Instructions and Advices To Use The Electronic Controller Logik 26-S
Instructions and Advices To Use The Electronic Controller Logik 26-S
Instructions and Advices To Use The Electronic Controller Logik 26-S
THE LOGIK 26-S IS AN INDUSTRIAL CONTROL EQUIPMENT (NOT A SAFETY ISTRUMENT) FOR THE OPERATION
OF A SCREW COMPRESSOR WITH SOFTWARE CLASS A (see EN 60730-1 and EN 60335-1).
THE INSTALLATION MUST BE MADE IN ACCORDANCE TO THE LOCAL AND INTERNATIONAL STANDARDS AND
REGULATIONS WHERE THE COMPRESSOR IS MANUFACTURED.
THE INSTALLATION AND START UP OF THE CONTROLLER MUST BE CARRIED OUT BY TRAINED PERSONNEL
WELL KNOW IN THIS MANUAL.
THE CONTROLLER HAS TO BE USED IN STANDARD INDUSTRIAL ENVIRONMENT AND IT CAN NOT BE USED IN
EXPLOSION RISK ENVIRONMENT, MARITIME AND MILITARY PURPOSE.
THIS MANUAL COULD BE SUBJET TO CHANGES; PLEASE CONTACT LOGIKA CONTROL TECHNICAL OFFICE IN
CASE OF DOUBT ON THE LAST VERSION.
ATTENTION
LA LOGIK 26-S EST UN CONTROLE EQUIPMENT INDUSTRIEL (PAS UN INSTRUMENT DE SECURITE) POUR LE
FONCTIONNEMENT D’UN COMPRESSEUR A VIS AVEC SOFTWARE DE CLASS A (voir EN 60730-1 et EN 60335-1).
L'INSTALLATION DOIT ETRE EFFECTUEE CONFORMEMENT AUX NORMES ET AUX REGLEMENTATIONS LOCALES
ET INTERNATIONALES OU LE COMPRESSEUR EST FABRIQUE.
L'INSTALLATION ET MISE EN MARCHE DE LA COMMANDE DOIVENT ETRE EFFECTUEES PAR DU PERSONNEL
QUALIFIÉ BIEN SAVOIR DANS CE MANUEL.
LE CONTROLEUR DOIT ETRE UTILISE DANS LA NORME ENVIRONNEMENT INDUSTRIEL ET IL NE PEUT PAS ETRE
UTILISE DANS UN ENVIRONNEMENT DE RISQUE D'EXPLOSION ET MARITIME FINS MILITAIRES.
CE MANUEL POURRAIT ETRE SOUS RESERVE DE MODIFICATION; S'IL VOUS PLAIT CONTACTER LOGIKA
CONTROL TECHNIQUE BUREAU EN CAS DE DOUTE SUR LA DERNIERE VERSION.
- Industrial control equipment for the operation and management of screw compressors only, pollution degree 2.
- In accordance to EC Directives:
- Directive:
- LVD : 2014/35/UE
- EMC: 2014/30/UE
- RHOS: 2011/65/EU
- based on the following harmonized standards applied:
- SAF-EMC: EN 60730-1
- RHOS: EN 50581
- In accordance to UL 508 (FILE #: E316817).
- Black auto-extinguishing box in ABS:
- a) according EC: IP64 for the front panel and IP20 for the other parts;
- b) according UL: type 1 and Type 12 for front panel mounting , installation in pollution degree 2 for the other parts
- Inputs and outputs via terminal-block board to wires (250V, 10A, 12-24AWG) tightening torque 8 Nm.
