GL315

SF6 circuit breakers 362 kV


Technical specification

abcd
T&D
Transmission
Technical characteristics

Description Advantages
- Optimisation of the use of arc energy enables
The GL300 series of SF6 circuit breakers are auto-
operation by means of a low energy spring
expansion type. They benefit both from our experience
mechanism.
and the latest technological development relating to
high voltage switchgear. - Spring mechanism for high reliability.
- Class C2 in capacitives switching.
The use of components produced in accordance with the
ISO 9001 certified quality assurance system ensures a - EHV lines operation.
high standard of reliability and availability.
- Shunt reactors closing and capacitor banks
operation.
The GL315 circuit breakers are made of two interrupting
chambers per pole. - Quick and easy erection on site.

Three operating mechanisms allow the circuit breaker Options


operation.
- Closing resistor.
The operating mechanism driving the circuit breakers - Monitoring system CBWatch-2.
from GL series are simplified, with charging time for
springs less than 10 s. - Point-on-wave controller RPH2.

GL315
Rated service voltage kV 362
Standards CEI ‘62 271-100’ ANSI
Rated permanent current A 4000
Rated frequency Hz 50 / 60 60
Rated peak withstand current kA 135 137
Rated dielectric withstand (at sea level)
- At power frequency kV 555 555
- At lightning impulse (1,2/50 µs wave) kV (peak) 1 300 1 300+chop wave
Rated short-circuit breaking capacity
Periodic component (r.m.s. value) kA 50
Aperiodic component % 50
First-pole-to-clear-factor 1,3
Rated short-circuit making current kA (peak) 125 137
Rated characteristics for short-line faults Z=450 W
Out-of-phase rated breaking capacity
Current kA 12,5
Rated line-charging breaking capacity (class C2)
Current A 315
Rated cable-charging breaking capacity (class C2)
Current A 355
Break-time ms £ 40 / 36
Rated operating sequence CO-15s-CO or O-0,3s-CO-3min-CO
Creepage distance (minimum value)
Between live parts and ground mm 7 500 … 11 260
Across terminals mm 13 480
Auxiliary supply voltages
Opening and closing circuits V 48 - 110 - 125 - 220 - 250 V (dc)
Heating circuits V 220 V (ac)
Motor V 110 - 220 V (dc) or 220 V (ac)
Environmental factors
Temperature : minimum / maximum °C -30 / +40*
Maximum wind velocity km/h 122 ... 160
Seismic withstand g 0,2 .... 0,5 *

* These performances are according to standard values.


Other values and particular applications on request.

2
Functions et Dimensions

GL315 - 362 kV
A A F
Dimensions mm
A 4 700
B 6 385
C 6 646
B G H C
E E 7 883
I F 4 863
G 912
H 1 296
I 1 000

Charged-discharged closing spring indicator


FK3-4
Breaker position indicator
A C Dimensions mm
A 814
B 780
. C 603
E D 578
. 25 E 1 073
F 94
The equipment supplied is manufactured in accordance with the
B F D 46
technical specification supplied with the order confirmation.

GL315 SF6 gas monitoring


Low voltage equipment SKY SKY+
Heating + lighting protection fuses breakers
The GL300 series circuit breakers
Motor protection fuses breakers
are fitted with a densimeter with
Supply protection by circuit breakers no yes three contacts to monitor the SF6
Position switch for closing spring yes yes gas density.
Excess running time of motor relay no yes
Closing circuit 1 1 The densimeter is mounted on the
Antipumping relay yes yes housing at the bottom of the pole
Local remote switch with push button (without key) yes yes column.
Tripping circuit 2 2
Second SF6 treshold pressure lock-out relays S+O or S+L* S+O or S+L* To check the densimeter there is no
Tripping coils supervision (without relay) yes yes need to empty the circuit breaker.
Out-of-phase S+O* S+O*
Available auxiliary (NO / NC) contacts 8/8 12/12
* - S = Signalling
- O = Automatic Opening
- L = Locking in position

3
Packing and Transport

ALSTOM attaches the greatest Packing procedure conform with the


importance to fully satisfying the recommandations of specifications
needs of its customers with respect (S.E.I. - S.N.E.) and national
H1
to the packing and transportation of standards. These procedures are
L1 goods. checked by insurance company
experts at the request of ALSTOM.

“ ã - ALSTOM - 2001. ALSTOM, the ALSTOM logo and any alternative version there of are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies.”
1- Packing They fulfil the requirements of all
our customers both in France and
Packing is well adapted to resist abroad.
W1 damage during transportation,
storage and on-site handling. 2 - Transport

The circuit breaker is disconnected


G1
from the operating mechanism
L3 W3 before shipment. Interrupting
chambers, columns and centralizing
cubicle are packed separately.
H3
The spring control mechanism is
vacuum packed in a reinforced
H2 G3
plastic envelope.

Réf : T&D/BPROB/GL315/Uke/HVB/AHT/02.02/FR/3044 - Content subject to modifications without notice.


The frame and accessories are
L2
packed in a small case, with the
support columns.
L4 W4
The elements (interrupting
chambers, support columns) of
W2
circuit breaker are filled with SF6 to
H4
an effective pressure of 0,3 bar at
20° C.
G2 G4

Operating Centralizing
Characteristics of the cases Chamber Column - Frame mechanism cubicle

Lenght mm L1 5 130 L2 4 530 L3 3 180 L4 1 330


Width mm W1 1 810 W2 1 730 W3 1 030 W4 780
Height mm H1 1 230 H2 1 300 H3 1 440 H4 1 730
Mass kg G1 3 420 G2 2 370 G3 1 690 G4 268