Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Instructions and Advices To Use The Electronic Controller Logik 18

Download as pdf or txt
Download as pdf or txt
You are on page 1of 25
At a glance
Powered by AI
The document provides instructions and advice for using an electronic controller for compressors. It details technical specifications, installation, functions, alarms, and warranty terms.

It is an instruction manual for the Logik 18 controller, covering installation, configuration, operation, alarms, maintenance timer functions, compressor control, and master/slave operation.

It has inputs/outputs via terminal blocks, an LCD display, 6 button keys, safety and EMC certifications, operating temperature range, power supply requirements, relay outputs, and digital inputs/outputs.

Instructions and Advices

to use the electronic controller


Logik 18
ORIGINAL INSTRUCTIONS

(INDUSTRIAL CONTROL EQUIPMENT)


39UG
FILE: E316817

01.12.11 Rev. 0.3 1


INDEX

CAUTIONS Page 3

TECHNICAL FEATURES Page 4

MOUNTING Page 5

ELECTRICAL DRAWINGS AND LEGEND OF THE CONNECTIONS Page 5

CONNECTION THROUGH SERIAL PORT RS232 Page 8

CONTROL PANEL Page 10

DESCRIPTION OF THE VISUALIZATIONS Page 11

OPERATIONS USER LEVEL Page 12

ENTER PASSWORD Page 13

SETTING PARAMETERS Page 14

MENU PP = PRESSURES Page 15

MENU PH = TEMPERATURES Page 15

MENU Pt = WORKING TIMER Page 15

MENU Ser = MAINTENANCE TIMER Page 16

MENU Hour = WORKING HOURS Page 16

MENU aL = ALARMS Page 16

MENU rES = RESET Page 17

MENU CoNF = COMPRESSOR CONFIGURATION Page 18

MENU PASS = CHANGE PASSWORD Page 18

MENU OIL = QUICK OIL DRAIN Page 19

ALARMS WITH IMMEDIATE COMPRESSOR SHUT OFF Page 20

WARNINIGS (VISUAL ALARMS) Page 21

HOW LOGIK 18 CONTROLS THE COMPRESSOR Page 22

MASTER/SLAVE OPERATION Page 24

WARRANTY TERMS Page 25

01.12.11 Rev. 0.3 2


CAUTIONS

THE LOGIK 18 IS AN INDUSTRIAL CONTROL EQUIPMENT (NOT A SAFETY


INSTRUMENT) FOR THE OPERATION OF A SCREW COMPRESSOR.

THE INSTALLATION MUST BE MADE IN ACCORDANCE TO THE LOCAL AND


INTERNATIONAL STANDARDS AND REGULATIONS WHERE THE COMPRESSOR IS
MANUFACTURED.

THE INSTALLATION AND START UP OF THE CONTROLLER MUST BE CARRIED OUT BY


TRAINED PERSONNEL WELL KNOW IN THIS MANUAL.

THE CONTROLLER HAS TO BE USED IN STANDARD INDUSTRIAL ENVIRONMENT AND


IT CAN NOT BE USED IN EXPLOSION RISK ENVIRONMENT, MARITIME AND MILITARY
PURPOSE.

THIS MANUAL COULD BE SUBJET TO CHANGES; PLEASE CONTACT LOGIKA CONTROL


TECHNICAL OFFICE IN CASE OF DOUBT ON THE LAST VERSION.

01.12.11 Rev. 0.3 3


TECHNICAL FEATURES

- industrial control equipment for the operation and management of screw compressors only; don’t mount and use in
explosive room.
- In accordance to CE regulation:
Low tension: 2006/95/CE
Safety: EN 60730-1 (General regulations)
EMC 2004/108/CE
- In accordance to UL 508 (FILE #: E316817).
- Inputs and outputs via terminal-block board to wires (300V, 15A, 18-14AWG).
- Black auto-extinguishing box in ABS:
a) according EC:
IP64 for the front panel and IP20 for the other parts;
b) according UL:
Type 1 and Type 12 for front panel mounting , installation in pollution degree 2 for the other parts
- Tightening torque: 8 Nm
- Working temperature: -10°C (14°F) ÷ 50°C (122°F) 90% RH (non condensing).
- Storage temeprature: -20 (-4°F) ÷ 70°C (158°F).
- Power supply: 12Vac ± 10% 50÷60 Hz (power of the transformer’s secondary: ~ 8 VA) from safety transformer.
- Max. current absorbed = ~ 250 mA.
- Visualization through custom back light LCD and nr. 2 led.
- nr. 6 key buttons.
- nr. 1 emergency stop button according EN 60947-5-1, IEC 947-5-1, contacts AC-15, 3 A, 240Vac.
- nr. 1 input for temperature probe.
- nr. 1 input for pressure transducer.
- nr. 3 digital inputs for connection to Logika Control phases unit.
- nr. 1 input for PTC or Klicson for motor protection (IN7).
- nr. 6 opto isolated digital inputs from 12/24Vac to detect:
IN 1 = thermal motor
IN 2 = thermal fan
IN 3 = remote start/stop
IN 4 = air filter pressure switch
IN 5 = separator filter differential pressure switch
IN 6 = settable as: door of the electrical cabinet open – control phase relay – generic alarm
- nr. 7 outputs via relay with contact 1.5A max. (general use):
RL1 = line contactor
RL2 = delta contactor
RL3 = star contactor
RL4 = load solenoid valve
RL5 = fan contactor
RL6 = settable as: condensate drain solenoid valve or compressor status
RL7 = settable as: alarm or compressor status
MAX. RATED CURRENT WITH ALL RELAYS CLOSED: 4.5A
- nr. 1 serial port RS232 for connection to a second compressor (Master/Slave operation), PC or GSM unit
(Supervision - Tele Assistance).