- Working temperature: 0°C (32°F) ÷ 50°C (122°F) 90% RH (non condensing)
- Storage temperature: -20 (-4°F) ÷ +70 °C (158°F)
- Power supply: 12Vac ± 10% 50 ÷ 60 Hz. (power of the transformer’s secondary: ~ 9 VA) from safety transformer
- Max. current absorbed = ~ 350 mA
- Visualization through back light alphanumerical LCD 20 digits x 2 rows and nr. 1 led for alarm status
- Messages selectable in 8 languages: Italian – English – French – German – Spanish – Portuguese –
Turkish – Russian
- nr. 6 key buttons: increase, decrease, enter, reset, start, stop
- nr. 1 input for temperature probe KTY
- nr. 1 input for pressure transducer (working pressure P1)
- nr. 1 input for auxiliary pressure transducer (internal pressure P2) or analog information from inverter
- nr. 1 input for PTC or Klicson for motor protection (IN8).
- nr. 7 opto isolated digital inputs from 12/24Vac to detect:
• IN 1 = emergency stop button
• IN 2 = thermal motor
• IN 3 = thermal fan
• IN 4 = remote start/stop
• IN 5 = air filter pressure switch
• IN 6 = separator filter differential pressure switch
• IN 7 = settable as: door of the electrical cabinet open – control phase relay – generic alarm
- nr. 3 digital inputs for connection to Logika Control phases unit.
- nr. 7 outputs via relay with contact 1.5A AC1 250Vac – 6 A AC1 250Vac total
• RL1 = line contactor
• RL2 = delta contactor
• RL3 = star contactor
• RL4 = load solenoid valve
• RL5 = fan contactor
• RL6 = settable as fan contactor, condensate drain, compressor status
• RL7 = settable as: alarm, fan contactor, condensate drain, compressor status
- nr. 1 real time clock with buffer battery, around 10 years electrical life
- nr. 1 24Vdc power supply input for PNP outputs
- nr. 1 24Vdc input from inverter to detect inverter fault
- nr. 2 PNP digital output to control the inverter (run and jog command)
- nr. 1 analog output 4÷20 mA for inverter operation
- nr. 2 serial output RS485 for:
• connection to other compressor for Master/Slave and/or Multiunit operation
• inverter communication
- Check min. and max. power supply to the controller
- Non volatile memory to store setting data, working hours, compressor status, alarm list
- The controller switches OFF due to micro interruption longer than ~ 300 m.s.
Weight: 470 g
Accessories:
- nr. 1 temperature probe KTY 13.5 for detection of the air end temperature: cable in silicone rubber, length 2.5 m,
working range –10 ÷ 130°C, resolution 1°C.
- nr. 1 pressure transducer 4-20 mA for working pressure control: 2 wires, AISI 316L stainless steel membrane,
working range 0 ÷ 15 bar, resolution 0,1bar, precision ± 0,1bar.
- nr. 1 Logika Control phases unit for power supply 230 ÷ 460V three phase
161 mm
1) Respect the working technical features and instructions on the electrical wiring; in special way both the cables of the
temperatures probes and pressure transducers must be isolated from the power cables and proper RC filters must be
placed on the contactors’ coils
2) On the back side of the controller there must be enough space for wiring and connectors.
3) The rear side of the controller must be protected against condensation, oil and dust.
4) Don’t wash the front panel by water injection; clean the front mylar with a soft cloth using soap water.
5) Low voltage and high voltage cables run on separate trunks.
6) The connection cables of temperature probe and pressure transducer must be placed in a trunk separate from the power
cables.
7) The connections cables of digital inputs must be placed in a trunk separate from the power cables.
8) The power cable of controller must NOT be placed in the same trunk of the power cables
Terminal M1
Pole 1-2 = power supply 12Vac
Terminal M3
Pole 1-2 = air end temperature probe
Pole 3-4 = pressure transducer (pole 3 = negative – pole 4 = positive)
Terminal M4
Pole 1 = pole 5 of the control phases (GND)
Pole 2 = pole 1 of the control phases (T)
Pole 3 = pole 2 of the control phases (S)
Pole 4 = pole 3 of the control phases (R)
NOTE: THE GND FROM THE CONTROL PHASES UNIT MUST NOT BE CONNECTED TO EARTH.
