Design String Inverters Shcneider
Design String Inverters Shcneider
Design String Inverters Shcneider
Conext CL 20000 E
Conext CL 25000 E
solar.schneider-electric.com
Conext CL Inverter
Conext CL 20000 E
Conext CL 25000 E
Solution Guide
solar.schneider-electric.com
Copyright © 2015 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric
Industries SAS or its affiliated companies.
Scope
This Guide provides technical information and design recommendations. It
explains the design requirements of each of the system components and
provides details on how to choose the correct recommendations.
The information provided in this guide does not modify, replace, or waive any
instruction or recommendations described in the product Installation and
Owner’s Guides including warranties of Schneider Electric products. Always
consult the Installation and Owner’s guides of a Schneider Electric product when
installing and using that product in a decentralized PV system design using
Conext CL inverters.
For help in designing a PV power plant contact your Schneider Electric Sales
Representative or visit the Schneider Electric website for more information at
solar.schneider-electric.com.
Audience
The Guide is intended for use by anyone who plans to construct or install a
system involving the Conext CL Inverter. The information in this manual is
intended for qualified personnel. Qualified personnel have training, knowledge,
and experience in:
Organization
This Guide is organized into seven chapters.
Chapter 1, Introduction
Related Information
You can find more information about Schneider Electric as well as its products
and services at solar.schneider-electric.com.
iv 975-0747-01-01 Revision B
Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD
Read these instructions carefully and look at the equipment (if applicable) to
become familiar with the device before trying to install, operate, service or
maintain it. The following special messages may appear throughout this bulletin
or on the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided,
will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided,
can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided,
can result in moderate or minor injury.
NOTICE
NOTICE indicates important information that you need to read carefully.
975-0747-01-01 Revision B v
Important Safety Instructions
DANGER
RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
This Solution Guide is in addition to, and incorporates by reference, the
relevant product manuals for the Conext CL Inverter. Before reviewing this
Solution Guide you must read the relevant product manuals. Unless specified,
information on safety, specifications, installation, and operation is as shown in
the primary documentation received with the products. Ensure you are familiar
with that information before proceeding.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRICAL SHOCK AND FIRE HAZARD
vi 975-0747-01-01 Revision B
Contents
Important Safety Instructions
1 Introduction
Decentralized Photovoltaic (PV) Architecture - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2
About the Conext CL Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3
Key Specifications of the Conext CL Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4
Key Features of Wiring Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4
2 Decentralized PV Solutions
Why Decentralize PV Solutions? - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2
Drivers for decentralizing system design - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2
Benefits with Conext CL for a Decentralized System Design - - - - - - - - - - - - - - - - - - - - - - - - 2–3
PV System Overview - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
PV System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
PV System Design Using Conext CL Inverters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5
Wiring Box selection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6
Selection criteria - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6
Building Blocks of a Decentralized PV Power Plant - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–9
Positioning Inverters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Inverter location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Option 1 (Inverters installed next to PV modules) - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12
Option 2 (Inverters installed next to AC Combiner groups) - - - - - - - - - - - - - - - - - - - - - 2–13
Option 3 (Inverters installed next to PV inverters without first-level AC Combiners) - - - - 2–14
Option 4 (Inverters installed next to LV/MV transformer) - - - - - - - - - - - - - - - - - - - - - - - 2–15
3 DC System Design
DC System Design - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
String and Array Sizing Rules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Number of PV Modules in the Series - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Minimum Number of PV Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3
Maximum Number of PV Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Number of PV Modules in Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
String Connections to Conext CL Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
DC String Arrangement and Cable Sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–6
DC System Component Design - The DC Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Typical use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Advantages of the offer - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10
4 AC System Design
AC System Design - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–2
Circuit Breaker Coordination - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3
Cascading or backup protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3
Discrimination - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3
AC Component Design - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4
The AC Switch Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5
Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5
Typical use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5
Advantages of the offer - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5
AC Cable sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–6
AC Combiner Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–7
Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–8
Typical use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–8
AC Re-Combiner Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–11
Distribution control - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–14
Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–15
Typical use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–15
Recommended System Design - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–16
System Technical Summary - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–16
CB Protection – Discrimination tables for selection. - - - - - - - - - - - - - - - - - - - - - - - - - - 4–17
6 Layout Optimization
Layout Design Rules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6–2
Layouts - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6–2
975-0747-01-01 Revision B ix
x
Tables
Table 2-1 Decentralized PV System Blocks - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–9
Table 3-1 DC Box Component Reference - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10
Table 4-1 AC Box Component Reference - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–6
Table 4-2 Percentage losses for Cu cable w.r.t maximum AC cable length - - - - - - - - - - - - - - - - 4–7
Table 5-1 Power loss values for transformer ratings and impedance - - - - - - - - - - - - - - - - - - - - 5–11
Table 7-1 De-rating for 500 Vdc and 800V, 230 Vac 25 Kw- - - - - - - - - - - - - - - - - - - - - - - - - - - - 7–5
Table 7-2 De-rating for 350 Vdcand 800V, 230 Vac 20 Kw - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7–5
975-0747-01-01 Revision B xi
xii
1 Introduction
WARNING
ELECTRICAL SHOCK HAZARD
• The Conext CL Inverters are transformerless inverters, suited for use with
PV modules that do not require the grounding of a DC polarity.
• In case of a “net metering” grid connection type, connection has to be
adapted to the local rules specified by the utilities.
• Always refer to national and local installation and electrical codes in
designing a power system.
Failure to follow these instruction can result in death or serious injury.
