Question Bank East Coast Railway
Question Bank East Coast Railway
Question Bank East Coast Railway
1. Indications for caution aspect is proceed and be prepared to pass next stop signal
at restricted speed.
5. Name of aspect and indication of UQMA signal and MACL signal are not same
11. Shunting can be performed in face of approaching train at class “A” station.
12. The block overlap and signal overlap in two aspect signalling and multi-aspect
signalling is 180 Mts.
13. A Warner signal(semaphore) is permissive signal and provided with a “P” marker.
14. Passenger warning board shall be placed at distance of 1KMts in rear of first stop
signal in a station with multi-aspect colour light signalling.
15. The block overlap in multi aspect signalling is more than L.Q. signal.
16. When distant signal display green aspect then it indicates run though condition.
20. Goods warning board shall be placed at distance of 1.4 KMts in rear of first stop
signal.
Page 1 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
21. Warner signal at OFF indicate run through condition on Loop Line.
22. On single line station signal overlap is reckoned form outer most point of station.
23. Location of shunting limit board & Last stop signal is same.
25. Block section limit board shall be provided at class B station on double line where
first point is a trailing point OR no point with lower quadrant signalling.
26. Visibility of Warner signal shall be 1.2 KMts for speed more than 100 KMPH.
28. If LC Gate is interlocked with advance starter then a G maker shall be provided
below advance starter.
30. Shunting limit board shall be placed at a distance of signal overlap from outer most
point on double line.
32. Catch siding protect block section and slip siding protect station section.
33. If speed is more than 50 kmph then one goods line need not be isolated from other
goods line.
35. More than one calling ON signal can be placed below a stop signal.
37. First stop signal on signal line normally shall be placed at distance of signal
overlap plus block overlap from outer most point.
Page 2 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
41. If speed is less than 50 KMPH, then isolation of a passenger line from other
connecting passenger line is not required.
42. Under special instruction means approval from commissioner of railway safety.
43. Swinger/top piece can not be used in the first & last channels
45. Normal swinger can not be used in the last but one channel
46. Swinger shall not be used in the adjacent channel on the same tappet
48. The total nos.of bridle bars at any given place of a channel 2 top bridle bar +2
bottom bridle bar in catch handle lever frame.
49. If the distance from the signal & 1st facing point or from one facing point to next
facing point is more than 180 Mts. then one holding bar to be provided.
50. If the distance from the signal & 1st facing point or from one facing point to next
facing point is more than 180 mtr then lock retaining bar to be provided
51. Dummy Lock need to be provided if an unconnected length of a bridle bar exceeds
more than 10 levers.
52. Use of top pieces shall be a last alternative for avoiding fouling notches
54. Signaling plan is prepared based on Type of Signaling, the class of Station
55. Size of Catch handle type lever frame will be in combination or multiples of 8 and
10
56. “Direct” type lever frame size will be in combination or multiple of 5 and 7
60. Clearence between the two tappets is 59 mm in Catch handle lever frame
61. The lock dog should be riveted with the only one bridle bar
Page 3 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
63. In SWCH type lever frame (SA1101/M) the pitch of the channel is 100 mm
64. In SWCH type lever frame (SA1101/M) the stroke of the tappet is 65 mm
67. The factor by which the route holding is achieved by interlocking between the
successive lock bars
68. The factor by which the route holding is the distance from the signal and first
facing point by limiting to 180 Mts.
69. The factor by which the route holding is achieved by the existence of lock bar
73. Any swinger/top piece can not be used in the first and the last channels.
75. Normal swinger can be used in the last but one channel.
76. Swinger always shall be used in the adjacent channel on the same tappet.
78. The numbering of bridle bar at any given place of a channel may be more than four
if required
79. Dummy Lock need not be provided if an unconnected length of a bridle bar to a
distance of more than 10 levers
80. Use of top pieces shall not be a last alternative for avoiding fouling notches.
83. Signal in advance locking the trailing points both ways is an arrangement of route
holding.
Page 4 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
86. The lock retaining bar is used in centralized MAUQ signalling for holding the route.
89. A facing lock bar is released by another trailing lock bar in the route of a train, is
called as successive lock bar locking.
90. Route method is normally adopted to prepare a locking table
95. Number of bridle bars in a conditional locking is equal to number of swingers plus
one
96. Testing of converse locking in locks normal is not necessary.
97. Spare levers are catered in the middle while numbering a layout with geographical
cum group method of numbering.
98. The signalling plan is prepared based on the engineering plan.
99. While deciding the size of the lever frame is in multiples of 8 and / or 10 in catch
handle type lever frames.
100. Level crossing gate numbering is done at the end of all groups while numbering
the yard with geographical-cum-group method.
101. Principles of interlocking are applicable only for lower quadrant signalling and not
for other types of signalling.
104. By tripping of one lever if the other lever is not locked it is called as loose locking
110. In a central cabin operated double wire signalling yard, the route holding is
achieved by clutch levers.
111. Normally geographical method is adopted for numbering the signals in a yard
112. Dummy dog to be used when the bridle bar is un supported for eight plungers
115. While numbering a signalling yard normally group cum geographical method is
not adopted.
116. An additional lock bar to be provided when the distance between the two
successive lock bars is more than 500 Mts
117. More important point released by less important point
119. In a conditional locking when the swinger is placed on a locking lever it is always
reverse swinger.
120. In a conditional locking number of swingers are equal to no. of locking levers
121. Shunt signal should lock slot in opposite direction through a condition having
separate overlap
122. The trap point releases the lock bar.
Page 6 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
125. Main line Home Signal Locks Loop lines slot having separate overlap.
126. A Running Signal released by shunt Signal below it (in same post).
127. A slot having separate overlap must not lock all others Slots
131. Space between two Tappet is 346 mm in double wire lever frame
132. A Signal shall lock the point for isolation though it may not be in the route and
negotiated by the train
133. Any swinger/top piece can be used in the first and the last channels.
135. Normal swinger can be used in the last but one channel .
136. Swinger shall be used in the adjacent channel on the same tappet.
138. The numbering of bridle bar at any given place of a channel may exceed four in
double wire lever frame.
139. Dummy Lock need to be provided if an unconnected length of a bridle bar to a
distance of more than 12 levers .
140. Use of top pieces need not be a last alternative for avoiding fouling notches.
146. Shaft collars are provided to maintain lever pitch in catch handle lever frame
Page 7 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
148. In Direct lever Back tail is meant for carrying a 25kg weight for long distance
signals.
149. In Direct lever Quadrants are fixed on T-section quadrant supporting bars.
154. In Direct lever locking box to attend maintenance and to attend failure.
157. D.W. Levers can be inserted on catch handle type to facilitate Outer, Warner &
LSS operations.
158. The locking will start to actuate by pressing the catch handle in ‘N & R’
161. Pressing releasing the catch handle in catch handle lever frame tappet will move
31mm
163. Quadrants are fixed on rectangular quadrant supporting bar in catch handle lever
frame
167. One of the arm is CURVED in Accommodating crank to facilitate connection & to
Page 8 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
accommodate cranks placed adjacent to it.
169. Accommodating crank 300mm x 300mm (12” x 12”) is used for lever pitch is
100mm(4”)
170. Accommodating crank 350mm x 350mm (14” x 14”) is used for lever pitch is
125mm(4”)
171. Accommodating crank arm sizes are 300mm x 300mm (12” x 12”) & 300mm x
400mm
172. Changing the alignment of rodding run.i.e., 500mm or 600mm Straight Arm Crank
is used
177. Rod Joints are used for connecting levers, crank, points,etc.,
178. Flush Joint is used at vertical crank towards out side leadout.
179. Screw Joint single end is used at lock plunger and lifting barried boom locking.
180. Screw Joint double end used for balancing of stroke at throw rod of point and lock
bar.
181. Eye Joint is used at radial guide, signal arm and circuit controllers
182. Wide Joint is used where two rod joints required at one place.
183. Lug Eye joint is use where two functions are operated from one lever.
184. Swan Neck & Goose Neck joints are used for point detection rods.
185. With turning of buckle in point adjusting screw we can shortening or lengthening of
rodding. ( T )
Page 9 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
191. Point rodding shall be solid and shall be in accordance with IRS Spec.no.S5
193. With lever in the middle position joints and lug eyes must not be located less than
300mm from roller stand.
194. Cranks and compensators should be so located in the main run that it leaves field
side clear for additional rodding run.
195. Cranks and compensators must not be fixed nearer a point rod roller than 900mm.
196. When rodding running under tracks must be arranged to permit the standard
spacing and packing of the sleepers.
197. The top of the rodding should not be less than 25mm below the bottom of the rails.
198. Whenever possible, the running of rods under rail joints should be avoided
199. Where a series of crossings have to be made each group must not be less than
two sleepers apart.
200. Rodding under L.C.Gates should preferably be run through standard reinforced
concrete channels having mild steel cover plates at the road level.
201. Where diversion in rodding run up to 20 degrees relief crank must be used.
202. The top of roller standards adjacent to tracks shall not be fixed more than 64mm
above rail level.
203. The distance from the nearest rod to the center of the track shall not be less than
1905mm on BG lines.
204. The distance from the nearest rod to the center of the track shall not be less than
Page 10 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1370mm on MG lines.
206. Minimum length of the off-set should not be less than twice the amount of the off-
set.
207. Where more than one off-set is necessary, a guide should be provided.
209. Two bolts at joints preferable to provide one bolt with head on top and the other
with head underneath.
212. Down rod length is more than 2M must be supported by a guide or guides in
order to prevent buckling.
215. The rod compensator is installed to compensate the linear motion of rods
(solid/tubular) due to temperature changes.
