Chapter 1
Chapter 1
CHAPTER 1
Introduction
The main power system protection function is to detect and disconnect the
faulted element. This prevents further damage in the faulted element and
protects the power system against the fault.
Another important function of protection systems is to provide an indication of
the fault in order to facilitate restoration. This is a target indication. In the past,
substation operation personnel used to read relay targets after a relay
operation and send the information to the relaying department. Modern digital
relays may send the information over a communications channel. Power
system operators may then use this information in real time to make better
restoration decisions.
We should not confuse this targeting function with fault location, which is an
accurate estimation of the faulted phase location on the transmission line. Fault
location information provided by digital relays helps line repair crews reduce
repair time.
Importance of protection
Transformer magnetizing currents can reach very high transient values during
transformer energizing. Transformer differential relays may misoperate for the
inrush current, so we need to take special design measures for transformer
differential relays.
The current of a distribution substation can reach high transient values when
we energize the substation after a long out-of-service period. The current may
be several times greater than the normal current for several seconds. This
results from the loss of natural diversity between loads. For example, during
hot weather, all refrigeration and air-conditioning systems will be ready to start
at the same time after a long service interruption. The starting currents of all
motors contribute to the transient cold-load restoration current.
Protective Systems
� Reliability
- Dependability
- Security
� Selectivity
� Speed
- System Stability
- Equipment Damage
- Power Quality
� Sensitivity
- High-Impedance Faults
- Dispersed Generation
� Simplicity
� Economics
- Protection Costs
- Equipment Costs
- Outage Costs
Electrical Protection in power Systems
1.Speed:
Speed is the ability of the protection system to operate in a short time after
fault inception. This is important in preserving system stability, reducing
equipment damage, and improving power quality. Relaying system operation
time includes relay and breaker operation time. We typically measure relaying
system operation time in cycles (periods of the power system frequency (1
cycle = 16.67 ms)). Breaker operation times are from 2 cycles to 8 cycles.
Instantaneous relay operating times are about 1 cycle. For example, a 1-cycle
relay and a 2-cycle breaker provide a fault clearing time of 3 cycles (about
50ms).
Clearing time: It is the time interval within which a faulty system element is
disconnected from the system.
Relay time: operating time of the protection relay from the instant of fault up to
the closure
of contacts in the trip circuit of the circuit breaker.
CB time: is the time from the closing of the trip circuit up to the time when the
current is interrupted (final arc extinction of the circuit breaker)
Relaying Classifications:
a) High speed: a relay that operates in less than a specified time. The
specified time in present practice is 50 milliseconds (2 – 3 cycles).
b) Ultra high speed: a relay that operates in 4 milliseconds or less.
II) Inverse time lag relay: the time operation is inversely proportional to the
magnitude of the quantity causing operation. The relay must separate the
meaningful and significant information with the necessary degree of
certainty. The relationship between the relay response time and its degree
of certainty is an inverse one.
2. Selectivity, discrimination
Protective relay systems that are well designed will always exhibit selectivity,
which means that the fewest possible numbers of relays will operate for a
given fault. To assure that the protective system is selective, relay coordination
studies must be performed.
Much of the time expended by the relay engineer consists of coordinating the
operation of adjacent relays to ensure that the proper relays operate, but that
those covering adjacent zones do not. To complicate this coordination, often-
nearby relays will have a secondary role as backup protection. Much more will
be said about backup protection and its coordination in the course.
Electrical Protection in power Systems
Zones of protection:
In the event of a fault in a zone, the protection of that zone should initiate the
tripping of the necessary circuit breakers to isolate that zone, and only that
zone, from all live supplies
The zone of protection of a relay consists of that part of the system covered by
the relay. One basic tenet of good protective relay practice is to maintain
overlapping zones of protection over the entire system. As an example,
consider a generator, its step-up transformer, a line, and a substation. Note
that the zones of protection and the switchgear locations are interrelated. As in
many design problems, the exact arrangement of the zones of protection will
depend on the design philosophy of the engineers involved.
The power system is divided into protective zones, which can adequately be
protected with minimum part of the system disconnection. Any failure occurring
within a given zone will cause the opening of all breakers within that zone.