IT’S THE GROUND OF THE CONTROLLER AND MUST BE CONNECTED TO GROUND OF THE CONTROL PHASES UNIT
Terminal M5
Pole 1 = IN 1 = emergency stop button (L)
Pole 2 = IN 2 = thermal motor (L)
Pole 3 = IN 3 = thermal fan (L)
Pole 4 = IN 4 = remote start/stop (L)
Pole 5 = IN 5 = air filter pressure switch (L)
Pole 6 = IN 6 = separator filter differential pressure switch (L)
Pole 7 = neutral = N
NOTE: the digital inputs you do not use have to be connected directly to 12-24V otherwise they generate the
related alarm, except IN5 that must not be connected in case you do not use it.
Terminal M6
Pole 1 = RL7 = alarm (configurable)
Pole 2 = RL6 = condensate drain solenoid valve (configurable)
Pole 3 = RL5 = fan contactor (configurable)
Pole 4 = RL4 = solenoid valve
Pole 5 = RL3 = star contactor
Pole 6 = RL2 = delta contactor (configurable)
Pole 7 = RL1 = line contactor
Pole 8 = common = 24 ÷ 230Vac
Terminal M7
Pole 1 = IN 7 = settable as door of electrical cabinet open – control phase relay – generic alarm (L)
Pole 2-3 = IN 8 = PTC or Klicson for motor protection
Terminal M9
These terminals to be connected only to the drive controlled by 4/20mA analog output
Pole 1 = Analog and/or digital GND and DGND from drive
Pole 2 = Inverter fault input, 24Vdc signal coming from drive (normally connected to drive alarm relay)
Pole 3 = 4/20mA analog output computed by Logik26S PID (when activated)
Pole 4 = PNP1 digital output from 24Vdc from drive (when analog output is active this is the run command for the drive)
Pole 5 = PNP2 digital output from 24Vdc from drive (when analog output is active this is the jog command for the drive)
Pole 5 = 24Vdc from drive
Contactors 24Vac I°
If the operation of the contactors and
II°
soenoid valves come through 24 Vac, the
digital inputs have to be connected to 24
Vac (see drawing on the right); on this 12 – 0
way when the pressure switch opens due
to high pressure, 24 Vac lacks and Power supply to
deenergize all the contactors, solenoid the controller
valve and digital: the controller detects Security pressure
all the digital inputs opened and signal High
switch for high
the alarm “SEC. PRESSURE SWITCH”. Pressure detection
pressure
Power
Powersupply
supplytotodigital
digital
inputs
inputsand
andutilities
uses
24 – 0
Contactors 230Vac I°
If the operation of the contactors and
II°
solenoid valves comes through 230 Vac, the
digital inputs have to be connected to 12
Vac; next to the contact of the pressure 12 – 0
switch, place and energize an auxiliary
relay and put the contact in serie to Power supply to
12 Vac (L) (see drawing on the right). the controller
When the pressure switch is closed, the Security pressure
auxiliary relay with contact closed supply switch for high
power to the digital inputs; the power pressure detection
supply of the controller is connected before
the contact of the relay.
Auxiliary relay
When the pressure switch opens, the
Power supply to digital
auxiliary relay opens power to the digital inputs
inputs; the controller detects all the digital Power supply to
inputs open and signal the alarm “SEC. the uses
230 – 0
PRESSURE SWITCH”.
To connect a serial net you have to pay carefully attention to some executive aspects:
1) Use flexible cable, shielded, twisted 22 AWG type.
2) Connect D- and D+ to two conductors of same couple and 0 to a third one (if available) or both conductors of a
second couple.
3) Connect the cable’s shield to only one end of 0.
4) DO NOT CONNECT the cable’s shield to the electrical ground of the plant.
5) The net MUST NOT BE LONGER than 400 meters.