PV System Overview
PV System
PV system modeling are:
• Site conditions
• Type of system
• Losses
Site conditions
It is very important to interpret site conditions carefully and model the exact
conditions in PV system design software. These conditions include shadow from
surroundings, ground slope, layout boundary conditions, rain water catchment
area, PV module string arrangements, shape of the layout, obstacles like power
lines, gas pipelines, rivers, archaeological conditions, and similar obstacles.
Once all possible factors affecting the PV system design are listed and
assessed, capacity of selected PV installation site can be determined for further
processing. Government agency permits and statutory clearances also depend
on these factors. Cost of the land and overall PV system varies with respect to
these conditions.
System
PV system installation can be grid tied or stand alone. It could be on the roof,
ground-mounted with tracking option, or it could be in a car park or facade-
mounted.
Modelling of system has to be considered using the most suitable option or may
be the main purpose of installation.
Losses
Any PV system has two major types of losses. Losses associated with
meteorological factors and losses due to system components.
Both rooftop and ground mount systems can be modeled and designed using
standard system blocks comprising of Conext CL inverters and user defined PV
modules and mounting solution.
A block of 250kW for rooftop solutions and 1000kW for ground mount solutions
can be considered to multiply several times to achieve the required capacity.
Smaller size of standard blocks like 100kW, can be defined in order to fit the
requirement of the user. A standard block is designed once for all respective
components and repeated several times in the installation. It reduces the efforts
and time to design the complete solution and increases the flexibility and speed
of construction. Manufacturing of components also becomes quicker as a
standard block uses the available ratings of components and equipment.
Ultimately, the overall design results in an optimized and reliable solution from all
perspectives.
Selection criteria
Under following situation or requirements, designer / client should choose either
of the available options for Conext CL wiring box.
Base Model
Front view
Provides DC and AC connections only; Cover majority of the applications with Essential + MC4 connectors Essential + Surge Protection Device Optimum + MC4 connectors
an external DC combiner box with fuse DC touch safe fuse holders and DC (SPD)
and switch is mandatory requirement; disconnection For Customer who wants to use MC4 For Customer who wants to use
Customer Use Case
connectors based on Essential model For customer who wants full protection MC4 connectors based on
For customer who has existing DC For customer who wants to eliminate especially high surge protection in Optimum model
combiner box or wants to develop own external DC box and use CL wiring frequent lightning area
DC combiner box box as DC combiner box
# of MPPT 2 2
# of strings per MPPT 1 4
Single MPPT config 1 MPPT included √, MPPT shorting terminal block and jumper are provided
DC connection DC cable gland entry thread size: M25 DC cable gland entry thread size: M25 MC4 PV connectors DC cable gland entry thread size: M25 MC4 PV connectors
Part number PVSCL20E100 (20kW) PVSCL20E200 (20kW) PVSCL20E201 (20kW) PVSCL20E300 (20kW) PVSCL20E301 (20kW)
(Inverter + wiring box) PVSCL25E100 (25kW) PVSCL25E200 (25kW) PVSCL25E201 (25kW) PVSCL25E300 (25kW) PVSCL25E301 (25kW)
Fuse Recommendation For calculating the PV fuse rating for a specific PV array installation, refer to the panel manufacturer documentation in addition to local electrical installation code.
Recommended Fuse: Part number: PV1510F, Make: Cooper Bussman Rating:1000 VDC, 15 A (Note: Not applicable for Base model)
975-0747-01-01 Revision B
Why Decentralize PV Solutions?
Router / switch
Enclosure
Power supply
Grounding Bonding cable --- External
system
Clamps and
Connectors
Positioning Inverters
DANGER
ELECTRICAL SHOCK AND FIRE HAZARD
Inverter location
PV system design with Conext CL string inverters emphasizes the location of
Inverter in the complete solution. The location of the inverter, in turn, drives
selection of wiring box and system components.
We propose four types of standard design blocks in order to fit almost all types of
installations. Each option has its advantage and disadvantage with respect to
other installation but for every particular instance respective option serves the
purpose in most efficient manner.
Conext CL
Advantages
• Less DC string cables
• Less DC I2R losses
• High Flexibility
• No need of dedicated structure for Inverter mounting
• Inverters close to PV modules reducing electrified portion of system
during fault
• Covering most of the usable space within boundary
• Schneider iC60 type of breakers can be used in AC combiners – up to 5
inverters
Disadvantages
• This type of inverter placement requires external AC switch immediately
after inverter
• Longer AC cables from Inverter to first level of AC combiners
• Higher AC cable losses
Selection criteria for Conext CL inverter wiring box variants for this option
• Base model + external DC box with DC fuses, DC SPD and DC switch
• Essential model + external DC SPD
• Optimum model
Conext CL
Advantages
• Less AC cables
• High Flexibility
• AC switch and AC SPD not required if considered in AC Combiner box
• Schneider iC60 type of breakers can be used in AC combiners – up to 5
inverters
Disadvantages
• Longer DC string cables might need to opt for higher size of DC cable
• Dedicated structures required for Inverter and AC combiner mounting
• Higher DC cable losses
• Use of RCD is probable
Selection criteria for Conext CL inverter wiring box variants for this option
• Base model + external DC box with DC fuses, DC SPD and DC switch
• Essential model + external DC SPD
• Optimum model
Conext CL
Advantages
• Less DC string cables
• Less DC I2R losses
• High Flexibility
• No need of dedicated structure for Inverter mounting
• Inverters close to PV modules reducing electrified portion of system
during fault
• Covering most of the usable space within boundary
• First level AC combiners avoided resulting in cost savings
Disadvantages
• This type of inverter placement requires external AC switch immediately
after inverter
• Very long AC cables from Inverter to AC combiners
• High AC cable losses
• High number of AC runs from Inverters to MV stations with increased
time and chances of connection mistakes
• Increased size of AC cable will require higher size of terminal blocks in
external AC combiner boxes
• Use of RCD is probable
Selection criteria for Conext CL inverter wiring box variants for this option
• Base model + external DC box with DC fuses, DC SPD and DC switch
• Essential model + external DC SPD
• Optimum model
Conext CL
Advantages
• Less AC cables
• High Flexibility
• AC switch and AC SPD not required if considered in AC Combiner box
• Easy access to Inverters for service and maintenance
• RCD not required
Disadvantages
• Longer DC string cables might need to opt for higher size of DC cable
• External DC switch box with SPD required to protect long DC strings
• Combining DC strings might lose benefit of separate MPPT
• Dedicated structures required for Inverter and AC combiner mounting at
MV station
• Higher DC cable losses
• Many long DC string cables increase possibility of wiring mistakes
Selection criteria for Conext CL inverter wiring box variants for this option
• Base model + external DC box with DC fuses, DC SPD and DC switch
• Essential model + external DC SPD
• Optimum model
DC System Design
DANGER
ELECTRICAL SHOCK AND FIRE HAZARD
Out of the listed tasks, String sizing is the most important one as many other
decisions depend on it. Like type and size of module mounting tables,
interconnection arrangements and cable routing.
