Republic of The Philippines Tanggapan NG Sangguniang Panlungsod City of Naga
Republic of The Philippines Tanggapan NG Sangguniang Panlungsod City of Naga
SECTION 2. – Scope. – This provisions of this ordinance shall cover the construction,
installation and maintenance of Electrical Poles and wires, Cables for Television and Telephone
Pole and cables/wires within the territorial jurisdiction of the City of Naga.
SECTION 4.- The Approved Pole Location Plan shall contain the following details;
SECTION 5. - It shall be prohibited for all utilities to work on distribution lines without
securing working permit/clearances from the office of the City Engineer and Traffic and
Transport Management Office.
SECTION 6.- Horizontal and vertical clearances of distribution lines shall be maintained
at all times in accordance with Philippine Electrical Code I and II. All redundant poles shall be
removed.
SECTION 7. Installation and/or delivery of transformer, generator and other large utility
equipments shall be allowed only from 10:00 PM to 5:00 AM. Prior to installation and/or delivery
of the abovementioned equipments, clearances from City Engineer’s Office and TTMO Shall be
obtained.
SECTION 8 - Definition of Terms.- As provided in this Ordinance, the following words
and phrases shall mean:
1. Approved Pole Location Plan: A detailed plan designed to regulate erection and
maintenance of poles and distribution lines of various utility companies and private
individual.
2. CBD – Central Business District
3. Electric Utility: CASURECO II or any other electric energy provider.
4. NEA: National Electrical Administration
5. Revised Philippine Electrical Code (PEC 1 @ 2): Updated edition of electrical code
as formulated by the Institute of Integrated Electrical Engineers of the Philippines
and approved by the Department of Public Works and Highways as basis for
regulation of all electrical installations in the Philippines.
6. Sag: The difference in elevation between the highest point of support of the
conductor and the lowest point of the conductor in the span
7. Service: The conductors and equipment for delivering energy from the electricity
supply system to the wiring system of the premises served.
8. Service Conductors: The supply conductors that extend from the street main or from
transformers to the service equipment of the premises supplied
9. Service Entrance The portion of electrical system from the service drop wire to the
service equipment of the premises supplied.
10. Service Drop: The overhead service conductors from the last pole or other aerial
support to and including the splices, if any, connecting to the service entrance
conductors at the building or other structure.
11. Service Lateral the underground service conductors between the street main,
including any risers at a pole or other structure or from transformers, and the first
point of connection to the service entrance conductors in a terminal box or meter or
other enclosures with adequate space, inside or outside the building wall. Where
there is no terminal box, meter or other enclosure with adequate space, the point of
connection shall be considered to be the point of entrance of the service conductors
into the building.
12. Utilities – All public utilities operating within the territorial jurisdiction of the City of
Naga such as, but not limited to Electric Cooperative/company, Telephone company,
cable television and the like.
SECTION 11. -.All newly constructed or renovated commercial building shall allocate
adequate space solely for electrical equipments installation and maintenance. The size of the
area shall comply with the requirements of the Revised Philippine Electrical Code.
SECTION 12. -. Height & Other Requirements – a) The minimum height of service
support in a building shall be 5.8 meters measured from the bottom of the bracket or pin
insulators.
b) Measured from the top the height of rain tight service head shall be 5.9 meters.
g) All secondary drop wire shall be allowed to cross street in one predetermined location.
h) All electrical installation shall be done in accordance with approved standards and
superior workmanship.
i) No electric pole shall be erected by the electric utility without prior approval from the
Office of the Building Official/Office of the City Engineer.
j) Distribution lines along Elias Angeles and General Luna shall be relocated in
accordance with the Approved Pole Location Plan.
SECTION 13. - All existing generator distribution lines shall be deemed illegal electrical
installations and shall be removed from the distribution system.
SECTION 14. - It shall be prohibited at all times to install portable generator along
established sidewalk and thoroughfares.
SECTION 15. – There shall be a uniform type of streetlight at CBD I and CBD II
a) No building shall be tapped to any telephone utility without prior approval from the
local building official.
b) All commercial establishments shall have central telephone terminal cabinet wherein
the capacity of which shall be enough to supply the required telephone lines of the building.
e) All telephone lines outside of a building shall be run in approved type conduit.
f) All traversing telephone drop wire shall be allowed only in traversing points as
indicated in the APLP.
g) Traversing telephone line shall be allowed underground as long as it will be done
through boring.
h) All communication poles shall be removed and telephone lines thereat shall be
transferred to electric cooperative poles.
j) All telephone lines shall maintain clearances in accordance with PEC, NEA and
electric cooperative standards.
k) All telephone line shall maintain sag not more than 0.30 per span.
l) All service drop conductor that run along with backbone lines shall be bundled with the
latter.
m) All telephone entrance shall be installed with a minimum height of 4.8 meters
measured from the top of rain tight service head.
n) Only one entrance per telephone provider shall be allowed for a building or structure.
Provided, that no distribution line shall be installed within private lots without the written
permission of the property owner.
SECTION 17. – The following shall be observed by all Community Cable Television
Company operating within the City of Naga:
a) All Community Cable Television supply cable outside of the building shall be installed
in approved type of conduits.
b) No additional pole shall be allowed for exclusive use of Community Cable Television.
c) All distribution cable of CCTV shall maintain clearances in accordance with PEC 1
and 2, NEA and electric cooperative standards.
d) All distribution cable of CCTV shall maintain allowable sag, which is not more than
0.30 per span.
e) All CCTV entrance shall be installed with a minimum height of 4.8 meters.
f) Only one entrance per CCTV provider shall be allowed for a building or structure.
g) All traversing CCTV drop wire shall be allowed only in traversing points as indicated in
the Approved Pole Location Plan.
Provided, that no distribution line shall be installed within private lots without the written
permission by the concerned property owner.
Article V- TRANSITORY AND PENAL PROVISION PROVISIONS
SECTION 18. – All public utility companies operating within the territorial jurisdiction of
the City of Naga is hereby given a period of one (1) year from the affectivity of this ordinance to
relocate their facilities and to comply with the requirements herein provided..
SECTION 20. – Separability Clause – If any provision or portion of this ordinance found to
be a violation of the constitution and declared invalid, the provisions or portion hereof which are
not so declared shall remain to be in full force and effect.
SECTION 21. – Repealing Clause – All ordinances, executive orders and rules and
regulations or parts thereof, which are inconsistent or in conflict with the provisions of this
ordinance are hereby repealed, amended or modified accordingly.
SECTION 22. – Effectivity – This ordinance shall take effect upon its approval and fifteen
(15) days after publication in a newspaper of local circulation.