217. The length of crank arm i.e, 300 mm (12”) is capable to take of up the
expansion/contraction of 60M (200 ft) of rodding connected to it.
218. This compensation range is limited to 22 ½° on either side of its means position as
a safe margin.
219. Compensator is able to convert pull motion into push and vice versa without
alteration of stroke
220. The initial setting of the crank arms should corresponds with prevailing
temperature.
Page 11 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
222. Where the normal crank is used the length of the shorter rod must be added to
the length of the longer rod to find out the total length of straight line/trans.
223. Where the reverse crank is used the length of the shorter rod must be
subtracted from the length of the longer rod.
225. Approximate linear expansion of rods 0.24” /100 Yds/10 F rise in temperature
226. For crossover point one compensator should be provided between cabin and
near end point and near end point to far end point one more compensator
should be provided
227. In rodding transmission there will be (2) Neutral points one at lever and other at
function.
228. The compensator is to provide exactly at centre of the two neutral points.
229. Points are said to be facing when a vehicle or a train moving over them can be
diverted from one track to the other
230. In loose heel switch the front bolts of the fish plate at heel joint are to be kept
sufficiently loose to allow for the easy movement of the switch.
231. In fixed heel switch the force required for the operation of point is increased.
232. In over ridding switches the tongue rail slides over the foot of the stock rail.
233. The length of tongue rail in BG in 1:8 1/2 turnout is 4722mm(Straight Switch)
234. The length of tongue rail in BG in 1:8 1/2 turnout is 7620 mm (Curved switch)
235. The length of tongue rail in BG in 1:12 turnout is 7620mm (Straight Switch)
236. The length of tongue rail in BG in 1:12 turnout is 9020mm (Curved Switch)
237. The length of tongue rail in BG in 1:16 turnout (90R) is 11000mm (Curved Switch)
238. The length of tongue rail in BG in 1:16 turnout (52Kg) is 13000mm (Curved Switch)
239. points in the two tonque rails to move in union the tonque rails are tied through
structure bars
242. Leading stretcher bar should be fixed on BG at a distance of 13” from the toe of
the switch rail.
243. Leading stretcher bar should be fixed on MG at a distance of 15” from the toe of
the switch rail.
244. Following stretcher bar having the size on MG is 2’9” x 2 1/2” x 3/8”
246. The following stretcher bar should be fixed on BG at a distance of 55” from the toe
of the switch rail.
247. The following stretcher bar should be fixed on MG at a distance of 54” from the toe
of the switch rail.
248. In point zone the track should be correct level and alignment
249. In loose heel switch they can be thrown both ways with ease and can be housed
against the stock rail by hand and remain there when the pressure is removed.
250. In fixed heel switch they normally lie in the mid-position and flex equally in the
normal and reverse positions.
251. Tongue rail is chipped/cracked over a small length aggregating to 200mm with in
the distance of 1000mm from its toe.
252. The lock bar & the Plunger is provided to prevent the unlocking of points while the
train is moving over it.
253. Lock bar driving attachment to be fixed at 14” (350 mm) from the toe of lock bar.
254. Three(3) lock bar stop are provided to ensure a fixed clearance below the rail level
by 38 mm (1 ½ “)
256. When the lock bar is normal, the FPL plunger should be clear by 12mm (1/2”)
from the split stretcher bar.
257. The clearance between stretcher notches and lock plunger shall not be more than
1.5 mm
Page 13 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
258. Detector is necessary to provide to detect the position of points and locks.
259. The function of Detector is to prove the correct normal or reverse setting and
correct locking of the point.
260. 2-Aspect lower quadrant semaphore signals are generally worked by single wire
transmission.
261. Day aspect of signal is Arm position horizontal is ‘ON’ and 45 to 60 degrees below
horizontal is ‘OFF’ position.
263. The counter weight balance lever itself is fitted below on the post at a min.
distance of 4 feet from the fulcrum of spectacle.
264. A signal post consists of two tubes of section ‘140mm’ and ‘168mm’ outer diameter
having each thickness of ‘7-9mm’.
265. In tubular signal post the maximum height being only ’10.5M’.
266. Where two or more lines diverge to the signals must be fixed on a bracket post.
268. Ladder on the signal post fixed at ‘225mm’ from the top of the post.
271. In counter weight balance lever 92mm hole is connected to shunt signal.
272. In counter weight balance lever 118mm hole is connected to ‘B’ type spectacle to
get 90mm stroke for 45 degrees.
273. In counter weight balance lever 154mm hole connected to ‘A’ type spectacle to get
130mm stroke for 50 degrees.
274. The lowest transmission wire should be about 150mm clear from the ground.
275. For running wire under level crossings, trenches are made along the level
crossings, the top being covered with mild steel plates of suitable size and the
inside surface of trench being plastered with cement.
Page 14 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
276. Sometimes wire run under L.C. Gates are made through pipes provided in the
level crossings.
277. Facile stroke lever may be employed at a distance of 60 to 80M from the signal.
280. Swing type gates are open either towards or away from the track.
282. The booms are provided according to the width of the road
283. Lifting barrier drum is connected by D.W. transmission with gear on the winch.
284. The movement of the lock wheel in lifting barrier winch is made less than one
complete revolution.
285. ‘E’ type key can be extracted only when the gate is closed
286. A light fringe is usually fitted to provide a barrier between the boom and road
surface , so that smaller animals of children may not pass through.
287. Lifting barrier boom height from road surface should be maintained between 0.8M
and 1M.
288. The boom shall be either painted with 300mm bands of alternate black and yellow
color or provided with approved type of retro-reflective strips.(
289. It shall be ensured that Boom locking is effective and it is not possible to lift the
boom by more than 10 degree from closed position.
290. Rope drum (fixed on pedestal) not inter changeable for assembly from RH to LH
and vice-versa.
291. Tunion Brackets not inter changeable for assembly from RH to LH and vice-versa.
292. Link assembly for bell not inter changeable for assembly from RH to LH and vice-
versa.
293. Pedestal on winch rope drum is mounted not inter changeable for assembly from
RH to LH and vice-versa.
Page 15 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
295. The gate equipments should be there as prescribed in the working rule
296. The Whistle Board are provided on track while approaching L.C.Gate.
297. The view for road users and the gateman of an approaching train is not obstructed.
299. The working instructions of the L.C.Gate is in the local language besides Hindi and
English.
300. At the time of taking cences Train, Motor vehicle, bullock carts&tongues taken as 1
unit
301. At the time of taking cences Cycle rickshaw & auto rickshaw taken as ½ unit
303. Fencing parallel to the track in L.C.Gate to be provided both side of track on either
side of road is 15M
305. Speed Breakers are provided at 20M from center of track on both sides
308. TVU is more than 6000 or L.C.Gate visibility is poor –Un manned gate is converted
into Manned gate.
312. E-type Key locks used for locking boom locking levers
319. The function of Lug & Feather is to operate the operating piece and to prevent the
insertion of wrong key .
320. Key turned clockwise lock bolt goes inside and key is locked.
321. Key turned anti clockwise lock bolt comes out and key is came out.
327. Double wire levers can be replaced without disturbing other levers.
0
328. Double wire levers rotate through 180 , when operated from normal to reverse.
329. The stroke transmitted to the tappet is 40mm when a lever is operated from normal
to reverse.
330. Locking tappet stroke of a clutch lever is 12 mm upwards when tripped at Normal.
Page 17 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
336. Locking tappet stroke of Rack & Pinion lever is 40 mm upwards while operating
from Normal to Reverse.
337. Locking tappet stroke of Rack & Pinion is 40 mm downwards while operating from
Reverse to Normal.
338. Locking tappet stroke is 20 mm upwards while operating from Normal to Pull of the
miniature lever.
339. Locking tappet stroke is 20 mm downwards while operating from Normal to Push
of the miniature lever.
340. 500 mm stroke Direct lever operates the signal without detector up to 1200 Mts.
341. 600 mm stroke Direct lever operates the signal without detector greater than 1200
Mts.
342. 500 mm stroke Clutch lever operates the Points up to 500 Mts.
343. 600 mm stroke Clutch lever operates the Point up to 730 Mts.
344. 500 mm stroke Clutch lever operates the Detector up to 600 Mts.
345. 600 mm stroke Clutch lever operates the Detector up to 730 Mts.
346. 500 mm stroke Clutch lever operates the Signal with Detector up to 600 Mts.
347. 600 mm stroke Clutch lever operates the Signal with Detector up to 730 Mts.
349. Rack& Pinion lever can operate the single end points up to 460 Mts.
350. Rack& Pinion lever can operate the single end points up to 460 Mts.
351. The Rack& Pinion lever can operate the double end points up to 275 Mts.
352. The rope drum and the lever handle are rigidly fixed in the Direct lever.
354. Rope drum and the lever handle are connected through a spring loaded clutch
355. Rope drum can rotate independent of the lever handle in clutch lever
356. 85 Kgs tension difference in the transmission should not cause the clutch lever to
trip
357. Coupling of levers economizes cost of material of one transmission.
Page 18 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
361. Coupling of levers economizes cost of one signal mechanism when located on the
same signal post.
363. The two levers should be adjacent in the lever frame for coupling.
364. The two levers should bear consecutive numbers for coupling.
365. Length of transmission between the two coupled functions should not be greater
than 73 Mts. (T)
368. Pull wires of both the coupling device levers are connected to the coupling device
levers in Push-Pull coupling.
369. Return wire of first operated lever and Pull wire of second operated lever are
connected are connected to the coupling device levers in Pull-Pull coupling.