- Check min. and max. power supply to the controller.


- Non volatile memory to store setting data, working hours, compressor status, alarm list.
- The controller switches OFF due to micro interruption longer than ~ 300 m.s..

Accessories:
- nr. 1 temperature probe KTY 13.5 for detection of the air end temperature: cable in silicone rubber, length 2.5 m,
working range –10 ÷ 130°C, resolution 1°C, precision ± 1°C.
- nr. 1 pressure transducer 4-20 mA for working pressure control: 2 wires, AISI 316L stainless steel membrane,
working range 0 ÷ 15 bar, resolution 0,1bar, precision ± 0,1bar.
- Windows™ application for remote control (Super Vision and Tele Assistance).
- nr. 1 Logika Control phases unit:
a) for power supply 380 ÷ 400V three phase
b) for power supply 230V three phase
c) for power supply 440 ÷ 460V three phase

01.12.11 Rev. 0.3 4


MOUNTING

Use the drawing below as overall dimensions to mount the controller.

106 mm OVERALL DIMENSIONS

161 mm

ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS

AVVERTENZE PER I COLLEGAMENTI

NOTES ON THE CONNECTIONS

Respect the working technical features and


instructions on the electrical wiring; in
special way both the cables of the
temperatures probes and pressure
transducers must be isolated from the
power cables and proper RC filters must be
placed on the contactors’ coils.
Besides pay attention low voltage and high
voltage cables run on separate trunks.
- On the back side of the controller there
must be enough space for wiring and
connectors.
- The rear side of the controller must be
protected against condensation, oil and
dust.
- Don’t wash the front panel by water
injection; clean the front mylar with a soft
cloth using soap water.

NOTE: the inputs not used have to be


connected to 12-24V directly, except IN4 if
not used has not to be connected

01.12.11 Rev. 0.3 5


LEGEND

Terminal M1
Poles 1-2 = power supply 12Vac

Terminal M2
Pole 1 = GND
Pole 2 = RX
Pole 3 = TX
Pole 4-5 = input PTC for motor protection (IN 7)
(Total resistance of operation = 2.900 ohm – Total resistance of restoration = 1.600 ohm)

Terminal M3
Poles 1-2 = air end temperature probe
Poles 3-4 = pressure transducer (pole 3 = negative - pole 4 = positive)

Terminal M4
Pole 1 = Pole 1 of the control phases unit (L3)
Pole 2 = Pole 2 of the control phases unit (L2)
Pole 3 = Pole 3 of the control phases unit (L1)
Pole 4 = Pole 5 of the control phases unit (GND)
NOTE: THE GND FROM THE CONTROL PHASES UNIT MUST NOT BE CONNECTED TO EARTH.
IT’S THE GROUND OF THE CONTROLLER AND MUST BE CONNECTED TO IT.

Terminal M5
Pole 1 = IN 1 = thermal motor (L)
Pole 2 = IN 2 = thermal fan (L)
Pole 3 = IN 3 = remote start/stop (L)
Pole 4 = IN 4 = air filter pressure switch (L)
Pole 5 = IN 5 = separator filter differential pressure switch (L)
Pole 6 = IN 6 = settable as: door of the electrical cabinet open – control phase relay – generic alarm
Pole 7 = common (N)

Terminal M6
Pole 1 = RL7 = alarm or compressor status
Pole 2 = RL6 = condensate drain solenoid valve or compressor status
Pole 3 = RL5 = fan contactor
Pole 4 = RL4 = load solenoid valve
Pole 5 = RL3 = star contactor
Pole 6 = RL2 = delta contactor
Pole 7 = RL1 = line contactor
Pole 8 = common = 24 ÷ 230Vac

01.12.11 Rev. 0.3 6


EXAMPLE OF CONNECTION TO THE SECURITY PRESSURE SWITCH

Contactors 24Vac
If the operation of the contactors and I°
soenoid valves come through 24 Vac,
the digital inputs have to be connected II°
to 24 Vac (see drawing on the right);
on this way when the pressure switch
12 – 0
opens due to high pressure, 24 Vac
lacks and deenergize all the contactors,
solenoid valve and digital: the controller Power supply to
the controller
detects all the digital inputs opened and
signal the alarm “AL21”. Security pressure
switch for high
pressure detection

