Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

02 - 1000V & 1500V DC Disconnector

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

www.moeller.

net

www.eaton.com

Main and Group Switches in


Photovoltaic Applications

Product Information
N...S1-DC Switch-Disconnectors
Switch-disconnectors for 1250/1500 V DC 1
Content

Ordering
Content

Switch-disconnectors 2
Bridge kits 2

Technical data
Switch-disconnectors 3
switch-disconnectors and bridge kits:
Reduction of rated operational current 4

Dimensions
Switch-disconnectors N2..., N3... 5
Switch-disconnectors N4..., 6

CA01215001Z-en www.eaton.com
2 Switch-disconnectors
Switch-disconnectors for 1250/1500 V DC, 2 pole
N...S1-DC
Circuit-breakers for 1250/1500 V AC, 2 pole
Switch-disconnectors for 1250/1500 V DC, 2 pole

Rated opera- Short-circuit Fixed mounted Price


tional current protective See Price Std. pack Notes
= rated device max. Part no. List
uninterrupted fuse gR- Article no.
current characteristic Euro
DG
In = I u
A A gR

Switch-disconnectors for 1250/1500 V DC S = screw connection


160 200 N2-4-160-S1-DC 442.00 1 off S IEC/EN 60947-3
127732 43 Main switch characteristics including positive drive to
200 200 N2-4-200-S1-DC 657.00 S IEC/EN 60204 and VDE 0113.
127733 43 Isolating characteristics to IEC/EN 60947 and VDE 0660.
Busbar tag shroud to VDE 0160 Part 100.
250 315 N2-4-250-S1-DC 803,00 S Switch-disconnectors N can, in addition, be combined
154940 43 with voltage releases NZM...-XU, NZM...-XA and
320 500 N3-4-320-S1-DC 1,095.00 S auxiliary contacts
127734 43 as well as with remote operator NZM...-XR...
Terminal type:
400 500 N3-4-400-S1-DC 1,269.00 S
For 2 pole switching, series connection of two poles
142267 43
each is required. See accessories bridge kits.
500 500 N3-4-500-S1-DC 1,483.00 S
142268 43

800 – N4-4-800-S1-DC 2,742.00 S


119890 43
1000 – N4-4-1000-S1-DC 3,284.00 S
119891 43 N...S1-DC can not be combined with withdrawable units
and/or connection on rear.
1250 – N4-4-1250-S1-DC 3,909.00 S Can not be combined with early-make auxiliary contacts
119886 43 NZM-...XHIV or box terminal NZM2-4-XKC at Ui > 1000 V DC.
1400 – N4-4-1400-S1-DC 4,797.00 S For non-earthed networks > 1000 V DC the installation
119887 43 must be configured such that the likelihood of a double
earth fault is negligibly small.
1600 – N4-4-1600-S1-DC 4,960.00 S
152552 43

Rated operational For use with Number of Protec- Part no. Price Std. pack
current poles tion class Article no. per item
In Euros
DG
A

Bridge kits
Model contains parts for upper switch side for 4 pole switches N...-S1-DC that are used as 2 pole switches for DC.
The links each connect two contacts in series. Incoming unit and outgoer at bottom or top, user-definable.
N4-4-... ≥ 1250 A: alternate connection at bottom through module plates NZM4-4-XKM2S-1600.
Jumper kit with cover 160 at 70 °C N2-4-…S1-DC 2 pole IP2X NZM2-4-XKV2P 87.00 1 off
200 at 65 °C 131730 43
incoming unit at top 160 at 70 °C N2-4-…S1-DC 2 pole IP2X NZM2-4-XKV2POU 107.00
outgoer at bottom or 200 at 65 °C 144070 43
in reverse
Jumper kit with cover 400 at 70 °C N3-320(400)-S1-DC 2 pole IP2X NZM3-4-XKV2P 149.00
131731 43

Jumper kit with 400 at 70 °C N3-400(500)-S1-DC 2 pole IP00 NZM3-4-XKVI2P 124.00


insulating plates and 500 at 50 °C 142269 43
phase isolator

Jumper kit with cover 400 at 70 °C N3-400(500)-S1-DC 2 pole IP1X NZM3-4-XKV2P-K 207.00
and heat sink 500 at 55 °C 142271 43
500 at 40 °C IP2X