(T)
370. L.Q. Main and Loop Line home signals are connected in Push-Pull coupling.
371. L.Q. or U.Q. Ist loop and 2nd loop home signals are connected in Push-Pull
coupling. (T)
372. A starter and a shunt below starter are connected in Push-Pull coupling.
373. Two shunt signals one below the other are connected in Push-Pull coupling.
374. A Home Signal and a Calling on signal below Home signal are connected in Push-
Pull coupling. (T)
Page 19 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
376. Main line Home signal on a multiple aspect signalling territory are connected in
Pull-Pull coupling. (T)
377. Outer and Warner Signals located on the same post are connected in Pull-Pull
coupling. (T)
378. Hook lock is adopted to prevent the tripping of a coupled clutch lever.
382. The point mechanism movement during unlocking of point is 127 mm.
383. The point mechanism movement during Point setting stroke 268mm. (
T)
384. The point mechanism movement during unlocking of point is105 mm. (
T)
385. The total movement of rack during its lever operation is 200 mm.
386. Broken wire lock is adopted to prevent the operation of points when the last pull
wire is broken
387. Broken wire lock pawls must be tested once in every quarter.
389. The width of the locks on the EFPL is 38 mm independently for N and R___
391. The two locks on the EFPL are separated by the distance by 158 mm.
392. Separation of locks on EFPL facilitates economy in operation of point and lock.
394. The pitch of the notches on split lock stretchers with EFPL is 127 mm in BG
Page 20 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
397. The movement of cross slide during point operation in EFPL is zero mm.
398. PWI must bring the track on either side of the point to correct alignment.
399. PWI must ease off rail joints on either side of points to be interlocked
400. PWI must close the stock rail joints associated with lock bars.
401. PWI must provide ballast fully and pack all points which are to be interlocked.
402. PWI must take adequate measures to prevent creep in the vicinity points.
403. PWI must provide creep and level pillars to prevent creep in the vicinity points.
404. PWI must arrange the sleepers on adjacent track to facilitate rod/wire transmission
to cross.
405. PWI must provide and fix special timbers where required
406. PWI must provide gauge tie plate correctly PWI must adjuste loose heel switches
so that they can be thrown both way with ease
407. Loose heel switches can be housed against the stock rail by hand and remain
there when the pressure is removed.
408. The planed surface of the switch rail should fully house against the stock rails for a
sufficient length.
409. Fixed heel switches lie in the mid-position and flex equally in the normal and
Reversed positions. .
410. Point should be fitted with fitted flexible stretchers so that they flex equally in the
normal and reverse Positions
411. Point should be fitted provided with a stop for the open position of a single switch
layout.
412. Facing point lock is fixed at 500mm from the gauge face in B.G.
413. Signal mechanism should prevent inaccuracies in the transmission of lever strokes
helps display of correct signal aspects.
Page 21 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
415. Signal mechanism should co-relate the down rod movement with that of the
mechanism drum.
416. Signal mechanism should make the maximum torque required for signal operation
417. Signal mechanism should increase the range of signal operation & ease of lever
operation.
420. The cam paths are identical in the Universal signal mechanism
421. Concentric path of Signal mechanism provides stability to the 'ON' and 'OFF'
aspects of the Signal arm
422. 0 - 450 - 900 Signal Mechanism is used for working 3 aspects main line Home
used for working 3 aspects main line Home
423. 450 - 0 - 900 Signal Mechanism is used for working the distant signal.
435. Detector detects the correct relation between switch and stock rails.
436. Detector locks the points in the last operated position when the detector is
operated.
437. Detector locks the points in the last operated position if the detector transmission
wire opposite this rim breaks.
439. Locking Rim establishes correct relation between switch and stock rails.
440. Locking Rim locks the points in the last operated position when the wire opposite
this rim breaks.
442. Control Rim acts as a limiting stop in the event of wire breakage
443. Control Rim helps the locking to lock the points in the last operated position in the
event of wire breakage
444. Control Rim helps the Locking rim to lock the points in the last operated position in
the event of wire breakage.
445. Control Rim helps the Detecting rim to lock the points in the last operated position
in the event of wire breakage.
447. Double wire compensator introduces initial tension 68 kgs. in the transmission
wires with the transmission at rest.
448. The compensator levers should be locked during operation of the lever.
452. Compensator levers are free to oscillate when the transmission is at rest
Page 23 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
456. Inter distance between two pulleys stakes should not be greater than 20 Mts in
case of Signals.
457. Inter distance between two pulleys stakes should not be greater than 15 Mts in
case of Points.
458. Inter distance between two pulley stakes should not be greater than 15 Mts in case
of Detectors.
459. Inter distance between two pulleys stakes should not be greater than 15 Mts in
case of Signals with Detectors.
462. Bottom most pulley should be 300 mm clear of ground in the D.W transmission.
464. Wires and ropes must not scrap against walls protecting covers platform ramps,
rails and sleepers.
465. At level crossing gate transmission should run in RCC troughs and steel cover
plates.
466. Transmission running in the diversion from straight up to 10 0 should run through
diversion pulley.
468. Transmission running in the diversion greater than should run through horizontal
diversion wheel of dia 225 mm.
469. For rod running under the track, the top of the rod shall not be less Than 40 mm
below the bottom of the rail.
470. The distance between any OHE mast and the point rod shall not be less than 40
mm.
471. Each rod shall be provided with an insulator immediately outside the cabin in the
lead-out as close to the cabin as possible.
Page 24 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
472. An additional insulator shall be provided between the last adjustable crank and
the point/lock bar
473. If the rod transmission is more than 400 metres, additional insulators shall be
provided on each rod at every 400metres
474. The distance between two consecutive insulators on the same rod should be
lesser than 300 metres.
475. The wire insulator shall conform to IRS Spec. No. S47-74.
476. An insulator shall be provided in each wire near the gear of operation
478. The horizontal distance between two wires shall not be less than 60 mm
479. The vertical distance between two wires shall not be less than 200 mm.
480. The lever frame and other metallic frames of the cabin shall be connected together
to a separate earthing.
481. The earthing shall not be provided at every location box where cable terminate.
482. Earth connected for lightening discharger should not be more than 10 Ohms
483. Earth connected for equipment should not be less than 10 Ohms.
484. Earth connected Axle counter cable (screened) in ac electrified area should not be
more than 1 Ohm.
485. Where more than one earthing arrangements are employed, the distance between
earthing electrodes shall not be less than 6metres.
486. The clearance of equipment earths from system earths provided by the Electrical
Dept. of Railways or any other administration shall not be less than 30 meters
487. The cables laid parallel to the track buried at a depth of 2 m minimum.
489. If cable is laid one meter from the RE mast its trench depth shall not be more than
0.5m.
490. If cable is laid in concrete/HDPE pipes up to 3 meters on either side of mast, the
distance between the mast and trench can be reduced to 0.5 meters
491. If the cable is laid at more than 0.5 meters depth the distance between trench and
mast shall not be less not be less than 3 meters.
492. In the vicinity of traction sub station the cables shall be laid on the side of the track
opposite to the sub-station side
Page 25 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
493. Cables shall be laid at least 10 meters away from the switching station earthing
494. During track crossings, the cables should cross the track at right angles
495. During track crossings, the cables can cross the track under points and crossings
496. During track crossings, the cables are to be laid in concrete pipes while crossing
the track.
497. During track crossings, the cables shall be buried at a depth of 1.0 metre below the
bottom of the rail.
498. At out side of station limits, the cable shall be laid 5 to 6 meters from the nearest
centre line of the track.
499. At with in station limits, the cable shall be laid not less than 5.5 meters from the
nearest centre line of the track
500. Stray voltage in a track circuit shall not be more than 100mV.
501. The total stray current shall not exceed 10mA for a track circuit length less
than100m
502. The total stray current shall not exceed 10mA for a track circuit length more
than100m
503. Only 09 ohms track relay should be used in AC RE area
505. In DC single rail track circuit feed end is protected by “B type” choke.
508. Maximum length of DC track circuit with QBAT relay and choke at feed-end is
450m
509. Electro static effects in signalling circuit can be nullified by transferring the circuits
in to Under ground cables.
510. Electro static effects in signalling circuit directly proportional to Length of
parallelism.
511. Electro static effects in signalling cable inversely proportional to distance of
separation between catenary and cable.
512. If whole of the return current passing the rails, then the voltage induced in a
signalling cable which laid equal-distance from catenary & rail is 35v/km
513. In screened cable by earthing of metallic sheath voltage induced in cable is
reduced.
Page 26 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
514. Catenary current in old design is 600A D/L, 300A in single line.
517. Rail reduction factor in old design is 0.56 for S/L 0.4 for D/L.
519. A common design was adopted for single and double/multiple track electrified
sections in old design
520. Due to electro-magnetic induction the voltage induced in signalling scrneed cable
in old design is 35V/KM.
521. Due to electro-magnetic induction the voltage induced in signalling un-scrneed
cable in old design is 95V/KM.
522. Max. Length of a circuit parallelism with screened cable is 3.5 km in old design.
523. Max. Length of a circuit parallelism with un-screened cable is 1.9 km in old design.
524. Glow voltage of 12v signal bulb on primary of signal transformer (110/12) is 21V.
525. Glow voltage of 12v signal bulb on secondary of signal transformer (110/12) is 5V.
527. Direct feeding range of signals with un- scrneed cable in old design is 330m
528. Shelf type line relays tested under BSS 1659, RE.Spec. 187/11, are only AC
immunised
529. In case of track relays Copper slugs & a magnetic shunt is used to make the relay
to AC immunised.
530. In case of Shelf type line relays no extra materials used to make relay AC
immunised.
531. AC. immunized Shelf type track relay is immune to 65VAC
Page 27 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
540. Catenary current in new design is 1000A D/L, 800A in single line.
545. Rail Reduction Factor in new design for 0.3926 Single Line.
546. Rail Reduction Factor in new design for 0.566 Single Line.
547. Using of screened cable discontinued since we are unable to maintain earth
resistance as 0.2ohams to get 0.4 screening factor.
