Introduction To Power System Protection
Introduction To Power System Protection
Protection
1
Possible consequence of inadequate protection
2
• Types of Faults:
• Short Circuit faults
• Open circuit faults (open conductor)
• Complex faults (broken conductor)
• Inter turn faults in windings
• Abnormalities:
• Overload, power swings, over and
undervoltage…etc
• Fault Calculation
• Fault Current is approximately 10 to 20 times
normal full load current. To understand the relay
performance, you must know how severe is the
fault. Fault calculation, mostly symmetrical fault,
aided with the knowledge of unsymmetrical fault
is required. This knowledge is required to find
out the condition at the relaying point under fault
conditions, for example, voltage at relaying point
and current passing through relays. Based on
this you can deduce what the relay will see.
3
• Behaviour of current and voltage
transformers (CT & VT) – As protective
• equipment cannot be connect directly on
line, they are the major link between the
primary system and the relays. They will
supply signals to relays. It is therefore
necessary to study how they behave
under normal and fault conditions. At the
end of this study you should be able to
choose a suitable CT and VT.
4
The following definitions are generally used in
relation to power system protection:
• a. Protection System: A complete arrangement
of protection equipment and other devices
required to achieve a specified function based
on a protection principal
• b. Protection Equipment: A collection of
protection devices (relays, fuses, etc.). Excluded
are devices such as CT’s, CB’s, Contactors, etc.
• c. Protection Scheme: a collection of protection
equipment providing a defined function and
including all equipment required to make the
scheme work (i.e. relays, CT’s,CB’s, batteries,
etc.)
• Sensitivity
Is a function of the volt-ampere input to a
protective device to cause operation.
Sensitivity is a term frequently used when
referring to the minimum operating current
of a complete protective system. A
protective system is said to be sensitive if
the primary operating current is low.
5
• Selectivity
• Is the attribute of protective device
whereby only the faulty part of Electric
system is disconnected.
• Stability
• It is the attribute of a protective system
whereby it remains passive under all
conditions and faults external to the
relevant zone.
• Setting:
• Is the assigned quantity (current, voltage,
power, etc) at a relay will function under
specified conditions, and/or the assigned
time in which the relay will function under
specified conditions.
• The C/s of relays is such that their
operating time at the setting current is
infinite. The minimum current to cause
operation is a finite time must be not more
than 1.3 times the setting current.
6
• The Distance setting:
Is the maximum distance a fault can be from
the relay to cause operation.
• The Impedance setting of a distance
measuring relay is the maximum ratio of
voltage to current for which operation
occurs.
• Speed
• Apparatus to be protected:
The elements of a power system covering
generation, transmission, distribution and
utilization that require to be protected are:
• Generators and Transformers
• Bus bars
• Capacitors and Reactors
• Motors
7
• Zones of protection, primary and back-up
protection:
A protective scheme is divided into
protected zones. The protection of the
network consists of one or more
overlapping zones.
8
Overlapping around CB
• Components of Protection
• Relays - Relays are the heart of protective
schemes. There are many diverse designs, each
aims at achieving particular results. They may
be electromagnetic, solid state or even micro-
processor based. There are two main groups of
relays. The first group belong to relays designed
to detect and to measure abnormal conditions.
The second group are auxiliary relays, designed
to be connected in the auxiliary circuits
controlled by the measuring relay contacts, and
to close (or open) further contacts usually in
much heavier circuits.
9
• Current transformers (C.T.) - The rated
secondary current of all C.T.s are
standardised at either 5A or 1A. There are
two types of C.T.s, for protection and for
measurement. C.T.s used for protection
are usually designed to handle fault
current. Their accuracy at rated current is
usually worse than measurement C.T.s.
C.T.s used for measurement usually
produced more accurate output at current
not larger than 20% above rated current.
They are not expected to function correctly
at excessive currents.
10
• Derivation of Relaying Quantities.
11
Zero-sequence relay connection using system neutral current
The use of negative sequence bridge to supply a negative sequence current relay
12
• Trend of Protection Development
• Electromagnetic relays:
• Date back to the 30s. Many electromagnetic
relays are still in use today. The most well
known example being the induction disc
overcurrent relays.
• Static relays
• Application begins in the 60s. Early models have
a lot of problems due to the leakage current from
transistors and components used. The 2nd and
latter generations have overcome these
problems and they are now very reliable.
• Digital relays
Research and development can be dated back to
the 60s. In early developments, the focus is in
using one computer to provide many protective
functions and replace many protection relays,
say, to look after the whole substation, due to
the high cost of computers. The low cost of
computers nowadays have of course reverse the
direction of development and the development
trend is to use dedicate processor for individual
protection function.
• Adaptive relays:
• A function within a protective relay or system
that automatically adjusts the operating
characteristics (setting or state change) of the
relay system in response to changing power
system conditions can be said to have an
adaptive function. The adaptive function may
require additional measurements or signals or it
may use the normal protective relaying input
signals or it may use the normal protective
relaying input signals combined with enhanced
signal processing techniques for its operation.
13
• Intelligent relays
Relays that can handle limited unknown
conditions by giving them prior training.
Overcurrent Protection:
• Advantages over Overcurrent Relaying:
• – Greater instantaneous trip coverage
• – Lower sensitivity to source impedance
changes
• – Better sensitivity to fault currents
• – Reduced sensitivity to load
• – Easier coordination with other distance
relays
If I p ⇒ Trip
I f ≺ I p ⇒ Block
If : Fault Curent
Ip: Pickup value of relay
14
T = Functio ( I f − I p )
T : Re lay operating Time
15