Efficient and Safe Operation of Indirect Fired Heaters F.D. Marlett
Efficient and Safe Operation of Indirect Fired Heaters F.D. Marlett
Efficient and Safe Operation of Indirect Fired Heaters F.D. Marlett
HEATERS
F.D. MARLETT
F. D. MARLEn
Northwestern Utilities Limited
I
, t
WEATHER SlRlPPING I
RUBBER GASKET
33mm PLUG
33mm PLUG
FIGURE 1: Northwestern Utilities Limited indirect fired heater model NUL LH 10-lC-XHY33 shell assembly, nominal heat transfer
capacity rating =10 kilowatts.
cap to reduce the effects of wind currents on the burner system, outdoor firebox burner assembly. The fuel gas valve train and
and to prevent rain, snow, birds, etc., from entering the stack. The manifold serves as a heater control system, featuring a combina-
burner assembly and exhaust stack are each bolted to the firetube tion of primary safety control, safety control and operating con-
to permit their removal to gain access to the firetube to remove trol. Its inlet connection branches into three parallel runs: main
any build-up of soot, dirt, etc. burner gas line; pilot burner gas line; bath thermostat/pressuriza-
The high pressure gas coil, which may also be referred to as a tion gas line.
gas tube bundle, is typically located inside the upper half of the The bath thermostat is an operating control with an adjustable
heater shelL A gas coil is normally a serpentine pattern consisting bath temperature set point; via controlling a pressurization gas
of several straight passes or runs of welded steel pipe traversing supply it activates the combination bath temperature control/shut-
the length of the heater shell, with 180° return pipe bend intercon- down valve to regulate fuel gas input flow to the main burner.
nections. The gas coil has inlet and outlet straight pipe connec- During the main burner firing operation mode, pressurization gas
tions running to outside the heater shell, terminating with ANSI is partially dumped via a bleed line and burned adjacent to the
class flanges for connection to the installation site natural gas pip- pilot burner, instead of venting such gas unburned to the atmos-
ing system. A helical gas coil is used in the small heat transfer phere and representing undesirable methane gas emissions, a safe-
capacity NUL heater I110del shown in Figure 1. ty hazard, and wasted energy and revenue. The safety pilot valve,
Northwestern' Utilities Limited's heater shells operate at or near also referred to as a pilotstat, is a primary combustion safety con-
atmospheric pressure. The shell is capped at either end with bolted trol sensing the presence of pilot burner flame, preventing fuel gas
cover plates. The gas coil inlet and outlet pipe connections pass flow to the pilot and main burner in the event of pilot burner
through, and are welded to, the shell end cover plate opposite to flame outage.
the firebox burner assembly end, and the gas coil is removable Although water is the preferred heater bath medium and is
from the shell to facilitate inspection and maintenance. This plate compatible with a NUL bath maximum operating temperature of
has a coupling for a bath temperature indicator, using a thermow- about 82°C (= 180°F), it is not used because of the possibility of
ell and dial face thermometer. The firetube straight pipe runs pass freezing, since winter ambient temperatures may be as low as -
through, and" are welded to, the shell end cover plate opposite to 40°C (= -40°F) at some NUL installation sites, and heaters may
the gas coil inlet and outlet pipe connection flanges end, with the experience flame outage. Consequently, an aqueous ethylene gly-
firebox being removable from the shell. This plate has a coupling col solution with corrosion inhibitors is used, with about a 50/50
for a bath temperature controller (thermostat). A drain valve is weight per cent ethylene glycol-deionized/demineralized water
located at the bottom of each shell end cover plate. At the top of, mix concentration for providing adequate freeze protection.
and bolted to, each shell end cover plate is a removable heater lift-
inglug. On top of the heater shell is an expansion/fill tank, also
referred to as a water saver. This tank is used for the initial filling Codes and RegUlations
of the heater shell bath, and is kept at a suitable liquid level during
heater operation to permit the shell to be completely filled with NUL's indirect fired heater high pressure gas coils are designed
the bath. The heater shell is supported with steel plate legs. The and fabricated in accordance with requirements of the Alberta
heater shell outer surface is thermally insulated for outdoor instal- Boilers Safety Association (ABSA). Northwestern Utilities
lations, buUs left uninsulated for building indoor locations to pro- Limited has a Quality Control Manual and a registered Quality
vide space heating. Control Program and Welding Procedure; welding complies with
The fuel gas supply take-off is located in the installation site ASME requirements.
natural gas pipeline downstream of the heater gas coil outlet An intake flame arrester is an essential component of an indi-
flange connection, with a downstream fuel gas line connected to a rect fired heater, for installation sites where a combustible gas or
fuel gas valve train and manifold attached to the outside of the vapour in the surrounding area is a possibility. Associated flame