chapter 1- relay introduction
chapter 1- relay introduction
Load break switch:- is used to open and close the system under
no load and full load condition.
Components of Protection System
Isolating switch:- Open the ckt during no load condition
For failures within the region where two or more zones are
overlapped, more circuit breaker get tripped than minimum necessary
to disconnect the faulty element
If there are no overlaps then dead spot may exist, which means
circuit breaker lying within the zone may not trip even through the
fault occurs, may cause damage to the healthy system
Overlapping zones in the primary relaying
Protective Relay
The fault in the power system can not be completely avoided but
can be minimized
The protective relaying plays an important role in:
Sensing the fault
Minimizing the effect and damage of faults
Improve the service
The relays are compact and self contained devices which can
sense the abnormal condition.
The ratio of turns in the primary and secondary windings determines the
amount by which the current is stepped down
This is connected series with the the line carrying high current.
usually rated for 5A, connected to the coil of normal range ammeter
.
Voltage Transformers (VT)
A voltage transformer, Potential Transformer (PT) is a device used
to step down high voltages to lower, safer levels for measuring and
monitoring purposes.
The ratio between the primary and secondary windings determines the
amount by which the voltage is stepped down.
Voltage
Current
Frequency
Phase angle
Function of Protective Relaying
Detection of abnormal conditions: monitor electrical parameters such as
voltage, current, frequency, and phase angle to detect abnormal conditions
such as overcurrent, under/over voltage, over-frequency, and phase
imbalances.
Fault isolation: when a fault is detected, protective relays quickly isolate
the faulty section of the power system by tripping the circuit breakers or
disconnecting devices to prevent the fault from spreading to other areas.
Coordination of protection devices: designed to coordinate with other
protection devices in the system to ensure that the correct device operates
first and isolates the fault while minimizing the impact on the rest of the
system.
Selective tripping: programmed to selectively trip only the specific circuit
breakers or devices that are necessary to isolate the fault, minimizing the
disruption to the rest of the system and reducing downtime.
Monitoring equipment health: relays are equipped with diagnostic
features that monitor the health and performance of the equipment,
providing early warnings of potential failures and preventing catastrophic
events.
Category of Protection
Overcurrent protection: detects excessive current flow in a circuit and trips
the breaker to prevent damage to equipment.
Voltage protection: ensures that the voltage levels in a circuit remain within
predefined limits to prevent damage to equipment.
Short circuit protection: detects short circuits in a circuit and trips the
breaker to prevent damage to equipment.
Ground fault protection: detects ground faults in a circuit and trips the
breaker to prevent electrical shocks and damage to equipment.
Differential protection: compares the input and output currents of a
transformer or a generator to detect any abnormalities and trip the breaker if
necessary.
Distance protection: measures the impedance of a transmission line to
detect faults and trip the breaker to isolate the faulted section.
Overvoltage protection: detects voltage surges in a circuit and trips the
breaker to protect equipment from damage.
Under-voltage protection: ensures that the voltage levels in a circuit do not
drop below a certain threshold to prevent damage to equipment
Category of Protection
The protection provided by the protective relaying equipment
can be categorized
Primary Protection: is the first line of defense and is
responsible to protect all the power system elements
from all the type of faults
The relay C, D, G and H are primary relays while A, B, I and J are the
backup relay.
Protective Relaying Scheme
The protective relaying is the team work of the following
components.
Current transformers
Voltage transformers
Protective relays
Time delay relays
Auxiliary relays
Secondary circuits
Trip circuits
Current setting
desirable to adjust the pick-up current to a required value.
usually achieved by the use tapping the relay operating coil.
Example
Suppose that an over current relay having current setting of
125% is connected to a supply circuit through a current
transformer of 400/5.
The rated secondary current of C.T. is 5 amperes.
Therefore, the pick-up value will be 25% more than 5 A
i.e. 5x1 .25 = 6.25 A. It means that with above current setting, the
relay will actually operate for a relay coil current equal to or
greater than 6.25A
Important terms
Plug-setting multiplier (PSM)
It is the ratio of fault current in relay coil to the pick-up current