inverter providing the minimum voltage start-up of the same, and secondly, to
avoid failures in the inverter from surge, with the main objective of maximizing
electricity production.
By defining:
The Standard Test Conditions (STC) for measurement are the irradiation
conditions and temperature of the solar cell, widely used to characterize the
cells, PV Modules and solar generators and defined as follows:
To determine the temperature of the cell in any situation using the following
formula:
Where:
For this use case, let's calculate the incident radiation when we have a Vmp of
1000 W/m2 and ambient temperature of 35 °C. Assume that NOCT of PV module
correspond to 48 °C (standard value from manufacturer’s data sheet),
The temperature difference of the cells relative to Standard Test Conditions will
be:
As the manufacturer indicates the variation with temperature of the open circuit
voltage, Vmp to obtain the temperatures of cells shall be indicated by the power
from the PV Module at this temperature divided by the intensity of maximum
power at the same temperature.
This approximation is always the most correct, as the intensity is much more
stable compared to the voltage and it will be possible to assimilate the intensity
variation with temperature of the intensity of a short circuit with the maximum
power.
In the second extreme case, the maximum number of PV panels in series that
can be installed to connect the inverter, is given by the ratio between the
maximum input voltage of the inverter and the open circuit voltage of PV Modules
in a situation where the inverter starts with an ambient temperature of 0º C.
Conext CL inverter starts at 130W nominal power value and consider that
approximately we can get to 40 W/m2 radiation accident.
The temperature difference of the cells relative to Standard Test Conditions will
be:
-3.6 – 25 = - 28.6 ºC
Since the maximum voltage is 1,000 V borne by inverters we can know the
maximum number of panels to be placed in series will be: for a 300Wp Poly C-Si
module,
Any chosen configuration between 13 to 20 modules will fit, but 20 would be the
most desirable choice.
The tool is easy to use and available for both Mac and Windows users. The
following link can be used to download the tool.
http://solar.schneider-electric.com/product/conext-designer/
Any string to be connected to each MPPT input has to be within this limit of Short
circuit current for Independent MPPT operation.
For a Single MPPT operation (MPPT inputs shorted) current limits to follow are
62A for Impp and 77A for Isc.
For the sizing of Strings to connect with Conext CL inverters, one must observe
the short circuit current of PV Module it is going to connect with and number of
parallel string being connected to each MPPT or overall. If there is any multiplier
to be considered based on local standardization or safety authorities, cables and
overcurrent protection devices should be rated for this multiplier (like 25%
overrated).
The DC switch provided with Conext CL inverter is rated 40A DC current and it
breaks both MPPT inputs simultaneously when operated.
20kW Conext CL Inverter if connected to four strings, can be used without fuses
but just using Y type string connectors (near PV modules) to combine two strings
into one and terminating one cable on each MPPT terminal. This solution is most
economical option for string connections. Similar approach is not possible for
25kW CL Inverters as more than two strings in parallel requires fuses to avoid
reverse currents in case of fault in one of the parallel connected strings.
All DC string cables should be designed for not more than 1% voltage drop.
2KLI
Vd = -------------------------------
Cm
Vd
Pct_Vd = ----------- 100
Vop
Where:
When a Conext CL inverter is selected with Basic wiring box model, user should
carefully define the DC side protection and disconnect requirement depending
upon the location of inverter with respect to PV module strings.
There are several ways modules can be installed using some standard racking
options. We suggest our customers to analyze following parameter before
deciding the type of arrangement to interconnect.
Example:
Since this set up does not end up in a complete number, we have following
choices:
8. Connect shadowed strings to same MPPT and others to the different MPPT to
achieve maximum harvest.
9. Do not combine separate ratings of PV modules in one string
Now considering above basic rules and given situation, we decide to connect 20
PV modules of 300Wp in one string and 5 strings to each inverter.
The other way to connect the string when portrait arrangement is chosen can be:
Figure 3-2 String arrangement and interconnection example with Portrait oriented modules
It is essential to understand and select the right circuit components when any PV
system is designed. After the cables, racking and strings, we will move on to the
next circuit component identified as DC Box.
Function
1. SW60DC switch – Disconnects each MPPT input of the inverter from the DC
line disconnect.
2. PRD-DC – Protects the inverter against voltage surges coming from DC lines
(Applicable for the Base model only and if circuit required additional SPD).
3. MX+OF releases / MN releases Controls the release of the switches remotely
for emergency purpose – For Rapid shutdown purpose of for fireman safety
requirement.