The system can be divided into the following protective zones:
A zone of protection may be closed or open. When the zone is closed, all
power elements inside the zone are protected. All the circuit breakers inside
the zone must trip.
Consider a fault at F1. This fault lies in a closed zone and will cause C.B.s ( B1 )
and ( B2 ) to trip. The fault at F2, being inside the overlap between the zones of
protection of the T.L. and the B.B. , will cause B1, B2, B3 & B4 to trip.
Now consider a fault at F3. This fault lies in two open zones. The fault should
cause B6 to trip. B5 is the backup and will trip if B6 fails to clear the fault (fails to
trip).
3. Sensitivity
A protective system is said to be sensitive when it will operate for very small
internal fault currents. If an overhead conductor breaks and falls on dry ground
or hedges, the fault current can be very small, and it is quite a problem to
provide a protection sufficiently current-sensitive to detect this fault condition.
Electrical Protection in power Systems
Sensitivity is the ability of the protection system to detect even the smallest
faults within the protected zone. It is important to ensure the detection of high-
impedance faults or the reduced contribution to faults from small, dispersed
generators.
4. Reliability
Dependability means that each relay sends a trip signal when a fault is
present in its zone. It is defined as the measure of the certainty that the relays
will operate correctly for all the faults for which they are designed to operate
Security means that no relay sends a trip signal if no fault is present in its
zone. It is the measure of the certainty that the relays will not operate
incorrectly for any fault.
Electrical Protection in power Systems
Protective relays define the primary protection zones. Relays use system
currents and voltages as input signals. We will see during the course that
current information is instrumental for the relays in determining fault location.
Then, current transformer location defines the limits of the primary protection
zones in many cases.
In lower-voltage systems we use bushing-type current transformers installed
inside breaker and transformer bushings. In this case, protection zones overlap
around the breaker, and the breaker lies in the ovelapping zone. A breaker
fault produces the tripping of all breakers at both zones.
In higher-voltage installations we use multiwinding current transformers. We
use different secondary windings for the relays of the two protection zones.
The overlapping zone is inside the current transformer. The probability of an
overlapping-zone fault is very low. The price we pay for this arrangement is
that it could be necessary to trip some Zone B breakers with Zone A relays to
completely disconnect some Zone B faults.
Electrical Protection in power Systems
The figure shows the one-line diagram of a power system and helps illustrate
the concept of backup protection. The tie circuit breaker (T) is assumed to work
normally closed. For a fault at CD, Line Breakers 5 and 6 should operate as
the primary protection. If Protection 5 fails to operate, with existing technology,
we have two possibilities for cutting the fault current contribution from A, B, and
F: open Breakers 1, 3 and 8; or open Breakers 2 and T. In any case, backup
protection needs time delay. The primary protection needs to be given an
opportunity to operate before using the decision of a backup operation.
Electrical Protection in power Systems
5. Simplicity
Types of Relays
Relays may be classified in several ways, but here we look at their logical
performance.
In other words, the fundamental type of relay is determined by its function. One
functional classification system is given in the table below:
1. Magnitude Relays
2. Directional Relays
3. Ratio Relays
4. Differential Relays
5. Pilot Relays
Note that these types are not always mutually exclusive; for example, a relay
may be a ratio relay and also be a directional relay. Despite this, these terms
are commonly used and should be understood.
the frequency is below its setting). A current magnitude relay may be combined
with a directional relay to make a directional overcurrent relay.
Rated value
It is the value of the energizing quantity, marked on the rating plate, on which
the performance of the relay is based. In the case of a current-operated relay,
its rated current will normally be the rated secondary current of the C.T. to be
used with the relay (i.e. 1 A or 5 A).
Setting value
It is the nominal value(s) (usually as a percentage of rated value), marked on
the setting plug (or dials) of the relay, at which the relay is designed to operate
(e.g. 40% of 5 A). Since a protective relay and its C.T. cannot be considered
separately, the setting of a protective system is often quoted as a percentage
of the, rated primary current of the C.T.
Dropout or reset time: dropout is the value below which the relay resets and
opens its contacts to return to its normal position.
Drop-out / pick-up ratio is called Reset Ratio or Holding Ratio
Electrical Protection in power Systems
AC 90 – 95 %
DC 60 – 65 %