Power supply to digital


inputs and uses
24 – 0

Contactors 230Vac I°
If the operation of the contactors and
solenoid valves comes through 230 Vac, the II°
digital inputs have to be connected to 12
Vac; next to the contact of the pressure 12 – 0
switch, place and energize an auxiliary
relay and put the contact in serie to
Power supply to
12 Vac (L) (see drawing on the right).
the controller
When the pressure switch is closed, the
Security pressure
auxiliary relay with contact closed supply
switch for high
power to the digital inputs; the power pressure detection
supply of the controller is connected before
the contact of the relay.
When the pressure switch opens, the Auxiliary relay
auxiliary relay opens power to the digital Power supply to the
inputs; the controller detects all the digital Power supply to digital inputs
inputs open and signal the alarm “AL21”. the uses
230 – 0

01.12.11 Rev. 0.3 7


CONNECTION THROUGH SERIAL PORT RS 232

Master – Slave connection LOGIK18 / LOGIK 16-S

GND 1 1 Logik 18 Logik 16-S

RX 2 2
Terminal M2 Terminal M4
TX 3 3 GND Pole 1----------------------Pole 3
Pole 2----------------------Pole 5
4 4 RX Pole 3----------------------Pole 4
5 5 TX

Logik 18 Logik 16-S

Master – Slave connection LOGIK 18 / LOGIK 25-S

GND 1 1 GND Logik 18 Logik 25-S


RX 2 2 RX
Terminal M2 Terminal M2
TX 3 3 TX Pole 1-----------------------Pole 1
Pole 2-----------------------Pole 3
4 4 +V
Pole 3-----------------------Pole 2
5 Logik 25-S
Logik 18

Master – Slave connection LOGIK 18 / LOGIK 18

GND 1 1 GND Logik 18 Logik 18


RX 2 2 RX
Terminal M2 Terminal M2
TX 3 3 TX Pole 1-----------------------Pole 1
Pole 2-----------------------Pole 3
4 4 Pole 3-----------------------Pole 2
5 5

Logik 18 Logik 18

Connection LOGIK 18 / PC

GND 1 Logik 18 PC
1
6
RX 2
Terminal M2 D’Sub 9 poles
TX 3 Pole 1------------------Pole 5
Pole 2------------------Pole 3
9
4 Pole 3------------------Pole 2
5
5

NOTE: in case of connection to PC through serial port RS232 or connection of single compressor (RS232) or several
compressors (RS485) to GSM unit, select the parameter nc into menu ConF (COMPRESSOR CONFIGURATION).

01.12.11 Rev. 0.3 8


INSTRUCTION FOR SERIAL CONNECTION RS232 AND/OR RS485

NOTES ON THE WIRING: wrong wiring can damage both the controller and other devices connected to the
serial port.

Be careful to the following technical points below:


1. Use flexible, twisted pair, earth shielded cable, type 22 AWG.
2. The total length of the net has to be no more than:
- 5 m for serial connection through RS232
- 400 m for serial connection through RS485
3. In serial connection RS485 the maximum devices connectable are 32 units.

NOTES ON INSTALLATION
• The signal wire must be placed in electrical trunk separated from power cables or dangerous cables like the wires
of lighting and so on….
• Don’t place the signal wires near power bus-bar, lamps, transformers and high frequency antenna.
• The signal cable must be minimum 2 m far from heavy inductive load (motors, inverters and control / patch
board).
• Don’t pull the cables by strength over 12 Kg; stronger strength can damage the wires and reduce the signal
transmission on the line.
• Don’t twist, knot, crush and fray the wires.
• Use always a single cable without cut it to make the connection between two devices.
• Pay attention to wire stripper.
• To be sure that the connection is well done, sign the position of terminal block with the colour of the wire.

01.12.11 Rev. 0.3 9


CONTROL PANEL

3 1 4

00 0
bar
psi 5
2 MS
I

0000 0
°C
Hrs °F 8
6 min
sec
7
0
9 00 000
10 11 12

RESET

MEANING OF ICONS

1 Compressor loading (icon lightened) – compressor unloading (icon blinking).


2 Remote start - stop enabled.
3 Compressor working into Master/Slave operation.
4 Working pressure detected (in the main visualization) or name of the parameter (into the different menu)
5 Unit of the pressure detected (in the main visualization).
6 Unit of timer and counter (into the proper menu).
7 Compressor status or temperature detected (in the main visualization) or value of the parameters (into the
different menu).
8 Unit of the temperature (in the main visualization).
9 Alarm detected (in the main visualization).
10 Code of the alarm detected (in the main visualization) or number of the menu (into the menu).
11 Icon indicating you’re into the menu.
12 Indication of the compressor status (in the main visualization) or number of the parameter (into the different
menu).

01.12.11 Rev. 0.3 10


DESCRIPTION OF THE VISUALIZATIONS

1) Power ON to the controller and the l’ LCD visualizes the following:

31 bar

OFF

2) From OFF goes to RUN by pushing the button I ; the LCD visualizes the following:

bar
31
°C
60 5
r vn
3) The possible compressor status are the followings:
Status Visualization Icon

Waiting for starting (timer t5) On blinking

Compressor starting Visualization of pressure - temperature and message


rvn blinking blinking

Compressor loading Visualization of pressure – temperature and message


rvn lightened

Compressor unloading for set Visualization of pressure – temperature and message


pressure reached rvn blinking

Set
Compressor in set
Visualization of the pressure
if remote
Compressor going to stop OFF blinking start/stop
(unload running)
opened
OFF if remote
Compressor off start/stop
Visualization of the pressure opened
See description on quick oil drain
Quick oil drain
(visualization of message OIL )

Compressor shut off for alarm Stop + alarm code

01.12.11 Rev. 0.3 11


FUNCTION OF THE KEY BUTTONS

From the main visualization, pushing the button the LCD visualizes in sequence the working hours, software
release and serial number of the compressor the manufacturer can enter in the parameter S-n. into menu 8

ConF (COMPRESSOR CONFIGURATION).