6) Max connectable units through serial net RS 485 is 32.
7) In case of connection via serial line RS485 you have to set the parameter C08 into menu 04 Compressor setup:
this is the number you need to combine to the recognition of the controller.
8) The units on serial net RS485 must be connected without any reversal: pole D+ to D+, pole D- to D-, pole 0 to 0.
9) In case of connection with more than 2 units it is necessary to provide only one line without any deriving.
At the terminal both starting and ending the net it is possible to place (in parallel to D- and D+) a termination
resistance 120 Ohm.
In the picture below you can see the connection of 4 units on serial net RS485 by using a shielded cable with two
twisted couples.
NOTES ON THE WIRING: wrong wiring can damage both the controller and other devices connected to the
serial port.
2 3 4 5 6
1
T6
T5
T2 T1 T3 T4
7a 8 7b
According the pic. above and related icons, the main visualization can be described as below:
1. General icons, where be present the following:
• I01, Condensate drain in operation
• I02, Multiunit operation
• I03, Master/slave operation
• I04, Maintenance messages
2. Alarm or maintenance messages: if an alarm is detected the display visualizes the icon I05, if maintenance timer is
over visualizes icon I04.
3. Start/stop by timer activated.
4. Time (hours and minutes).
5. Icons I12 when fan ON
6. Air end temperature
7. Inverter area: data visualized when output 4/20mA or RS485 inverter are enabled. In case output 4/20mA is
activated the display shows the PID frequency set (F) and eventual data set on the input 4/20mA (parameter
C19). In case of inverter via RS485 all the data from the inverter are visualized: frequency (F), current (I), power
(P) and temperature (T). Data are visualized on the right side (7b) or left side (7a) according the inverter
configuration is on the air end temperature or working pressure.
8. Compressor status: icons from I07 to I13 as below:
• Compressor OFF
• Witing for safety timer
• Pressure set
• Remote start/stop open
• Compressor ON
• Waiting for start/stop by timer (in this case the display visualizes the day of the week and time of the
next ON by timer).
• Waiting for internal pressure P2 lower than parameter AP4
9. Pressure area:
• Working pressure (BIG) and stop/start pressures.
• Aux pressure transducer (if enabled).
• Icon I17, motor run
• Icon I18, load solenoid valve open
In case of alarm, the below side of the display (7a, 7b and 8) visualizes the alarm message
The controller is provided with 6 key-buttons with following functions: (with reference to the above pic.):
- T1, decrease, select down
- T2, increase, select up
- T3, change or confirm
- T4, reset or back
- T5, stop compressor
- T6, start compressor
1
In a normal operation status, the icons will not be visualized all together: here they are just to show their own position in the display.
I05 Alarm
Main visualization: icons related to compressor status located lower row (centre)
I12 Stop by timer: the display visualizes day and time of the next start
I14 Fan ON
I21 Contrast
I22 Language
To change the Start pressure push and the data starts blinking; change the value by using and/or and confirm
the new one by : the data stops blinking. By the button R you can abort the modification.
To change the Stop pressure, push and the data starts blinking; change the value by using and/or and confirm
the new one by : the data stops blinking. By the button R you can abort the modification.
After the last label or by pushing the button R, you can shift back to the main visualization.
ESC FUNCTION
In any part of the menu you can shift back to the main visualization by pushing for about 5 seconds.
ANTIPANIC FUNCTION
In any label or sub-menu related to the setting and/or visualizations, after 180 seconds from the last pushing of a button,
the controller shift back to the main visualization without saving any change you have not confirmed.
M1 MAIN MENU
To enter the setting, push and the display visualizes the flow menu including the following labels related to other sub-
menu reported in the table below.
In case you push for 3 seconds the display visualize the label related to the password allowing to select the levels to
access the different parameters (1-service 1, 2-service 2, 3-factory).