Typical use
1. The DC box is an optional offer, but is necessary when:
• Local regulations require the use of external DC switch disconnects
• Local regulations require the disconnection of DC lines remotely
(generally as close as possible to the PV modules) in case of emergency
• The lightning risk assessment concludes that protection by SPD is
required
• However, DC Box is required when the base model is chosen
2. The PV array of each MPPT input is preferably disconnected separately
• One switch disconnect per DC input
3. DC box is installed close the PV modules when:
AC System Design
DANGER
ELECTRICAL SHOCK AND FIRE HAZARD
AC low voltage circuits with high amount of power needs extreme care to achieve
reliability, safety and highest level of availability of system. Selection of circuit
breakers (MCB and MCCBs), Disconnect switches, Protection devices and
Cables is the key to achieve all three objectives.
• Cascading
• Discrimination
If the insulation fault is specifically dealt with by earth leakage protection devices,
discrimination of the residual current devices (RCDs) must also be guaranteed.
Discrimination
This consists of providing coordination between the operating characteristics of
circuit breakers placed in series so that should a downstream fault occur, only
the circuit breaker placed immediately upstream of the fault will trip.
Standard IEC 60947-2 defines a current value ls known as the discrimination limit
such that: if the fault current is less than this value ls, only the downstream circuit-
breaker D2 trips if the fault current is greater than this value ls, both circuit-
breakers D1 and D2 trip. Just as for cascading, discrimination must be verified
by tests for critical points.
AC Component Design
Right after Conext CL inverter AC terminals, an AC switch box should be installed
depending on the distance from the first AC combiner. This AC switch box may or
may not have an AC surge protective device. If the wiring box for inverter is
Optimum or Optimum+, C switch box can be selected without AC surge
protection device.
Function
1. iC60H, 40A MCB protects and disconnects inverter from the AC line.
2. Quick PRD protects the inverter against voltage surges coming from AC
lines.
Typical use
1. The AC box is an optional offer, but is necessary when:
• the distance or an obstacle between inverter and AC combiner box
prevents the safe disconnection of the inverters at the AC combiner box
level and/or
• the distance between inverter and AC combiner box is more than 10 m
and may prevent the safe surge voltage protection of the inverter at the
AC combiner box level
2. AC box is located near the inverter
• generally needs an outdoor enclosure
3. Possible long distance between AC switch box and AC combiner box
• requires cross-section terminals for output cabling higher than 6 mm2
(maximum cross-section of the cables at the AC plug)
AC Cable sizing
AC Cable sizing calculation consists of ampacity, voltage drop, short circuit
calculation and thermal de-rating of AC cables.
To limit the power loss up to acceptable limits, after selecting a suitable size of
cable with proper ampacity, short circuit rating and voltage grade the most
important part is to calculate voltage drop. We advise to keep AC cable overall
power losses in range of <1%. This would ensure smooth operation of multiple
units in parallel at one transformer LV winding.
100U
%Vd = -----------------
Un
Where:
AC cable sizes between Conext CL inverters and AC Combiner boxes will mostly
depend on the distance between them. Output current of Conext CL 20kW
inverter is 32A and 25kW Inverter is 37A (33A for NA version) Considering the
de-rating factors due to cable laying methodology and thermal de-rating due to
conduits, mostly 16 mm2 4 core AL cable fits in to the most instances.
It is essential to calculate and consider the correct fault level on each combiner
bus level in order to select the right size of cable, MCB, MCCB and RCD, Surge
protection and Disconnect devices.
If the AC cable length exceeds 10 m (32.8ft), the use of an AC switch box closer
to the inverter is recommended. This switchbox can be used to connect higher
size of cable, if required to avoid voltage drop.
Table 4-2 Percentage losses for Cu cable w.r.t maximum AC cable length
AC Combiner Box
AC combiner box is first level combiners, mostly located in the PV field in large
utility scale projects. AC combiner box houses the first level protection for
Inverters on AC side (if not applied in AC box). The outgoing line from AC
combiner to LV/MV station holds disconnects or if required, it should be
protected with circuit breakers.
Function
1. Combines AC currents coming from several inverters.
2. Isolates the combiner box from AC line.
3. Output switch-disconnector, INS type.
4. Protects AC lines to inverters against over-currents.
5. Circuit breaker C60 N/H/L (according prospective current), four poles, C
curve, 40 A (for CL 20kW) & 63A (for CL 25kW).
6. Protects inverters against voltage surges from AC line.
7. Quick PRD, 4p.
8. If not done at the AC box level.
Typical use
1. AC combiner box is located near the inverters.
2. Long distance between AC combiner box and AC distribution box.
3. Requires high cross-section terminals for output cabling.
This time the Fault current reduces to 10.84kA allowing to select C120H MCB
with 15kA fault level.
Following graph indicates the relation between Iscmax and length of LV array
cable.
Please note that size and type of cable selected here affects the fault level on
bus-bar of AC combiner box. So length as well as size of cable should be
considered carefully to select the economical yet most effective and safe circuit
breaker solution.
For a combiner box connected to Re-combiner box with 120mm2 size AL cable
of 20m length and Re-combiner box connects to a 1000kVA 22kV/400V, 6%
transformer.
Fault level at AC combiner bus bar = Voltage × Voltage correction factor C/ Fault
impedance
For a 1000KVA, 22kV / 400V transformer with Voltage factor c=1.05 and Short
circuit impedance 6% and Load loss of 10550kW,
= 400×400×0.06/1000×1000
= 0.0096 Ohms
= 10550×400/10002×10002
= 0.001688 Ohms
= 17.64 kA
So for this scenario Following will be the choice of circuit breakers with
calculated fault current.
