Protection Fundamentals
Protection Fundamentals
Protection Fundamentals
EP505
Protected circuit
WHAT ARE PROTECTIVE RELAYS?
Over Voltage
Over loads
Unbalanced Operation
Power Swings
Transformer Inrush Currents
Faults
Short Circuits
Short Circuits with Ground
Open Conductors
FAULT TYPES (SHUNT)
PROTECTION REQUIREMENTS
• Protect Equipment
• Protect People &Property
• Separate Faulty section
from power system
• Restore normal operation
INSTRUMENT TRANSFORMER
Multiples of pick-up
TYPES OF PROTECTION
Differential
current in = current out
Simple
Very fast
Very defined clearing area
Expensive
Note CT polarity
dots
This is a through-
current
representation
Perfect waveforms,
no saturation
DIFFERENTIAL
Note CT
polarity dots
This is an
internal fault
representation
Perfect
waveforms, no
saturation
TYPES OF PROTECTION
Voltage
Uses voltage to detect fault or abnormal condition
May employ definite time or inverse time curves
May also be used for undervoltage load shedding
Simple
May be slow
Selectivity at the cost of speed (coordination
stacks)
Inexpensive
TYPES OF PROTECTION
Frequency
Uses frequency of voltage to detect power
balance condition
May employ definite time or inverse time curves
Used for load shedding & machinery
under/overspeed protection
Simple
May be slow
Selectivity at the cost of speed can be expensive
TYPES OF PROTECTION
Power
Uses voltage and current to determine
power flow magnitude and direction
Typically definite time
Complex
May be slow
Accuracy important for many applications
Can be expensive
TYPES OF PROTECTION
Distance (Impedance)
Uses voltage and current to determine impedance of fault
Set on impedance [R-X] plane
Uses definite time
Impedance related to distance from relay
Complicated
Fast
Somewhat defined clearing area with reasonable
accuracy
Expensive
Communication aided schemes make more selective
X ZL
DISTANCE (CONT)
• Relay in Zone 1 operates first
• Time between Zones is called CTI
T2 ZB
ZA
T1
21 21
A B
Source
DISTANCE (CONT)
PROTECTION ZONES
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Bus zone Bus zone Bus zone
Unit Generator-Tx zone Line zone
Transformer zone Motor zone
Transformer zone
~
Generator XFMR Bus Line Bus XFMR Bus Motor
PRIMARY AND BACK UP PROTECTION
A- Primary protection
Primary protection
operation should be as
fast as possible, preferably
instantaneous, for stability
and power quality reasons.
PRIMARY AND BACK UP PROTECTION
B- back up protection
•used in case of primary protection
failure
•, backup protection needs time
delay. The primary protection needs
to be given an opportunity to operate
before using the decision of a backup
operation.
DIRECTIONAL PROTECTION
for fault F1
Relay s pick up :
Primary : 3 & 4
Back Up : 1 & 6 (time delay)
Relays not operate : 2 &5
DIRECTIONAL PROTECTION
1 2
for fault F2
Relay s pick up :
Primary : 5 & 6
Back Up : 3 after that 1 (time delay)
Relays not operate : 2& 4
CLASSIFICATIONS OF RELAYS
b. static 1970s
c. digital 1980s
b. moving coil
c. Induction
d. Thermal
STATIC RELAYS
Incorrect: 2.1%
QUESTIONS?