Pushing the LCD visualizes the following:

Hrs
T
15432

the total working hours of the compressor.


Pushing and/or the LCD visualizes in sequence:
L = load working hours - P = working percentage - n--
n- = starts/hour - s-n = serial number
reL = software release with own proper values.
In every step by pushing R the LCD shift back to the main visualization.
When the total working hours are visualizes, pushing the LCD visualizes the maintenance timer, always selectable
by and/or ; in sequence:
Caf = change air filter - COf = change oil filter - Csf = change separator filter - C-- = change oil - C-h = check
compressor with own proper residual timer.
After the visualization of C-h , pushing again, the LCD shift back to the main visualization.

Till on the main visualization, by pushing flow the menu down; enter to the menu and to the modification of the
parameters according the password levels reported in the chapter of every single menu.

In the main visualization, pushing the modification of the Start and Stop pressures is enabled.
Pushing once, the LCD visualizes the following:

bar
7 5
PSTrt

with the value of the start pressure blinking; by the button and/or change the value and confirm it by ; the
LCD shift to the modification of the Stop pressure, visualizing the following:

bar
8 5
PSTop

with the value of the Stop pressure blinking.


Follow the same procedure used to change the Start pressure and confirm by .
Once the data has been confirmed, the LCD shift back to the main visualization.

01.12.11 Rev. 0.3 12


The button R resets the alarm visualized on the LCD further to quit the menu during the programming.
Button I = compressor start
Button 0 = compressor stop

ENTER THE PASSWORD

When the compressor is OFF pushing and together it’s possible to enter the password for the programming of
the parameters; the LCD visualizes the following:

PA1
--

By the buttons and/or select the password level you need to enter (PA1 ÷ PA3) and confirm by the button

: according the password level you need to enter, the LCD visualizes the number of digits as per the figures to enter
with the first digit blinking:
- selecting PA1 = nr. 2 digits (default password 22)

- selecting PA2 = nr. 4 digits (default password 4444)

- selecting PA3 = nr. 5 digits (default password 66666)

Pushing the button R shift back the previous visualization.


Once the password level has been confirmed, enter the first digit by the button and/or and confirm it by ;
the next digit starts blinking.
Enter the next digits following the same procedure used for the first one.
When you enter the number, the button R is used to shift back to the previous digit, in case it’s wrong.
Confirming the last digit the password is accepted and you can enter to program the menu and parameters according
the level selected; in case the you enter a wrong password the LCD visualizes the following:

PA1
-Err-

The message -Err- blinks for 3 seconds to indicate the password is wrong and then the LCD shift back to the main

visualization.

PASSWORD MISSED
In case you’ve missed or forgotten the password number, it’s possible to restore the password default (on all 3 levels)
according the following procedure:
take power off, in case the controller is powered; supply power again and keep on pushing the button for 5
seconds.
The message reset blinks on the LCD to indicate the restoring of the password default is in progress.

01.12.11 Rev. 0.3 13


SETTING PARAMETERS
When the compressor is OFF, once the password has been entered correctly, in the main visualization by pushing
enter to the main menu and the LCD visualizes the following:

PP
01
PP (Pressures) indicates the first menu and 01 its own number into the main menu.
When you are into the menu flow, the icon with proper number of the menu are always visualized on the LCD.
- By the buttons and/or flow the menu up/down.
- By the button confirm the menu you need to enter and the LCD visualizes as follow:

P01 CODE OF THE PARAMETER

15 DEFAULT VALUE OF THE PARAMETER

01 NUMBER OF THE MENU YOU ARE INTO

- By the buttons and/or select the code of the parameter you need to change or by pushing R shift back to
the main menu; pushing on the last parameter, the LCD shift back to the menu you enter.
- By the button confirm the parameter selected; the setting value starts blinking to indicate the change is enabled.
- By the buttons and/or change the value and confirm it by .
- Pushing R shift back to the selection of the parameters without any change.

MENU FLOW

MENU Password Display DS2


1-Pressures 0 pp
2-Temperatures 1 pH
3-Working timer 1 pt
4-Maintenance timer 1 ser
5-Working hours 0 Hour
6-Alarms 0 aL
7-Reset 1 res
8-Compressor configuration 1 Conf
9-Password 1 pass
10-Quick oil drain 1 OIL

NOTE
After the visualization of the last menu, the controller quit the setting automatically and the compressor is OFF; after
120 seconds the password level is missed.
For safety reasons, after 120 seconds from the last pushing of any button, the controller quit the setting automatically,
loading the parameters changed.
ANTIPANIC FUNCTION: in every step of the setting , pushing the button for 5 seconds, the LCD shift back to the
main visualization.

01.12.11 Rev. 0.3 14


MENU 1 PP = PRESSURES

Parameters pertinent to the pressures.