AC Re-Combiner Box
• The AC Re-Combiner box is adapted according to the type of grid box and
the requirements of the utility.
• The AC Re-Combiner box is divided into two parts:
• LV AC Re-Combiner to connects to all AC combiner boxes while
protecting the cabling and possibly measuring currents
• LV connection to connect to the grid box while ensuring compatibility
with grid box and utility requirements
AC Re-combiner box is or mostly will be located at LV-MV station inside the kiosk
or outside on concrete pad. All incoming lines from AC Combiners in PV field are
connected to incoming line’s molded case type circuit breakers and outgoing to
LV transformer winding can be connected to either a MCCB or an Air circuit
breaker depending on the space requirements.
Selection of these MCCBs and ACB should be following the similar rule we
encountered for AC Combiners. It is worth to notice once more that
discrimination and cascading of circuit breakers helps to design more accurate
protection philosophy as well as can save lot of capital cost because of the
reduced fault level capacity of components due to limitation feature.
= 400×1.05/(ZTR-LV+Zgrid)×sqrt3
Considering the MV connection at 22kV and Grid short circuit power of 500MVA,
we will use following values to calculate Grid impedance at LV side of
transformer.
MV voltage: 22kV,
Short circuit power from grid: 500MVA,
Transformer LV voltage: 400V,
Voltage factor c for MV grid: 1.1,
Size of transformer: 1000KVA
ZMV-grid = (RMV-grid2+XMV-grid2)1/2
= 1.0648 Ohms
= 1.059476 Ohms
= 1.059476 (4002/220002)
= 0.00035 Ohms
ZTR-LV = 400×400×0.06/1000×1000
= 0.0096 Ohms
= 10550×400/10002×10002
= 0.001688 Ohms
= 0.009450432 Ohms
Using the above four values in formulae for Bus-bar fault level calculation,
= 25.26 kA
Selection of incoming circuit breaker, bus-bar and outgoing circuit breaker shall
be based on this fault level calculation and nominal rated current.
Distribution control
Distribution control may be required for monitoring purposes.
Function
1. Combines AC currents coming from the AC combiner boxes.
2. Connects to the grid box while ensuring compatibility with the grid box and
compliance with grid connection requirements.
3. Protects the AC lines connected to the AC combiner boxes
• using C120 circuit breakers or Compact NSX according current and
Fault level at bus bar, optionally with Vigi modules.
4. Protects against voltage surges coming from AC lines
• using type 1 or type 2 SPD, protected by circuit breaker.
5. Isolates the AC Re-Combiner box (and the whole PV installation) from the AC
line.
6. Optionally, monitors currents and energies at each input.
• Use of µLogic™ 5.2E module for protection and monitoring purposes.
7. When a remote emergency shutdown is required, an optional release MN or
MX is used at the LV connection stage.
Typical use
1. Different types of AC Re-Combiner box are required according to the type of
grid box and to the need for an external protective relay.
2. In the case of connecting only one AC combiner box, only the LV connection
stage of the AC Re-Combiner box is required.
3. The AC Re-Combiner box can be located indoors or outdoors, normally
close to the grid box.
4. Buildings protected with lightning rods require the use of type 1 SPDs at AC
Re-Combiner box level.
AC Re-combiner: 8 incoming, 1
outgoing, SPD
Incoming – NSX type MCCB 200A, curve
C, 3P
Outgoing – Compact NS or NT type Air CB
1600A with TM-D or Micrologic trip unit, 3P
Surge protection on Main bus-bar – iPRD
65r
Bus bar – Cu, 400V, 30kA (mostly with
500MVA grid capacity)
Grounding bus, Metal enclosure (IP 54 or
higher)
AC Combiner*:
5 incoming, 1 outgoing, SPD
Incoming – iC60- N (upto 10kA) or H (upto
15kA) type MCB 40A, curve C, 4P
Outgoing – Interpact INS250-200A type
Switch-Disconnect, 4P
Surge protection on Main bus-bar – iPRD
40r
Bus bar – Cu, 400V, 15kA (if Cable to Re-
combiner is <95mm2 for >30m)
Grounding bus, Metal enclosure (IP 54 or
higher)
AC Cables:
AC Combiner to Re-combiner 4C, 1.1kV
grade, AL, XLPE, 95mm2 or higher
Inverter to AC Combiner –
4C, 1.1kV grade, AL, XLPE, 16mm2 or
higher
DC Cables:
Module strings to Inverter
4 or 6 mm2, solar PV grade 1000V, UV
protected
Surge arrestors protect the electrical wiring, components and system from
lightning surges. Role of surge arrester is to drive the lightning current to the
earth in very short time (<350 microseconds). However surge arrestors are not
intended to be exposed to a permanent over voltages. In that case, it might
create a short circuit and may damage the switch board. iPRD PV-DC direct
current surge arresters are designed to protect against Over voltages due to a
lightning strike: of the "DC" input to the inverter and of Photovoltaic panels.
• The protection level of SPD must be lower than the impulse withstand voltage
level of equipment protected by SPD
• For a TNC grounding scheme, 3P SPDs should be used
• For a TNS grounding scheme, 3P+N SPDs should be used.
• If the PV system is installed in vicinity (within 50m) of a lightning protection
rod or lightning termination, Type 1 SPD will be required to safeguard the
inverter from lightning discharge currents as It is used to conduct the direct
lightning current, propagating from the earth conductor to the network
conductors.
• Geographical conditions cause the specific level of Lightning Flash density.
Based on the level of lightning flash density and commercial value of
equipment protected, level of surge protection has to be decided and so is
the fault level (kA) of SPD.
