Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Gac Esd5500

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

2

JUNE 2000
MPC
PRODUCT
TECHNICAL
INFORMATION
ESD5500E SERIES
SPEED CONTROL UNIT
PTI 1002E
INTRODUCTION
The ESD5500E Series speed control unit is an all electronic
device designed to control engine speed with fast and precise
response to transient load changes. This closed loop control,
when connected to a proportional electric actuator and sup-
plied with a magnetic speed sensor signal, will control a wide
variety of engines in an isochronous or droop mode. It is
designed for high reliability and built ruggedly to withstand the
engine environment.
Simplicity of installation and adjustment was foremost in the
design. Non-interacting performance controls allow near opti-
mum response to be easily obtained.
The primary features of the ESD5500E Series speed control
unit are the engine STARTING FUEL and SPEED RAMPING
adjustments. The use of these features will minimize engine
exhaust smoke experienced prior to attaining engine operat-
ing speed.
Other features include adjustable droop and idle operation,
inputs for accessories used in multi-engine or special applica-
tions, protection against reverse battery voltage, transient
voltages, accidental short circuit of the actuator and fail safe
design in the event of loss of speed sensor signal or battery
supply.
The ESD5500E Series speed control unit is compatible with all
GAC proportional actuators except the ACB2000 electric
actuator. When the ESD5500E Series speed control unit is
used with a ADC100 Series electric actuator, the DROOP
adjustment range will be less due to this actuator's low current
demand.
DESCRIPTION
Engine speed information for the speed control unit is usually
received from a magnetic speed sensor. Any other signal
generating device may be used provided the generated fre-
quency is proportional to engine speed and meets the voltage
input and frequency range specification. The speed sensor is
typically mounted in close proximity to an engine driven ferrous
gear, usually the engine ring gear. As the teeth of the gear pass
the magnetic sensor, a signal is generated which is propor-
tional to engine speed.
Signal strength must be within the range of the input amplifier.
An amplitude of 0.5 to 120 volts RMS is required to allow the
unit to function within its design specifications. The speed
signal is applied to Terminals C and D of the speed control unit.
Between these terminals there is an input impedance of over
33,000 ohms. Terminal D is internally connected to Terminal
E, battery negative. Only one end of the shielded cable should
be connected.
When a speed sensor signal is received by the controller, the
signal is amplified and shaped by an internal circuit to provide
an analog speed signal. If the speed sensor monitor does not
detect a speed sensor signal, the output circuit of the speed
control unit will turn off all current to the actuator.
A summing circuit receives the speed sensor signal along with
the speed adjust set point input. The speed range has a ratio
of 8:1 and is adjusted with a 25 turn potentiometer. The output
from the summing circuit is the input to the dynamic control
section of the speed control unit. The dynamic control circuit,
of which the gain and stability adjustments are part, has a
control function that will provide isochronous and stable per-
formance for most engine types and fuel systems.
The speed control unit circuit is influenced by the gain and
stability performance adjustments. The governor system sen-
sitivity is increased with clockwise rotation of the gain adjust-
ment. The gain adjustment has a range of 33:1. The stability
adjustment, when advanced clockwise, increases the time
rate of response of the governor system to match the various
time constants of a wide variety of engines. The speed control
unit is a P I D device, the D, derivative portion can be varied
when required. (See Instability section.)
During the engine cranking cycle, STARTING FUEL can be
adjusted from an almost closed, to a nearly full fuel position.
Once the engine has started, the speed control point is
determined, first by the IDLE speed set point and the SPEED
RAMPING circuit. After engine speed ramping has been
completed, the engine will be at its governed operating speed.
At the desired governed engine speed, the actuator will be
energized with sufficient current to maintain the desired en-
gine speed, independent of load (isochronous operation).
The output circuit provides switching current at a frequency of
about 500 Hz. to drive the actuator. Since the switching
frequency is well beyond the natural frequency of the actuator,
there is no visible motion of the actuator output shaft. Switch-
ing the output transistors reduces its internal power dissipation
for efficient power control. The output circuit can provide
current of up to 10 amps continuous at 25C for 12 and 24 VDC
battery systems. The actuator responds to the average current
to position the engine fuel control lever.