PASSWORD FORGOTTEN
In case of password forgotten or missed you have to switch power off to the controller; restore power and keep on pushing
the for more than 5 seconds. During this time the display visualizes the blinking message “Reset Password”;
release the arrows button when the message changes into “Password reset”.
M1-1 INFO
This sub-menu visualizes the following info:
1. Working hours
2. Load hours
3. Load % during last 100 working hours (updated every 5 hours)
4. Frequeny set on output 4/20mA (if enabled)
5. Starts/hour
6. Flow Air Delivered
7. Serial number
8. Software release
M1-2 PASSWORD
In this sub-menu you can change the password codes saved.
Parameters, setting range, default and levels are reported in the table below:
C20.1 Time Fan ON 10÷9999s Time ON fan in case of temperature probe disabled 500 3
C20.2 Time fan OFF 10÷9999s Time OFF fan in case of temperature probe disabled 500 3
0=Disabled
C21 Input Fault Inverter 0/1/2 1=Input enabled, managed normally open 0 3
2=Input enabled, managed normally closed
C22 Lubricating time 1 ÷ 999s Activation time of lubricating relay 2 3
C23 Interval lubricating 0 ÷99990m Time to lubricate 11000 3
NOTES:
C01–RESTART: in case of power off, by selecting “Man”, the compressor doesn’t start automatically and the display
visualizes "POWER OFF"; by selecting “Aut.”, the compressor restart automatically according a delay time set Wt5: during
this time the display visualizes the “WAIT”.
If you change the default setting, it is recorder into the alarm buffer and you can cancel it by general reset only.
C05–SAFETY: if you set “YES”, once the timer “CAF” will be over, the display visualizes the message “Shut-off for safety”;
you can erase it into this parameter only and set it as “Safety = NO”; in this case the alarm code change into “Change air
filter”.
C07–MULTIUNIT OPERATION: set “0”, the compressor works by standing alone.
Set “1”, the compressor communicates with a second unit via serial RS232 as Master/Slave (see related working program)
and the controller visualizes the parameters 07.1 e 07.2.
C07.1–TIMER MASTER / SLAVE: time to switch Master into Slave; if the difference of working hours between the two
compressors is bigger than the setting of this parameter, the unit with more hours will not be Master as long as the other
will reach the same.
C07.2–TIMER SLAVE: after power ON, if the Master unit has not reached the stop pressure until the time setting in this
parameter, the Slave will start to support.
C08–COMPRESSOR Nr.: in case of Master/Slave enabled, the compressor set as 1 will be the Master unit.
C09–SERIAL NUMBER: LCD visualizes the serial number on the third lower right side row from the bottom.
Push to edit.
You can select the characters by the arrows buttons; by shift forward to the next character or enter a new one, by ESC
shift back to the previous one; you can delete the editing by pushing ESC when the cursor in on the first character.
You can save the data by enter two SPACE in a row or by reaching the max. number of characters (15).
C17–Shut-off for C—h: alarm related to the maintenance timer C—h (check compressor); if you set “YES”, 100 hours
before the timer is over, the compressor stops showing alarm STOP FOR AL32 – CHECK COMPRESSOR.
You can reset the alarm and restart the compressor for the next 100 hours and every 50 working minutes the display
remind to maintenance C—h.
Once the residual 100 working hours are over, the compressor will stop again; you can reset such alarm by resetting the
maintenance timer only.
C18–Output 4/20mA: allow to upload factory default parameters in menu M1-9. Two different default set are provided
according regulation is related to the working pressure or air end temperature.
C22-C23: These parameters are enabled if one of the relay is configured as per setting value 7 (lubricating). In this case
the relay allows automatic lubricating according the setting on C22 and C23. The time to lubricate is calculated on BL timer
that is not visible for the reason used on this function.
NOTE: WP5 is visualized just in case the compressor has been set to Master/Slave operation (see menu 4 Compressor
SETUP).
