Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Mni Herm: Near Condensing Boiler and Volume Water Heater

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

LAARS

OmniTherm
®

Near Condensing
Boiler and Volume Water Heater

Up to 7:1 Turndown Ratio


Electronic Fuel-to-Air Ratio Control
Up to 90% Thermal Efficiency
Stainless Steel Heat Exchanger
Indoor/Outdoor Rated
Laars Linc® Intuitive Touch Screen Controls
Low Return Water Temperatures Allowed
®
Omni Therm
THE LAARS
OMNITHERM
ADVANTAGE:

Designed with Performance and Practicality in Mind

OmniTherm, the new measure for installation


flexibility, stands in a performance class of it’s own. It
can as easily be applied in replacement applications
as it can be in new installations.

1) Long Life, Stainless Steel Heat Exchanger: 4


• Protects against heat exchanger
corrosion and fouling 5
• High efficiency levels
• Allows for low temperature return water
2) Available for use with Category I, II, III or IV
1
Venting Applications
3) Category I or III Low Temperature Operation 2
• Unique heat exchanger design and control
logic allow for return water temperatures 3
down to 85°F without the need for an
external mixing system
4) Up to 7:1 Combustion Turndown (Category II/IV)
• Increases overall efficiency by properly
matching load requirements with firing rates 6

5) Laars Linc Intuitive to Use Control System


• Icon driven, easy to navigate menu structure
• Large color touchscreen
6) Vertical Configuration
• Small footprint takes up less floor space
• Easily fits through doors and into tight
mechanical rooms.
Laars OmniTherm Boilers and Volume Water Heaters include INDUSTRY
advanced features that bring tangible results to building owners. LEADING
At the heart of the OmniTherm is a patent pending stainless steel TECHNOLOGY
corrosion resistant heat exchanger, industry leading Electronic
Air-to-Fuel ratio combustion control and the advanced
Laars Linc control platform. All of this has been combined for
the first time in a near condensing heating platform intended
for use in Category I, II, III or IV applications.

Electronic Air-to-Fuel Ratio Control Brings


Performance to a Whole New Level

The OmniTherm is outfitted with the latest in temperature compensated mass flow
combustion control technology. This technology offers one of the highest levels of
combustion accuracy and performance available.
Optimized performance, reduced emissions, and reliable operation lower
operational costs and increase savings.

• Peak Performance: Optimal combustion and low emission levels


are achieved by maintaining the ideal gas density levels within
the air-fuel mixture regardless of operational demands.

• Maximized Efficiency Levels: Electronic management of premix


process maintains proper oxygen levels for ideal combustion.

• High Efficiencies at All Firing Rates: Real-time air-to-fuel ratio


compensation control results in highest possible efficiencies
throughout the entire turndown range.

• Stable Performance: Electronic mass flow sensors adjust to


supply pressure fluctuations to improve performance stability
as compared to traditional pneumatic valve technology.

• Reliable Operation: Drifting from original set points over


time is eliminated, keeping the OmniTherm operating at
peak efficiencies.

• Quick Response Rate: Real time measurements of pressure,


air flow, gas density, and temperature are monitored for fast
acting adjustments to heating demands.
®
LAARS LINC®
LAARS LINC CONTROLS
ARE A STEP BEYOND Powerful control logic is easily managed via icon
SMART, THEY’RE driven, touch screen technology. The result is an intuitive
INTUITIVE to use control system with the intelligence to manage
installations from the simple to the complex.

ADVANCED EASE OF USE FUNCTIONALITY:

• HOME SCREEN BOILER STATUS: The home screen • LAARS LINC CONTROL TO DISPLAY HANDSHAKE:
shows the operational status of the boiler; all set points, If for any reason a display or control board needs to be
status of each pump, and boiler run status. replaced, the parameter set is automatically transferred
from the remaining display or control board to the
• QUICK START CONFIGURATOR: Simply touch the replaced component. Parameters are stored on both the
“Quick Start” icon on the home screen to access the most display and control to auto populate either one!
commonly-used parameters for systems that don’t require
advanced set up. • INTELLIGENT REDUNDANCY: Laars Linc cascade logic
includes a built-in redundancy; via either a lag unit’s
• USB DATA CONNECTION: The USB connection allows internal setpoint, or a configurable redundant leader. A
for easy transfer of parameter sets from one boiler to bank of boilers will continue to operate even if the master
another and for the boiler’s history data to be transferred control goes down, keeping buildings warm and hot water
to a USB memory device. flowing!