548. New screening factor is 0.91.
549. Due to electro-magnetic induction the voltage induced in signalling cable in new
design on D/L is 95V/KM
550. Due to electro-magnetic induction the voltage induced in signalling cable in new
design on S/L is 120 V/KM
551. Direct feeding range of signals on D/L in new design is 226m.
558. Maximum permissible separation between Point Contractor and GRS 5E Point
Page 28 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
Machine on single line is 400m
559. Maximum permissible separation between Point Contractor and GRS 5E Point
Machine on double line is 630m
560. AC. Immunity level of IRS-24 point machine is 90V
561. Maximum permissible separation between Point Contractor and IRS-24 Point
Machine on single line is 910m
562. Maximum permissible separation between Point Contractor and IRS-24 Point
Machine on double line is 2.1KM.
563. Maximum permissible separation between Point Contractor and SIEMENS IA type
Point Machine on double line is 1.1KM.
564. Maximum permissible separation between Point Contractor and SIEMENS IB type
Point Machine on double line is 2.1KM.
565. Maximum permissible separation between Point Contractor and SIEMENS IB type
Point Machine on single line is 1650M.
566. Maximum permissible separation between Point Contractor and SIEMENS IC type
Point Machine on double line is 1850M.
567. Maximum permissible separation between Point Contractor and SIEMENS IC type
Point Machine on single line is 2.2 KM.
568. AC. Immunity level of SIEMENS IB type Point machine is 300V
570. As per RDSO specification No.S24/90 - for Electrical Point Machine non-trailable type,
specifies the A.C. immunity level of Electrical Point Machine shall not be less than
160V RMS at 50 Hz
571. If the load current is 8A and backup time required is 10Hrs then recommended
capacity of Lead Acid Cell is 80AH
572. During the preparation of electrolyte always add acid to distilled water only, but not
water to acid.
573. In Lead Acid cells, electrolyte level should be maintained at 12mm to 15mm above
the plates.
574. If the Lead acid cells are continuously used in “FLOAT Charging” then equalising
charge must be given once in 3 months.
575. In Lead Acid cells, Boost charging current must given at the rate of C/10 Amp
576. LMLA cells are preferred over VRLA cells for signalling application.
577. 60V battery charger is having the provision for charging the 30 or 31 or 32 no. of
cells.
Page 29 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
578. Battery charger can able to give the constant output voltage with the input
Voltage variation of 160VAC to 270VAC.
579. 110V battery charger is having the provision for charging maximum 55 no. of cells.
580. In IRS: 86/2000 Battery charger the boost charging current control & float voltage
adjustment is possible only in Auto mode.
581. Blanking of signals due to power supply failure can be effectively and economically
prevented by using IPS.
582. In IPS system, inverters are configured with (1+1) configuration.
583. All the DC-DC converters except for Relays (internal) of IPS system are used in
(N+1) load sharing configuration.
584. In IPS system, Inverter output is used for the load of DC Track circuits.
585. In case of IPS system, normally only one Battery bank is used.
586. An inverter is used in IPS system to convert the A.C. power into D.C. power.
587. DC-DC converters of IPS system for Relays (internal) are used in (N+1) load
sharing configuration.
588. SMRs of IPS system are provided with in (N+2) load configuration.
589. In IPS system Inverter-2 will be automatically connected to the load, when Inverter-
1 output is failed.
590. In IPS system CVT or AVR will be automatically connected to the load, when
Inverter-1 and Inverter-2 output is failed.
591. With IPS System, DG set is not required
592. Class B and Class C arresters are used in IPS for stage1 and stage2 protection
593. IPS system generates Start D.G set audio-visual alarm with 50% depth of
discharge of Battery bank.
594. IPS system generates Stop D.G set audio-visual alarm whenever FRBC / SMR
change over to float mode from boost mode.
595. Hexagonal shape of a solar cell provides more utilization area
Page 30 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
604. Conventional Lead Acid Cells are suitable for Solar panel
608. In OFF-Line UPS the relay will be OFF condition when AC input is present
609. UPS backup time can be increase by increasing the capacity of the battery
611. In OFF-Line UPS the battery will be charge only when the inverter is ON
612. For UPS with rating higher than 2KVA IGBT device is used in power amplifier
stage
613. The grids and separators will be effected if the specific gravity of electrolyte is
below 1.240
614. The internal resistance is minimum at specific gravity 1.240 in Lead Acid cell
615. Capacity of a Lead Acid cell is directly proportional to its length of service
616. The Initial charging current is less than normal charging current
619. The battery which is kept continuously under “Float charging” should be given “
Equivalising charge” to compensate low or uneven Sp. Gravities of cells
620. Buckling is one of the causes for internal short circuit
622. Buckling of cell plates takes place due to excessive charging or discharging
631. Gas recombination principle is used in maintaince free sealed L.A. battery
634. Distilled water to be added during initial charging to maintain the level
639. Calcium alloy is having lower self discharge and increased conductivity
641. The active material on the positive plates in Lead Acid cell is Spongy Lead
Page 32 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
645. Efficiency of a secondary battery is defind as the ratio of input divided by output
647. Fuel tank in diesel engine should be cleaned for every 250 hours of working
650. Governor throttle regulates the amount of fuel supplied to the engine
654. The 3 pins of CLS lamp are provided to prevent lamp theft
657. 1SL 18 lamp and SL 35 A lamp can not used in cascaded off aspect.
658. LED signal unit and SL 35 A lamp can not used in cascaded off aspect.
659. Siemens ON ECR can be used in aspect control circuit with LED signal.
660. No load current of signal transformer shall not be more than 15 Milli Amps.
666. Auxiliary filament of triple pole lamp will also burn while main filament is burning.
Page 33 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
667. Proceed aspect of Distant Signal in single distant territory indicate run-through
condition always.
668. The Distant Signal in double distant territory has total three aspects.
671. Dead Approach to be provided where the sufficient length of Approach Track
circuit cannot be provided.
672. Indication locking is to be provided where there is no rigid connection between the
lever and its function.
673. The back locking on a signal lever will be effective at B position.
674. The purpose of UYR1 and UYR2 circuits is to release the after the train is
received signals.
675. The purpose of ‘NA’ band contact across HR relay is to achieve cross
protection to HR relay .
676. The purpose of GECR contact in HR circuit is to avoid the bobbing of the signal
when the signal ahead is changing its aspects.
677. The purpose of JR back contact in HR circuit is to cancellation is not in progress
when the signal is being initiated.
678. To perform the function of lock bar, in power signalling track circuit & lever lock ll
be provided.
679. When a stop signal is taken off, the crank handle must be in locked condition.
680. In junction type route indicator, the maximum number of routes can be displayed
is seven .
681. In junction type route indicator, to energize UECR minimum three
nos. of route lamps must be in lit condition.
682. The maximum number of routes which can be indicated by using
stencil type route indicator is four.
683. Approach locking is provided for the goods loop starter.
Page 34 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
694. In home signal HR circuit points in the over lap must be proved.
696. In home signal HR circuit track circuit in the route must be proved.
697. In home signal HR circuit track circuit in the berthing portion must be proved.
698. In home signal HR circuit track circuit in the over lap must be proved.
699. In home signal HR circuit crank handle in and locked must be proved.
700. In home signal HR circuit route release relays dropped position must be proved
701. In home signal HR circuit route cancellation relays dropped position must be
proved.
702. In home signal HR circuit calling on signal below home signal not operated position
must be proved
703. In home signal HR circuit one signal one train feature must be proved.
704. In home signal HR circuit route lamps lit for diverging line must be proved.
705. In home signal HR circuit route lamps not lit for straight line must be proved.
706. In home signal HR circuit LC gate closed and locked condition must be proved.
Page 35 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
710. To ensure the signal ahead is not blank in the HR circuit of home, only Main line
starter HECR & DECR in parallel are proved.
711. The points in isolation must be proved in HR circuit of calling on signal.
712. All tracks in the route overlap and berthing shall be proved in home signal HR.
713. For shunt signal, the route locking is up to berthing track included.
714. For approach locking of loop line starter, the berthing track alone is proved.
715. Calling signal detects all the points, which the main signal above it detects
excluding the overlap points.
716. Generally Dead Approach locking is provided for a home signal of wayside station.
717. The CO signal will have that many numbers of routes as many overlaps available.
718. The CO signal locks the starter ahead and vice versa.
721. In panel interlocking, all signals except CO signal will have cancellation period of
120 seconds.
722. In panel interlocking for way side stations, the starter signal is provided with
cancellation period of 240 seconds.
723. It shall not be possible to insert the crank handle extracted from one group of
points in the point machine of any other group of points.
724. For cross protection of HR relay, UCR front contact is used.
725. On complete arrival of the train, SM normalized the signal knob but route not
released due to one of the back lock track failed, but SM reversed the gate control
knob and slot was sent to gate lodge with a time delay 120 seconds to open the
gate.
726. For home signal DR to pick up, it is sufficient that main line starter DR is in pick up
condition.
727. When economizer pushbutton is pressed to extract the crank handle, the lock coil
is energized only after dropping of CHLR.
728. When SM’s key is taken out, still it is possible to take off a signal from the panel.
729. In route setting type interlocking, when signal knob is reversed, the route setting
relay LR is energized to operate points to required position.
730. In RRI, point knob has to be kept in ‘C’ position, for automatic operation of points.
Page 36 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
731. In route setting panel interlocking with domino type panel with all buttons, two
common point group buttons are provided i.e. one for normal and other for reverse.