Parameters AP1..AP4 are visualized if the security transducer has been configured in COMPRESSOR SETUP and if the
parameter C19 set 1 only.
AP4 is the max. internal pressure allowing to run the motor. (see icon I13, page 11).
M1-6 TEMPERATURES
In this menu you can change the setting related to the temperature.
Parameters, setting range, default and password level are reported in the table below:
M1-7 TIMER
In this menu you can change the setting related to the temperature.
Parameters, setting range, default and password level are reported in the table below:
NOTE: changing the set value, the new one is loaded once the counting in progress is over.
NOTE:
If you set the parameter a value different from 0 on the parameter DR0, you enable the inverter operation via RS485 and
related alarms 60, 61,62.
After the last parameter DA9 comes “Setup Drive” that allows to start the setting of the inverter; it means to send the
parameters from DR1 to DA9 to the inverter. Moreover all the required settings to make the system Logik26S+Drive
working, such as drive PID enable, drive PID setpoint and feedback source and so on, are programmed to the drive also.
Confirming “Setup Drive” the LCD visualizes the following screen:
Setup Drive
Drive ready
ScrewTemp
100°C
FEEDBACK MUL
WorkPress
WP1
MUL
MUL
PI5
WT3 PI1
+ +
100°C 1,0 1,0 1,0=20mA
- +
SETPOINT SUM MUL ∑ SUM MUL SUM
MUL OUT
WP3+WP4 -0,1 PI7 - 0,0=4mA
2 x WP1
1
PI2(xPM1)
PI4 PI6
1
MUL ∆
-1
PI3 PID
C18
Parameters, setting range, default and password level are reported in the table below:
Default Password
Function Description Setting range
Press/Temp level
PI1 PID prop. gain -99.99s÷ 99.99s 2.50/5.00 3
PI2 PID int. time -99.99s÷ 99.99s 10.00s/15.00s 3
PI3 PID der. time -99.99s÷ 99.99s 0.00s/0.01s 3
PI4 PID out scaling -99.99s÷ 99.99s 1.00/4.00 3
PI5 Adder multipl. -99.99s÷ 99.99s 0.00/1.60 3
PI6 Adder offset -2.00÷2.00 0.00/0.76 3
PI7 PID low limit -2.00÷1.00 0.00/-100 3
FR1 Min. Freq. 0Hz÷(FR2 – 5Hz) 25Hz/25Hz 3
FR2 Max. Freq. (FR1 + 5Hz) ÷ 500Hz 50Hz/50Hz 3
PT1 Ramp up time 0,1s ÷99,9s 5,0s 3
PT2 Ramp down time 0,1s ÷99,9s 5,0s 3
PT3 Jog Ramp time 0,1s ÷99,9s 5,0s 3
PM1 PID I gain multiplier 0,01 ÷9,99 1,00 3
NOTE:
For all the above parameters two default set are provided according the way of control (set on parameter C18).
PID output (limited to the interval 0..1) is transposed to output current: frequency FR1 (PID output=0) correspond 4mA,
frequency FR2 (PID output=1) correspond 20mA.
You have to set the frequency reference on the inverter so that 4mA/20mA input correspond the frequency ranged you
need. You have to set such range both on parameters FR1 and FR2.
PT3 is the duration of the acceleration/deceleration time in case the compressor has to reach the download status; in this
case inverter reaches the minimum frequency FR1 according ramp PT3.
In case of compressor loading the ramps are PT1, while the speed goes up and PT2 while speed goes down.
In case of pressure regulation, PM1 alters the integrating effect of the error on the setpoint; specially integral time PI2 is
multiplied for PM1 when the pressure is over setopint.
Set PI2 or PI3 zero, the related integration or derivative action is disabled.
The counting is related to the ON time of the line contactor (RL1) and goes on backward: when the counting reaches 0, the
display shows the related message and goes on as negative counting.
