Chapter - 1 Introduction
Chapter - 1 Introduction
6. Design the basic protection scheme for generator and power transformer
7. Design the basic protection scheme of transmission lines, feeders and bus bars.
4
1- Need for Protective Apparatus.
5
Zones of Protection
• The general philosophy for the use of relays
is to divide the system into separate zones,
which can be individually protected and
disconnected on the occurrence of a fault, in
order to permit the rest of the system to
continue in service wherever possible as
shown in Figure 1.15.
• It can be seen that the adjacent zones
overlap, otherwise there could be some
portion which is left out and remains
unprotected.
• Each of the zones may be implemented using
a different relaying principle so if the fault
happens in the overlapped portion, the
minimum number of circuit breakers will
trip, avoiding disconnection of the rest of the
system.
• If the fault is within the zone, it is called an
internal fault, otherwise it is called an
external fault.
1- Cont. Need for Protective Apparatus.
7
1- Cont. Need for Protective Apparatus.
• The back-up
protection in this
case produces trip
command to its
circuit breaker
without waiting for
the primary
protection to do its
job.
• This results in
operation of both
the primary and the
back-up, resulting
in a longer and
unnecessary
disruption to the
system.
Various Principles of Power System Protection
2. Distance relay: It compares voltage with current at the same end. This, in effect,
measures the impedance between the relay location and the fault point which is
directly proportional to the distance, so it is called distance relay.
3. Directional over-current relay: It uses the phase shift between the current and the
voltage at the relay location to detect the direction of the fault. In case of a double-
end feed system, or parallel lines, or a ring main system, a fault gets fed from both
sides. In order to be selective, the relay must be sensitive to the direction of fault
power flow, so it is called directional relays.