Jumper kit with 500 at 65 °C N3-500-S1-DC 2 pole IP00 NZM3-4-XKVI2P-K 181.00


insulating plates, 142270 43
phase isolators and
heat sinks

Jumper kit with cover 1250 at 65 °C N4-4-…S1-DC 2 pole IP2X NZM4-4-XKV2P 430.00
1400 at 40 °C 119888 43

Jumper kit with phase 1400 at 65 °C N4-4-1400-S1-DC 2 pole IP00 NZM4-4-XKV2P-K 900.00
isolators and heat 1500 at 65 °C N4-4-1600-S1-DC 152553 43
sinks 1600 at 40 °C

CA01215001Z-en www.eaton.com
Switch-disconnectors 3
Technical data
N...S1-DC
Circuit-breakers, switch-disconnectors for 1000 V AC/DC
Technical data

Switch-disconnectors 1250/1500 V DC N2-4...S1-DC N3-4...S1-DC N4-4...S1-DC


max. 250 A max. 500 A max. 1600 A

Rated operational voltage Ue V DC 1250 1250 1500


Rated uninterrupted current with terminal jumpers
at 40° C Iu A 250 500 1600
at 65° C Iu A 250 500 1500
Rated operating current Ie 250 (DC 22-A) 500 (DC 22-A) 1600 (DC 22-A)
Rated short-time withstand current t =0.1 s Icw kA 3 6 25
Rated conditional short-circuit current Iq kA 15 15 –
With back-up fuse up to 1000 V A gR 315 500 –
Maximum operating frequency Ops/h 120 60 60
Lifespan
mechanical Operations 20000 15000 10000
(of which max. 50 % trip by shunt/undervoltage
release)
Electrical Operations 2500 (DC 22-A) 1000 (DC 22-A) 500 (DC 22-A)
Rated insulation voltage Ui V DC 1250 1250 1500
For use in IT electrical power networks V DC 1000 1000 1000

Notes N...S1-DC can not be combined with withdrawable units and/or connection on rear.
Can not be combined with early-make auxiliary contacts NZM-...XHIV or box terminal NZM2-4-XKC
at Ui > 1000 V DC.
Terminal type N...S1-DC:
for 2 pole switches series connection of two poles each is required.
See accessories jumper kits NZM...-4-XKV2P

CA01215001Z-en www.eaton.com
4 Switch-disconnectors
Temperature dependency
N...S1-DC
Temperature dependency

Reduction of the rated operational current (derating) under particular ambient conditions
Basic devices Bridge kits Bus- Mount- Temperature compensation coefficient
bar tag ing 20 °C 30 °C 40 °C 50 °C 55 °C 60 °C 65 °C 70 °C
shroud posi-
tion

Switch-disconnector
N2-4-160-S1-DC +NZM2-4-XKV2P(OU) IP2X s 1 1 1 1 1 1 1 1
w 1 1 1 1 1 1 1 1

