 55
9
55 and 66 Yes
B1 and B2 Yes AC F+
AC 4
1 and 2, 3, 7, 8, 9 No AC F-- 3
1 and 55, B1, and B2 No
4 and B1 and B2 No 8 5 B1 B2 1 2
55 and B1 and B2 No
Any stator lead and
ground No
6
Figure 7-16 Stator Continuity 3-Phase 7
8.1 General
See Figure 8-1 through Figure 8-3 for component the following tables. Check each component using a
testing. multimeter to verify that the switches function and that
voltage is present at each component.
With the generator set battery connected, check the
generator wiring harness and the components listed in
Controller 10-amp circuit Connect the ohmmeter to the Place the ohmmeter on the If functional—zero or very low
breaker and wiring battery positive (+) cable and the R x 1000 scale. ohms. No reading (infinity)—
P1-14 lead. open circuit or circuit breaker
Note: The J4 and P4 leads must tripped.
be connected to perform this test.
Kohler Co. offers three remote panels for connection to Generally, if the sender changes its resistance values as
the generator set: its respective pressure/temperature changes, it is
working correctly. An inoperative sender will either be
D a panel with a start/stop switch open or shorted. Refer to Figure 8-4 and Figure 8-5 for
resistance values.
D a panel with a start/stop switch and two gauges
(engine oil pressure and water temperature) 2-Meter and 4-Meter Panels
D a panel with a start/stop switch and four gauges Temperature Resistance
(DC voltmeter, engine oil pressure, water 60_C (140_F) 134 ± 10 ohms
90_C (194_F) 51.5 ± 4 ohms
temperature, and hourmeter) 100_C (212_F) 38 ± 3 ohms
Remote switch: grey/black wire Place the ohmmeter on the R x 1 Continuity—the switch is
terminal and black wire terminal. scale. functional.
Press the rocker switch to the
STOP position.
Genset ON light, gauge lights, Connect the red test lead to P3-4 Place the controller rocker switch If 12-volts DC is present and the
DC voltmeter, and hourmeter and black test lead to P3-1. to the START position. Stop the component does not function
generator set when the test is after the J3 is connected to the
complete. controller P3, replace the
Generator set does not need to component(s).
be running, just cranking for this
test.
Note: If the hourmeter is not
illuminated, test it by connecting
it to a 12-volt battery.
Note: The hourmeter is polarity
sensitive.
Water temperature gauge Connect the red test lead to P3-4 Start the generator set for the If 0.5--12-volts DC is present and
(socket side) and black test lead test. the gauge does not function after
to P3-2 (socket side). the J3 is connected to
controller—replace the gauge.
Oil pressure gauge Connect the red test lead to P3-4 Start the generator set for the If 0.5--12-volts DC is present and
(socket side) and black test lead test. the gauge does not function after
to P3-3 (socket side). the J3 is connected to the
controller—replace the gauge.
Note: Check continuity of gauge wiring and extension harness before replacing components.
Note: The voltage regulator is located in the controller 7. Lift the controller from the rubber mounts while
box. Remove the controller cover to service the guiding the leads through the bottom hole of the
voltage regulator. Adjustments are possible controller box.
without removing the voltage regulator from the
controller.
2
Disassembly Procedure:
558863
5
1
3 4
1. Armature
2. Armature retaining bolt 558865
3. Rotor leads
4 4. Rectifier board
558869
1. Bolts (8)
2. Rotor assembly
558867
1. Sling
2. Fan guard
3. Two-jaw puller
1
5588610
1. Drive disc
2. Rotor
3. Bolt
9.2 Reassembly
1. Clamp the rotor in a soft-jaw vise. Install a new 1. O-ring 5588612
drive disc on the rotor. Tighten the eight bolts to
38 Nm (28 ft. lbs.) See Figure 9-10. Figure 9-11 Stator Installation
3 5588611
1. Drive disc
2. Rotor
3. Bolt
5588613
Figure 9-10 Drive Disc Installation 1. Alignment marks
2. Install the rotor/drive disc assembly on the engine Figure 9-12 Alignment Marks
flywheel using eight washers and bolts. Tighten
6. Use the hoist to raise the alternator end. Remove
the bolts to 19 Nm (14 ft. lbs.)