In standard operation, the speed control unit performance is
isochronous. Droop governing can be selected by connecting
terminals K and L and the percent of droop governing can be
varied with the droop adjustment control. The droop range can
be decreased by connecting Terminals G and H.
The speed control unit has several performance and protec-
tion features which enhance the governor system. A speed
anticipation circuit minimizes speed overshoot on engine start-
up or when large increments of load are applied to the engine.
Engine idle speed can be remotely selected and is adjustable.
Accessory inputs to achieve variable speed operation and
multi-engine control can be accepted by the ESD5500E Series
speed control unit from GAC load sharing modules, automatic
synchronizers, ramp generators and other accessory engine
control modules. Protection against reverse battery voltage
and transient voltages is provided. The design is fail-safe in the
event of loss of speed sensor signal or battery supply.
3
SPECIFICATIONS
Isochronous Operation/Steady State Stability ........................................................................................ 0.25% or better
Speed Range/Governor ............................................................................................................... 1K7.5K Hz continuous
Speed Drift with Temperature .................................................................................................................... 1% Maximum
Idle Adjust CW ....................................................................................................................................... 60% of set speed
Idle Adjust CCW ................................................................................................................................. Less than 1200 Hz.
Droop Range ...................................................................................................................................... 1 5% regulation*
Droop Adj. Max. (K-L Jumpered) ............................................................................. 400 Hz., 75 Hz. per 1.0 A change
Droop Adj. Min. (K-L Jumpered) .................................................................................. 15 Hz., 6 Hz. per 1.0 A change
Speed Trim Range .............................................................................................................................................. 200 Hz.
Remote Variable Speed Range ..................................................................................... 500 7.5 Hz. or any part thereof
Terminal Sensitivity
J .................................................................................................... 100 Hz., 15 Hz / Volt @ 5.0 K Impedance
L ..................................................................................................... 735 Hz., 60 Hz / Volt @ 65 K Impedance
N ................................................................................................ 148 Hz., 10 Hz / Volt @ 1 Meg. Impedance
P ....................................................................................................................... 10 VDC Supply @ 20 ma Max.
Ambient Operating Temperature Range ......................................................................... -40 to +180F (-40 to +85C)
Relative Humidity ............................................................................................................................................. up to 95%
All Surface Finishes ............................................................................................. Fungus Proof and Corrosion Resistant
Supply ..................................................... 12 or 24 VDC Battery Systems (Transient and Reverse Voltage Protected)**
Polarity ........................................................................................................................ Negative Ground (Case Isolated)
Power Consumption .......................................................................................... 50 ma continuous plus actuator current
Actuator Current Range @ 77F (25C) - (Inductive Load) ....................... Min. 2.5 Amps ...... Max. 10 Amps continuous***
Speed Sensor Signal ........................................................................................................................... 0.5120 Volts RMS
Vibration ................................................................................................................................................ 1G @ 20100 Hz.
Testing ...................................................................................................................................... 100% Functionally Tested
Dimensions ................................................................................................................................. See Outline (FIGURE 1)
Weight ............................................................................................................................................... 1.2 lbs (545 grams)
Mounting ........................................................................................................................ Any Position, Vertical Preferred
*Droop is based on a speed sensor frequency of 4000 Hz. and an actuator current change of 1 amp from no load
to full load. Applications with higher speed sensor signals will experience less percentage of droop. Applications
with more actuator current change will experience higher percentages of droop. See droop description for specific
details on operation of droop ranges. When used with the ADC100 actuator the droop percentage will be less due
to the actuators low current consumption.
**Protected against reverse voltage by a series diode. A 15 amp fuse must be installed in the positive battery lead.
***Protected against short circuit to actuator (shuts off current to actuator), unit automatically turns back on when
short is removed.
PERFORMANCE
ENVIRONMENTAL
INPUT POWER
RELIABILITY
PHYSICAL
ESD 5500E SERIES SPEED CONTROL UNITS
ESD 5500E .......................................... Standard Unit ESD 5520E ................ Suitable for low inertia actuators
4
DIAGRAM 1. ESD5500E Series Wiring Diagram and Outline
WARNING
An overspeed shutdown device, independent of the
governor system, should be provided to prevent loss of
engine control which may cause personal injury or
equipment damage. Do not rely exclusively on the
governor system electric actuator to prevent overspeed.