Parameter Description Setting values Password Default


P01 Top range transducer 15 - 16 3 15 bar
P02 High pressure alarm (P03+0,5) ÷ (P01-0,5) 2 11,0 bar
P03 Stop pressure (P04+0,2) ÷ (P02-0,2) 0 10,0 bar
P04 Start pressure 3 ÷ (P03-0,2) 0 8,5 bar
P05 Start pressure slave 2,8 ÷ (P04-0.2) 0 8,3 bar
P06 Offset pressure transducer -2,0 ÷ +2,0 2 0 bar

NOTE: the parameter P 05 is visualized if the parameter con into the menu 8 ConF (compressor configuration) has
been selected 1 or 2 (Master/Slave operation).
After the last parameter, the LCD shift back to the message PP.

MENU 2 PH = TEMPERATURES

Parameters pertinent to the temperatures.

Parameter Description Setting values Password Default


H01 High air end temperature alarm (WT2+2°) ÷ 125 3 110 °C
H02 High air end temperature warning (WT3+2°) ÷ (WT1-2°C) 3 105 °C
H03 Temperature Start fan 30 ÷ ( WT2-2° ) 2 70 °C
H04 ∆T. Stop fan 5 ÷ 15°C 2 10 °C
H05 Low air end temperature alarm -10 ÷ +15 2 0 °C
H06 Offset temperature probe -10 ÷ +10 °C 3 0 °C

After the last parameter, the LCD shift back to the message PH.

MENU 3 Pt = WORKING TIMER

Parameter Description Setting values Password Default


T01 2 ÷ 20 sec 3 5 sec
T02 10 ÷ 50 ms 3 20 ms
T03 1 ÷ 60 sec 3 2 sec
T04 Unload timer 1 ÷ 10 min 2 4 min
T05 Safety timer 10 ÷ 240 sec 3 60 sec
T06 RL6 On 1 ÷ 10 sec 1 2 sec
T07 RL6 Off 1 ÷ 10 min 1 3 min
T08 Master/Slave rotation 0 ÷ 200h 2 100 h
T09 Timer slave 1 ÷ 99min 2 5 min

NOTE: the parameters t08 and t09 are visualized only if the parameter con into the menu Conf (Compressor
configuration) has been selected 1 or 2 (Master/Slave operation).
The parameter t08 set as 0 doesn’t allow the Master/Slave rotation.
Changing the set value, the new one is loaded once the timer in progress is elapsed.
After the last parameter, the LCD shift back to the message Pt.

01.12.11 Rev. 0.3 15


MENU 4 Ser = MAINTENANCE TIMER

This menu allows to set time for the maintenance to the compressor.

Parameter Description Setting values Default Livello Pin


Caf Change air filter 100÷3000 1-2-3 2.000 h
C0f Change oil filter 100÷10000 1-2-3 2.000 h
CSF Change separator filter 100÷10000 1-2-3 4.000 h
C-- Change oil 100÷10000 1-2-3 8.000 h
C-h Check compressor 100÷10000 1-2-3 500 h

After the last parameter, the LCD shift back to the message Ser .

NOTE
1) Changing the set value, automatically the value of the timer changes.
2) The new value is loaded once the timer in progress is elapsed or after the reset of the timer.
3) If the parameter C-h
C-h is set as 9.999 hours, the proper alarm will not be generated.
4) The counting is pertinent to the ON time of the line contactor (RL1) and it comes backwards; when the counting
reaches 0, the LCD visualizes the proper alarm and the timer goes on as negative counting; the storage of the
working hours comes every 15 minutes; if during the counting the power is off, the part of 15 minutes is lost.

MENU 5 Hour = WORKING HOURS

Into this menu it’s possible to visualize the working hours, load working hours, working percentage, starts/hour, serial
number of the compressor and software release.
The LCD visualizes the short name of the parameter (t, L, P, n--, s-n , reL ) with the proper value.

By the buttons and/or flow the timer up/down and by R shift back to the previous menu.
NOTE: it’s possible to change both “Total hours” and “Load hours” if password level 3 has been enabled.
Pushing the first figure starts blinking to be modified; by and/or select the new figure and
confirm it by and going to the next figures to set according the same procedure.
Confirming the last figure, the new value will be loaded into the memory.
During the setting, in case you need to come back to the previous character, push the button R .

MENU 6 AL = ALARMS

Visualization of the last 20 alarms code detected; the 21st erases the 1st and so on.
The LCD visualizes the following:

008
06 2
008 indicates the alarm code detected (make reference to the alarm list at page 20 and 21 of this manual)
2 indicates the times the alarm has been detected.
By the button and/or flow the alarm list up/down; by the button R shift back to the previous menu.
In case there is no alarm stored, the LCD visualizes the message “---- “.

01.12.11 Rev. 0.3 16


MENU 7 RES = RESET

In this menu it’s possible to make the following reset:

p-f = maintenance timer (password level = 1-2-3)


A-L = alarm list (password level = 1-2-3)
t-h = working hours (password level = 3)
G-G = general reset and load of the default values (password level = 3)

Enter into the menu by the button and the LCD visualizes the following:

P-F
rESEt
07
By the button and/or select the reset; by the button R shift back to the previous menu.