the wood block from under the locator plate. Lower
3. Align the fan to the rotor/drive disc assembly using the generator set and install a bolt, a large washer,
the mark created in the disassembly procedure. two small washers, and a locknut on each
Install the fan to the drive disc using eight screws, vibromount. Tighten the mounting bolts to 28 Nm
four spacers, washers, and locknuts. (20 ft. lbs.).
Note: Position the lock washers against the Note: Check the generator set nameplate to verify
rectifier board. the original voltage configuration.
9. Install the three spacers and bolts to mount the 13. Connect the P4 (22-pin) connector. Connect the
rectifier board to the armature. ground strap using bolt, washer, and lock washer
(install the lock washer against the ground strap).
10. Position the field leads at the top. Install the exciter
field using four bolts and washers. Connect P5, P6, 14. Install the controller cover.
P7, and F1 connectors. See Figure 9-13.
15. Install the end panel with the louvered openings
2 down.
1
16. Reconnect all of the external connections—the
exhaust line to the mixing elbow, the fuel line to the
fuel pump filter inlet, the water line to the seawater
pump, the remote start panel to the controller P3
5 connector, the AC output leads in controller, and
the battery cables to the battery (negative (--) lead
last).
3
5588614
1. P7 connector
2. P6 connector
3. F1 connector
4. Exciter field
5. Exciter field bolts (4)
WARNING WARNING
Electro Switch
L1 L1
To Generator 2 1 3 4 2 1 3 4
To Shore
Set Power
L2 L2
6 5 7 8 6 5 7 8 To Shore
To Generator
Set Power
L0
10 9 11 12
To Load
To Load
L1 L1
1 2 6 5
To Generator 1 2 6 5 To Shore
Set Power
L2 L2
3 4 8 7 To Generator 3 4 8 7 To Shore
Set Power
L0
9 10 14 13
To Load
To Load
L1 L1
3 2 4 1 To Shore 3 2 4 1
To Generator
Set Power
L2 L2
7 6 8 5 To Generator 7 6 8 5 To Shore
Set Power
L0
11 10 12 9
To Load
To Load
TP-5399-5
L1 L1
3 2 4 1
L2 L2
To Generator 7 6 8 5 To Shore
Set Power
L3 L3
11 10 12 9
L0 L0
15 14 16 13
L1 L2 L3 L0
To Load
I-940
Water temp.
gauge
Oil pressure
gauge
TP-5588-7
P N
Stop
Local P1-9
10-amp
switch
fuse
P 47 43 N
Start W.T. O.P.
P1-14 P2-4 P2-5 P2-6 sender sender
K2 Relay
circuit
K1 board
70 47 43 N 5 7C
Grey/
P3-4 P3-5 Black P3-6 P3-1 P3-2 P3-3
J3-4 J3-5 J3-1 J3-2 J3-3
Violet Stop Black Tan L. Blue
J3-6
Yellow/
Red Remote
Start
switch
Gen. ON light
Water temp.
gauge
Oil pressure
gauge
DC voltmeter
Hourmeter
TP-5588-7
The following list contains abbreviations that may appear in this publication.
