Protection of Transformer and Circuits
Protection of Transformer and Circuits
The electrical equipment and circuits in a substation must be protected in order to limit the damages
due to abnormal currents and over voltages.
All equipment installed in a power electrical system have standardized ratings for short-time withstand
current and short duration power frequency voltage. The role of the protections is to ensure that these
withstand limits can never be exceeded, therefore clearing the faults as fast as possible.
In addition to this first requirement a system of protection must be selective. Selectivity means that any
fault must be cleared by the device of current interruption (circuit breaker or fuses) being the nearest to
the fault, even if the fault is detected by other protections associated with other interruption devices.
As an example for a short circuit occurring on the secondary side of a power transformer, only the
circuit breaker installed on the secondary must trip. The circuit breaker installed on the primary side
must remain closed. For a transformer protected with MV fuses, the fuses must not blow.
They are typically two main devices able to interrupt fault currents, circuit breakers and fuses :
• The circuit breakers must be associated with a protection relay having three main functions:
• Measurement of the currents
• Detection of the faults
• Emission of a tripping order to the breaker
• The fuses blow under certain fault conditions.
Transformer protection
Stresses generated by the supply
Two types of over voltages may stress and even destroy a transformer:
• The lightning over voltages due to lightning stroke falling on or near an overhead line supplying
the installation where the transformer is installed
• The switching over voltages generated by the opening of a circuit breaker or a load break
switch for instance.
• Depending of the application, protection against these two types of voltage surges may be
necessary and are often ensured by means of ZnO surge arrestors preferably connected on the
MV bushing of the transformer.
Stresses due to the load
A transformer overload is always due to an increase of the apparent power demand (kVA) of the
installation. This increase of the demand can be the consequence of either a progressive adjunction of
loads or an extension of the installation itself. The effect of any overload is an increase of the
temperature of oil and windings of the transformer with a reduction of its life time.
The protection of a transformer against the overloads is performed by a dedicated protection usually
called thermal overload relay. This type of protection simulates the temperature of the transformer’s
windings. The simulation is based on the measure of the current and on the thermal time constant of
the transformer. Some relays are able to take into account the effect of harmonics of the current due to
non-linear loads such as rectifiers, computers, variable speed drives etc. This type of relay is also able
to evaluate the remaining time before the emission of the tripping order and the time delay before re-
energizing the transformer.
In addition, oil-filled transformers are equipped with thermostats controlling the temperature of the oil.
Dry-type transformers use heat sensors embedded in the hottest part of the windings insulation.
Each of these devices (thermal relay, thermostat, heat sensors) generally provides two levels of
detection:
1. A low level used to generate an alarm to advise the maintenance staff,
2. A high level to de-energize the transformer.
Internal faults in oil filled transformers
In oil filled transformers, internal faults may be classified as follow:
1. Faults generating production of gases, mainly:
2. Micro arcs resulting from incipient faults in the winding insulation
3. Slow degradation of insulation materials
4. Inter turns short circuit
5. Faults generating internal over pressures with simultaneously high level of line over currents:
6. Phase to earth short circuit
7. Phase to Phase short circuit.
These faults may be the consequence of external lightning or switching over voltage.
Depending on the type of the transformer, there are two kinds of devices able to detect internal faults
affecting an oil filled transformer.
• The Buchholz dedicated to the transformers equipped with an air breathing conservator (
The buchholz is installed on the pipe connecting the tank of he transformer to the conservator. It traps
the slow emissions of gasses and detect the flow back of oil due to the internal over pressures
DGPT (Detection of Gas, Pressure and Temperature) protection relay for integral filled transformer
•
[b] Contacts of the DGPT (cover removed)
Concerning the monitoring of gas and temperature the buchholz and the DGPT provide two levels of
detection:
1. A low level used to generate an alarm to advise the maintenance staff,
2. A high level to trip the switching device installed on the primary side of the transformer (circuit
breaker or load break switch associated with fuses).
In addition, both the buchholz and the DGPT are suitable for oil leakages detection.
Overloads and internal faults in dry type transformers
The dry type transformers are protected against over-heating due to possible downstream overloads by
a dedicated relay monitoring thermal sensors embedded in the windings of the transformer
The internal faults, mainly inter turns and phase to earth short circuits occurring inside a dry type
transformers are cleared either by the circuit breaker or the fuses installed on the primary side of the
transformer. The tripping of the circuit breakers when used is ordered by the phase to phase and phase
to earth over current protections.
Inter turns faults need a dedicated attention:
1. They generally generate moderate line over currents. As an example when 5 % of a HV winding
are short circuited the line current of the transformer does not exceed 2 In, for a short circuit
affecting 10 % of the winding the line current is limited around 3 In.
2. Fuses are not appropriate to clear properly such currents
3. Dry type transformers are not equipped with additional protection devices such as DGPT
dedicated to internal faults detection.
Hence, internal faults generating low level of line over current may not be safely cleared by fuses.
Protection by means of over current relay with adequate characteristic and settings is preferred
(Schneider Electric VIP relay range for example).
Selectivity between MV fuse operation and LV circuit breaker tripping, for transformer protection
MV fuse and LV circuit breaker configuration