Invensys Ech210b
Invensys Ech210b
Invensys Ech210b
GENERAL DESCRIPTION
ECH 200
air-air
air-water
water-water
motor-condensing
single circuit, with 1 or 2 compressors
(steps). 7 models are available:
CODE
MW320010
MW320020
MW320012
MW320022
MW320030
MW320032
MW320040
MW320600
MW320602
MODEL
ECH 210
ECH 210A
ECH 210B
ECH 210BA
ECH 211
ECH 211B
ECH 215B
EKP 200
EKP/S 200
DESCRIPTION
2-STEP CHILLER
2-STEP CHILLER WITH OPTIONAL ANALOG OUTPUT
2-STEP CHILLER AND INTERNAL PROPORTIONAL FAN + MODBUS
2-STEP CHILLER WITH OPTIONAL ANALOG OUTPUT + MODBUS
2-STEP, HEAT PUMP
2-STEP, HEAT PUMP AND EXTERNAL PROPORTIONAL FAN + MODBUS
2-STEP, HEAT PUMP + FAN ON/OFF WITH INTERNAL RELAY + MODBUS
REMOTE KEBOARD FOR ECH 200, WALL MOUNTING
REMOTE KEBOARD FOR ECH 200, WITH TEMPERAUTRE SENSOR,
WALL MOUNTING
Hot Start
Anti-freeze
Parameter
setting
from
the
keyboard or through a personal
computer
INSTALLATION
ANALOG INPUTS
There are 4 analogue inputs: 3
temperature probes, NTC probe (ST1
ST3), 1 configurable input for NTC probe
or for signal 4...20 mA (ST4).
Available configurations:
ST1
ST2
ST3
ACCESSORIES
ST4
Probe absent
NTC input: water/air at input
Digital input: request for heating
Digital input: temperature controller request
differential NTC input
Probe absent
NTC input Outlet water/air, anti-freeze
Digital input: Cooling request
Probe absent
NTC input: condensation
Input 4..20mA for condensation
Input 4..20mA for dynamic setpoint
NTC input: anti-freeze for water-water
machines with automatic (internal) reversing
of coolant gas
NTC probe: temperature controller in
heating mode for water-water machines with
manual reversal on water side
Probe absent
NTC input: condensation
Multifunctional digital input
NTC input: outdoor temperature
DIGITAL INPUTS
There are 5 voltage-free digital inputs
(ID1ID5).
ST1, ST2 and ST4 can be added to them
if configured as digital inputs. The
following configurations are available:
ID1:
ID2:
ID3
ID4
ID5
ST4
Flowswitch
Remote On-off
USER INTERFACE
triac outputs
1 keyboard output
Serial outputs
Relays
The following configurations are
available:
RL1
RL2
RL3
RL4
Compressor
Pump
Reversing valve
Boiler
LED
ALL
ON if compressor 1 active
OFF if compressor 1 is inactive
BLINK if safety timings are in
progress
ON if defrosting is active
Triac
TK
(NO
on
215B)
Label
1
2
A
B
Description
Remote Keyboard
(rear view)
ECH 200 (rear view)
Connector A
Connector B
ECH 200
2/6
DISPLAY
DIS PLAY
TEMPERATURE
CONTROL FUNCTIONS
OPERATING MODES
BOILER/ELECTRICAL HEATERS
cooling
heating
stand-by
off
The operating mode can be selected
from the keyboard or from the digital
inputs according to set parameters.
Unless the machine is configured as a
motorised condensing type, activation
and de-activation of loads depends
dynamically on the set temperature
control
functions,
on
the
temperature/pressure values measured
by the probes and on setpoints.
DYNAMIC SETPOINT
The regulation algorithm may be used to
modify the set point automatically on the
basis of outdoor conditions.
The purpose is to save ECH and to
compensate for drops in machine
performance if outside temperatures are
particularly demanding.
AUTOMATIC CHANGE-OVER
Changes from cooling to heating
according to parameters and ambient
conditions.
DIFFERENTIAL TEMPERATURE
CONTROL
PARAMETERS
By means of a set of parameters, one can
set the different types of machine and
the operating values of the different
algorithms. Parameters can be set in the
following ways:
instrument keyboard
Copy Card
HOT START
This HEAT mode function enables
ventilation only if the internal exchanger
is sufficiently hot. Unpleasant cold air
flows are thus avoided.
ANTI-FREEZE
If a refrigerating water internal exchanger
is supplied, this function prevents water
icing in cooling mode, by activating a
heater.