A, amp ampere cfm cubic feet per minute exh. exhaust
ABDC after bottom dead center CG center of gravity ext. external
AC alternating current CID cubic inch displacement F Fahrenheit, female
A/D analog to digital CL centerline fglass. fiberglass
ADC analog to digital converter cm centimeter FHM flat head machine (screw)
adj. adjust, adjustment cmm cubic meters per minute fl. oz. fluid ounce
ADV advertising dimensional CMOS complementary metal oxide flex. flexible
drawing substrate (semiconductor) freq. frequency
AHWT anticipatory high water cogen. cogeneration FS full scale
temperature COM communications (port) ft. foot, feet
AISI American Iron and Steel conn. connection ft. lbs. foot pounds (torque)
Institute cont. continued
ALOP anticipatory low oil pressure ft./min. feet per minute
CPVC chlorinated polyvinyl chloride g gram
alt. alternator crit. critical
Al aluminum ga. gauge (meters, wire size)
CRT cathode ray tube gal. gallon
ANSI American National Standards CSA Canadian Standards
Institute gen. generator
(formerly American Standards Association genset generator set
Association, ASA) CT current transformer GFI ground fault interrupter
AO anticipatory only Cu copper gnd. ground
API American Petroleum Institute cu. in. cubic inch gov. governor
approx. approximate, approximately cw. clockwise gph gallons per hour
AR as required, as requested CWC city water-cooled gpm gallons per minute
AS as supplied, as stated, as cyl. cylinder gr. grade, gross
suggested D/A digital to analog gr. wt. gross weight
ASE American Society of Engineers DAC digital to analog converter HxWxD height by width by depth
ASME American Society of dB decibel HC hex cap
Mechanical Engineers dBA decibel (A weighted) HCHT high cylinder head temperature
assy. assembly DC direct current HD heavy duty
ASTM American Society for Testing DCR direct current resistance
Materials HET high exhaust temperature
deg., ° degree hex hexagon
ATDC after top dead center dept. department
ATS automatic transfer switch Hg mercury (element)
dia. diameter HH hex head
auto. automatic DI/EO dual inlet/end outlet
aux. auxiliary HHC hex head cap
DIN Deutsches Institut fur Normung HP horsepower
A/V audio/visual e. V.
avg. average (also Deutsche Industrie hr. hour
AVR automatic voltage regulator Normenausschuss) HS heat shrink
AWG American Wire Gauge DIP dual inline package hsg. housing
AWM appliance wiring material DPDT double-pole, double-throw HVAC heating, ventilation, and air
DPST double-pole, single-throw conditioning
bat. battery
DS disconnect switch HWT high water temperature
BBDC before bottom dead center
DVR digital voltage regulator Hz hertz (cycles per second)
BC battery charger, battery
charging E, emer. emergency (power source) IC integrated circuit
BCA battery charging alternator EDI electronic data interchange ID inside diameter, identification
BCI Battery Council International EFR emergency frequency relay IEC International Electrotechnical
Commission
BDC before dead center e.g. for example (exempli gratia)
IEEE Institute of Electrical and
BHP brake horsepower EG electronic governor Electronics Engineers
blk. black (paint color), block EGSA Electrical Generating Systems IMS improved motor starting
(engine) Association
in. inch
blk. htr. block heater EIA Electronic Industries
Association in. H2O inches of water
BMEP brake mean effective pressure
EI/EO end inlet/end outlet in. Hg inches of mercury
bps bits per second
EMI electromagnetic interference in. lbs. inch pounds
br. brass
emiss. emission Inc. incorporated
BTDC before top dead center
eng. engine ind. industrial
Btu British thermal unit
EPA Environmental Protection int. internal
Btu/min. British thermal units per minute
Agency int./ext. internal/external
C Celsius, centigrade
EPS emergency power system I/O input/output
cal. calorie
ER emergency relay IP iron pipe
CARB California Air Resources Board
CB circuit breaker ES engineering special, ISO International Organization for
engineered special Standardization
cc cubic centimeter ESD electrostatic discharge J joule
CCA cold cranking amps est. estimated JIS Japanese Industry Standard
ccw. counterclockwise E-Stop emergency stop k kilo (1000)
CEC Canadian Electrical Code etc. et cetera (and so forth) K kelvin
cfh cubic feet per hour
Use the information below and on the following pages to Steps for common hardware application
identify proper fastening techniques when no specific
1. Determine entry hole type: round or slotted.
reference for reassembly is made.
