Electronic controller
INFOLOGIC®
For ROLLAIR®
62 305 451 99 ed00
WARRANTY
The INFOLOGIC® has a warranty for 12 months from the date of commissioning
or a maximum of 18 months from date of manufacture (which ever occurs first).
The warranty shall be applicable only if the installation conditions and the maintenance operations
specified in this user manual are followed.
The guarantee is limited to replacing parts that are recognised as defective by our services.
NOTA :
This user manual complies with the requirements stipulated by the guidelines on machine
safety 98 / 37 / CE and is valid for machines carrying the CE label.
CONTENTS
06/07
Page 2 62 305 451 99
Chapter 1 - Safety Measures
SAFETY
The personnel using the INFOLOGIC® shall use safe work practices and respect the local instructions and regulations concerning safety and
hygiene.
All electrical tests shall be carried out according to the professional rules. Always cut off the electrical power supply before starting any kind
of maintenance work.
INSTALLATION
The electrical cabinet should have a free access for facilitating maintenance, the location of INFOLOGIC® shall allow at any moment the
visibility of luminous indicators and the digital display.
QUALIFICATION
The INFOLOGIC® shall be used only by competent, trained and qualified personnel; the manipulation of parameters can modify the
characteristics and the performances of the compressor.
EXTERNAL CONTROL
The Stop and Start buttons on the controller are deactivated when the INFOLOGIC® control is on "remote" or "LAN".
To stop the machine with the controller, it must first be placed in Local mode (see § 3.17)
Chapter 2 - Introduction
2.1 - Control panel 1
2.2 - Introduction
In general, the INFOLOGIC® controller has following functions :
• Controlling the compressor
• Protecting the compressor
• Monitoring components subject to, service
• Automatic restart after voltage failure (made inactive in the works)
06/07
62 305 451 99 Page 3
2.3 - Autornatic control of the compressor
The regulator maintains the net pressure between programmable limits by automatically loading and unloading the compressor. A number of
programmable settings, e.g. the unloading and loading pressures, the minimum stop time and the maximum number of motor starts are taken
into account.
The regulator stops the compressor whenever possible to reduce the power consumption and restarts it automatically when the net pressure
decreases.
Shut-down warning
A shut-down waming level is a programmable level below the shut-down level.
If one of the measurements exceeds the programmed shut-down warning level, this will aiso be indicated to warn the operator before the shut-
down level is reached.
S10
13 10 11 14 9 8 7 6 5
06/07
Page 4 62 305 451 99
Ref. Name Function
9 Pictograph Alarm.
06/07
62 305 451 99 Page 5
3.2 - Display
Description
1
Pictograph Description
Compressor status LOAD (during loaded running, the horizontal arrow flashes).
Dew-point temperature.
Service pictograph.
06/07
Page 6 62 305 451 99
3.4 - Main screen
Procedure
When the voltage is switched on, the Main screen is shown automatically, showing in short the operation status of the compressor and the
outlet pressure:
Main screen, typical example
bar
6,8
The screen shows that the compressor is running loaded (the horizontal arrow flashes) and that the outlet pressure is 6.8 bar(e).
3.5.1 - Description
5 4 3
• If the outlettemperature of the compressorelementexceeds the shut-down warning level (105 °C /221 °F), alarrn LED (4)
will light up and the related pictograph will appear fiashing.
Main screen with warning element outlet temperature
flashing
bar
6,6
• Press arrow key (3), the actual compressor element temperature appears.
Warning screen, element outlet temperature
06/07
62 305 451 99 Page 7
flashing
°C
106
The screen shows that the temperature at the outlet of the compressor element is 106°C.
• It remains possible to scroil through other screens (using keys 3 and 5) to check the actual status of other parameters.
• Press button (1) to stop the compressor and wait until the compressor has stopped.
• Switch off the voltage, inspect the compressor and remedy.
• The warning message will disappear as soon as the warning condition disappears.
• If the dew-point temperature exceeds the warning level (not programmable), alarrn LED (4) will light up and the related pictograph
will appear fiashing.
Main screen with warning dew-point temperature
flashing
bar
6,6
• Press arrow key (3) until the actual dew-point temperature appears.