732. OVSR relay picks up automatically when run through signals are given and train
cleared berthing track.
733. LC gate opening is possible without any time delay, after complete arrival of train
but route not released.
734. In all buttons route setting type panel, the NNR drops the moment NRR picks up.
735. One signal one train movement is achieved through TSR circuit.
736. When SM locks the panel, RR dropping is prevented by SMCR front contact
bridging the knob reverse contact.
737. When signal is taken off the CHFR relay drops , thereby Crank handle is locked in
the EKT can not be taken out.
738. In ASR circuit indication, back & approach locking were proved.
739. For cancellation of a signal, JSLR picks up through its own ASR drop contact only
after the signal knob is normalized.
740. The track locking is proved in WLR circuit of a point.
741. With the help of one front contact maximum three repeater relays can be
energized.
742. OVSR relay picks immediately when the train clears the back lock tracks ,
occupies berthing track and stops at the foot of the starter.
743. UYRs are made slow to release because ASR picks up through UYRs up and
UYRs pick up through ASR back contact.
744. UCR front contact is proved in ASR so that ASR drops the moment route checking
is completed.
745. When the train arrives on the berthing track and stops at the foot of the starter, the
overlap cancellation takes place automatically and OVSR picks up after 2 minutes
time delay.
746. The calling signal locks the main signal above it.
747. when the signal is in taken off condition, if the SM turns LC gate controlling knob to
reverse, then the gate man can extract the LC gate key for the opening the gate.
748. In route setting panel interlocking, NNR picks up through the back contact of NRR,
the moment ALSR picks up.
749. When the ASR (proved in point WLR cct) drops, the WLR still can pick up and
point can be operated.
750. The GECR relay remains in pickup when any one of the aspects is burning in the
signal.
Page 37 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
752. In relay interlocking, the interlocking is checked at UCR, ASR & HR stages.
753. The two types of relay interlocking are Non route setting type and Route setting
type.
754. The two types of relay interlocking are panel interlocking and RRI.
755. The two types of interlocking are Non route setting type interlocking & panel
interlocking.
756. The two types of interlocking are route setting type interlocking and RRI
757. Track indications on the panel when track is clear and route set and locked is white
strip lights.
758. Track indication on the panel when track is occupied or failed is red
759. Track indications on the panel when the track is clear and route set locked is
yellow strip lights (LEDs)
760. Track indications on the panel when the track is clear and route set & locked is
green strip lights (LEDs).
761. when no route is set and no track failed the indications on the panel for tracks is
blank.
762. Point knobs used in RRI are of 3 position type.
763. In route setting type inter locking points are to be operated to correct position
before signal is taken off.
764. Non route setting type / panel interlocking the points are to be operated manually
before clearing the signal.
765. When UCR picks up , ASR concerned will be dropped either in PI or in RRI.
766. The points will be set automatically in RRI when signal button and route button are
pressed simultaneously.
767. In panel interlocking LR relay sets all the relevant points to the correct position
automatically.
768. The point switches used in route setting type inter locking will have three positions
i.e. N, C and R.
769. For automatic operation of points in RRI , the point knob has to be set to centre (
C ) position.
770. When the point switch 3 positions is kept in the centre ( C) position then both NC &
RC switch contacts are made to facilitate automatic point operation.
771. In case of Electronic Interlocking System, Non-Interlocking period is less
Page 38 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
775. By using Object Controllers Main signalling cables between Equipment Room
(Relay Room) and Location Box of field functions can be eliminated.
778. In Electronic interlocking system, executive software is common to all EI’s of same
company manufacturing the same model.
779. In Electronic interlocking system, executive software cuts off vital supply voltage to
output relays, in case of unsafe failures.
786. Non-Vital I/O cards are required in Microlok-II system only when the system is
required to be interface with conventional Control cum Indication Panel.
787. In Microlok-II system RS-485 ports are used for vital interface.
788. In Microlok-II system RS-232 ports are used for Non-Vital data interface.
789. In Microlok-II card file, maximum 20 nos. of Input / Output interface cards can be
accommodated.
790. In Microlok-II card file, CPU card occupies the space of 2 slots.
791. In Microlok-II card file, Power supply card occupies the space of 1 slot.
Page 39 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
792. In Microlok-II CPU card is provided with FLASH ROMs / EEPROMs for storing the
executive and application software.
794. In Microlok-II, each address select PCB jumper settings are unique and shall
match with the definition of cards in application program.
795. In Microlok-II card file, keying plugs prevents plugging of wrong type of card.
796. In Microlok-II, address select PCB is used to address particular slot of the card
797. The EEPROM PCB is placed on the 48 Pin connector of the CPU card to store
Site-specific configuration data.
799. Main Signalling Cable can be totally eliminated with Microlok-II as a Distributed
Interlocking System.
800. For a 4-road station with Microlok-II as a Distributed Interlocking is costlier over
Microlok-II as a Centralised Interlocking system.
801. The SIMIS S basic system meets the Generic CENELEC SIL3 safety standards.
802. The SIMIS-S is following the coded mono processing as TWO 1-out-of-1
processors in standby configuration.
803. In SIMIS S System, Reaction time of less than 1.5 seconds for showing a
restrictive aspect after a hazardous event occurs.
804. SIMIS S System behavior is Fail-safe, if failures occur within the system or the
operating modules
Page 40 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
809. In SIMIS S System, Digital Input Modules (Vital) and Digital output Modules (Vital)
are provided with hot swapping feature.
810. In SIMIS S System, Provides Interface between the profibus and I/O modules in an
Electronic Terminal station.
811. Electric lever lock is used where mechanical control on a electrical equipment is
required.
812. Maximum THREE slides can be placed in the EPD.
813. C and D detection slides of EPD are not inter-changeable where as siemens point
machine are inter-changeable.
814. When in and out type of FPL is used then A type lock slid shall be used in EPD.
815. When in and out type of FPL is used then B type lock slid shall be used in EPD.
816. When RKT key is to be transmitted then 1,2 & 3,5 contacts are in make
condition.
817. When point is set and lock in reveres then RC & RD contact will makes.
818. When point is not set and lock in normal then RC & NC contact will makes.
819. When point machine switching unit is taken out then RD & ND contact will makes.
823. Function of top roller and bottom roller of Siemens point machine switching
assembly is detect setting of switches and locking of switches respectively.
824. IRS point machine contains total four detection and control contacts.
826. Siemens point machine friction clutch adjustment should be done at site.
827. When point is in mid position all control and detection contacts are in made
position in Point machine.
828. The normal condition of “K” and “H” contacts in Signal machine circuit is open.
Page 41 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
831. The motor of IRS and Siemens point machine are interchangeable
832. Electrical parameter of The motor of IRS and Siemens point machine are same
833. Thrust of The of IRS and Siemens point machine are same
835. Block back is a message given to the driver to enter into block section
836. The wring of Normal & Reverse polarity instrument are Identical in Neal’s Token
Instrument
837. Double line Block instrument should have 2 indicator only
838. Double line Block instrument can be used for single line working
840. In DLBI all the Block operation are done at sending end.
845. The object of providing Block Instrument is to prevent more than one train in a
block section at a time
846. Absolute Block working is to maintain space internal between two trains
847. The Driver is a Absolute Block working should not enter into the Block section
without proper Authority
848. Token is handed over to the driver of a train as an authority to proceed
849. At a time max no of tokens extracted from a pair of Block instruments are 2 No s
850. To connect pair of NBT instrument we require 2 lines wire and earth return
851. On a single line where trains work under absolute Block system every train in its
progress from one block station to next shall be signalled over the block
instruments
Page 42 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
852. Inserting the token into the block instrument indicate that the train is in his
custody/train reached safely by the S.M
853. I R S Drg No for Neal’s ball token instruments is SA 20701/M
856. Different hole configurations are provided to distinguish the token belonging to
block instruments of different block section
857. SM’s key when ‘out’ in NBT will mechanically lock the bottom (operating) handle
and Top Handle only
858. Top handle can only be locked in its position at 85 from the vertical
860. We can turn the top handle upto a maximum of 180 when token is not inserted
862. LSS control key can extract only in TGT Position of B/H
863. When tokens are available in the instrument it is possible to turn the block handle
to TCF
864. When tokens are available in the instrument it is possible to turn the block handle
to TGT
865. Safety catch allows declutching of commentator shaft from spring clutch shaft
while turning the handle from line close to TCF/TGT
866. Lubrication is done with Axle oil medium grade to IS: 1628
867. Checking the polarity of NBT instruments is done by not less then superior grade
(JE)
868. Adequate Distance is the distance sufficient to ensure safety
869. 6 types no: of types of block workings are existing in Indian railways
Page 43 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
881. Time Release Indicator operated during push back normalisation of the Block
Instrument
882. Time Release indicator displays green with locked and changes to white with free
when operated.
