Climaveneta CVM 20 Manual
Climaveneta CVM 20 Manual
Climaveneta CVM 20 Manual
TECHNICAL DESCRIPTION
TECHNICAL DESCRIPTION
CVM 20
C 5005 CV/04 99
CONTENT
DESCRIPTION OF THE CONTROLLER .................................................. ................................................. ............. four
4.1 Description of the user interface ............................................... .............................. 8 4.2 Starting the
unit .................. ................................................. ................................................. 8 4.3 Switching off the
unit ............................................... ................................................. ...................... 8 4.4 Switching on the
compressor .................................. ................................................. .................................. 8 4.5 Switching off the
compressor .............................. ................................................. .................................. 8 4.6 Compressor status and
LED status .................................. .................................... 8 4.7 Display of temperature
values .......... ................................................. ............................... 9 4.8
Alarms .......................... ................................................. ............................... ......................................... 9 4.8.1
Refrigerant circuit and/or compressor alarm .............................. ...................................... 9 4.8.2 General
emergency ...... ................................................. ................................................. .. 9
3
Machine Translated by Google
Controller Description
four
Machine Translated by Google
Terminals Purpose
No.Terminals Description
5
Machine Translated by Google
1.3 AC inputs
No.Terminals Description
Using the remote start and stop of the unit: For the correct functioning of the
unit, it is necessary to set the delay time between the signals of the remote start and stop of the unit and the
start and stop of the water
pump.
OFF
ON
OFF
Minimum 60 s Minimum 60 s
The presence of delays is mandatory, since when the compressor is pumped down (performed when the
compressor is stopped), the pump must be turned on. Otherwise, the flow switch will operate and the compressor
may fail. In this case, Climavento will not be liable for warranty. In addition, when using remote start and shutdown
(from an external contact or via control protocol), the following minimum pulse widths must be observed:
ON
OFF
Minimum 60 s
360 s minimum
A flow switch must be installed downstream of the evaporator to comply with warranty requirements.
6
Machine Translated by Google
liquid line
liquid line
CLIMAVENETA, RS 232/485,
36 RS485+ ............................................... ................ 99
CONVERTER FOR PRINTER
7
Machine Translated by Google
4. Software
4.1 Description of the user interface
The keyboard is shown in Fig.1. If
the POWER LED is on, it means that the electronic controller is powered.
nutrition.
Before switching on the unit, make sure that it has been supplied with power for at least 8 hours. This allows the
oil to be heated to the correct temperature and the gaseous refrigerant to be removed from the compressor
crankcase.
Press the ON/OFF button. The button's LED will light up.
Press the ON/OFF button. The button indicator will turn off.
Press the C1 or C2 button to turn on the desired compressor. The corresponding button
indicator will light up.
Press button C1 or C2 to turn off the corresponding compressor. The corresponding button indicator
will turn off.
This shutdown should only be used for emergency shutdown of the unit as this shutdown does not pump down
the compressor and may result in compressor failure not covered under warranty. Proper shutdown of the
compressor is done with the ON/OFF button
eight
Machine Translated by Google
Press the TEMP button. The IN LED will light up. The temperature value will appear on the display.
Press the TEMP button. The OUT LED will light up. The display will show the value
temperature.
4.8 Accidents
There are two types of alarms: compressor or refrigeration circuit alarm and general alarm.
Press the ALARM LIST button. The alarm code will appear on the display. Use the up and down arrow buttons to check
for other alarm codes.
Reset accident.
Press button C1 or C2 depending on which compressor or circuit is in trouble. If the cause of the alarm is removed (SEL
LED flashes), the alarm status will be reset.
Press the ALARM LIST button. The alarm code will appear on the display. Use the up and down arrow keys to check for
other alarm codes.
Press the ON/OFF button. If the cause of the alarm has been removed (the alarm code flashes on the display), the alarm
status will be reset.
9
Machine Translated by Google
5. List of alarms
The code Reset type
Type of accident Cause of the accident
accidents accidents
E000 Fault protection system M Low water flow rate
freezing evaporator.
E204 Pressure alarm at Displayed The setpoint has not been reached in the circuit
pumping out the disconnected only in the list pumping pressure value
compressor. accidents
E206 Circuit 1. Low pressure. A/M Insufficient flow rate
water through the evaporator.
Evaporator contamination
An insufficient amount
refrigerant in the system.
ten
Machine Translated by Google
Evaporator dirty.
An insufficient amount
refrigerant in the system.
Designations:
eleven
Machine Translated by Google
6. Regulation
Press the SET button. The button's LED will light up.
The temperature setpoint will appear on the display.
To confirm the entered value, press the SET button. This button's LED
will go out.
To change the temperature increment value, enter the program and change
the value of the first parameter
Please note: all settings are made depending on the inlet water temperature
evaporator
12
Machine Translated by Google
7 Printer output
Data is transmitted via the RS485 serial port located on the main
controller printed circuit board. You can connect a DPU/printer with serial to this port.
data port.
During printing, the LED on the print button flashes. If the printer is repeatedly
the PRINT command is given, the printing process stops.
Example
TIME : 0025 TIME : 0000
13
Machine Translated by Google
Press and hold the ON LINE and POWER ON buttons for at least 2 seconds. This will print the printer's
configuration as defined by its DIP/switches.
If the DIP/switch states are different from the above, please refer to the printer's instruction manual or contact
CLIMAVENETA
fourteen
Machine Translated by Google
8. Customization
8.1 Entering the menu
To enter the user menu, do the following: 1. Turn off the compressor
(see par. 5.5). 2. Press the MENU button. The code P000 will appear
on the display. 3. Use the up arrow and down arrow keys to scroll
through the list of options. 4. To view the value of the selected parameter, press the TEMP button, and
use the keys
“arrow up” and “arrow down” set the desired value. To return to the
parameter list, press the TEMP button again.
5. To exit the menu, press the MENU button. 6. Turn
on the compressor (see paragraph 5.4)
“arrow up” and “arrow down” set the desired value. To return to the
parameter list, press the TEMP button again.
5. To exit the menu, press the MENU button. 6. Turn
on the compressor (see paragraph 5.4)
Attention! To download the changed values, it is necessary to disconnect the CVM20 from the mains
(using the input switch), and after a few seconds, turn it on again. Access to the factory settings is
only allowed by authorized CLIMAVENETA engineers.
Changing these settings yourself can lead to serious malfunctions of the unit and its failure.
fifteen
Machine Translated by Google
9 Parameter list
PARAMETERS AVAILABLE TO THE USER
M - unit parameters
CI - parameters of the refrigeration circuit
CO - compressor parameters
16
Machine Translated by Google
1 - temperature
at the exit
17
Machine Translated by Google
21 1 one 2
31 1 2 3
42 2 0 2
52 2 one four
eighteen
Machine Translated by Google
45 —— — —
46 —— — —
47 —— — —
48 —— — —
19
Machine Translated by Google