Warning screen, element outlet temperature
flashing
°C
9
3.6 - Shut-down
3.6.1 - Description
06/07
Page 8 62 305 451 99
3.6.2 - Compressor element outlet temperature
5 4 3
If the outlet temperature of the compressorelementexceeds the shut-down level (110 °C/230 °F, programmable) the compressor will be shut-
down, alarm LED (4) will flash, automatic operation LED (5) will go out and the following screen will appear:
Main screen with shut-down indication, element outlet temperature
flashing
bar
6,6
• Press arrow key (3) until the actual compressor element temperature appears.
Shut-down screen, element outlet temperature
flashing flashing
°C
111
The screen shows that the temperature at the outlet of the compressor element is 111°C.
• Switch off the voltage and remedy the trouble.
• After remedying and when the shut-down condition has disappeared, switch on the voltage and restart the compressor.
flashing
bar
6,6
06/07
62 305 451 99 Page 9
3.7 - Servioe waming
3.7.1 - Description
A service warning will appear when the service timer has reached the programmed time interval.
4 3 2
• If the service timer exceeds the programmed time interval, alarm LED (3) will light up.
• Press arrow key (2) to scroll to <d06> and the service symbol is shown. Press key (1), the actual reading of the service timer
appears and is shown in <hrs> or <xI000 hrs> (if the service timer value is higer than 9999).
Example of service timer screen
<d06>
<hrs>
4002
The screen shows that the reading of the service timer is 4002.
• Press arrow key (2) to scroll to <d01 > and the running hours symbol is shown.
Press key (1), the actual reading of the service timer appears and is shown in <hrs> or <xl 000 hrs> (if the service timer value is
higer than 9999).
<d01>
<hrs>
8000
• Stop the compressor, switch off the voltage and carry out the service actions. See section Preventive maintenance schedule.
• The longer interval service actions must aiso include the shorter interval actions.
In the example above, carry out ail service operations belonging to the 8000 running hours interval
as well as those belonging to the 4000 running hours interval.
• After servicing, reset the service timer. See section Calling up/resetting service timer.
06/07
Page 10 62 305 451 99
3.8 - Scroiling through all screens
3 2 1
Control panel
Scroli keys (2 and 3) can be used to scroll through ail screens. The screens are divided into register screens measured data screens, digital
input screens (numbered as <d.in>, <d.01>, ... ), parameter screens (numbered as <P.01>, <P.02>, ... ) protections screens (numbered as <Pr.
0 1 >, ... ) and test screens (numbered as <t.01>, ... ).
During scrolling, the numbers of the screens appear consecutively. For most screens, the unit of measurement and the related pictograph are
shown together with the screen number.
In the event of a waming or a shut-down, the corresponding pictograph is blinking on the main screen.
Example
<hrs>
<d.01>
The screen shows the screen number <d.0 1 >, the unit used <hrs> and the related pictograph for running hours. Press enter key (1) to call up
the actual running hours.
In the event of a warning or a shut-down, the corresponding pictograph is blinking on the main screen.
06/07
62 305 451 99 Page 11
3.8.2 - Overview of the screens
<P.05> Modifying a service timer See section Calling up/modifying service timer
<P.06> Setting of unit for temperature See section Calling up/modifying unit for
temperature
<P.07> Setting of unit for pressure See section Calling up/modifying unit for
pressure
<P.08> Selection for function: Automatic restart See section Activating automatic restart
after voltage failure after voltage failure
<P.09> Selection between Y-D or DOL starting See section Selection between Y-D or
DOL starting
<P.10> Setting of load delay time See section Calling up modifying load delay time
<P.l 1> Setting of minimum stop time See section Calling up modifying minimum
stop time
<P.12> Setting a password See section Activating password protection
06/07
Page 12 62 305 451 99
3.9 - Menu flow
bar
˚C ˚C
˚C
bar bar
˚C
hrs
˚C ˚F ˚C
hrs hrs
x1000 hrs s s
x1000 hrs s s
06/07
62 305 451 99 Page 13
3.10 - Calling up outiet and dew-point temperatures
Control panel
3 2 1
bar
6,6
°C
83
°C
3
06/07
Page 14 62 305 451 99
3.11 - Calling up running hours
Control panel
3 2 1
bar
6,6
• Press arrow key (2) until <d.01> is shown and then press enter key (1) :
Control panel
3 2 1
06/07
62 305 451 99 Page 15
Starting from the Main screen :
bar
6,6
• Press arrow key (2) until <d.02> is shown and then press enter key (1) :
Control panel
3 2 1
bar
6,6
• Press arrow key (2) until <d.03> is shown and then press enter key (1) :
<hrs >
5000
The screen shows the unit used <hrs> and the value <5000>: the module hours of the compressor are 5000 hours.
