Autostart 700 (Model Numbers AS3/E ) : Engine/Generator Controller Installation Reference Sheet
Autostart 700 (Model Numbers AS3/E ) : Engine/Generator Controller Installation Reference Sheet
Autostart 700 (Model Numbers AS3/E ) : Engine/Generator Controller Installation Reference Sheet
mi5316
th
revision B, 8 October 2001
catalogue section 75
Engine/Generator Controller
Installation Reference Sheet
Front Facia
4 position operating
mode keyswitch:
Off/reset
Lamp Test
Auto
Test (Manual)
Speed calibration:
Connect 0 1mA meter (meter
+VE to pin 17, meter VE to
pin 1), run the engine at
normal speed, then adjust
potentiometer until meter
reads 0.75mA.
SERIES 700
START FAIL
LOW OIL PRESS
HIGH TEMP
OFF LAMP
RESET TEST AUTO TEST
OVERSPEED
MAINS FAIL
7 status/fault LEDs
CHARGE FAIL
PLANT FAIL
TIME DELAYS
4 56
78
23
STOP START
TEMP INPUT
NO
INTERLOCK
OIL INPUT
MAINS FAIL VE
9 01
S1
1 23
BATTERY VE
CHARGE FAIL
BATTERY +VE
NOT USED
MAG PICKUP
AUTO MODE O/P
CRANK O/P
BATTERY +VE
FUEL O/P
ALARM O/P
LOAD RELAY NO
LOAD RELAY COM
LOAD RELAY NC
L Generator AC
N 300 V rms MAX
LAMP TEST
1mA METER +VE
7 89
4 56
AUTOSTART 700
1 to 9
Panel Installation
mains
contactor
M L1
A L2
I L3
N N
S
92
UVR
MCR
LOAD
L1 L2 L3 N
gen
contactor
L1 G
L2 E
L3 N
N E
R
A
T
O
R
MCR1
GCR1
+ve DC
GCR
fuse
5A
1
3
8
WL
Magnetic
Pickup
D
E
2
5
Calibration/
RPM meter
0 - 1mA
75 Ohm
17
6
Auto
ve DC
20
Autostart
700
22
23
L Generator AC 50/60Hz.
N 300 VAC max.
Lamp test input/output
Tacho/calibration meter output
test/manual start
test/manual stop
ve
High Engine Temp. (HET) input
Interlock (plant fail) input: ve DC
Low Oil Pressure (LOP) input
Mains fail input
L1 L2 L3 N
1 2 3 4 5 6
14
15
16
17
18
19
20
21
22
23
(mm)
No connection
Magnetic pickup input
Auto mode output: +ve, 250mA
Crank relay output: +ve, 16A max.
+ ve DC (feed for relays)
Fuel relay output: + ve, 16A max.
Alarm relay output: + ve, 5A max.
NO
CO Load relay output:
NC volt free contacts
4
5
6
7
8
9
10
11
12
13
S2 S3 S4 S5
92
HET
START
60 SEC
LOP
C/BACK
60 MIN
21
9
7
10
11
12
13 1A
18
19
14
15
plant fail
(interlock)
RFL
manual
stop
manual
start
% OVERSPEED COOL
RST
RAL
Fuel
Starter
Alarm
Electrical Connection
Electrical connection to the Autostart 700 is via individual 1/4 inch blade
terminals. All connections should be made with Autostart switched off and
the wiring isolated from the DC/AC supply:Pin Function
1
3
7
9
Crank output
Fuel output
Pins 7 and 9 give positive DC outputs (max. rating 16 Amps) for the
control of engine fuel and starter motor circuits. Murphy recommend the
connection of slave relays with suppressed coils between each output
and the fuel/starter motor solenoid coils.
10 Alarm output
Pin 10 gives a positive DC output (maximum rating 5 Amps) when
Autostart has detected a fault and has shutdown the engine.
11 Load relay: normally open contact
12 Load relay: change-over contact
13 Load relay: normally closed contact
The load relay is a volt-free set of SPCO relay contacts, used for the
control of the generator contactor. The relay activates immediately
after a generator start, provided that the generator is running within
normal frequency, voltage and oil pressure limits. Once the mains fail
input de-activates, the load relay will remain energised (keeping the
generator on load) until the changeback timer has expired.
14 Generator AC Live
15 Generator AC Neutral
DANGER !
HIGH VOLTAGE
ve DC
Description
ms5893