Start reset by pushing the button for 3 seconds: the message reset blinks for few seconds to indicate the reset is

in progress.
In case of selection and confirmation of the parameter p-f (maintenance timer), the LCD visualizes the following:

CAF
rESEt
07
pushing and/or flows the maintenance timer up/down to make possible the reset of each single timer.
Start the reset as explained above.
Pushing R shift back to the previous menu.
NOTE: general reset is allowed when compressor is OFF only.

01.12.11 Rev. 0.3 17


MENU 8 ConF = COMPRESSOR CONFIGURATION

Parameter Description Setting values Password Default


r-- Restart 0 (manual) – 1 (automatic) 1 0
FAS Control phases 0 (no) – 1 (yes) 1 1
0 (disabled) – (door open)
in6 Input IN6 3 0
2 (control phases relay) – 3 (generic alarm)
in7 Input PTC 0 (disabled) – 1 (enabled) 3 0
0 (condensate drain) – 1 (compressor status)
rl6 Output RL6 3 0
2 (always activated)
rl7 Output RL7 0 (alarm) – 1 (compressor status) 3 0
t4 Timer t04 0 (fixed timer) – 1 (variable timer) 1 1
S-- Safety 0 (no) – 1 (yes) 1 0
L-P Low voltage 0 (no) – 1 (yes) 1 1
Unit of the
c_F 0 =C - 1 =F 1 °C
temperature
b_P Unit of the pressure 0 = bar - 1 = psI 1 bar
n-- Starts/hour 6 ÷ 20 2 6
p-- Air flow 1.0 ÷ 200.0 3 1m3/min
con Connection 0 (stand alone) – 1 (Master/Slave) 2 1
nc Compressor nr. 0 ÷ 32 2 1
S-n Serial number 00000 ÷ 99999 3 00000

After the last parameter, the LCD shift back to the message Conf.
NOTA: the change of the parameter r -- (manual/automatic) is stored into the alarm list and it’s possible to reset by
general reset only.

MENU 9 PASS = CHANGE PASSWORD

In this menu it’s possible to change the password numbers of the three different levels.
Passwords are called PA1 (Service 1) - PA2 (Service 2) - PA3 (Factory).

To enter in the menu, confirm by and the LCD visualizes:

PA1
--
09
By the button and/or select the password level you need to change and confirm by while by R shift back
to the previous menu.
Once the editing is enabled, the first digit starts blinking and you can change it by the button and/or ; confirm
the first digit by shift forward to the next digit starts blinking; follow the same procedure to change all the next
digits; confirming the last one, the new password number is saved automatically.
NOTE: during the change, the button R allows to go back to the previous digit in case it has been edited wrong.

01.12.11 Rev. 0.3 18


MENU 10 OIL = QUICK OIL DRAIN

If this menu is selected when the compressor is not loading or running unload for pressure set reached, the LCD
visualizes the following with the Start blinking:

31 bar

StArt
10 ßOIL
In this status, pushing the button I , the compressor starts.
If the pressure is over 2.0 bar, the line contactor (RL1) is energized while the load solenoid valve (RL4) is not; the LCD
visualizes the following:

31 bar

-P-
10 ßOIL
with -P- blinking to indicate to blow down pressure to allow the quick oil drain process.

When the pressure goes down 2.0 bar, the load solenoid valve is energized and the LCD visualizes the following:

1 9 bar

run
10 ßOIL
with the message r un blinking to indicate the quick oil drain is in progress.

Stop the drain by the button and the LCD shifts back to the main menu.

01.12.11 Rev. 0.3 19


ALARMS WITH IMMEDIATE COMPRESSOR SHUT OFF

Code Meaning Cause


01 EMERGENCY STOP Emergency stop button opened (IN 1)
02 MOTOR OVERLOAD Thermal motor opened (IN 2)
03 FAN OVERLOAD Thermal fan opened (IN 3)
04 NO PHASE One or more phases are missed longer than 300 m.s.
05 WRONG PHASE Phases inverted
07 DOOR OPENED IN6 opened (parameter iN6 in menu Conf has been selected as door switch (1)
11 HIGH PRESSURE ALARM Working pressure over set P02
12 TEMP. PROBE FAILURE Air end temperature probe failure
13 HIGH AIR END TEMPERATURE Air end temperature over set H01
14 LOW AIR END TEMPERATURE Air end temperature probe lower than set H05
18 POWER FAULT In case of power off and compressor set as manual restart
19 CONTROLLER FAILURE The controller is not working properly
20 HIGH MOTOR TEMPERATURE Input IN7 (PTC) opened
21 INPUT POWER FAULT All digital inputs IN1 ÷ IN6 opened (security pressure switch opened, if mounted)
If the parameter in 6 in menu Conf has been selected as control phase relay
23 INPUT IN6
(2) or generic alarm (3)
25 SEPARATOR FILTER Separator filter differential pressure switch opened (IN5)

ALARMS WITH COMPRESSOR SHUT OFF AFTER 30 SECONDS UNLOAD RUN

Code Meaning Cause


26 PRESSURE TRANSDUCER FAILURE Pressure transducer failure
Power supply to the controller lower than 9,5Vac; reset accepted when
28 LOW VOLTAGE
voltage overcomes 10,6Vac
Timer CAF elapsed; alarm detected only if the parameter Safety is set
29 SECURITY
YES
Air end temperature over set H02
H02 . Reset with temperature lower than
30 HIGH AIR END TEMPERATURE
H02 -5°C

NOTE: in case of shut off alarm RL7 (if it set as alarm operation) is energized and the alarm message is stored into
the alarms memory; after the cause of the alarm has been solved, push the button to reset the alarm and restart
the compressor.
If the alarm “Low voltage” (code 28) has been disabled in menu ConF , it will not be detected.