06/07
Page 16 62 305 451 99
3.14 - Calling up loading hours
Control panel
3 2 1
bar
6,6
• Press arrow key (2) until <d.04> is shown and then press enter key (1) :
<hrs >
1755
The screen shows the unit used <hrs> (or <x1000 hrs> and the value <1755>: the loading hours of the compressor are 1755 hours.
Control panel
3 2 1
06/07
62 305 451 99 Page 17
Starting from the Main screen :
bar
6,6
• Press arrow key (2) until <d.05> is shown and then press enter key (1) :
<x1000>
10,10
This screen shows the number of unload to load actions (times 1 or if " 1 000> lits up times 1000). The number of unioad to load actions is
10100.
5 4 3
Starting from the Main screen :
bar
6,6
• Press arrow key (3) until <d.06> is shown and then press enter key (2) :
<hrs>
1 191
This screen shows the unit used <hrs> (or <xl 000> hours x 1000) and the value < 1191 >: the compressor has run 1191 hours since the
previous service.
06/07
Page 18 62 305 451 99
After servicing, see section Service warning, the timer has to be reset :
• Scroli to register screen <d.06> and press enter key (2).
• The reading (e.g. 4000) will appear.
• Press enter key (2), if a password is set enter the password. The reading will flash (indicating that resetting is possible).
• Press enter key (2) to, reset the timer to <0.000> or press reset key (1) to cancel the operation.
3 2 1
bar
6,6
• Press arrow key (2) until <P.01 > is shown and then press enter key (1). The actually used control mode is shown <LOC> for local
control, <rE> for remote control or <LAn> for LAN control.
• Press enter key (1) and if necessary enter the password. The actually control mode is blinking. Use keys (2) and (3) to change the
control mode.
• Press enter key (1) to program the new starting mode or press reset key to cancel.
3 2 1
06/07
62 305 451 99 Page 19
Starting from the Main screen :
bar
6,6
• Press arrow key (2) until <P.02> is shown and then press enter key (1). The actually used node ID is shown.
• Press enter key (1) and if necessary enter the password. The actually used node ID is blinking. Use keys (2) and (3) to change the
node ID.
• Press enter key (1) to program the new node ID or press reset key to cancel .
3 2 1
bar
6,6
• Press arrow key (2) until <P.03> is shown and then press enter key (1). Pressure band 1 <Pb.l> is shown on the display, key (2) can
be used to scroll to pressure band 2 <Pb.2>.
• Press enter key (1) on desired pressure band. The load level of the selected pressure band appears, key (2) can be used to scroil to
the unload level.
Loading pressure
bar
6,4
06/07
Page 20 62 305 451 99
Unloading pressure
bar
7,0
• Press enter key (1) to modify the load level (value starts blinking). A password may be required. Use keys (2) and (3) to change the
load pressure.
• Press enter key (1) to program the new values or press reset key to cancel.
3 2 1
bar
6,6
• Press arrow key (2) until <P.04> is shown and then press enter key (1). The active pressure band 1 <Pb.1 > is shown
on the display.
• Press enter key (1) to modify the pressure band selection (a password may be required). The active pressure band <Pb.1 >
starts blinking.
Pb.1
• Press key (2) to modify the active pressure band. Press enter key (1) to, confirm or reset key to cancel.
06/07
62 305 451 99 Page 21
3.21 - Calling up/modifying service timer setting
Control panel
3 2 1
bar
6,6
• Press arrow key (2) until <P.05> is shown and then press enter key (1) : the setting of the service timer is shown in <hrs> (hours)
or <xl000 hrs> (hours x 1000). Example: <4000 hrs> means the timer is set at 4000 running hours.