• AUTO CONFIGURING CASCADE: Up to 8 units can be


• VARI-PRIME® PUMP CONTROL: This unique fixed delta
automatically configured by simply connecting the controls
T control functionality is included on OmniTherm Category
and selecting the master boiler. The intelligence of Laars
II and IV boilers and works in conjunction with a variable
Linc takes over to auto configure the remaining follower
speed boiler pump. As the boiler’s firing rate changes,
boilers. No need to register each follower!
the Vari-Prime control modulates the signal to a variable
speed boiler pump to ensure a user-programmable
• MULTIPLE PUMP CONTROL: System pump, boiler pump
temperature rise is maintained across the boiler. Pump
and domestic water pump operation, each with time
electrical savings as high as 70% can be realized via this
delay.
configuration vs. constant speed pump installations.

• BacNET MSTP AND MODBUS RTU ON BOARD
DIMENSIONAL DATA A B

Air Inlet

G
D Gas Inlet

Vent Collar

Condensate
Trap

2,000 - 3,000 MBH 1,250 - 1,750 MBH C Water Water


Outlet Inlet

“G” Water NOTE: The unique design of this


“A” “B” “C” “D” Gas Inlet &
Model appliance requires connection to
Conn. Outlet
a condensate drain, including the
in. (cm) in. (cm) in. (cm) in. (cm) NPT NPT
Category I / III model.
1250 24½ (62) 27 (69) 39 (99) 66 (168) 2” 2½”
1500 24½ (62) 27 (69) 39 (99) 66 (168) 2” 2½”
1750 32 (81) 43 (109) 53 (135) 69 (175) 2” 3”
2000 32 (81) 43 (109) 53 (135) 78 (198) 2” 3”
2500 32 (81) 43 (109) 53 (135) 78 (198) 2” 3”
3000 32 (81) 43 (109) 53 (135) 85 (216) 2” 3”

ELECTRICAL DATA

1250 1500 1750 2000 2500 3000


Voltage Current Current Current Current Current Current

FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

120V, 1 phase 9.4 11.8 20 9.4 11.8 20 9.2 11.5 20 9.2 11.5 20 N/A N/A N/A N/A N/A N/A

208V, 1 phase N/A N/A N/A 4.8 6.0 15 5.0 6.3 15 5.0 6.3 15 5.0 6.3 15 N/A N/A N/A

220/240V, 1 ph N/A N/A N/A 4.8 6.0 15 4.8 6.0 15 4.8 6.0 15 4.8 6.0 15 N/A N/A N/A

208V, 3 phase N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 5.2 6.5 15 6.2 7.8 15
480V, 3 phase N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 2.2 2.8 15 2.7 3.4 15
600V, 3 phase N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1.8 2.3 15 2.2 2.8 15

VENTING DATA

General Air System Data Category II and IV Vent Data Category I and III Vent Data
3,4
Air Collar Size Maximum Maximum Typical Maximum Typical3
Vent Collar Category IV Vent Collar Category III
Model “E” and Ducted Ducted Air Pipe Category IV Category II Category III Category I
Size Vent Pipe Size4 4 Size Vent Pipe Size4
Air Pipe Size 1 Length¹ Vent Pipe Length Vent Pipe Size Vent Pipe Length4 Vent Pipe Size

inches cm ft2 m inches cm inches cm ft2 m inches cm inches cm inches cm ft2 m inches cm

1250 6 15 100 30.5 6 15 6 15 100 30.5 12 30 12 30 6 15 100 30.5 12 30

1500 6 15 100 30.5 6 15 6 15 100 30.5 12 30 12 30 6 15 100 30.5 12 30

1750 8 20 100 30.5 8 20 8 20 100 30.5 14 36 14 36 8 20 100 30.5 14 36

2000 8 20 100 30.5 8 20 8 20 100 30.5 14 36 14 36 8 20 100 30.5 14 36

2500 8 20 100 30.5 8 20 8 20 100 30.5 16 41 16 41 8 20 100 30.5 16 41

3000 10 25 100 30.5 10 25 10 25 100 30.5 16 41 N/A N/A N/A N/A N/A N/A N/A N/A

1. Intake air pipe may be single-wall galvanized steel pipe, 24 gauge minimum, and properly sealed.
2. Equivalent Feet: To calculate, measure the linear feet of the pipe and add 5 ft (1.5m) for each elbow used.
3. Category I and II vent pipe sizes shown are typical, but may not meet the requirements of every system.
4. Category II, III, and IV vent pipe must be stainless steel complying with UL1738, and properly sealed.
OmniTherm Models OCH and OCV for Category II & IV Venting