• After having chosen the surge protection device for the installation, the
appropriate disconnection circuit-breaker is to be chosen from the opposite
table. Its breaking capacity must be compatible with the installation’s
breaking capacity and each live conductor must be protected. E.g. 3P+N
SPD must be combined with a 4P MCCB or MCB.
The surge arrester base can be turned over to allow the phase/neutral/earth
cables to enter through either the top or the bottom. They offer remote reporting
of the “cartridge must be changed” message.
Depending on the distance between the “generator” part and the “conversion”
part, it may be necessary to install two surge arresters or more, to ensure
protection of each of the two parts.
• to protect the inverter you need to have Protection level Up (surge arrester)
< 0,8 Uw (inverter)
• if the distance between the module and inverter > 10m, a second surge
protection should be installed close to the module except if Up < 0,5 Uw
(module)
Uw is the impulse withstand.
So, 3.9 < 0.8 x 6 = 4.8kV: the protection of the inverter is good.
And, 3.9 < 0.5 x8 = 4kV: there is no need of additional surge arrestor to
protect the modules.
The following diagram indicates the additional SPD requirement considering that
impulse withstand voltage of PV module is lesser than Up of SPD inside Conext
CL inverter.
In the case of PV architecture without an earthed polarity on the DC side and with
a PV inverter or with galvanic isolation, it is necessary to:
Schneider Electric has certified coordination between the surge arrester and its
disconnection circuit breaker (IEC 61643-11 2005 version). The following
diagram indicates the possible coordination with Type 2 SPDs.
For the installations with lightning rod within 50m of area, Type 1 SPDs to be used
with following coordination with disconnecting devices.
The choice of these methods governs the measures necessary for protection
against indirect-contact hazards.
The type of connection of the electrical system (that is generally of the neutral
conductor) and of the exposed parts to earth electrode (s)
The use of earth fault protection of overcurrent protective switchgear which clear
only relatively high fault currents or the use of additional relays able to detect and
clear small insulation fault currents to earth
For the two following reasons the double fault situation shall be absolutely
avoided: Insulation monitoring devices or overcurrent protection in earthed
system shall detect first fault and staff shall look after the first fault and clear it
with no delay:
• The fault level could be low (e.g. two insulation faults or a low short-
circuit capability of the generator in weak sunlight) and below the
tripping value of overcurrent protection (circuit breaker or fuses).
However, a DC arc fault does not spend itself, even when the current is
low. It could be a serious hazard, particularly for PV modules on
buildings.
• Circuit breakers and switches used in PV systems are designed to break
the rated current or fault current with all poles at open-circuit maximum
voltage (UOC MAX). To break the current when UOC MAX is equal to
1000V, for instance, four poles in series (two poles in series for each
polarity) are required. In double ground fault situations, the circuit
breaker or switches must break the current at full voltage with only two
poles in series. Such switchgear is not designed for that purpose and
could sustain irremediable damage if used to break the current in a
double ground fault situation.
The ideal solution is to prevent double ground faults arising. Insulation monitoring
devices or overcurrent protection in grounded systems detects the first fault.
However, although the insulation fault monitoring system usually stops the
inverter, the fault is still present. Staff must locate and clear it without delay. In
large generators with sub arrays protected by circuit breakers, it is highly
advisable to disconnect each array when that first fault has been detected but
not cleared within the next few hours.
The configuration of the MV transformer should take into account the local grid
frequency and should meet local and regional standards.
The following standard sizes of transformers are listed under IEC and the table
indicates generalized power loss values for transformer ratings and impedance.
Table 5-1 Power loss values for transformer ratings and impedancea
On load losses No load losses
Ucc Sn Dk Ck Bk Ak E0 D0 C0 B0 A0
100 kVA 2150 W 1750 W 1475 W 1250 W 320 W 260 W 210 W 180 W 145 W
160 kVA 3100 W 2350 W 2000 W 1700 W 460 W 375 W 300 W 260 W 210 W
250 kVA 4200 W 3250 W 2750 W 2350 W 650 W 530 W 425 W 360 W 300 W
315 kVA 5000 W 3900 W 3250 W 2800 W 770 W 630 W 520 W 440 W 360 W
400 kVA 6000 W 4600 W 3850 W 3250 W 930 W 750 W 610 W 520 W 430 W
500 kVA 7200 W 5500 W 4600 W 3900 W 1100 W 880 W 720 W 610 W 510 W
630 8400 W 6500 W 5400 W 4600 W 1300 W 1030 W 860 W 730 W 600 W
(4%)
6% 630 8700 W 6750 W 5600 W 4800 W 1200 W 940 W 800 W 680 W 560 W
(6%)
800 kVA 10500 W 8400 W 7000 W 6000 W 1400 W 1150 W 930 W 800 W 650 W
1000 13000 W 10500 W 9000 W 7600 W 1700 W 1400 W 1100 W 940 W 770 W
kVA
1250 16000 W 13500 W 11000 W 9500 W 2100 W 1750 W 1350 W 1150 W 950 W
kVA
1600 20000 W 17000 W 14000 W 12000 W 2600 W 2200 W 1700 W 1450 W 1200 W
kVA
2000 26000 W 21000 W 18000 W 15000 W 3100 W 2700 W 2100 W 1800 W 1450 W
kVA
2500 32000 W 26500 W 22000 W 18500 W 3500 W 3200 W 2500 W 2150 W 1750 W
kVA
Schneider Electric offers Minera PV type high efficiency oil immersed transformer
for photovoltaic systems up to 1250kVA and 36kV, 50/60 Hz.
Monitoring System Design: Commercial Rooftops and Small Ground Mounted Farms
Each Conext CL Inverter has a data logging capacity and an in-built web server
that helps you to monitor performance and perform diagnostics of the single
inverter locally at the site. Additionally, Schneider Electric will launch several
other offers for remote monitoring and control of Conext CL enabled
decentralized PV plants.