N2-4-200-S1-DC +NZM2-4-XKV2P(OU) IP2X s 1 1 1 1 1 1 1 0.95


w 1 1 1 1 1 1 0.95 0.92
N2-4-250-S1-DC Data on request

N3-4-320(400)-S1-DC +NZM3-4-XKV2P IP2X s 1 1 1 1 1 1 1 1


w 1 1 1 1 1 1 1 1

+NZM3-4-XKVI2P IP00 s 1 1 1 1 1 1 1 1
w 1 1 1 1 1 1 1 1

N3-4-500-S1-DC +NZM3-4-XKVI2P-K IP00 s 1 1 1 1 1 1 1 0.97


w 1 1 1 1 1 1 0.97 0.95

+NZM3-4-XKVI2P IP00 s 1 1 1 1 0.97 0.95 0.92 0.89


w 1 1 1 0.97 0.95 0.92 0.89 0.87

+NZM3-4-XKV2P-K IP1X s 1 1 1 1 1 0.98 0.95 0.92


w 1 1 1 1 0.97 0.94 0.91 0.89

+NZM3-4-XKV2P-K IP2X s 1 1 1 0.95 0.92 0.89 0.86 0.83


w 1 1 0.98 0.93 0.9 0.87 0.84 0.81

N4-4-800(1000)-S1-DC +NZM4-4-XKV2P IP2X s 1 1 1 1 1 1 1 1


w 1 1 1 1 1 1 1 1
N4-4-1250-S1-DC +NZM4-4-XKV2P IP2X s 1 1 1 1 1 1 1 0.97
w 1 1 1 1 1 1 0.97 0.95
N4-4-1400-S1-DC +NZM4-4-XKV2P IP2X s 1 1 0.94 0.92 0.9 – –
N4-4-1600-S1-DC w 1 1 0.97 0.91 – – – –
+NZM4-4-XKV2P-K IP00 s 1 1 1 0.98 0.961) 0.941) 0.931) 0.911)
w 1 1 1 0.98 0.961) 0.941) 0.931) 0.911)

Notes Mounting position:


v = vertical, h = horizontal
Incoming unit and outgoer at bottom or top, user-definable.
1) Incoming unit from bottom only.

CA01215001Z-en www.eaton.com
Switch-disconnectors 5
N2, N3
Switch-disconnectors, 4 pole Jumper kit
Size 2: basic devices

N2-4 NZM2-4-XKVP
149 93

103

b a
70 25 5

88
f 35
M8 x 22

19.5

24.5

3
80

24
R1

95
N
145
135

184

100
72.5

88
35 35 35

M4 x 85/20 140
SW5
f 35

35 78.7
a b
f5 140 f5

Switch-disconnectors, 4 pole
N3-4
166 ① Blow out area, minimum clearance to other parts
120.5
② Minimum clearance to adjacent parts

b a
90 31 5
f 60
20.5

M10 x 30
28 29.5

135
123.4

R 205

N
95
234
216

275

117

SW5 M5 x 75
45
f 60

69.7
a b

f5 185 f5

Jumper kit
NZM3-4-XKV2P... NZM3-4-XKVI2P...
325
110 155 66.25
31
191.55
200
106

445.5

M10 x 40
390

M5 x 25

45 45 45
185 185

CA01215001Z-en www.eaton.com
6 Switch-disconnectors
N4
Switch-disconnectors, 4 pole
N4-4
140 207 ① Blow out area, minimum clearance to other parts
138 ≤ 690 V : 100 mm
b ≤ 1500 V : 200 mm
a 33 8

f 100
② Minimum clearance to adjacent parts

44
≤ 1000 V : 15 mm
108

≤ 1500 V : 70 mm

119
171.5
180

21
117
313
401

N
87.5
15

M5 x 110
o 10.5
b
15

100 100
45 70 25
f 15 f 15
280

Jumper kit
NZM4-4-XKV2P
280 125.5

NZM4-4-XKV2P
108.5

M10 x 60
SW 16
466
522

171.5

o 13

SW 16
32

56

NZM4-4-XKM2S-1600
16

70 70 70 33 20
50

280

NZM4-4-XKV2P-K
240 80.5

NZM4-4-XKV2P-1400

M10 x 65
201

SW 16

M10 x 55
SW 16
613
647

o 13
32

56

NZM4-4-XKM2S-1600
16

70 70 70 33 20
50

280

CA01215001Z-en www.eaton.com
Eaton Corporation Adresses worldwide:
www.moeller.net/address
Eaton is a leading energy
management company. Eaton E-Mail: info-int@eaton.com
operates worldwide with products, Internet: www.moeller.net
systems and services in the www.eaton.com
electrical, hydraulic, aerospace,
truck and automotive sectors. Publisher:
Eaton Electric GmbH
Hein-Moeller-Straße 7-11
Eatons Electrical Sector D-53115 Bonn

Eatons Electrical Sector is the © 2011 by Eaton Industries GmbH


Änderungen vorbehalten
worldwide leader in products, CA01215001Z-EN/ICD-MTD/SRA 04/11
systems and services for energy (04/11)
distribution, safe electricity supply
and automation in industrial,
residential and purpose-built
buildings, public facilities, energy
providers, commerce and OEMs.
Eaton Electrical Sector includes the
brands Cutler-Hammer®, Moeller®,
Micro Innovation, Powerware®,
Holec®, MEM®, Santak® and MGE
Office Protection Systems™.

www.eaton.com

You might also like