BOILER SIZING DATA VOLUME WATER HEATER SIZING DATA

OmniTherm Hydronic Model OCH (Category II & IV Vent) OmniTherm Volume Water Heater Model OCV (Category II & IV Vent)

Input Rate Output Rate EfficiencyTurndown Input Rate Output Rate Efficiency Turndown
Model Model
MBH kw MBH kw % Thermal % Combustion Ratio MBH kw MBH kw % Thermal Ratio

1250 1250 366 1098 322 87.8 87.7 5:1 1250 1250 366 1125 330 90 5:1
1500 1500 440 1307 383 87.1 87.2 7:1 1500 1500 440 1335 391 89 7:1
1750 1750 513 1523 446 87.0 86.7 7:1 1750 1750 513 1540 451 88 7:1
2000 1999.9 586 1756 514 87.8 87.5 5:1 2000 1999.9 586 1800 527 90 5:1
2500 2499.9 733 2193 643 87.7 87.0 7:1 2500 2499.9 733 2250 659 90 7:1
3000 3000 879 2589 759 86.3 86.6 7:1 3000 3000 879 2610 765 87 7:1

BOILER WATER FLOW REQUIREMENTS


Temperature Rise

20°F (11°C) 25°F (14°C) 30°F (17°C) 35°F (19°C) 40°F (22°C)
Model
Flow Headloss* Flow Headloss* Flow Headloss* Flow Headloss* Flow Headloss*

gpm l/m ft m gpm l/m ft m gpm l/m ft m gpm l/m ft m gpm l/m ft m

1250 110 416 25.0 7.6 88 333 16.4 5.0 73 276 11.5 3.5 63 238 8.6 2.6 55 208 6.6 2.0

1500 131 495 34.8 10.6 105 397 22.9 7.0 87 329 16.0 4.9 75 284 12.1 3.7 65 246 9.1 2.8

1750 152 576 19.5 5.9 122 462 13.4 4.1 102 386 9.4 2.9 87 329 6.4 2.0 76 288 4.2 1.3

2000 176 666 24.9 7.6 140 530 16.6 5.1 117 443 11.8 3.6 100 379 8.5 2.6 88 333 6.2 1.9

2500 219 829 36.1 11.0 175 662 24.7 7.5 146 553 17.9 5.5 125 473 13.4 4.1 110 416 10.4 3.2

3000 259 980 65.2 19.9 207 784 40.7 12.4 173 655 28.1 8.6 148 560 20.4 6.2 129 488 15.6 4.8

*Headloss is for boiler only (no piping)

VOLUME WATER HEATER WATER FLOW REQUIREMENTS


1-10 Grains Per Gallon Hardness 11-15 Grains Per Gallon Hardness

Model Flow Rate Headloss* Temp Rise Flow Rate Headloss* Temp Rise

gpm l/m ft m °F °C gpm l/m ft m °F °C


1250 85 322 16.1 4.9 26 14 104 394 23.6 7.2 21 12
1500 90 341 17.9 5.5 29 16 110 416 26.3 8.0 24 13
1750 120 454 12.9 3.9 25 14 150 568 19.6 6.0 20 11
2000 135 511 16.1 4.9 26 14 170 644 24.4 7.4 21 11
2500 140 530 17.2 5.2 31 17 170 644 24.4 7.4 26 14
3000 150 568 21 6.4 35 19 183 693 31.5 9.6 28 16
*Headloss is for the heater only (no piping)
Allowable pH is 6.5 to 9.5

VOLUME WATER HEATING RECOVERY DATA

Temperature Rise

Model 40°F (22°C) 50°F (25°C) 60°F (33°C) 70°F (39°C) 80°F (44°C) 90°F (50°C) 100°F (56°C)

gph L/h gph L/h gph L/h gph L/h gph L/h gph L/h gph L/h

1250 3293 12463 2634 9971 2195 8309 1881 7122 1646 6232 1463 5539 1317 4985

1500 3920 14837 3136 11870 2613 9891 2240 8478 1960 7418 1742 6594 1568 5935

1750 4568 17290 3654 13832 3045 11527 2610 9980 2284 8645 2030 7684 1827 6916

2000 5268 19942 4214 15953 3512 13294 3010 11395 2634 9971 2341 8863 2107 7977

2500 6578 24899 5262 19919 4385 16599 3759 14228 3289 12449 2923 11066 2631 9959

3000 7767 29401 6214 23521 5178 19601 4438 16801 3884 14701 3452 13067 3107 11761
OmniTherm Models ONH and ONV for Category I & III Venting