A secondary shutoff device, such as a fuel solenoid must
be used.
APPLICATION AND INSTALLATION
INFORMATION
The speed control unit is rugged enough to be placed in a
control cabinet or engine mounted enclosure with other dedi-
cated control equipment. If water, mist, or condensation may
come in contact with the controller, it should be mounted
vertically. This will allow the fluid to drain away from the speed
control unit.
Extreme heat should be avoided.
5
B. Rotate the STABILITY adjustment clockwise until instabil-
ity develops. Gradually move the adjustment counterclock-
wise until stability returns. Move the adjustment one division
further to insure stable performance.
C. Gain and stability adjustments may require minor changes
after engine load is applied. Normally, adjustments made at no
load achieve satisfactory performance. A strip chart recorder
can be used to further optimize the adjustments.
If instability cannot be corrected or further performance im-
provements are required, refer to the section on SYSTEM
TROUBLESHOOTING.
Starting Fuel Adjustment
The engines exhaust smoke at start-up can be minimized by
completing the following adjustments.
1. Place the engine in idle by connecting Terminals M & G.
2. Adjust the IDLE speed for as low a speed setting as the
application allows.
3. Adjust the STARTING FUEL CCW until the engine speed
begins to fall. Increase the STARTING FUEL slightly so that
the idle speed is returned to the desired level.
4. Stop the engine.
One of two methods of operation for the ESD5500E may
now be selected.
Method 1: Start the engine and accelerate directly to the
operating speed (Gen Sets, etc.).
or
Method 2: Start the engine and control at an idle speed for a
period of time prior to accelerating to the operating speed. This
method separates the starting process so that each may be
optimized for the lowest smoke emissions.
Method 1
Remove the connection between Terminals M & G. Start the
engine and adjust the SPEED RAMPING for the least smoke
on acceleration from idle to rated speed. If the starting smoke
is excessive, the STARTING FUEL may need to be adjusted
slightly CCW. If the starting time is too long, the STARTING
FUEL may need to be adjusted slightly CW.
Method 2
Replace the connection between Terminals M & G with a
switch, usually an oil pressure switch. Start the engine. If the
starting smoke is excessive, the STARTING FUEL may need
to be adjusted slightly CCW. If the starting time is too long, the
STARTING FUEL may need to be adjusted slightly CW.
When the switch opens, adjust the SPEED RAMPING for the
least amount of smoke when accelerating from idle speed to
rated speed.
WIRING
Basic electrical connections are illustrated in Diagram 1.
Actuator and battery connections to Terminals A, B, E, and F
should be #16 AWG (1.3 mm sq.) or larger. Long cables
require an increased wire size to minimize voltage drops.
The battery positive (+) input, Terminal F, should be fused for
15 amps as illustrated.
Magnetic speed sensor connections to Terminals C and D
MUST BE TWISTED AND/OR SHIELDED for their entire
length. The speed sensor cable shield should be ideally
connected to terminal D. The shield should be insulated to
insure no other part of the shield comes in contact with engine
ground, otherwise stray speed signals may be introduced to
the speed control unit. With the engine stopped, adjust the gap
between the magnetic speed sensor and the ring gear teeth.
The gap should not be any smaller than 0.020 in. (0.45 mm).
Usually, backing out the speed sensor 3/4 turn after touching
the ring gear tooth will achieve a satisfactory air gap. The
magnetic speed sensor voltage should be at least 1 VAC RMS
during cranking.
ADJUSTMENTS
Before Starting Engine
Check to insure the GAIN and STABILITY adjustments, and
if applied, the external SPEED TRIM CONTROL are set to mid
position.