883. Switch S2 is used for cancellation of line clear
888. TOL indicator displays red indication with ‘train on line’ before the train enter into
block section
889. PB1 used to transmit DC Pulses for exchanging bell code signals
890. PB2 is a push button used in conjunction with PB1 to transmit frequency
modulated code
891. Movement of the handle to TCF, TGT and back to normal position from TCF or
TGT is controlled by a electrical lock
892. For turning the handle to TGT the lock is initially energises at X position but gets
force dropped before X’ and it attracts at X’ position for further movement to TGT
893. Check locking is provided to ensure the conscious co-operation of the operator at
the other end
894. Check locking is effective while turning the handle from
TGT to Normal
Page 44 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
895. Block handle assembly consist of 24 sets of spring contacts actuated during the
cause of handle operation
896. Buzzer BZ1 operates when in a train enters block section
897. Buzzer BZ1 operates when a train clears the block section
900. SM’s key when removed the Instrument is inoperative for all functions
901. SM’s key when removed it is possible for the reception of bell code signal or
reception of transmission of TOL code
902. Shunt key can be removed only in line closed or TGT position
905. If the shunt key is removed the Instrument handle in locked mechanically
906. If the shunt key is removed the instrument handle is locked electrically
907. Insertion and extraction of shunt key can be done with out SM’s key in the
Instrument
908. Transmitter gives a FM output when the DC feed us connected to
it by different selection
909. The modulating frequency is selected by the transmitter according to the condition
of the Block Instrument
910. Receiver gives DC output for energising either CR1 or CR2 irrespective of the
modulating frequency of the code received
911. The receiver is switched on when the DC feed is connected through the relevant
selections
912. Level adjustment switch is a three position switch associates with the Receiver
913. The level of the signal output of the transmitter can be adjusted by level
adjustment switch
914. Attenuator associates with the transmitter
915. Attenuator can be set to introduce the required db loss on the received signal
Page 45 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
917. PBPR energised when PB1 is pressed when TOLR relay is energised
with Block handle in ‘R’ position
918. PBPR when energised connects to line battery –ve & +ve on L1 & L2
Respectively
919. PBPR when dropped connects NR relay to line
926. TELR is energised when the pressed switch of hand micro telephone is pressed
927. TELR connects to telephone current to the line through its back contact
928. TELR isolates transmitter and receiver from lines as they are connectedto lines
through its back contact
929. 3R is line clear cancellation Relay
930. 3R picks up after about 120 seconds on operating switch S1 during cancellation of
line clear
931. TRSR sticks in the LX’ position of the operating handle
932. TRSR release when the train passes last vehicle Track circuit
933. TOLR picks up only before CR2 picks up at train receiving station
934. TOLR operated when the train occupies the first vehicle track circuit when the
operating handle is in TGT position.
935. TER operates when switch S1 is operated
936. TER operates when switch S1 is operated and LSS controls Normalised
939. CR2 energises TOLR in the other end instrument during TOL code Transmission
941. The Normal coil of TOLK is energised through back contact of TOLR
942. To Release coil of TOLK is energised through XX’ and YY’ contact
of Block handle
943. ASR and HSR are conflicting Relays in FM Instrument
944. ASR picks up when block handle is in TCF position with TRSR energised
945. The front contact of ASR controls the feed to the LSS
(True/False)
946. To pick up ASR, TRSR front contact is required
947. Bell circuit is having two parallel path one with BLR front contact
another with NR Back contact
948. Back contacts of CR1 and CR2 relays have been proved to
ensure that ‘PBPR’ relay will not be energised while receiving
modulated frequencies
949. To Ensure that relays NR and BLR are not picked up simultaneously front contact
of NR relay is proved in BLR circuit
950. Back contact of ‘PBPR’ and front contact of PBPR are proved in
DC feed circuit of TX and RX respectively
951. Front contacts of CR1 & CR2 have been proved into DC feed circuit for transmit to
ensure that no code except the code of bell signals can be generated unless the
code relays are de-energised
952. Since TOL to be transmitted automatically, front contact of PBPR is not provided
in DC feed circuit to the Transmitter
953. Receiver to be in readiness to receive the TOL code the DC feed circuit is taken
via 2R relay block contact with the block handle at R position
954. Press contact of the PB2 in the DC feed circuit of the transmitter prevent DC feed
to TX while acknowledging TOL code
955. Block handle contact BX and DY are included in the DC feed circuit to the receiver
minimises the battery consumptions
956. SM’s key contact has not been proved in the DC feed circuit of
Transmitter to ensure that the TOL indicator will display immediately to block
section is occupies irrespective of the position of SM’s key
957. Cross protector to the lock magnet coil is given through CR1 and
CR2 front contact
Page 47 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
958. TX and RX are connected to line through the back contact of ‘TELR to ensure
that during conversation on telephone no code in transmitted or received by the TX
& RX respectively at either end
959. The telephone set is connected to the lines through to front contact of TELR
960. The TELR feed is taken through to back contact of CR1 & CR2 andTOLR to
ensure that during transmission and reception of TOL code to telephone is
disconnected
961. The front contact of TOLR is included in the TELR pick up circuit to ensure that
the telephone circuit is disconnected the movement
TOLR picks up to transmitter or receive TOL code
962. TOLR is made slow to release since its energising circuit is through the front
contact of TRSR and stick circuit is through back contact of
963. TRSR is made slow to release to provide the conditions required for the energises
circuit of TOLR in which the front contact of TRSR and back contact of FVTPR
included
964. Switch S1 Reverse contact has been included in the ASR circuit
972. Pressing TGB and BCB at train sending station transmits ‘Train going to ‘ to the
instrument at the other end
973. After the Instrument at the receiving end in set to TCF & TGT code is transmitted
back to train sending end
974. When train arrives operation of push button BCB & TCB simultaneously at the
receiving end reraly in transmission of the Line closed code to the train sending
end instrument
975. The user had to provide EKT instruments for shunt key and stop/catch siding
control key where required
Page 48 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
976. TOL or Free indication lit on establishment without the requirement of BCB or
panel lamp Button pressed
977. The Non co-operative feature is destroyed by locking up of the instrument
980. To cancel ‘Train going to’ condition before the train enter the block
section BCB & LCB must be operated at both station concurrently
981. Set the Block instrument to line closed when the train pushes back to the
dispatching station BCB & LCB must be operated at sending station concurrently
982. All operational codes are transmitted only when LCB or TGB is presses with BCB
at the transmitting station
983. ‘Train on line’ Buzzer operates only at the receiving station
984. Train on line code is suppressed by the sending station by keeping the pressed
TGB
985. SNR proves the Normal position of all the signals and their control levers/knobs
pertaining to that block section
986. Picking up of SNR indirectly proves that shunt key and slip/catch
siding keys are out position
987. SNR picks up by pressing BCB along with TGB/LCB buttons
991. Though feed to other relay from the external circuit is available it does not pick up
however SNR indication is available
992. TAR picks up through external battery
993. TAR de-latches to Normal through line battery once the instrument assumes to
line closed position
994. ASTR picks up once FVT is actuated
995. Dropping of ASTR in TGT position initiates transmission of Automatic TOL code
996. ASTR picks up and stock while initiating push back normalization
997. Non Energization of this relay will not permit the instrument to change to TGT
Page 49 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
even on receipt of answer back TGT code
998. TCKR at transmitting and CRR relay at receiving end are in series through to line
with the line battery at the transmitting end
999. In the line circuit at the receiving end RCKR front contact is proves
1001. Generator and transmission of a pulse is done at the transmitting end while the
terminator of a pulse are ordered by the circuit at the receiving end
1002. RCKR prepares the instrument for automatic answer back
1003. CTR by its state of energization or deenergization decides whether the instrument
is receiving or transmitting respectively
1004. CTR relay front contact the line battery to lien while its back contact connect
CRR(R)/CRR (R) to line
1005. LCCPR drops when line closed code is received from line
1006. Picking up to LCCPR enables to TGTR or TCFR to release and switches on CTR
for answer back when necessary
1007. LCCPR allows line closed code transmission as an automatic reply code
only when to enquiry code is line closed code and _____________
1008. PTR & NTR are used respectively to connect –ve /+ve of the line battery on line at
the transmitting instrument
1009. LR is the relay that is reacted on front by CRR(R) or TCKR while the instrument is
receiving or transmitting respectively
1010. Zener Diode is provided across the condenser of 3CR relay to have a contact time
delay irrespective of the voltage variation
1011. 1 CR os having toe branches one with TCKR and other with RDR respectively
effective during transmission and reception of code
1012. PZR & NZR _____ the polarity of the front pulse of code that is received
1013. When the SM acknowledges the TOL code by pressing BCB to transmit a bell
code to TOLAR at the sending station __________ and causes
TOLTR drop to stop the transmission of TOL codes
1014. PCR picks up at the end that initiates line closed operation
1015. TGTR picks up on successful reception of TCF code and releases when line
closed code is received
1016. TCFR picks up when TCF code is received and releases on reception of line
closed code
1017. ASCR picks up and locks the signal when cancellation is initiated
Page 50 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1019. Train shunt Resistance (TSR) is directly proportional to the Relay voltage.
1020. Ballast resistance (RB) is directly proportional to the length of the Track circuit.
1021. Dead section on the point zone shall not be more than 1.8 m (6’) for B.G.
1022. The value of the regulating resistance used in the D.C track circuit in AC RE area
is 0-30Ω (adjustable)
1023. Minimum permissible Ballast resistance of a D.C track circuit in Block section shall
be 2 Ω/ K.M
1024. Minimum permissible value of TSR for a D.C track circuit shall be 0.5 ohms.
1025. Maximum length of DC Track Circuit in AC RE area using QBAT is 750 m with B
type choke at both ends.
1026. The maximum limit of voltage drop across DC track relay of QTA2 is up to 300% of
its pick up value.
1027. The total stray current as measured, shall not exceed 10 milliamps if the length of
the track circuit is less than 100metres.
1028. The total stray current as measured, shall not exceed 100 milliamps if the length of
the track circuit is more than or equal to 100metres.
1029. Stray voltage shall not be more than 100mv irrespective of length of track circuit.
1030. The insert to insert resistance of a sleeper should not be less than 500 ohms
1032. Insulation Resistance Testing of Glued Joints is done with 100V DC Megger.
1033. Insulation Resistance of a glued joint in Dry condition shall not be less than 25 MΩ
when a meggering voltage of 100V DC is applied across the joint.