BOILER SIZING DATA VOLUME WATER HEATER SIZING DATA

OmniTherm Hydronic Model ONH (Category I & III Vent)* OmniTherm Volume Water Heating Model ONV (Category I & III Vent)*

Input Rate Output Rate Efficiency Input Rate Output Rate Efficiency
Model Model
MBH kw MBH kw % Thermal % Combustion MBH kw MBH kw % Thermal

1250 1250 366 1060 311 84.8 84.2 1250 1250 366 1063 311 85

1500 1500 440 1259 369 83.9 83.3 1500 1500 440 1260 369 84

1750 1750 513 1472 431 84.1 83.4 1750 1750 513 1488 436 85

2000 1999.9 586 1668 489 83.4 84.0 2000 1999.9 586 1720 504 86

2500 2499.9 733 2075 608 83.0 83.0 2500 2499.9 733 2150 630 86

* Category I & III venting achievable due to the on/off firing configuration of models ONH and ONV

BOILER WATER FLOW REQUIREMENTS

Temperature Rise

20°F (11°C) 25°F (14°C) 30°F (17°C) 35°F (19°C) 40°F (22°C)
Model
Flow Headloss* Flow Headloss* Flow Headloss* Flow Headloss* Flow Headloss*

gpm l/m ft m gpm l/m ft m gpm l/m ft m gpm l/m ft m gpm l/m ft m

1250 106 401 23.6 7.2 85 321 15.4 4.7 71 268 11.1 3.4 61 229 8.2 2.5 53 201 6.2 1.9

1500 126 476 33.0 10.1 101 381 21.9 6.7 84 318 16.1 4.9 72 272 12.0 3.7 63 238 9.0 2.7

1750 147 557 18.4 5.6 118 446 12.9 3.9 98 371 8.2 2.5 84 318 5.9 1.8 74 279 3.8 1.2

2000 167 631 24.4 7.4 133 505 15.7 4.8 111 421 11.2 3.4 95 361 7.8 2.4 83 316 5.9 1.8

2500 207 786 33.7 10.3 166 628 23.9 7.3 138 524 17.2 5.2 119 449 12.9 3.9 104 393 9.8 3

*Headloss is for boiler only (no piping)

VOLUME WATER HEATER WATER FLOW REQUIREMENTS

1-10 Grains Per Gallon Hardness 11-15 Grains Per Gallon Hardness
Model Flow Rate Headloss* Temp Rise Flow Rate Headloss* Temp Rise

gpm l/m ft m °F °C gpm l/m ft m °F °C

1250 85 322 16.1 4.9 25 14 104 394 23.6 7.2 20 11

1500 90 341 17.9 5.5 28 16 110 416 26.3 8.0 23 13

1750 120 454 12.9 3.9 25 14 150 568 19.6 6.0 20 11

2000 135 511 16.1 4.9 25 14 170 644 24.4 7.4 20 11

2500 140 530 17.2 5.2 31 17 170 644 24.4 7.4 25 14

*Headloss is for the heater only (no piping)


Allowable pH is 6.5 to 9.5

VOLUME WATER HEATING RECOVERY DATA

Temperature Rise
Model 40°F (22°C) 50°F (28°C) 60°F (33°C) 70°F (39°C) 80°F (44°C) 90°F (50°C) 100°F (56°C)

gph L/h gph L/h gph L/h gph L/h gph L/h gph L/h gph L/h

1250 3188 12049 2550 9639 2125 8033 1821 6885 1594 6024 1417 5355 1275 4820

1500 3780 14288 3024 11431 2520 9526 2160 8165 1890 7144 1680 6350 1512 5715

1750 4463 16868 3570 13495 2975 11246 2550 9639 2231 8434 1983 7497 1785 6747

2000 5160 19504 4128 15603 3440 13003 2948 11145 2580 9752 2293 8668 2064 7802

2500 6450 24380 5160 19504 4300 16253 3686 13931 3225 12190 2867 10836 2580 9752
A A
S S
M M
E E

H HLW

Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583


Headquarters: 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
9 Brigden Gate, Halton Hills, Ontario, Canada, L7G 0A3 • 905.203.0600 • Fax 905.636.0666
www.LAARS.com
Litho in U.S.A. © Laars® Heating Systems Co. 20-10 Document 1443C

You might also like