Protector® QS
PROTECTOR® QS SERIES
Series Standby Generators
Liquid-Cooled Gas Engine
1 of 11
FEATURES
INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
¡
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it This state-of-the-art power maximizing regulation system is standard on
doesn’t stop there. Total commitment to component testing, reliability all Generac models. It provides optimized FAST RESPONSE to changing
testing, environmental testing, destruction and life testing, plus testing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
to applicable CSA, NEMA, EGSA, and other standards, allows you to electronically torque-matching the surge loads to the engine. Digital
choose GENERAC POWER SYSTEMS with the confidence that these voltage regulation at ±1%.
systems will provide superior performance.
SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
¡
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
¡ TEST CRITERIA:
PROTOTYPE TESTED NEMA MG1-22 EVALUATION G ENERAC TRANSFER SWITCHES. Long life and reliability are
¡
synonymous with GENERAC POWER SYSTEMS. One reason for this
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
ISO
9 0 0 1:
2008
Protector ® QS Series
®
(All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271)
Protector ® QS Series
®
22 • 27 • 32 • 38 • 48 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
120/240 V, 1Ø, 1.0 pf 22 92 22 92 100
RG022 120/208 V, 3Ø, 0.8 pf 22 76 22 76 80
120/240 V, 3Ø, 0.8 pf 22 66 22 66 80 3 of 11
120/240 V, 1Ø, 1.0 pf 27 113 25 104 125
RG027 120/208 V, 3Ø, 0.8 pf 27 94 25 87 100
120/240 V, 3Ø, 0.8 pf 27 81 25 75 90
120/240 V, 1Ø, 1.0 pf 32 133 32 133 150
120/208 V, 3Ø, 0.8 pf 32 111 32 111 125
RG032
120/240 V, 3Ø, 0.8 pf 32 96 32 96 100
277/480 V, 3Ø, 0.8 pf 32 48 32 48 60
120/240 V, 1Ø, 1.0 pf 38 158 38 158 175
120/208 V, 3Ø, 0.8 pf 38 132 38 132 150
RG038
120/240 V, 3Ø, 0.8 pf 38 114 38 114 125
277/480 V, 3Ø, 0.8 pf 38 57 38 57 60
120/240 V, 1Ø, 1.0 pf 48 200 48 200 200
120/208 V, 3Ø, 0.8 pf 48 167 48 167 175
RG048
120/240 V, 3Ø, 0.8 pf 48 144 48 144 150
277/480 V, 3Ø, 0.8 pf 48 72 48 72 80
Note: Fuel pipe must be sized for full load. Exercise cycle 95 2.7 1 3.9 38
For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG) 25% of rated load 204 5.8 2.16 8.5 82
RG048 50% of rated load 392 11.1 4.14 15.7 151
For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
75% of rated load 547 15.5 5.8 22.8 220
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and
SCAQMD permitting purposes. 100% of rated load 756 21.5 7.96 31.3 302
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Protector ® QS Series
®
22 • 27 • 32 • 38 • 48 kW operating data
ENGINE COOLING
22 kW 27 kW 32 & 38 kW 48 kW
Air flow (inlet air including alternator and combustion air in cfm/cmm) 2400/68 2400/68 2200/62.3 4350/123.2
System coolant capacity (gal/liters) 2.5/9.5 2.5/9.5 2.5/9.5 3/11.4
4 of 11
Heat rejection to coolant (BTU per hr/MJ per hr) 99,000/104.5 105,000/110.8 145,000/153 186,000/196.2
Maximum operation air temperature on radiator (°C/°F) 60/150
Maximum ambient temperature (°C/°F) 50/140
COMBUSTION REQUIREMENTS
Flow at rated power (cfm/cmm) 68/1.9 68/1.9 106/3 163/4.6
SOUND EMISSIONS
Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode* 61 61 58 63
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load* 70 70 64 68
*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfm/cmm) 165/4.7 180/5.1 300/8.5 414/11.7
Exhaust temperature at muffler outlet (°C/°F) 482/900 538/1000 579/1075 552/1025
ENGINE PARAMETERS
Rated Synchronous rpm 1800
CONTROLLER FEATURES
2-Line Plain Text LCD Display.........................................................................................................................................Simple user interface for ease of operation.
Mode Switch: Auto ...............................................................................................................................................Automatic Start on Utility failure. 7 day exerciser
Off............................................................................................................................Stops unit. Power is removed. Control and charger still operate.