1034. Insulation Resistance of a glued joint in wet condition shall not be less than 3 KΩ.
1035. The measured TSR value of a track circuit should be always higher than the
minimum TSR of 0.5 ohms.
Page 51 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1037. Minimum permissible ballast resistance out side station yard is 1 Ω/Km
1038. Track Relay used for track circuit length up to 100 m is 2.25 Ω
1039. Track Relay used for Track Circuit length more than 100 m is 2.25 Ω
1041. Regulating resistance (Round Type) used in DC track circuit of Non-RE area is 0-
15 Ω.
1044. When TPR drops, it indicates that the Closed Track Circuit is not occupied by the
train.
1045. Transverse Bonds are provided between Positive Rails in DC Single Rail Track
Circuit.
1046. Transverse Bonds are provided between Negative Rails of adjacent DC single rail
track circuits.
1047. Rail Resistance is directly proportional to the length of The Track Circuit.
1048. Rail Resistance shall not exceed 0.5 Ω/Km., if Track Circuit Length is more than
700 m.
1049. Rail Resistance shall not exceed 1.5 Ω/Km., if Track Circuit Length is less than
700 m.
1050. Under minimum Ballast Resistance condition, for the QBAT Track Relay, voltage
across the track relay shall not be less than 125% of its Rated Pick UP Value.
1051. Under minimum Ballast Resistance condition, voltage across the track relay shall
not be less than 125% of its Rated Pick UP Value except for QBAT.
1052. The insert-to-insert resistance of a PSC sleeper should be more than 500Ω for use
in D.C track circuit.
1053. When drop shunt test is done with 0.5ohm resistance the relay voltage should not
Page 52 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
be more than 85% of drop away voltage.
1054. As per SEM the availability of GFN liners should be ensured up to 97% for proper
working of DC track circuit.
1055. Where Ballast conditions are poor, AFTC of more than 450m length should be of
the centre fed version.
1056. Where Ballast conditions are poor, AFTC of less than 450m length shall be of the
end fed version.
1057. Siemens FTGS track circuits are not coded track circuits.
1058. ‘S’ bonds are used where Siemens AFTC is followed by ALSTOM AFTC.
1059. If ALSTOM AFTC is followed by ALSTOM AFTC, ‘S’ bonds can be used.
1062. In SIEMENS AFTC, 8 different types of data signals are available for each carrier
frequency.
1063. In SIEMENS AFTC, receiver-I card checks received signal amplitude and
frequency
1065. Transmitter card of SIEMENS AFTC is a frequency dependent card i.e. separate
card is required for each frequency.
Page 53 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1076. Audio Frequency Track Circuit can be a Joint Less Track Circuit except in Point
Zone Track Circuit.
1079. In ALSTOM AFTC, only three different types of data signal are available for each
carrier frequency.
1080. DTC-24 is suitable for long length track circuits
1081. Train shunt Resistance (TSR) is directly proportional to the Relay voltage.
1082. Ballast resistance (RB) is directly proportional to the length of the Track circuit.
1083. Dead section on the points zone shall not be more than 1.8 m (6’) for B.G.
1084. The value of the regulating resistance used in the D.C track circuit in AC RE area
is 0-30Ω (adjustable)
1085. Minimum permissible Ballast resistance of a D.C track circuit in Block section shall
be 2 ohms per k.m.
1086. Minimum permissible value of TSR for a D.C track circuit shall be 0.5 ohms.
1087. The distance between two cross bonds shall not be more than 100m, used in D.C.
track circuit used in AC RE area.
1088. The minimum length of a D.C track circuit is 26 meters (2 rail lengths) normally.
1089. Insulation resistance of a glued joint shall not be less than 3k ohms in wet
condition When meggered with 100 V D.C Megger.
1090. Transverse Bonds are provided between negative rail to negative rail, in continous
single rail D.C track circuit zone
1091. Maximum length of DCTC in RE using QBAT is 750 mtrs.
1093. ‘B’ type choke is to be provided in DCTC is of 120 ohms impedance and 3 ohms
resistance.
Page 54 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1094. Two sets of Tx / Rx coils are required at one detection point to establish the
direction of traffic.
1095. Transmitter coils are always connected inside the rail
1096. Preparatory reset prepares to reset the axle counter and ensures that the SM/ASM
pilot the train.
1097. In preparatory reset, after resetting, axle counter continues to show occupied until
one train movement in the section carries out correct balancing of track section.
1098. In UAC, both the Transmitter coils are connected in Series.
1099. In analog axle counter, the receiver output signal due to passage of train is an
amplitude modulated signal.
1100. In axle counter for each axle passing over detection point causes a ‘dip’ in the
receiver signal.
1101. In universal or multi entry axle counter evaluator consists of 8No.s of cards
including Power Supply card.
1102. Main purpose of trolley suppression track circuit is to prevent the conversion of
pulses from the dip caused by trolley wheel.
1103. In Universal Axle counter, the transmitter signal frequency is 5 KHz
1104. In Universal Axle counter, with one evaluator unit maximum 8 detection points can
be connected.
1105. Trolley suppression track circuit is provided in card no. 4 for ABCD channels.
1106. Trolley suppression track circuit is provided in card no. 5 for EFGH channels
1108. Channel voltage after attenuator pads of card no 1 &2 is 105mv AC.
1110. Transmitter & Receiver cables should be put in HDPE pipe for safety and laid at a
depth of >1 meter from bottom of rail.
1111. Axle counter Transmitter cables and receiver cables of individual track devices can
be laid in same pipe.
1112. In CEL single section digital axle counters, event logger card is optional with each
set of axle counters used for monitoring the one track section.
1113. Phase reversal modulation technique is used in digital axle counters to avoid the
trolley suppression track circuit.
1114. In SSDAC of CEL make, SCC-1 generates the frequencies of 21KHz carrier
Page 55 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
signals, which is transmitted to 1ST set of Tx coils.
1115. In SSDAC of CEL make, SCC-2 generates the frequencies of 21KHz carrier
signals, which is transmitted to 2nd set of Tx coils.
1116. In SSDAC of CEL make, when the train wheel passes over the axle detectors, the
Rx signal gets phase modulated.
1117. In SSDAC of CEL make, the SCC conditions the modulated signal and
demodulates it to generate valid train pulses.
1118. Amplitude modulation technique is used in digital axle counters to avoid the trolley
suppression track circuit.
1119. SSDAC- ELDYNE (AzLS) is containing 2 out of 2 micro-controllers to count the
axles, establish the track occupancy of a track section.
1120. The AzLS, consisting double rail contact Sk30H and an electronic unit.
1121. In AzLS, Analog card of Electronic Unit generates Tx signal, Amplifies Rx signal,
does phase sensitive rectification and also generates wheel pulse of MESSAB and
RADIMP.
1122. In AzLS, Digital card of Electronic Unit Counts wheel pulse, Determines RCD,
Supervises Rail Contact, Codes telegrams.
1123. AzLS can be configured as a single section axle counter with one Rail Contact
(RC) and Electronic Control Unit (EAK) combination at both ends of the section
and with a two-wire fault tolerant link (FTL) between the two.
1124. In AzLS, additional Digital PCB or evaluator card is not required to be used at the
common detection point (EAK).
1125. AzLS could be configured in a double section application including point zone
application.
1126. Axle detectors do not detect push trolley with 4 / 6 / 8 spokes.
1127. In CEL MSDAC, Each field unit is connected to Central Evaluator on half Quad
cable in Star Configuration.
1128. Supervisory Card in UAC identifies the direction of Train movement.
1130. Duplicate In Counts & Out counts are Generated by Logic Card
Page 56 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1135. Only one Pulse shaper card ( card 3 ) has Trolley suppression in UAC
1137. We can monitor the health of remote SSDAC unit with Event logger card.
1138. High pass filter is used in Pulse shaper card to filter Noise
1139. Ist unit of SSDAC sends power supply to second unit over PDCU
1145. If entry end of SSDAC has TX1, TX2 then exit end has TX2 TX1 in the direction of
travel.
1146. In preparatory reset, as soon as SM presses button signal can be taken off.
1147. In MSDAC, all EJBs can communicate with each other directly.
Page 57 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1162. Duplicate In Counts & Out counts are Generated by Logic Card
1168. Only one Pulse shaper card ( card 3 ) has Trolley suppression in UAC
1170. We can monitor the health of remote SSDAC unit with Event logger card.
1171. High pass filter is used in Pulse shaper card to filter Noise
1172. Ist unit of SSDAC sends power supply to second unit over PDCU
1179. As speed increases, the distance between Block Joint to Detection point may be
decreased for trolley
Page 58 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1189. If entry end of SSDAC has TX1, TX2 then exit end has TX2 TX1 in the direction of
travel.
1190. Incrementing / Decrementing is done in UAC.
1193. One section with SSDAC has ______ Nos of vital relay (s)
1199. In preparatory reset, as soon as SM presses button signal can be taken off.
1201. In MSDAC, all EJBs can communicate with each other directly.
Page 59 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1214. Data logger records data of analog signals & digital signals.
1216. For making reports, printing of data is possible locally as well as at centralized
place
1217. Relay data is stored with respective to date and time in the datalogger system,
only when there is a change in status of the relay.
1218. In networking of Dataloggers modems are required to be provided.
Page 60 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno True Or False
1225. With the help of datalogger, Train Signal passing at Danger events may not be
analysed.
1226. With the help of datalogger, Speed of a Train can be analysed
1228. With the help of datalogger, power supply fluctuations can be analysed
1229. In AWS, opto coupler card senses the aspects information of signal and connects
the same to track magnet.
1234. ACD prevents train collision in the mid section and station sections.
1237. In ACD, UHF radio modem communication is used for tracking the train.
1240. Alerting the driver and regulating the train speed to 25KMPH, when it detects
(through the Loco ACD of other train) that it has stopped in mid-section.