WARNINGS (VISUAL ALARMS)

Code Meaning Cause


35 SETTING DATA FAILURE Default data loaded
36 AIR FILTER Air filter pressure switch closet (IN4)
Power supply to the controller lower than 11.6Vac with automatic reset
39 LOW VOLTAGE
when the voltage rise to 12Vac
40 HIGH VOLTAGE Power supply to the controller over 14.5Vac
42 RS232 FAILURE Communication interrupted
47* MAX. STARTS/HOUR Starts/hour has reached the value set in parameter Starts/hour (menu 7)

47* The alarm code “Max. starts/hour” informs the compressor will not stop; it will run continuously load/unload
according the pressure, until the expiration of 1 hour time from the first starting in the hour.
NOTE:
1) In case of warnings RL7 is energized intermittently (if it is set as alarm).
2) In case of message visualized (if it has not automatic reset), pushing the button the message reset, de-exciting
RL7 and storing the message into the alarm memory.
3) The code alarm 42 reset automatically when the communication restart properly.

01.12.11 Rev. 0.3 20


MESSAGES VISUALIZED IN ALARM LIST ONLY

Code Meaning Cause


48 MANUAL RESTART Restart set from automatic into manual
49 AUTOMATIC RESTART Restart set from manual into automatic

MAINTENANCE MESSAGES

Code Meaning Cause


50 CHANGE AIR FILTER Counter of the timer set into menu Ser parameter CAF elapsed
51 CHANGE OIL FILTER Counter of the timer set into menu Ser parameter COF elapsed
52 CHANGE SEP. FILTER Counter of the timer set into menu Ser parameter CSF elapsed
53 CHANGE OIL Counter of the timer set into menu Ser parameter C-- elapsed
54 CHECK COMPRESSOR Counter of the timer set into menu Ser parameter C-h elapsed

With message visualized on the LCD, the relay RL7 is excited intermittently (if it’s set as alarm); pushing the button
the message is reset and RL7 unexcited.
After the maintenance request by the message has been carried out, reset the counter into menu Ser ; if the counter

has not been reset, every 50 working hour or next ON to the compressor, the LCD visualizes the maintenance
message.

01.12.11 Rev. 0.3 21


HOW LOGIK 18 CONTROLS THE COMPRESSOR

Safety timer t05

Pushing the stop button 0 , the compressor stops according the following procedures:
a) if the compressor is running load, changes into unload running for the time set on t05; during this time the

restart is accepted by the button I ; once the timer t 05 is elapsed, the compressor stops and the LCD visualizes
the message OFF ;

b) if the compressor is running unload and the timer t04 is higher than t 05 , once t04 is elapsed, the compressor

stops and the LCD visualizes the message OFF ; if the timer t04 is lower than t05 , t05 starts counting and when

it’s over, the compressor stops and the LCD visualizes the message OFF ;

c) if the compressor is OFF due to pressure set reached, it stops and the LCD visualizes the message OFF ;

d) when the compressor stops and the message OFF is visualized, the timer t05 starts; during this time if the start

button I is pushed, the message OFF starts blinking and the compressor will not start till the timer t05 will be
elapsed.
In case the compressor stops due to an alarm, the timer t05 starts; during this time if the alarm message is reset and

the button I is pushed, the message OFF starts blinking and the compressor will start when the timer t05 is
elapsed only.

Operation of the load solenoid valve (RL4)


1 ) t04 set as fixed time = 0

When the pressure reaches the stop pressure, RL4 turns off, the LCD visualizes the pressure and the timer
t04 starts; when the timer is over, if the pressure is not below the start set, the compressor stops;
when the timer is in progress, if the pressure goes down the start set, the load solenoid valve turns on and the LCD
visualizes the pressure while the timer t 04 erases.

2) t04 set as variable time = 1

On the first start the compressor works as point 1; on the next cycle the controller counts the time the pressure
spend to decrease from stop to start set; if this time (tx) is higher than the set on t 04 , the next unload run t04 will

be reduced of 1 minute and so on up to a minimum time of 2 minutes.


Nel momento in cui tx diventa minore di t04 variato, il ciclo di vuoto successivo tornerà ad essere conteggiato

come il tempo impostato su t 04.

ATTENTION: on the contact of the relay operating the load solenoid valve is mounted an RC Filter (22 η F
+ 100 Ω ) sized for power of 4.7W; in case a less power load solenoid valve is used, if the valve keeps on
powered even if the contact of the relay is opened, the RC Filter must be eliminated by cutting the
terminal of the resistor R11.

