Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

RAMCRO

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Technical Data

Document Reference UL 13
17/02153R1

RAMCROil - INSTRUMENTATION Cable


For standard applications, low smoke, Halogen Free

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, LSZH-Sheath

MAC0203HEEXN-UL13 XLPE/IAM/CAM/LSZH
Application
These cables are designed to connect electronic instrumentation, analog and digital signal circuits. This cable does not spread flame to the top of the tray in
the Vertical-Tray Flame Test in UL 1685.

Construction 2x2x16AWG
Nominal
Formation 2 Pairs Unit Value
Section 16AWG
Conductor Plain annealed copper wire, 7 strand mm 1,5
Insulation Cross Linked Polyetilene - XLPE mm 2,3
Colour Code White, Black + Numbered Tapes

Individual Screen 0,026 mm Aluminium / PETP tape over tinned copper drain wire
Wrapping at least 1 layer of plastic tape 0,023 mm
Collective Screen 0,026 mm Aluminium / PETP tape over tinned copper drain wire

Inner Sheath N.A.


Armour N.A.
Outer Sheath Thermoplastic Low Smoke, Halogen Free - LSZH - Black mm 14,5
Cable Printing RAMCRO S.p.A. – (UL) Listed E345186 Type PLTC - 2 pr 16 - Shielded -
75°C + BATCH + METER MARKING

Technical Data & Standard References


Fire Propagation:
- Test on single cable IEC 60332-1
- Test on bunched cables IEC 60332-3 Construction Reference Standard: UL 13
Type of Cable: PLTC Cable
- Vertical Tray Flame Test UL1685 Low Voltage Directive 2014/35/UE
Limiting Oxygen Index (LOI) (min 37%) Other References:
Smoke Density IEC 61034 - NEC code, sec. 725 PLTC,
Amount of halogen acid gas IEC 60754-1 (max 0,5%) - NEC code, sec. 727 ITC,
- UL 1685
Acidity (ph value) and conductivity IEC 60754-2
- ASTM D 1239
Sunlight resistance UL 1581 section 1200 - NF C 32-020
Notes - IRAM IAP

Electrical & Mechanical Data

Conductor Cross-section Nom. 16AWG Temperature Range:


DC Resistance per core at 20° C max Ω/km 13,5 During Operation °C -30° C up to +90°C
Insulation Resistance at 20° C min MΩ*km 5000 During Installation °C -5° C up to +50°C
Mutual Capacitance max nF/km 150
Inductance max mH/km 1 Min. Bending Radius mm 8 x cable diameter
Test Voltage - Core/Core V 2000 Max Pulling Tension N/mm2 260
Test Voltage - Core/Screen V 2000 Weight Approx kg/km 270
L/R Ratio max µH/Ω 40
Operating Voltage V 300

Issued by: SABRINA_PMS Date of issue:


Prepared by RAMCRO Tech Via Marzorati, 15 - 20014 Nerviano - Milan - Italy / www.ramcro.it 20/12/2017 00:00
Creator: LDG Transfer to third parties only under authorization by Ramcro S.p.A. Form 2
Printing errors excepted. Subject to alterations.