NIVETEC NT CT Nivelco NIVOCONT K
NIVETEC NT CT Nivelco NIVOCONT K
NIVETEC NT CT Nivelco NIVOCONT K
C O N D U C T I V E L E V E L S W I TC H E S
S W I T C H E S
L E V E L
A P P L I C AT I O N
Level switches, based on the conductivity principle, can be applied to liquids with conductivity higher than 10 µS/cm. For detecting the level, probes are immersed into
the tank. These probes (and the tank wall if conductive) serve as contacts of an electric circuit. Probes can be of single or multiple rod versions. A maximum of 4 probe-
rods can fit in the multiple probe with an additional reference probe if tank wall is not conductive. The probe length should be in accordance with the level to be detected.
Filling liquid in the tank will change the electrical conductivity between tank wall (or the reference probe) and probes. The established connection will be converted and
will activate a relay providing for output.
VERSIONS
Level switch and probe Compact level switch
M A I N F E AT U R E S
Level Switches Probe and relay in one unit
KRK-512 KRK-522 KKH-22
Level switching 2 independent relay outputs for 1 level Probe and relay in one unit
Filling-emptying control 2 independent relay outputs for 2 1 or 2 independent relay outputs for pump
Selectable NO/NC relay function independent levels control or differential level switching
Adjustable sensitivity 2 relay outputs for pump control Selectable NO/NC relay function
Adjustable delay time, Selectable NO/NC relay function Switch on/off delay
Adjustable delay ON and delay OFF time Adjustable delay ON and delay OFF time Adjustable sensitivity
Delay time display Adjustable sensitivity AC/DC versions
AC/DC versions AC/DC versions Delay time display
Adjustable delay ON and delay OFF time
M6 nut
M6 nut
ACCESSORIES D E R AT I N G
Probe Separator
DIAGRAM
Pressure (MPa)
Temp.
°C
m
1 vessel, 1 level 1 vessel, 1 level
o
c
KRK-512-5 KRK-512-5
.
1 vessel, 2 levels 2 vessels, 1-1 level
o
c
KRK-522- KRK-522-
l
1 vessel, 1 level 1 vessel, 2 levels
C O M PAC T L E V E L S W I TC H E S
e
v
M6 nut
i
KKH-212-5 KKH-222-5
ORDER CODES
Level Switches Compact Level Switches
Single channel
NIVOCONT K R K - 5 1 2 - NIVOCONT K K H - 2 2-
NIVOCONT K R K - 5 2 2 -
NIVOCONT K S - 0 NIVOCONT K L N - 2
Type Code Housing Code No. of Probes Code Length Code Length Code
Single probe, PP socket P Aluminum 2 1 pc + ref. probe 1* 0m 0 0m 0
Single probe, Plastic 3 2 pcs + ref. probe 2 1m 1 0,5 m 5
S
carbon steel socket
3 pcs + ref. probe 3 2m 2
Single probe, 1.4571 N
4 pcs + ref. probe 4 3m 3
Housing H * Only with plastic
housing
Submersible K
S P E C I F I C AT I O N S O P E R AT I O N
KRK-512-5
L E V E L S W I TC H E S
Filling
KRK-512-5 KRK-522-
(galvanic isolation) 110, 24 V
Power supply (Un) 24…240 V AC/DC 230 V AC AC/DC max
level
– 15…+10% min
KRK-522-
C O M PA C T L E V E L S W I TC H E S Operation
KKH-212-5 KKH-222-5
24 V…240 V AC/DC
Power supply (Un)
– 15…+10%
Power consumption max. 2 VA / W max. 4 VA / W
Ambient temp. – 20 °C…+50 °C
Process temperature max. +80 °C
Pressure 1 bar
Number of probes 2+s* 4+s*
Probe voltage 3,5 V AC
Probe current max. 0,2 mA max. 0,4 mA
Sensitivity Adjustable: 5 kOhm…100 kOhm
Fixed on-delay 1,5 sec
On and off-delay 0,5…10 sec
Output 1x SPDT 250 V 8A, AC1 2x SPDT 250V 16A, AC1
2x M20x1,5 for Ø6…12 mm cables, terminal block
Electrical connection
max. 2,5 mm2 / with insulation 1,5 mm2
Electrical protection Class II.
Process connection 1 1/2” BSP
Probe socket
PP
material
Housing material Polycarbonate
Ingress protection IP 67
660 g 800 g
Mass
(without probe stems) (without probe stems)
*s = reference probe