• Data-logger
• Power supply
• Revenue grade
energy meter
• Extended I/Os
Conext SmartBox Conext SmartBox is designed to be a true plant operator assistant for
configuration, monitoring and diagnostics.
1. SmartInstall
• installation wizard for speedy set-up
2. SmartConfig
• ability to configure all the inverters in the plant with minimum manual data
entry
• file import option to easily replicate standard configurations
3. SmartDiagnose
• on demand 10 seconds data logging for accurate fault diagnostics
• various energy and events log export options for deeper data analysis
4. Other key features
• plant and inverter performance analysis with up to five years of data
• configurable e-mail alerts on device faults
Conext Insight Conext Insight is the remote monitoring and asset management platform to help
you maximize ROI of your PV investments.
Remote monitoring for small to large rooftop and plant (64 inverters) – Smart-
Box BA
• Inverters and accessories (e.g. sensors/meters etc.) are daisy chained to
Conext SmartBox using RS-485
• Conext SmartBox connects to Conext Insight via router
Remote monitoring and control of 5MW ground mounted solar farm (200
inverters of 25kW each) – SmartBox ES
• Plant is divided into four blocks of 1.25MW (50 inverters each)
• Total five Conext SmartBox-ES in master-slave configuration connected using
optical fiber network:
Figure 5-11 Remote monitoring and control of a 5MW ground mounted plant
(200X25kW Conext CL inverters) using Conext SmartBox - ES in master-slave
mode and Conext Insight portal
Meteocontrol: www.meteocontrol.com
Solar-Log: www.solar-log.com
Enerwise: www.enerwise.asia
Deck: www.deckmonitoring.com
Grid Connection
Connecting to a Public LV network
Grid Box
1. The connection to an LV network is made through a grid box provided by the
utility.
• Interface is at the terminals of the metering unit or at those of the main
circuit breaker.
• Grid box can be located indoors or outdoors.
2. The grid box is divided into two parts:
• Service connection area accessible only by the utility for service needs
(metering, disconnecting)
• User connection area accessible by the customer for safety needs
(isolation, protection…)
3. User connection area is generally equipped with a main circuit breaker.
• The main circuit breaker can be provided by the customer. If the main
circuit breaker is not included in the grid box, it must be integrated in the
distribution box.
4. Three types of grid boxes (GB1, GB2, GB3) are available to account for
varying types of grid connections.
LV connection interfaces
Depending upon the equipment and systems, size of Grid box changes and
sometime can be multiplied and divided.
Along with basic monitoring capability, Schneider offers very advance state of art
PV plant SCADA systems with Conext control monitoring platform as requested
by client.
Layouts
1. 250kW Layout with zigzag string connections
2. 250kW Layout with straight string connections
• Distributed Inverters
• Grouped Inverters
3. 500kW Layout with all three types of inverter location configurations
4. 1000kW Layout with grouped Inverters
5. 1000kW Layout with distributed inverters
975-0747-01-01 Revision B
1 x Compact NSX400 4P MCCB
01 250kVA Transformer
lot 4-6 sqmm Cu, PV solar cables
lot 25 sqmm, 4 core AL, XLPE cables
lot 95 sqmm, 4 core AL, XLPE cables
lot 185 sqmm 1core, 2 Runs/ phase AL, XLPE cables
00 11/22/33 kv Ring main unit ( RM6 or Flusarc)
01 Meatering & Monitoring system
De-centralize solution - Inverters spreaded in the PV field & installed on PV module structures
6–3
Layouts
6–4
Layout Optimization
Inverters
AC Combiners
Bill of materials for Layout
De-centralize solution Details
1000 PV Modules - 310 Wp, Poly C-Si Modules 01 AC Re-combiner - 400A (optional) lot 95 sqmm, 4 core AL, XLPE cables Layout - 1000kW system
10 Inverters - 25kW Conext CL Inverters 2 x NSX250- Curve C 4P MCCB lot 240 sqmm 1core, 2 Runs/ phase AL, XLPE cables DC Capacity - 1200kWp
16.5 Tables of 5 rows in landscape for module mounting 1 x Compact NSX400 MCCB 01 11/22/33 kv Ring main unit ( RM6 or Flusarc) AC Capacity - 1000kW (40X25 kW Conext CL)
50 Strings of 20 Modules each 01 250kVA Transformer 01 Meatering & Monitoring system Layout type - Inverters spreaded on PV field
02 AC Combiners - 200A ( 5 inverters to 1 combiner ) lot 4-6 sqmm Cu, PV solar cables Mounted on PV module structure
5 x iC60-40A Curve C 4P MCB lot 25 sqmm, 4 core AL, XLPE cables Structure - 5 rows in landscape, 50 mod / Table
1 x INS250-200A 4P Disconnect
975-0747-01-01 Revision B
975-0747-01-01 Revision B
Inverter
AC Combiner
Inverter station AC Combiner
Inverter station near T/F
6–5
Layouts
6–6
Layout Optimization
O/D Transformer
Inverter Stations
Grid Box
4000 PV Modules - 300 Wp, Poly C-Si Modules 01 AC Re-combiner - 1500A lot 95 / 120 sqmm, 4 core AL, XLPE cables Layout - 1000kW system
40 Inverters - 25kW Conext CL Inverters 5 x NSX250- Curve C 4P MCCB lot 300 sqmm 1core, 2 Runs/ phase AL, XLPE cables DC Capacity - 1200kWp
80 Tables of 5 rows in landscape for module mounting 1 x Compact NS1600 N/H 4P MCCB 01 11/22/33 kv Ring main unit ( RM6 or Flusarc) AC Capacity - 1000kW (40X25 kW Conext CL)
200 Strings of 20 Modules each 01 1000kVA Transformer 01 Meatering & Monitoring system Layout type - Inverters grouped at AC combiners
04 AC Combiners - 200A ( 5 inverters to 1 combiner ) lot 4-6 sqmm Cu, PV solar cables DC cables extended from Strings