2. Determine exit hole type: fixed female thread (weld
Bolt/Screw Length: When bolt/screw length is not given,
nut), round, or slotted.
use Figure 1 as a guide. As a general rule, a minimum
length of one thread beyond the nut and a maximum
For round and slotted exit holes, determine if
length of 1/2 the bolt/screw diameter beyond the nut is hardware is greater than 1/2 inch in diameter, or
the preferred method. 1/2 inch in diameter or less. Hardware that is
greater than 1/2 inch in diameter takes a standard
Washers and Nuts: Use split lock washers as a bolt
nut and SAE washer. Hardware 1/2 inch or less in
locking device where specified. Use SAE flat washers
diameter can take a properly torqued whiz nut or
with whiz nuts, spiralock nuts, or standard nuts and
spiralock nut. See the diagram below.
preloading (torque) of the bolt in all other applications.
3. Follow these SAE washer rules after determining
See General Torque Specifications and other torque exit hole type:
specifications in the service literature.
a. Always use a washer between hardware and a
slot.
Preferred Nut/Bolt Clearance
1 2 b. Always use a washer under a nut (see 2 above
for exception).
3 2
1
3
G-585
5
4
6
G-585
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
Use the following torque specifications when service oiled threads. Increase values by 15% for nonplated
literature instructions give no specific torque values. threads. All torque values are +0%/--10%.
The charts list values for new plated, zinc phosphate, or
Drive Styles
External Tooth Lock
Hex
Internal Tooth Lock
Hex and Slotted
Internal-External Tooth Lock
Phillipsr
Slotted
Hex Socket
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No. Dimensions Part No. Dimensions Part No. Dimensions Type
Hex Head Bolts (Grade 5) Hex Head Bolts, cont. Hex Nuts
X-465-17 1/4-20 x .38 X-6238-14 3/8-24 x .75 X-6009-1 1-8 Standard
X-465-6 1/4-20 x .50 X-6238-16 3/8-24 x 1.25
X-465-2 1/4-20 x .62 X-6238-21 3/8-24 x 4.00 X-6210-3 6-32 Whiz
X-465-16 1/4-20 x .75 X-6238-22 3/8-24 x 4.50 X-6210-4 8-32 Whiz
X-465-18 1/4-20 x .88 X-6210-5 10-24 Whiz
X-465-7 1/4-20 x 1.00 X-6024-5 7/16-14 x .75 X-6210-1 10-32 Whiz
X-465-8 1/4-20 x 1.25 X-6024-2 7/16-14 x 1.00
X-6024-8 7/16-14 x 1.25 X-6210-2 1/4-20 Spiralock
X-465-9 1/4-20 x 1.50 X-6210-6 1/4-28 Spiralock
X-465-10 1/4-20 x 1.75 X-6024-3 7/16-14 x 1.50
X-6024-4 7/16-14 x 2.00 X-6210-7 5/16-18 Spiralock
X-465-11 1/4-20 x 2.00 X-6210-8 5/16-24 Spiralock
X-465-12 1/4-20 x 2.25 X-6024-11 7/16-14 x 2.75
X-6024-12 7/16-14 x 6.50 X-6210-9 3/8-16 Spiralock