The storage of the hours comes every 15 minutes; if the power goes off during the counting such 15 minutes are missed.
If parameter C--h is set 10.000, the alarm “CHECK COMP.” is not enabled.
If parameter C-BL is set 29.999, the alarm “BEARING. LUB.” is not enabled (bearing lubricating).
By changing the set value than the count in progress is re-calculated.
Example: CAF, set 2000h, the counter is 1600, it means 400h has passed from reset. If yu change the set, for example
3000, the counter will change into 2600.
M1-11MAINTENANCE LIST
Memory related to reset of the maintenance timer with related date.
In case of empty memory the display visualizes the message “Memory empty”.
The memory keeps till 20 data, the twenty-first erases the first one and so on.
Once the maintenance requested has been carried out, you have to reset the related counter; if you don’t reset the timer
every 50 working minutes or every power on of the compressor the display visualized the related maintenance message.
M1-12ALARMS LIST
List of the alarm detected with related progressive number, date, time and cause.
For maintenance alarm the display shows the icon I04 , while the icon I05 for shut-off alarm.
Memory capacity of 20 alarms: the twenty-first erases the first one and so on; if the memory is empty the display visualizes
the message “Memory empty”.
M1-14RESET
Select the message you need and push Enter button: the display visualizes a confirmation message
To start reset select YES.
Now the display visualizes the blinking message “RESETTING” for about few seconds
NOTE:
GENERAL reset is allowed when the compressor is “OFF” only; the controller will load all factory default values.
NOTE:
Every time a shut-off alarm is detected, both relay set as alarm led DL1 are activated; the alarm message is stored into the
alarm list; once the cause of the alarm has been erased, push the button R to reset the message and start the compressor.
NOTE:
• In case of warning the relay set as alarm output is activated with intermittency further to led DL1; the alarm
message is stored into the alarms list.
• When the message is visualized (in case it has not automatic reset), by pushing the button R you can reset the
message.
MAINTENANCE MESSAGES
Code Description Cause
50 CHANGE AIR FILTER Timer CAF in menu 10 elapsed
51 CACHANGE OIL FILTER Timer COF in menu 10 elapsed
52 CHANGE SEP. FILTER Timer in menu 10 elapsed
53 CHANGE OIL Timer C— in menu 10 elapsed
54 CHECK COMPRESS. Timer C-h in menu 10 elapsed
55 CONCHECK BEARINGS Timer C-BL in menu 10 elapsed
WAITING Wt5 Timer MOTOR STARTS Press< IN SET Timer UNLOAD FOR UNLOADING
Wt5=0 P.Start Wt4=0 SET REACHED
0 SHUT OFF
ALARM
Press<P.Start Press>P.Stop
LOADING
0
I
The symbols into the above squares indicate the compressor status showed on the main visualization of the LCD.
The back is grey while the symbol is blinking.
Motor start
When the motor is activated the icon is visualized on the part related to the pressures.
Motor starts according the following procedure:
1. Line contactor and star contactor are activated for the time set on Wt1.
2. Star contactor deactivates and pause for the time set on Wt2.
3. Delta contactor activation.
4. Wait for time on Wt3, activation of load solenoid valve by exciting RL4.
Pushing
0 the compressor stops according the following procedure:
1. If the compressor is loading it switches to unloading for the time set on Wt5; during timer in progress restart is
accepted by the start button.
2. If the compressor is running unload and the value of Wt4 in progress is higher than Wt5 setting, the compressor stops
while Wt4 will be over.
3. If the value of Wt4 in progress is lower than Wt5 setting, Wt5 goes counting and the compressor will stop once Wt5 is
over.
Once the compressor stops for reaching pressure set, the timer Wt5 starts: during that time if you push the start
button, the display visualizes and the compressor will not start till the Wt5 counting is over.
In case the compressor stops due to alarm detection, till timer Wt5 starts: during that time, if you rest the alarm and push
the start button, the symbol start blinking and the compressor will not start till Wt5 counting is over.