Preset the ESD5500E as follows:
STARTING FUEL ................ FULL CW (Maximum Fuel)
SPEED RAMPING .............. FULL CCW ( Fastest)
Start Engine
The speed control unit governed speed setting is factory set at
approximately engine idle speed. (1000 Hz., speed sensor
signal)
Crank the engine with DC power applied to the governor
system. The actuator will energize to the maximum fuel
position until the engine starts. The governor system should
control the engine at a low idle speed. If the engine is unstable
after starting, turn the GAIN and STABILITY adjustments
counterclockwise until the engine is stable.
Governor Speed Setting
The governed speed set point is increased by clockwise
rotation of the SPEED adjustment control. Remote speed
adjustment can be obtained with an optional 5K Speed Trim
Control. (See Diagram 1.)
Governor Performance
Once the engine is at operating speed and at no load, the
following governor performance adjustment can be made.
A. Rotate the GAIN adjustment clockwise until instability
develops. Gradually move the adjustment counterclockwise
until stability returns. Move the adjustment one division further
counterclockwise to insure stable performance.
6
Idle Speed Setting
If the IDLE speed setting was not adjusted as detailed in
Starting Fuel Adjustment section, then place the optional
external selector switch in the IDLE position. The idle speed
set point is increased by clockwise rotation of the IDLE
adjustment control. When the engine is at idle speed, the
speed control unit applies droop to the governor system to
insure stable operation.
Speed Droop Operation
Droop is typically used for the paralleling of engine driven
generators.
Place the optional external selector switch in the DROOP
position, DROOP is increased by clockwise rotation of the
DROOP adjustment control. When in droop operation, the
engine speed will decrease as engine load increases. The
percentage of droop is based on the actuator current change
from engine no load to full load. A wide range of droop is
available with the internal control. Droop level requirements
above 10% are unusual.
If droop levels experienced are higher or lower than those
required, contact the factory for assistance.
After the droop level has been adjusted, the rated engine
speed setting may need to be reset. Check the engine speed
and adjust the speed setting accordingly.
Accessory Input
The AUXilary Terminal N accepts input signals from load
sharing units, auto synchronizers, and other governor system
accessories, GAC accessories are directly connected to this
terminal. It is recommended that this connection from acces-
sories be shielded as it is a sensitive input terminal.
If the auto synchronizer is used alone, not in conjunction with
a load sharing module, a 3 M ohm resistor should be con-
nected between Terminals N and P. This is required to match
the voltage levels between the speed control unit and the
synchronizer.
When an accessory is connected to Terminal N, the speed will
decrease and the speed adjustment must be reset.
When operating in the upper end of the control unit frequency
range, a jumper wire or frequency trim control may be required
between Terminals G and J. This increases the frequency
range of the speed control to over 7000 Hz.
Accessory Supply
The + 10 volt regulated supply, Terminal P, can be utilized to
provide power to GAC governor system accessories. Up to 20
ma of current can be drawn from this supply. Ground reference
is Terminal G. Caution: a short circuit on this terminal can
damage the speed control unit.
Wide Range Remote Variable Speed Operation
Simple and effective remote variable speed can be obtained
with the ESD5500E Series control unit.
A single remote speed adjustment potentiometer can be used
to adjust the engine speed continuously over a specific speed
range. Select the desired speed range and the corresponding
potentiometer value. (Refer to TABLE 1.) If the exact range
cannot be found, select the next higher range potentiometer.
An additional fixed resistor may be placed across the potenti-
ometer to obtain the exact desired range. Connect the speed
range potentiometer as shown in Diagram 2.
To maintain engine stability at the minimum speed setting, a
small amount of droop can be added using the DROOP
adjustment. At the maximum speed setting the governor
performance will be near isochronous, regardless of the droop
adjustment setting.
Contact the factory for assistance if difficulty is experienced in
obtaining the desired variable speed governing performance.
TABLE 1. Variable Speed Range Potentiometer Value
Speed Range Potentiometer Value
900 Hz. 1K
2,400 Hz. 5K
3,000 Hz. 10K
3,500 Hz. 25K
3,700 Hz. 50K
DIAGRAM 2.
*Select Proper Potentiometer Value from Table 1.