• Press enter key (1) to modify this value (a password may be required), the value blinks. Use arrow keys (2 and 3) to modify
this setting.
• Press enter key (1) to program the new value and to retum to the parameter screens.
3 2 1
06/07
Page 22 62 305 451 99
Starting from the Main screen :
bar
6,6
• Press arrow key (2) until <P.06> is shown and then press enter key (1). The possible settings are: <°C> and <°F>; the actually used
unit is shown.
• Appuyer sur la touche Entrée (1) (l'unité clignote), puis utiliser les touches fléchées (2 et 3) pour sélectionner une unité de
température différente.
• Appuyer sur la touche Entrée (1) pour programmer la nouvelle unité, puis appuyer sur la touche de réarmement pour revenir aux
écrans de paramètres.
3 2 1
bar
6,6
• Press arrow key (2) until <P.O> and the possible settings are shown <Mpa>, <psi>, and <bar>, press enter key (1) and the actually
used unit is shown.
• Press enter key (1) (unit starts blinking) and use arrow keys (2 and 3) to select another unit of pressure.
• Press enter key (1) to program the new unit of pressure and press reset key to return to, the parameter screens.
06/07
62 305 451 99 Page 23
3.25 - Selection between Y-D or DOL starting
Control panel
3 2 1
Starting from the Main screen :
bar
6,6
• Press arrow key (2) until <P.09> and the motor pictograph is shown and then press enter key (1). The actually used starting mode is
shown <Y-d> for Y-D (star-delta) or <doL> for DOL (direct-on line).
• This parameter can only be modified after entering a code. Consult us if the parameter is to be changed.
3 2 1
Starting from the Main screen :
bar
6,6
• Press arrow key (2) until <P.10> and the compressorload pictograph is shown and then press enter key (1) :
06/07
Page 24 62 305 451 99
<s>
10
• This screen shows the load delay time 10 and the unit <s> seconds. To modify this value press enter key (1).
• An optional password may be required, the value starts blinking and arrow keys (2) and (3) can be used to modify the value.
• Press enter key (1) to prograrn the new value, press reset key to cancel.
3 2 1
bar
6,6
• Press arrow key (2) until <P.11> and the motor pictograph is shown and then press enter key (1) :
<s>
10
• This screen shows the minimum stop time 10 and the unit <s> seconds. To modify this value press enter key (1).
• The value starts blinking and arrow keys (2) and (3) can be used to modify this value.
• Press enter key (1) to program the new value.
06/07
62 305 451 99 Page 25
3 2 1
bar
6,6
• Press arrow key (2) until <P.12> and press enter key (1) :
<PASS>
3 2 1
06/07
Page 26 62 305 451 99
A number of protection settings are provided. The protection screens are numbered <Pr.>, the pictograph shown with the protection screen
indicates the purpose of the protection.
Possible combinations are <Pr.> followed by a number and one of the next pictographs :
Pictograph Designation
<Pr> shown with the pressure pictograph shows the pressure protections.
<Pr.> shown with the element outlet temperature pictograph shows the element outlet temperature
protections.
<Pr.> shown with the dewpoint temperature pictograph shows the dewpoint temperature protections.
<Pr> shown with the ambient temperature pictograph shows the ambient temperature protections.
3 2 1
bar
6,6
• Press arrow key (2) until <Pr.> followed by a number and the element outlet temperature is shown and then press enter key (1):
<°C>
<Pr.01>
06/07
62 305 451 99 Page 27
<AL-H>
• The warning level for the high temperature waming level <AL-H> and the high temperature shut-down level <Sd-H>. Use scroll
keys (2 and 3) from the waming level to the shut-down level, press enter key (1) to modify the value
• The value appears on the display.
• Press enter key (1) to modify the value.
• An optional password may be required, the value starts blinking and arrow keys (2) and (3) can be use to modify the value.
• Press enter key (1) to program the new value, press reset key to cancel.
3 2 1
bar
6,6
• Press arrow key (2) until <t.01> is shown and then press enter key (1) :
06/07
Page 28 62 305 451 99
NOTES
06/07
62 305 451 99 Page 29
06/07
Page 30 62 305 451 99