Manual.......................................................................................... Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds............................................................................................................................................................. Standard
Engine Start Sequence...................................................................................................................... Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration)
Engine Warm-up...................................................................................................................................................................................................................... 5 sec
Engine Cool-Down...................................................................................................................................................................................................................1 min
Starter Lock-out.................................................................................................................................Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger......................................................................................................................................................................................................... Standard
Automatic Voltage Regulation with Over and Under Voltage Protection................................................................................................................................. Standard
Automatic Low Oil Pressure Shutdown................................................................................................................................................................................ Standard
Overspeed Shutdown............................................................................................................................................................................................... Standard, 72 Hz
High Temperature Shutdown................................................................................................................................................................................................ Standard
Overcrank Protection........................................................................................................................................................................................................... Standard
Safety Fused....................................................................................................................................................................................................................... Standard
Failure to Transfer Protection............................................................................................................................................................................................... Standard
Low Battery Protection......................................................................................................................................................................................................... Standard
50 Event Run Log................................................................................................................................................................................................................ Standard
Future Set Capable Exerciser............................................................................................................................................................................................... Standard
Incorrect Wiring Protection.................................................................................................................................................................................................. Standard
Internal Fault Protection...................................................................................................................................................................................................... Standard
Common External Fault Capability....................................................................................................................................................................................... Standard
Governor Failure Protection................................................................................................................................................................................................. Standard
Protector ® QS Series
®
22 • 27 • 32 • 38 • 48 kW available accessories
Model # Product Description
Generac's Mobile Link allows you to check the status of your generator from
anywhere that you have access to an Internet connection from a PC or with any
006463-3 Mobile Link™
smart device. You will even be notified when a change in the generator’s status
occurs via e-mail or text message. Note: Harness Adapter Kit required. 5 of 11
The Harness Adapter Kit is required to make liquid-cooled units compatible with
006478-0 Harness Adapter Kit
Mobile Link™.
005630-1 - 22, 27, 32 & 38 kW If the temperature regularly falls below 32 °F (0 °C), install a cold weather kit
Cold Weather Kit to maintain optimal battery temperature. Kit consists of battery warmer with
005632-1 - 48 kW thermostat built into the wrap.
005616-0 - 22, 27, 32 & 38 kW Extreme Cold Recommended where the temperature regularly falls below 32 °F (0 °C) for
006204-0 - 48 kW Weather Kit extended periods of time. For liquid cooled units only.
005651-0 Base Plug Kit Add base plugs to the base of the generator to keep out debris.
Wireless Remote Recommended for use with the Wireless Remote on units up to 60 kW, required
006665-0
Extension Harness for use on units 70 kW or greater.
E-stop allows for immediate fuel shutoff and generator shutdown in the event of
006510-0 E-Stop
an emergency.
Protector ® QS Series
6 of 11
SERVICE ITEM 2.4L NOTES:
OIL FILL CAP EITHER SIDE
22 & 27 kW
OIL DIP STICK RIGHT SIDE 1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 1885 (74.2") LONG.
RADIATOR/EXHAUST
OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
DISCHARGE AIR AIR INTAKE
(BOTH SIDES) OIL DRAIN HOSE LEFT SIDE 2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
(BOTH SIDES) AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
RADIATOR DRAIN LEFT SIDE
BATTERY 12V APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
COOLANT RECOVERY BOTTLE LEFT SIDE
GRP 26
Drawing #0K8624-A (1 of 2)
EXHAUST MUFFLER
ENCLOSED WITHIN CIRCUIT BREAKER
GENERATOR ENCLOSURE SEE NOTE 3
631 [24.8]
DOOR TYP
REAR ENCLOSURE
COVER PANEL
980
SEE NOTE 4
[38.6] VICE ACTION LATCH,
RADIATOR/EXHAUST
OVERALL ONE PER DOOR,
DISCHARGE AIR
HEIGHT CUSTOMER ACCESS ONE LIFT OFF
48
ASSEMBLY, CONTROL [1.9] DOOR PER SIDE
PANEL ACCESS, TYP OF GENERATOR
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
1040
48 [40.9] 776 [30.6] 45 1490 [58.7] TYP
[1.9] OVERALL WIDTH [1.8]
FUEL LINE CONNECTION 1580 [62.2]
3/4" NPT FEMALE COUPLING TYP
OVERALL LENGTH
WEIGHT DATA
WEIGHT WEIGHT
ENCLOSURE SHIPPING WEIGHT
ENGINE/KW GENSET ONLY SHIPPING SKID
MATERIAL KG [LBS]
KG [LBS] KG [LBS]
2.4L 22KW AL 410.5 [905] 30 [66] 440 [971] DIMENSIONS: MM [INCH]
2.4L 27KW AL 426 [940] 30 [66] 456 [1006]
installation layout
®
13.5 X 29.5
22 & 27 kW
674
CIRCUIT BREAKER [26.5]
NEUTRAL AND CUSTOMER STUB-UP
CONNECTION OPENING AREA
104.5
[4.11]
28 9 51
[1.1] [.4] [2.0]
100
[3.9]
96 [3.8]
DIMENSIONS: MM [INCH]
installation layout
Drawing #0K8624-A (2 of 2)
®
Protector ® QS Series
7 of 11
Protector ® QS Series
8 of 11
SERVICE ITEM 2.4L NOTES:
RADIATOR/EXHAUST OIL FILL CAP EITHER SIDE
32 & 38 kW
DISCHARGE AIR AIR INTAKE OIL DIP STICK RIGHT SIDE 1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2255 (88.8") LONG.