L
L
G J K L
CW
*
7
SYSTEM TROUBLESHOOTING
SYSTEM INOPERATIVE
If the engine governing system does not function, the fault may be determined by performing the voltage tests described in
Steps 1, 2, 3, and 4. (+) and (-) refer to meter polarity. Should normal values be indicated as a result of following the trouble
shooting steps, the fault may be with the actuator or the wiring to the actuator. See the actuator publication for testing details.
STEP TERMINALS NORMAL READING PROBABLE CAUSE OF ABNORMAL READING
1 F(+) & E(-) Battery Supply Voltage (12 or 24 VDC) 1. DC battery power not connected. Check for blown fuse.
2. Low battery voltage.
3. Wiring error.
2 C & D 1.0 VAC RMS min., while cranking 1. Gap between speed sensor and gear teeth too great.
Check gap.
2. Improper or defective wiring to the speed sensor.
Resistance between terminals C and D should be 30
to 1200ohms.
3. Defective speed sensor.
3 P(+) & G(-) 10 VDC, Internal Supply 1. Short on terminal P. (This will cause a defective unit.)
2. Defective Speed Control.
4 F(+) & A(-) 1.0 - 2.0 VDC while cranking 1. SPEED adjustment set too low.
2. Short/open in actuator wiring.
3. Defective speed control.
4. Defective actuator. See Actuator Troubleshooting.
UNSATISFACTORY PERFORMANCE
If the governing system functions poorly, perform the following tests.
TEST
1. Do not crank. Apply DC power to the
governor system
2. Manually hold the engine at the
desired running speed. Measure the
DC voltage between Terminals A (-)
& F(+) on the speed control unit.
1. Measure the voltage at the battery
while cranking.
2. Momentarily connect Terminals A and
F. The actuator should move to the full
fuel position.
1. Measure the actuator output.
Terminals A & B, while running under
governor control.
SYMPTOM
Engine overspeeds
Actuator does not
energize fully.
Engine remains
below desired
governed speed.
PROBABLE FAULT
1. Actuator goes to full fuel. Then, disconnect speed
sensor at Terminals C & D.
If actuator still at full fuel speed control unit defective.
If actuator at minimum fuel position - erroneous speed
signal. Check speed sensor data.
1. If the voltage reading is 1.0 to 2.0 VDC,
a) SPEED adjustment set above desired speed.
b) Defective speed control unit.
2. If the voltage reading is above 2.0 VDC,
a) Actuator or linkage binding.
3. If the voltage reading is below 1.0 VDC,
a) Defective speed control unit.
4. Gain set too low.
1. If the voltage is less than 7V for a 12V system, or
14V for a 24V system, replace the battery if it is weak
or undersized.
1. Actuator or battery wiring in error.
2. Actuator or linkage binding.
3. Defective actuator. See actuator troubleshooting.
4. Fuse opens. Check for short in actuator or actuator
wiring harness.
1. If voltage measurement is within approximately 2 volts
of the battery supply voltage, then fuel control
restricted from reaching full fuel position. Possibly due
to interference from the mechanical governor,
carburetor spring or linkage alignment.
2. Speed setting too low.
SYSTEM TROUBLESHOOTING
Insufficient Magnetic Speed Sensor Signal
A strong magnetic speed sensor signal will eliminate the
possibility of missed or extra pulses. The speed control unit will
govern well with 0.5 volts RMS speed sensor signal. A speed
sensor signal of 3 volts RMS or greater at governed speed is
recommended. Measurement of the signal is made at Termi-
nals C and D.
The amplitude of the speed sensor signal can be raised by
reducing the gap between the speed sensor tip and the engine
rind gear. The gap should not be any smaller than 0.020 in
(0.45 mm). When the engine is stopped, back the speed
sensor out by 3/4 turn after touching the ring gear tooth to
achieve a satisfactory air gap.
Electromagnetic Compatibility (EMC)
EMI SUSCEPTIBILITY The governor system can be ad-
versely affected by large interfering signals that are conducted
through the cabling or through direct radiation into the control
circuits.
All GAC speed control units contain filters and shielding
designed to protect the units sensitive circuits from moderate
external interfering sources.
Although it is difficult to predict levels of interference, applica-
tions that include magnetos, solid state ignition systems, radio
transmitters, voltage regulators or battery chargers should be
considered suspect as possible interfering sources.