X-465-14 1/4-20 x 2.75 X-6210-10 3/8-24 Spiralock
X-465-21 1/4-20 x 5.00 X-129-15 1/2-13 x .75 X-6210-11 7/16-14 Spiralock
X-465-25 1/4-28 x .38 X-129-17 1/2-13 x 1.00 X-6210-12 1/2-13 Spiralock
X-465-20 1/4-28 x 1.00 X-129-18 1/2-13 x 1.25 X-6210-15 7/16-20 Spiralock
X-125-33 5/16-18 x .50 X-129-19 1/2-13 x 1.50 X-6210-14 Spiralock
X-125-23 5/16-18 x .62 X-129-20 1/2-13 x 1.75
X-129-21 1/2-13 x 2.00 X-85-3 5/8-11 Standard
X-125-3 5/16-18 x .75
X-129-22 1/2-13 x 2.25 X-88-12 3/4-10 Standard
X-125-31 5/16-18 x .88
X-129-23 1/2-13 x 2.50 X-89-2 1/2-20 Standard
X-125-5 5/16-18 x 1.00
X-125-24 5/16-18 x 1.25 X-129-24 1/2-13 x 2.75
X-125-34 5/16-18 x 1.50 X-129-25 1/2-13 x 3.00
X-129-27 1/2-13 x 3.50 Washers
X-125-25 5/16-18 x 1.75
X-125-26 5/16-18 x 2.00 X-129-29 1/2-13 x 4.00 Bolt/
230578 5/16-18 x 2.25 X-129-30 1/2-13 x 4.50 Part No. ID OD Thick. Screw
X-125-29 5/16-18 x 2.50 X-463-9 1/2-13 x 5.50
X-129-44 1/2-13 x 6.00 X-25-46 .125 .250 .022 #4
X-125-27 5/16-18 x 2.75 X-25-9 .156 .375 .049 #6
X-125-28 5/16-18 x 3.00 X-129-51 1/2-20 x .75 X-25-48 .188 .438 .049 #8
X-125-22 5/16-18 x 4.50 X-129-45 1/2-20 x 1.25 X-25-36 .219 .500 .049 #10
X-125-32 5/16-18 x 5.00 X-129-52 1/2-20 x 1.50 X-25-40 .281 .625 .065 1/4
X-125-35 5/16-18 x 5.50 X-25-85 .344 .687 .065 5/16
X-125-36 5/16-18 x 6.00 X-6021-3 5/8-11 x 1.00 X-25-37 .406 .812 .065 3/8
X-125-40 5/16-18 x 6.50 X-6021-4 5/8-11 x 1.25 X-25-34 .469 .922 .065 7/16
X-6021-2 5/8-11 x 1.50 X-25-26 .531 1.062 .095 1/2
X-125-43 5/16-24 x 1.75 X-6021-1 5/8-11 x 1.75
X-125-44 5/16-24 x 2.50 X-25-15 .656 1.312 .095 5/8
273049 5/8-11 x 2.00
X-125-30 5/16-24 x .75 X-25-29 .812 1.469 .134 3/4
X-6021-5 5/8-11 x 2.25
X-125-39 5/16-24 x 2.00 X-25-127 1.062 2.000 .134 1
X-6021-6 5/8-11 x 2.50
X-125-38 5/16-24 x 2.75 X-6021-7 5/8-11 x 2.75
X-6238-2 3/8-16 x .62 X-6021-12 5/8-11 x 3.75
X-6238-10 3/8-16 x .75 X-6021-11 5/8-11 x 4.50
X-6238-3 3/8-16 x .88 X-6021-10 5/8-11 x 6.00
X-6238-11 3/8-16 x 1.00 X-6021-9 5/8-18 x 2.50
X-6238-4 3/8-16 x 1.25
X-6238-5 3/8-16 x 1.50 X-6239-1 3/4-10 x 1.00
X-6238-1 3/8-16 x 1.75 X-6239-8 3/4-10 x 1.25
X-6238-6 3/8-16 x 2.00 X-6239-2 3/4-10 x 1.50
X-6238-17 3/8-16 x 2.25 X-6239-3 3/4-10 x 2.00
X-6238-7 3/8-16 x 2.50 X-6239-4 3/4-10 x 2.50
X-6238-8 3/8-16 x 2.75 X-6239-5 3/4-10 x 3.00
X-6238-9 3/8-16 x 3.00 X-6239-6 3/4-10 x 3.50
X-6238-19 3/8-16 x 3.25
X-6238-12 3/8-16 x 3.50 X-792-1 1-8 x 2.25
X-6238-20 3/8-16 x 3.75 X-792-5 1-8 x 3.00
X-6238-13 3/8-16 x 4.50 X-792-8 1-8 x 5.00
X-6238-18 3/8-16 x 5.50
X-6238-25 3/8-16 x 6.50