DISCHARGED MACHINE
In all operating modes except active
boiler or defrosting modes, the machine
is checked for leakage in the cooling
circuit or breakage of the reversal valve
(heat pump operation).
INTERNAL FAN
Up to 3 inputs can be configured to
command the same number of fan
speeds in the internal exchanger.
RECORDING OF DUTY HOURS
The device stores the number of duty
hours of the following in permanent
memory:
hydraulic pump
compressors
CONDENSATION CONTROL
The following speeds can be set for the
ventilation unit (located outside on the
heat exchanger, which acts as a
condenser: minimum speed, maximum
speed, SILENT speed corresponding to a
silenced operating condition (e.g. for
night-time).
DEFROSTING
Defrosting is active in HEAT mode only. It
is used to prevent ice forming on the
surface of the outside exchanger. Ice
ECH 200
3/6
DIAGNOSTICS
The controller can perform full systems
diagnostics of the machine and signal
alarms.
For some alarms the signal will not be
given for a certain amount of time,
preset by a parameter. For others, the
number of tripping events/hour is
counted. If, in the space of one hour,
these events exceed a set threshold
established by means of a parameter, an
alarm is activated and is then manually
reset.
Alarms with manual reset are reset by
pressing the ON-OFF button.
When an alarm is triggered, two things
occur:
CONNECTION
DIAGRAMS
ST3 probe configured as NTC
12AC
ALL
GND
12 AC 12 DC TC
GND
ST4
ST3
ST2
ID5
ID4
ID3
ID2
ST1
ID1
G H
Line
12 AC
ALL
12 AC
12 DC
GND
TC
GND
ST4
ID5
ID4
ST3
ID3
ST2
ID2
ST1
ID1
Line
Key
A
B
C
D
E
F
G
H
Description
Alarm exit
EMI Filter
CF control
TK / Relay 5 (215B)
Relay 1
Relay 2
Relay 3
Relay 4
ECH 200
4/6
TECHNICAL DATA
TECHNICAL DATA
Typical
Min.
12V~
10V~
50Hz/60
Hz
5VA;
1
25C
---
Max
.
14V
~
---
-----10C
----60C
30%
10%
90%
25C
-20C
85C
30%
10%
90%
ELECTRO-MECHANICAL
CHARACTERISTICS
120/240 V~
digital
outputs
24V~
outputs
Analogue
inputs
Digital
inputs
Terminals
and
connectors
Display and
led
Keys
Serials
n 4 relays 2A hp 240V~;
1/8 hp 120V~
Note: Total current on relays
must not exceed 8A
1 TRIAC 2 A
NOTE: HIGH VOLTAGE INPUTS
n 5 voltage-free digital
inputs
3 digits + sign;
5 red led
2 keys
n 1 serial 9600
n 1 serial 2400
SIGNAL
E00
E01
E02
E03
E04
E05
E06
E07
E11
E12
E13
E40
E41
E42
E43
E44
E45
E46
Remote Off
High pressure (digital)
Low pressure (digital)
Thermal cut-out for
compressor 1
Thermal cut-out for
condenser fan
Anti-freeze
Probe ST2 fault
Probe ST3 fault
High pressure / high
temperature (analogue)
Low pressure / low
temperature (analogue)
Thermal prot. for
compressor 2
Probe ST1 fault
Flowswitch
Probe ST4 fault
Anti-freeze alarm (waterwater machines with gas
reversal)
Machine out of coolant
Configuration error
Over temperature
COMPRE
SSOR 1
YES
YES
YES
YES
COMPRE
SSOR 2
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
RES 2
YES
RES.
1
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
Dimensions:
Front
panel
76x34x58mm
Container: PC+ABS plastic resin with
V0 extinguishing classification
Assembly: Panel, on 71x29mm hole
Panel Hole
PUMP
YES
YES
REGULATIONS
The product complies with the following
European Community Directives:
Secondary voltage:
12V~
Power: 5VA;
ECH 200
5/6
USE CONDITIONS
RESPONSIBILITY AND
RESIDUAL RISKS
PERMITTED USE
DISCLAIMER
This publication is the exclusive property
of Invensys Controls Italy S.r.l. which
absolutely forbids reproduction and
divulging of the same unless it expressly
authorises such acts. Nevertheless,
Invensys Controls Italy S.r.l. cannot
accept any responsibility due to use of
the said publication. This also applies to
any person or company involved in
creating and drafting this manual.
Invensys Controls Italy S.r.l. reserves
the right to make any modifications,
whether aesthetic or functional, without
any notice at any time.