If it is suspected that external fields, either those that are
radiated or conducted, are or will affect the governor systems
operation, it is recommended to use shielded cable for all
external connections. Be sure that only one end of the shields,
including the speed sensor shield, is connected to a single
point on the case of the speed control unit. Mount the speed
control unit to a grounded metal back plate or place it in a
sealed metal box.
Radiation is when the interfering signal is radiated directly
through space to the governing system. To isolate the gover-
nor system electronics from this type of interference source, a
metal shield or a solid metal container is usually effective.
Conduction is when the interfering signal is conducted through
the interconnecting wiring to the governor system electronics.
Shielded cables and installing filters are common remedies.
As an aid to help reduce the levels of EMI of a conductive
nature, a battery line filter and shielded cables are conve-
niently supplied by GAC in KT130. To reduce the levels of EMI
of a radiated nature, a shielded container P/N CA114 can be
sourced from GAC and its distributors.
In severe high energy interference locations such as when the
governor system is directly in the field of a powerful transmit-
ting source, the shielding may require to be a special EMI class
shielding. For these conditions, contact GAC application engi-
neering for specific recommendations.
Instability
Instability in a closed loop speed control system can be
categorized into two general types. PERIODIC appears to be
sinusoidal and at a regular rate. NON-PERIODIC is a random
wandering or an occasional deviation from a steady state band
for no apparent reason.
Switch C1 controls the Lead Circuit found in the ESD5500.
The normal position is ON. Move the switch to the OFF
position if there is fast instability in the system.
Switch C2 controls an additional circuit added in the ESD5500
that is designed to eliminate fast erratic governor behavior,
caused by very soft or worn couplings in the drive train
between the engine and generator. The normal position is
OFF. Move to the ON position if fast erratic engine behavior
due to a soft coupling is experienced.
The PERIODIC type can be further classified as fast or slow
instability. Fast instability is a 3 Hz. or faster irregularity of the
speed and is usually a jitter. Slow periodic instability is below
3 Hz., can be very slow, and is sometimes violent.
If fast instability occurs, this is typically the governor respond-
ing to engine firings. Raising the engine speed increases the
frequency of instability and vice versa. In this case, placing
switch C1 in the OFF position will reduce the speed control
units sensitivity to high frequency signals. Readjust the GAIN
and STABILITY for optimum control. Should instability still be
present, the removal of E1 to E2 jumper may help stabilize the
engine. Post locations are illustrated in Diagram 1. Again,
readjust the GAIN and STABILITY for optimum control. Inter-
ference from powerful electrical signals can also be the cause.
Turn off the battery chargers or other electrical equipment to
see if the system disappears.
Slow instability can have many causes. Adjustment of the
GAIN and STABILITY usually cures most situations by match-
ing the speed control unit dynamics. If this is unsuccessful, the
dead time compensation can be modified. Add a capacitor
from posts E2 to E3 (negative on E2). Post locations are
illustrated in Diagram 1. Start with 10 mfds. and increase until
instability is eliminated. The control system can also be opti-
mized for best performance by following this procedure.
If slow instability is unaffected by this procedure, evaluate the
fuel system and engine performance. Check the fuel system
linkage for binding, high friction, or poor linkage. Be sure to
check linkage during engine operation. Also look at the engine
fuel system. Irregularities with carburetion or fuel injection
systems can change engine power with a constant throttle
setting. This can result in speed deviations beyond the control
of the governor system. Adding a small amount of droop can
help stabilize the system for troubleshooting.
NON-PERIODIC instability should respond to the GAIN con-
trol. If increasing the gain reduces the instability, then the
problem is probably with the engine. Higher gain allows the
governor to respond faster and correct for disturbance. Look
for engine misfirings, an erratic fuel system, or load changes
on the engine generator set voltage regulator. If the throttle is
slightly erratic, but performance is fast, move switch C1 to the
OFF position. This will tend to steady the system.
If unsuccessful in solving instability, contact the factory for
assistance.
Power Drive Systems
Generator Control Specialists
PO Box 30
Grange Qld 4051
Ph 0500 800 225
Fx 07 3350 1654

You might also like