Lecture 1 - INTRODUCTION
Lecture 1 - INTRODUCTION
◼ Design the protection schemes for power systems and analyze the
performance of relay systems in a power system.
Recommended texts
◼ Short circuits
◼ Abnormal conditions
◼ Equipment failures
The basic electrical quantities which are likely to change during abnormal
conditions are current, voltage, phase-angle (direction) and frequency.
Protective relays utilise one or more of these quantities to detect abnormal
conditions on a power system.
The transformer is taken out of service for repair before the incipient
fault grows into a serious one. Thus, the occurrence of a major fault
is prevented. If the gas evolves rapidly, the Buchholz relay trips the
circuit breaker instantly.
The Components (Equipment) that need to be protected are Generators, Transformers,
Reactors , Lines, Buses, Capacitors
Relays: To convert the signals from the monitoring devices, and give instructions to
open a circuit under faulty conditions or to give alarms when the equipment being
protected, is approaching towards possible destruction.
Circuit breakers: These are used to make circuits carrying enormous currents, and also
to break the circuit carrying the fault currents for a few cycles based on feedback from
the relays.
Voltage transformers and current transformers: To monitor and give accurate feedback
about the healthiness of a system.
DC batteries: These give uninterrupted power source to the relays and breakers
independent of the main power source being protected.
Substation Components
15
Substation Components
16
Components
17
Protective Relays
The detection of a fault and disconnection of a faulty section or
apparatus can be achieved by using fuses or relays in conjunction
with circuit breakers.
For high voltage circuits (say above 3·3 kV), relays and circuit
breakers are employed to serve the desired function of automatic
protective gear.
The relays detect the fault and supply information to the circuit
breaker which performs the function of circuit interruption.
Relays
A protective relay is a device that detects the fault and initiates the operation of
the circuit breaker to isolate the defective element from the rest of the system.
Currents and voltages to relays are supplied via CT’s and PT’s.
Used to step down the current flowing through a conductor (TL) to magnitudes
that a relay can measure by applying a conversion ratio.
The primary winding is connected in series with the network whose current is to
be measured while the secondary ie connected to relay.
Current Transformer
The function of the CT is to reproduce in its secondary winding a current I’ that is
proportional to the primary current I
Rated Primary Current: The maximum primary current that the transformer has been
designed, eg the max current at which it can still comply with the relevant standard
specifications.
Rated Secondary current: the max secondary current that the transformer has been
designed for. The values are usually 1A or 5A.
Burden (in VA): the max load which can be connected to secondary of the
transformer
There are basically, two types of VTs used for protection equipment:
The electrical quantities which may change under fault conditions are
voltage, current, frequency and phase angle.
Through the changes in one or more of these quantities, the faults signal
their presence, type and location to the protective relays.
Having detected the fault, the relay operates to close the trip circuit of the
breaker.
This results in the opening of the breaker and disconnection of the faulty
circuit.
The relay circuit connection can be divided into three parts viz
This in turn closes the trip circuit of the circuit breaker, making
the circuit breaker open and isolating the faulty section from the
rest of the system.
In this way, the relay ensures the safety of the circuit equipment
from damage and normal working of the healthy portion of the
system.
27
Practical Relays
28
Requirements of Protective Relaying
The principal function of protective relaying is to cause the prompt
removal from service of any element of the power system when it starts to
operate in an abnormal manner or interfere with the effective operation of
the rest of the system.
ii. Speed
iii. Sensitivity
iv. reliability
v. simplicity
vi. economy
In order to provide selectivity to the system, it is a usual practice to divide the
When a fault occurs in a given zone, then only the circuit breakers within that
zone will be opened. This will isolate only the faulty circuit apparatus, leaving
the healthy circuits intact.
It may be seen from the figure above that there is certain amount of
overlap between the adjacent protection zones.
For a failure within the region where two adjacent zones overlap,
more breakers will be opened than the minimum necessary to
disconnect the faulty section. But if there no overlap, a failure in
the region between zones would not lie in either region.
Reset level: The value of current or voltage below which a relay opens its
Operating Time of Relay: The time which elapses between the instant when
actuating quantity exceeds the pickup value to the instant when the relay contacts
close.
Reset time of Relay: The time which elapses between the instant the actuating
quantity becomes less than the reset value to the instant when the relay contacts
returns to its normal position.
Reach of Relay: The actuating impedance in the relay is the function of distance