Thermoregulation of the fan (RL5)


When the delta contactor (RL2) is activated, the fan contactor (RL5) operates as follow:
a) if the air end temperature is equal or higher than H03
H03 = RL5 ON;
b) if the air end temperature is lower than (H03
H03 – H04) = RL5 OFF.

01.12.11 Rev. 0.3 22


Operation of RL6 set as condensate drain solenoid valve
Every time the load solenoid valve is powered (RL4), the condensate drain solenoid valve (RL6) is activated and
deactivated according the time set on the parameters t06 and t07 ; besides it’s deactivated every time the load

solenoid valve switches OFF.

Operation of RL6 set as compressor status


When the compressor is ON the relay is excited, when the compressor is OFF for pressure set reached, the relay is
unexcited.

Compressor stopped through remote start/stop input (IN3)


When the remote start/stop input (IN3) opens, the compressor stops according the following procedures:
a) if the pressure is between start and stop set (load solenoid valve is on and is visualized on the
LCD = compressor loading), the load solenoid valve turns off for the time set on t04 and the LCD visualizes the

blinking message StOP; when the timer is over, if the remote start/stop input (IN3) is still opened, the compressor

stops and the message StOP stops blinking; during the timer t04, if the remote start/stop input (IN3) should close

again, the compressor comes back under the pressure transducer operation;
b) if the pressure is between start and stop set, the load solenoid valve is off and is blinking (compressor
unloading), when the timer t04 is over, the compressor stops and the LCD visualizes the message StOP;

c) if the compressor is stopped due to reaching the pressure set, the LCD visualizes the message StOP .

Restart after power off


Automatic.
In case of power off, when the power comes back again, the compressor restarts from the operation previous to power
off: if it was ON, will follow the start procedure mentioned below, after the timer t05 ; during t05 in progress, the

message OFF blinks.

Manual.
In case of power off, when the power comes back again, the compressor doesn’t restart automatically and the display
visualizes the message P-OF ; after the message has been reset, the compressor will start by pushing I .

01.12.11 Rev. 0.3 23


MASTER/SLAVE OPERATION
After the two compressors has been connected through the proper terminal of serial port RS232 (max. length not
longer than 5 m; for longer lengths use the line converter RS232/485):
1) check the parameters t08 (timer to change Master into Slave) and t 09 (timer to start Slave in case Master can’t

reach the pressure set on first starting) into menu Pt are properly set;

2) if one of the 2 compressors has more working hours than t08, the other compressor will work till reaching the

working hours of the first compressor plus the hours set on t08; after this time only, the Master/Slave rotation will

be operated.

Pushing the Start button on one of the two compressors both are operated:
both LCD of the two compressors visualize the blinking message OFF for around 5 seconds: during this time the start

button I is not accepted; when the message OFF


OFF stops blinking, the button I is enabled.

Pushing the Stop button on one of the two compressors both are stopped
The common parameters of the 2 compressors in Master/Slave operation are:

P02 -P03-P04-P05, the parameter for Manual / Automatic restart and timer t08 e t09 .
Changing one of these parameters, the modification is transferred to the other compressor automatically.

Slave compressor starts only if:


1) On first ON, the Master has not reached the stop pressure until the time set on t 09 .

2) The pressure goes down the value set on P 05.

3) If one of the two compressors has the working hours higher than the time set in the parameter Timer Master/Slave
(working hours), the other compressor will work continuously till to get the same working hours of the first
compressor in addiction to the hours set in the parameter Timer Master/Slave; only after this time, the
Master/Slave rotation will be operated.
NOTE: the compressor stops when the pressure reaches the value of P03 .

Master/Slave rotation comes:


1) When the timer set on t 08 elapses.

2) In case Master compressor shuts off .

NOTE:
1) In case of maintenance on one of the 2 compressors, before to stop it remember to set both units into standing
alone operation and set it again into Master/Slave operation after the maintenance will be carried out.
2) In case of serial line failure both compressors become Master.

01.12.11 Rev. 0.3 24


WARRANTY TERMS

24 (twenty-four) months from the production date printed on the label of the serial number.

Temperature probe is not included in the warranty terms.

Both working and technical features of the controller must be fully respected: the warranty declines if the
controller has been opened or repaired by unauthorized personnel.
Operation or modification different from the original, wrong electrical wiring or bad assembling can be
cause of failures or malfunctioning of the controller; in these cases both warranty and own technical
features of the controller declines.

Technical features, drawings and any other document in this manual are property of Logika Control that
forbid any reproduction, even partial, of text and illustrations.

On its unquestionable judgement, Logika Control reserves the authority to modify the product to improve
operation and performance, besides to the right to withdraw the product from the production, in any time
and without notice.

REVISION INDEX
Revision 0 = Issue
Revision 0.1 = Issue for UL certification
Revision 0.2 = Upgrade to function “2” for RL7
Revision 0.3 = Extended parameter t03 to 60 seconds

LOGIKA CONTROL s.r.l.


Via Garibaldi, 83/a
20054 NOVA MILANESE – MI –
ITALY
Tel.: +39 0362 37001
Fax: +39 0362 370030
01.12.11 Rev. 0.3 25 Web: www.logikacontrol.it

You might also like