Stop the compressor through remote start/stop input - IN4 (status symbol )
When the input IN4 opens, the compressor stops according the following procedure:
1. If the compressor is loading, switch to unload running for the time set on Wt4 and the display visualizes the blinking
symbol (instead of ); once the timer is over, if IN4 is still open the compressor stops and the symbol stops
blinking.
During Wt4 counting, if IN4 closes the compressor turns back under pressure transducer control.
2. Once Wt4 is over, if the compressor is running unload, it stops and the display visualizes .
3. If the compressor is in stand-by status due to pressure set reached, the display visualizes the symbol .
Output 4/20mA ha sto be connected to the speed analog reference on the inverter.
In case of inverter air end motor, C18=1, the starting procedure change for the reason the sequence start/delta is not in:
relay RL2 is activated directl (and function air end motor activated), wait for time Wt3 (load time) and then RL4 is activated
(load solenoid valve). Activation steps for star and star/delta are by passed.
In this configuration RL3 is always de-energized.
For run command you can use also relay outputs RL2,RL5, RL6 or RL7, eventually through external relays. These outputs
have to be set through the parameters C13, C14, C15 and C16 (value 5 in case of C18=1 and value 1 in case of C18=2).
Make reference to the PID operating drawing reported in the menu of the programming (see ANALOG OUTPUT) for the
calculation made by the controller.
When the compressor is loading the inverter PID is enabled: pressure setpoint and feedback come through MODBUS.
When the compressor is running unload the controller forces a constant frequency equal to the minimum frequency of the
range provided for the motor.
The controller can reset possible failures or alarms from the inverter through MODBUS interface.
The controller provides the user with some working data from inverter as frequency, power, current, voltage and IGBT
temperature and in case of failure or warnings the alarm/fault message and code.
For the operation functions the controller read also the working frequency range from the inverter.
Even in this case the start motor cycle bypass start and star/delta steps.
Set C07 as 1 (2 in case of protocol Master/Slave new allowing to connect two inverter machines). In the same menu set the
time to switch Master into Slave (parameter C07.1) and the timer Slave comes into force in case Master is not enough at
the first staring (parameter C07.2).
Pushing
I on one of the 2 compressors to put into operation both units.
During power up you have to wait for 5 seconds before the connection between the two compressors start.
Pushing
0 on one of the 2 compressors to switch OFF both units.
In case IN4 opens on one of the two compressors, it stops both machines.
In case one of the parameters WP2÷WP5 is changed on one of the two compressors, all these parameters are copied on the
other compressor.
Parameters are: date and time, Restart (automatic or manual), weekly timer and DLS/Summer time.
MULTIUNIT OPERATION
Connect the compressor to the net RS485 with other machines and master unit (one controller for compressor Logik3xS oor
one controller for compressors room management Logik200) .
Pushing I on one of the Multiunit compressors, all the units are ON.
Pushing
0 on one of the Multiunit compressors, all the compressors are OFF.
For the Multiunit operation, see related document.
In case of maintenance on the compressor, you can set parameter C07.3=YES to shift to manual operation (start/stop).
Master is automatically informed and consider this compressor out of order.
24 (twenty-four) months from the production date printed on the label of the serial number.
Both working and technical features of the controller must be fully respected: the warranty declines if the controller has
been opened or repaired by unauthorized personnel.
Operation or modification different from the original, wrong electrical wiring or bad assembling can be cause of failures or
malfunctioning of the controller; in these cases both warranty and own technical features of the controller declines.
Technical features, drawings and any other document in this manual are property of Logika Control that forbid any
reproduction, even partial, of text and illustrations.
On its unquestionable judgement, Logika Control reserves the authority to modify the product to improve operation and
performance, besides to the right to withdraw the product from the production, in any time and without notice.
REVISION INDEX
Revision 0 = Issue