5 x iC60-40A Curve C 4P MCB lot 25 sqmm, 4 core AL, XLPE cables Structure - 5 rows in landscape, 50 mod / Table
1 x INS250-200A 4P Disconnect
975-0747-01-01 Revision B
975-0747-01-01 Revision B
O/D Transformer
Inverter Stations
Grid Box
4000 PV Modules - 310 Wp, Poly C-Si Modules 01 AC Re-combiner - 1500A lot 95 / 120 sqmm, 4 core AL, XLPE cables Layout - 1000kW system
40 Inverters - 25kW Conext CL Inverters 8 x NSX250- Curve C 4P MCCB lot 300 sqmm 1core, 2 Runs/ phase AL, XLPE cables DC Capacity - 1200kWp
80 Tables of 5 rows in landscape for module mounting 1 x Compact NS1600 N/H MCCB 01 11/22/33 kv Ring main unit ( RM6 or Flusarc) AC Capacity - 1000kW (40X25 kW Conext CL)
200 Strings of 20 Modules each 01 1000kVA Transformer 01 Meatering & Monitoring system Layout type - Inverters spreaded on PV field
08 AC Combiners - 200A ( 5 inverters to 1 combiner ) lot 4-6 sqmm Cu, PV solar cables Mounted on PV module structure
5 x iC60-40A Curve C 4P MCB lot 25 sqmm, 4 core AL, XLPE cables Structure - 5 rows in landscape, 50 mod / Table
1 x INS250-200A 4P Disconnect
6–7
Layouts
6–8
7 Frequently Asked
Questions (FAQ)
Safety Information
DANGER
ELECTRICAL SHOCK AND FIRE HAZARD
17. Which configuration will be preferred when? – to use both MPPTs or short the
MPPTs.
Schneider Electric recommends to use One MPPT configuration in case of
odd number of strings being connected to the inverter, if there is no
significant difference within strings (like shadowing or different tilt or a
different configuration). In case of difference in configuration of strings
(like tile, shadow, mismatch etc.) dual MPPT operation is advisable with
balanced input. Conext CL inverters are capable to handle 60-40 ratio of
imbalance in string power.
18. What if I connect unbalanced string combination (3 and 2 on each MPPT)
with Conext CL inverter?
Conext CL inverter is capable to connect 60-40% imbalance condition. So
user can connect 3-2 or 4-3 configuration. But be careful about not violating
the short circuit rating of the inverter DC input.
19. How a choice of transformer gets affected by the inverter’s operating
capability?
The inverter’s operational capability depends on Transformer in two aspects.
Parallel operation of inverter: Inverter’s parallel operation is function of short
circuit impedance (Z%) and transformer is a circuit component with very
large impedance portion of overall circuit. We recommend keeping the
Impedance of transformer as low as possible.
Conext CL inverter supports TNS,TNC, TN-C-S and TT wiring schemes. It
does not support IT scheme. When Transformer is selected, it is important to
match Utility side winging requirement as per Point of connection and Low
voltage side winding requirement as per the inverter’s operational
compatibility.
20. What is the limit of power factor Conext CL inverters are capable of?
Conext CL can operate within 0.8 lead and 0.8 lag power factor limit.
21. Does Conext CL inverter support LVRT requirement?
Yes. It does. LVRT requirement is specified in respective PV grid code of
country. Conext CL inverter firmware is programmed to follow the LVRT
requirement (curve) during certification of each country. Contact us to know
the list of countries Conext CL inverters are certified for.
22. Do I need to have power factory model of my PV plant if I use Conext CL
inverter? Can Schneider Electric provide it?
This requirement is generally requested by Utilities to include the model of
your power plant into their power system. We recommend that clients should
discuss this type of requirements with utility well ahead during the system
planning stage and choose the right wiring scheme and metering scheme. A
billable power factory model can be created based on client’s request. If you
have such a requirement, please contact us for further discussion.
23. What type of support I can have form Schneider Electric for designing
configuration of my PV system?
Schneider Electric provides ready reference documentation for designing the
system, for example, the solutions guide, installation manual, training
material, etc. If you need any additional information or services, contact us
for more discussion.
24. Which parameters I do have to confirm and use to order Conext CL
inverters?
Outside
Ambient in °C 350V 800V
20 20.08 20.08
30 20.08 20.08
40 20.08 20.08
44 20.08 20.08
50 19.97 20.08
54 17.24 18.04
60 13.54 14.84
44. Can we control the output of the inverter is 1% steps, what is the time
resolution?
1% steps is possible and time latency is 5 sec (max), typically 1 sec
45. How many inverters can be firmware upgraded at one time via Ethernet start
connection, one or multiple? Does it have to be in Intranet or Internet?
One , either of the network
46. How long does it take for Ethernet firmware upgrading for single inverter?
10 to 15 mins (approximately)
47. How can we ensure the wiring box top ports are protected from water and
dirt ingress until the inverters are mounted?
Can you please confirm that there are no other complications in the mounting
of these units separately, which will be installed upon the table frameworks?
Wiring box is IP65 with good protection from water and dirt. There is one
Connector cover which will protect all the connectors on the top of wiring
box. Make sure this cover will need to be remained till inverter mounting on
the top of the wiring box. Please find the details on question Number 26 on
page 7–5.