Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Generator Controller Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

GTR-17

Generator Controller
Manual

Tres Arroyos 329 - Haedo (1706)


Buenos Aires - Argentina

: (54-11) 4926-0600 / 4483-3630


: (54-11) 4627-3500

E-mail: cram@speedy.com.ar
Web Site: www.cramelectro.com
GTR-17

Table of Content
1. Controller Description...................................................................................................2
2. Profile ...........................................................................................................................2
3. Back Panel Function Description..................................................................................3
4. Case Dimension ...........................................................................................................4
5. Specifications ...............................................................................................................5
6. Controller Wiring Example............................................................................................6

Ver.:V1703 1
GTR-17

1. Controller Description
GTR-17 is low cost but multi-function diesel engine generator controller. It applies with
3 buttons and provides 3 kinds of operation mode: Manual, Auto, Off. No special training is
required due to the easy operation. Fault protection includes: Emergency stop, Over speed,
High water temperature, Low oil pressure, and Over crank. GTR-17 also displays the low
battery voltage warring, and indicates the running status and power status.GTR-17 equips
with high firm continental-type terminal that provides easy plug in and removal.
Furthermore, GTR-17 has 10 pins Dip switch for adjusting parameter according to system
requirements, and make it not only reducing stock but also meeting the various system
specifications. GTR-17 build-in 5 output powers relays which perform high power capacity
reach to 5 Amp (DC) that saves the wring for connection with extra power relays. No matter
in function, protection or operation performance. GTR-17 is your best choice.

2. Profile

Fig. 17 Front Panel

A、LED Indication
„ Emergency / Auxiliary Shutdown
„ Low Battery Warning
„ Over Speed Shutdown
„ High Water Temperature Shutdown
„ Low Oil Pressure Shutdown
„ Over Crank
„ Run
„ Power
B、Operation Buttons
„ ATS
Auto Start function by detect ATS terminal 12 grounded.
„ Off
Stop running engine or stand still / Reset Alarm.
„ Manual
Manual start engine directly.

Ver.:V1703 2
GTR-17

3. Back Panel Function Description

Fig. 2 GTR-17 Controller Back Panel


E u r o p i u m

Number Description Code

1 Input power (Battery +) ++

2 Ground (Battery -) GND

3 Output starter relay Motor

4 Output fuel valve relay Valve

5 Output alarm relay Alarm


S t y l e

6 Output stop relay Stop

7 Output Idle/Pre-heat relay Pre-Heat

8 Charge fire point Charge

9 Aux. switch shutdown Em.Stop


C o n n e c t o r

10 Input , High water temp. switch H.W.T.

11 Input, Low oil press. switch L.O.P.

12 Input , Auto start ATS

13 Input , Frequency detect terminal F.D1

14 Input , Frequency detect terminal F.D2

List 1 GTR-17 Terminal

Ver.:V1703 3
GTR-17

A、Dip switch settings function


„ Pin 1 & Pin 2:Valve on to stop engine timer
Valve on stop engine
Pin1 Pin2
delay
OFF OFF 5 sec
ON OFF 10 sec
OFF ON 15 sec
ON ON 20 sec

List 2 Stop Period


„ Pin3:System frequency【ON:50Hz;OFF:60Hz】
„ Pin4:Escape motor by oil pressure switch【ON:Enable;OFF:Disable】
„ Pin5:Pressure switch type【ON:Normal Open;OFF:Normal Close】
„ Pin6:Idle / Pre-heat output delay time【ON:10(120)Sec;OFF:1(300)Sec】
„ Pin7:Low DC Volt【ON:10.5VDC;OFF:21VDC】
„ Pin8 & Pin9 Cooling time:
Pin8 Pin9 Cooling time
OFF OFF 0 Sec
ON OFF 60 Sec
OFF ON 150 Sec
ON ON 300 Sec

List 3 Cooling Time


„ Pin10:Idle / Pre-heat Function Select【ON:Idle;OFF:Pre-heat】

4. Case Dimension

Fig. 3 GTR-17 Case Dimension of Back View Fig. 4 GTR-17 Case Dimension of Side View

Ver.:V1703 4
GTR-17

5. Specifications
DC supply:
8~36 VDC

Power Consumption:
Max.5 W

Measuring Frequency:
0~75 Hz (min AC Volt.25V ; max AC Volt. 300V)

Relay Output :
Start output:5A
Valve output:5A
Idle / Pre-heat output:5A
Alarm Output:5A
Stop output:5A

Ambient Temperature Range:


-10 ℃ ~ 60 ℃

Dimension (W * H * D):
72mm × 72 mm × 58 mm

Panel cut-out (W * H):


68 mm × 68 mm

Weight:
190g (0.42 lb.)

Protections and parameters:


Auxiliary shutdown protection : 1 Sec., Normal Close
Low battery warning : 5 Sec., 10.5 / 21 VDC
Over speed protection : 2 Sec.,55/66Hz
High water temp. protection : 2 Sec., Normal Open
Low oil pressure protection: 2 Sec., Normal Open / Normal Close
Over crank : 3 attempts
Cranking speed up limited : 0.5 Sec ., 20Hz
Safety on timer: 5 Sec (*)
(*) All alarms are ignored until safety on timer expired, except the emergency stop and over speed.

Ver.:V1703 5
GTR-17

6. Controller Wiring Example

Fig. 5 Controller wiring

Ver.:V1703 6

You might also like