(BOTH SIDES) (BOTH SIDES) OIL FILTER RIGHT SIDE REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
OIL DRAIN HOSE RIGHT SIDE 2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
RADIATOR DRAIN HOSE LEFT SIDE AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
COOLANT RECOVERY BOTTLE LEFT SIDE APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
Drawing #0K9268-A (1 of 2)
768 [30.2] RADIATOR FILL CAP ACCESS ROOF TOP STATE, AND LOCAL CODES.
CENTER OF GRAVITY AIR CLEANER ELEMENT RIGHT SIDE 3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
167 SEE NOTE 5 SPARK PLUGS LEFT SIDE - SEE SPECIFICATION SHEET OR OWNERS MANUAL
MUFFLER SEE NOTE 11 - ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
[6.6] 4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
DRIVE BELT EITHER SIDE
FAN BELT SEE NOTE 11 THE STUB-UP AREAS AS FOLLOWS:
BATTERY LEFT SIDE - HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL
535 CONNECTION, AND BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
[21.1] REFERENCE OWNERS MANUAL - LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
FOR PERIODIC REPLACEMENT 5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
PART LISTINGS. 6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
2.5" O.D. EXHAUST (USE STANDARD SAE TORQUE SPECS)
OUTLET 9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
REMOVE COVER BATTERY 12V, GRP 26 AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
TOP VIEW 11. EXHAUST MUFFLER AND FAN BELT ARE ENCLOSED WITHIN GENERATOR ENCLOSURE,
FOR ACCESS TO NEGATIVE GROUND
RADIATOR FILL CAP P/N: 077483 REMOVE FRONT PANEL TO ACCESS.
VICE ACTION LATCH,
EXHAUST MUFFLER ONE PER DOOR,
ENCLOSED WITHIN CIRCUIT BREAKER
759 [29.9] ONE LIFT OFF
GENERATOR ENCLOSURE SEE NOTE 3 DOOR TYP DOOR PER SIDE
OF GENERATOR
REAR ENCLOSURE
COVER PANEL
1171[46.1] SEE NOTE 4
RADIATOR/EXHAUST
OVERALL
DISCHARGE AIR HEIGHT
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS,
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
13.5 X 29.5
MOUNTING SLOTS
4X HIGH AND LOW VOLTAGE
STUB-UP AREA
786
[30.9]
STUB-UP
AREA
162 [6.4]
12 [.5] 9 [.4]
51 [2.0]
162 [6.4]
1733 [68.2] 217 [8.5] CIRCUIT BREAKER REMOVABLE STUB-UP ACCESS COVER
STUB-UP NEUTRAL AND CUSTOMER (SHIPPED LOOSE WITH GENERATOR)
AREA CONNECTION OPENING TO BE INSTALLED DURING GENERATOR
TOP VIEW INSTALLATION
850 [33.5]
116
[4.6]
DIMENSIONS: MM [INCH]
installation layout
Drawing #0K9268-A (2 of 2)
®
Protector ® QS Series
9 of 11
Protector ® QS Series
10 of 11
48 kW
COOLANT RECOVERY BOTTLE LEFT SIDE APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
P/N: 058208 RADIATOR FILL CAP ROOF TOP STATE, AND LOCAL CODES.
AIR CLEANER ELEMENT EITHER SIDE 3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
SPARK PLUGS EITHER SIDE - SEE SPECIFICATION SHEET OR OWNERS MANUAL
MUFFLER SEE NOTE 11 - ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
DRIVE BELT EITHER SIDE 4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
FAN BELT SEE NOTE 11
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
BATTERY RIGHT SIDE
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
REFERENCE OWNERS MANUAL - LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
508 5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
FOR PERIODIC REPLACEMENT
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
[20.0] PART LISTINGS. RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
240 721.4 9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
[9.4] CENTER OF GRAVITY SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
(SEE NOTE 5) 10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
REMOVE COVER AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
FOR ACCESS TO TOP VIEW 11. EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
RADIATOR FILL CAP VICE ACTION LATCH,
CIRCUIT BREAKER ONE PER DOOR,
EXHAUST MUFFLER
SEE NOTE 3 759 [29.9] ONE LIFT OFF
ENCLOSED WITHIN
DOOR TYP DOOR PER SIDE
GENERATOR ENCLOSURE
OF GENERATOR
REAR ENCLOSURE
1170 COVER PANEL
RADIATOR/EXHAUST [46.1] SEE NOTE 4
DISCHARGE AIR OVERALL
HEIGHT CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS, 58
BATTERY CHARGER [2.3]
LOCATED WITHIN TYP
SEE NOTE 4
WEIGHT DATA
WEIGHT WEIGHT
ENCLOSURE SHIPPING WEIGHT
ENGINE/KW GENSET ONLY SHIPPING SKID
MATERIAL KG [LBS]
KG [LBS] KG [LBS]
5.4L/48KW AL 705 [1555] 44 [98] 750 [1653]
installation layout
®
48 kW
786
CIRCUIT BREAKER [30.9]
NEUTRAL AND CUSTOMER STUB-UP
CONNECTION OPENING AREA
162
[6.4]
9
12
[.4] 51
[.5] 162 [2.0]
[6.4]
850 [33.5]
116 [4.6]
DIMENSIONS: MM [INCH]
installation layout
Protector ® QS Series
11 of 11