1241. TPWS facilitates to run the train at maximum permitted speed by providing the
indication to the driver 500 meters in advance of signal.
1242. TPWS facilitates to run the train at maximum permitted speed by providing the
indication to the driver 500 meters in advance of signal.
1243. TPWS facilitates normal operation of train in dense foggy condition where visibility
is near zero.
Page 61 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
1. The block overlaps and signal overlap in Multi aspect signal are _____________
& ____________ respectively.
a) 180 Mt b) 400 Mt c) 120 Mt d) 300 Mt
6. If distant signal in single distant territory display proceed aspect then it indicates-
----------
a) Run through on main line b) Run through on loop line
c) Train is going to be received on Main line d) all a,b &c
11. A catch siding shall be provided if the gradient stepper than 1:80 in near vicinity
of station and falling --------------
a) Away from station. b) Towards station c) Towards block section d) all a,b
&c
12. A slip siding shall be provided if the gradient stepper than 1:100 in near vicinity of
station and falling --------------
a) Away from station b) to words station
c) To words block section d) all a,b &c
13. If a semiautomatic stop signal is protecting LC gate as well as point then ----------
- shall be provided on the post.
a) ‘A’ marker b) illuminated ‘A’ marker c) ‘AG’ marker d) b&c
14. When the shunt signal and calling on signal is provided below stop signal then
sequenced from top is ---------------------------------- signal.
a) First calling on then shunt b) first shunt and then calling on c) Not
possible d) any of a, &b
Page 63 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
15. Aspects in distant signal in double distant signal territory is/ are
a) Attention b) a &c c) proceed d) caution
16. The passenger warning board shall be provided 1 Km in rear of ------------ signal.
a) Home b) first stop c) routed home d) nun of above
17. The section Gate under absolute block system shall be provided with -------
marker.
a) ‘G’ b) ‘AG’ c) ‘PG’ d) ‘A’
18. If two automatic block section and overlap ahead of an automatic signal is clear
of train then it will display --------------- aspect
a) Attention b) a OR d c) stop d) caution
19. The block overlap in class ‘C’ station provided with colour light signal is---------
a) 180Mt b) 400Mt c) 120Mt d) 580Mts
21. If speed is less than 15 KMPH then ------------- type route indicator shall be
provided.
a) Directional b) stencil c) multi lamp d) any one of three
22. Single Wire lever frame classified as
(a) 3 types (b) 2 types (c) 4 types
23. Length of the direct lever (SA 530) is
(a) 1455mm (b) 2275mm (c) 1980mm
24. Pitch of the Direct lever is
(a) 100mm (b) 125mm (c) 150mm
25. Angular Through of the Direct lever is
(a) 33 deg. (b) 52 deg. (c) 27 deg.
26. Stroke of the Tappet in Direct lever is
(a) 346mm (b) 277mm (c) 65mm
27. Pitch of the Channel in Direct Lever (SA-530) frame
(a) 110mm (b) 70mm (c) 63.3mm
28. Width of the Channel in Direct Lever (SA-530) frame
(a) 55mm (b) 70mm (c) 40mm
29. Max.No.of interlocking Bar in Direct Lever (SA-530) frame
Page 64 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
(a) Top=3, Bottom=3 (b) Top=3, Bottom=2 (c) Top=2, Bottom=2
30. Max.No.of channels in Direct Lever (SA-530) frame
(a) 5&8 (b) no limit (c) 2 &4
31. Bay in Direct Lever (SA-530) frame
(a) 8 or 10 (b) 1,2,3,4,5, 6 (c) 5 or 7
32. Length of the Catch handle (SA 1101) is
(a) 1455mm (b) 2275mm (c) 1980mm
33. Pitch of the Catch handle (SA 1101)
(a) 150mm (b) 125mm (c) 100mm
34. Angular Through of the Catch handle (SA 1101) is
(a) 33 deg. (b) 52 deg. (c) 27 deg.
35. Stroke of the Tappet in Catch handle (SA 1101) is
(a) 346mm (b) 277mm (c) 65mm
36. Pitch of the Channel in Catch handle (SA 1101) frame
(a) 110mm (b) 70mm (c) 55mm
37. Width of the Channel in Catch handle (SA 1101) frame
(a) 55mm (b) 70mm (c) 40mm
38. Max.No.of interlocking Bar in Catch handle (SA 1101) frame
(a) Top=3, Bottom=3 (b) Top=3, Bottom=2 (c) Top=2, Bottom=2
39. Max.No.of channels in Catch handle (SA 1101) frame (a) 5&8 (b) 2&4
(c) no limit
40. Bay in Catch handle (SA 1101) frame
(a) 8 or 10 (b) 1,2,3,4,5, 6 (c) 5 or 7
41. Length of the Ground lever
(a) 1455mm (b) 2275mm (c) 1980mm
42. Pitch of the Ground lever
(a) 150mm (b) 125mm (c) 100mm
43. Angular Through of the Ground lever
(a) 33 deg. (b) 52 deg. (c) 27 deg.
44. Stroke of the Tappet in Ground lever
(a) 346mm (b) 277mm (c) 65mm
45. Pitch of the Channel in Ground lever frame
(a) 110mm (b) 63.3mm (c) 55mm
46. Width of the Channel in Ground lever frame
(a) 55mm (b) 70mm (c) 40mm
47. Max.No.of interlocking Bar in Ground lever frame
(a) Top=3, Bottom=3 (b) Top=3, Bottom=2 (c) Top=2, Bottom=2
48. Max.No.of channels in Ground lever frame
(a) 5&8 (b) 2&4 (c) no limit
49. Bay in Ground lever frame
(a) 8 or 10 (b) 1,2,3,4,5, 6 (c) 5 or 7
Page 65 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
50. To alter the stroke to the required magnitude
(a) Relief Crank (b) Adjustable Crank (c) Vertical Crank
51. It will convert vertical movement into horizontal movement.
(a) Accommodating Crank (b) Adjustable Crank (c) Vertical Crank
52. First crank used in a rod transmission (a)
Accommodating Crank (b) Horizontal Crank (c) Vertical Crank
53. Adjustable sleeve in Adjustable Crank can be shifted in steps of
(a) 10mm (b) 12mm (c) 15mm
54. Last crank used in rod transmission
(a) Adjustable Crank (b) Horizontal Crank (c) Vertical Crank
55. To adjust the required stroke ----- crank is used
(a) Accommodating Crank (b) Adjustable Crank (c) Vertical Crank
56. Solid rod dia.
117. Specific gravity of the fully-charged Lead Acid cell is ________ in terms of
Hydrometer reading.
A) 1180 B) 1200±5 C) 1210±5 D) 1240±5
118.Automatic Battery charger of 24V can charge maximum ______ no. of cells in
manual Mode
Page 69 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
A) 24 B) 12 C) 13 D) 14
119.Recommended current rating of Battery charger for charging 120AH Lead Acid
cell is _______________.
A) 12 A B) 24 A C) 30 A D) 40 A
120.For charging of 200 AH cells _____________ amp capacity charger is required.
A) 20 A B) 24 A C) 30 A D) 40 A
121.Boost charging voltage of the lead acid cell is ______
A) 2.2 V B) 2.3 V C) 2.4 V D) 2.7 V
122.Initial charging voltage of the lead acid cell is _________
A) 2.2 V B) 2.3 V C) 2.4 V D) 2.7 V
123.Float charging voltage of the Automatic battery charger (IRS: 86/200) is
adjustable from ________ per cell.
A) 2.12 to 2.3 V B) 2.2 to 2.3 V C) 2.12 to 2.4 V D) 2.12 to 2.7 V
124.For Chargers used for Axle counter installations, the r.m.s ripple shall be less
than______.
A) 10mV B) 50mV C) 100mV D) 200mV
125.Chargers used for Axle counter installations, the peak to peak noise voltage shall
be less than 50mV.
A) 10mV B) 50mV C) 100mV D) 200mV
126.Battery charger working in manual mode, the charger output voltage shall be
_____ V per cell.
A) 2.2 V B) 2.25 V C) 2.3 V D) 2.4 V
127.Battery charger generates low battery alarm when the battery voltage falls to
______ V per cell.
A) 1.95 V B) 2.0 V C) 2.2 V D) 2.25 V
128.Battery charger generates start DG set non-resettable alarm when the battery
voltage falls to 1.90V/cell.
A) 1.9 V B) 2.0 V C) 2.2 V D) 2.25 V
129.Battery charger isolates battery from the load when the battery voltage falls to
________V per cell.
A) 2.0 V B) 2.15 V C) 2.2 V D) 1.8 V
130. When cascading is used in aspect control circuit them signal lamp to be used
Page 70 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
is/are--------
a) SL18 b) SL21
c) SL35 d) a&c both
131. The signal lamp to be used in directional route indicator is/are ------------------
a) SL33 b) SL13
c) SL35 d) SL25
132. Locking provided in siemens and IRS point machine is ---------------- type.
a) Rotary b) straight trough
c) in & out d) clamp type
133. The signal lamp to be used in multi-lamp route indicator is/are ------------------
a) SL33 b) SL13
c) SL35 d) SL25
134. The signal lamp to be used in shunt signal (parallel) is/are -----------------
a) SL33 b) SL13
c) SL35 d) SL25
135. When point is not set , not lock OR both then ------------------ makes.
a) RC contact b) NC contact
c) RD contact d) a&b both
136. The signal lamp to be used in shunt signal (series) is/are ------------------
a) SL65 (60 voilt/25 watts) b) SL13
c) SL35 d) SL25
137. The signal lamp terminal voltage shall not be more than ------------- of rated
voltage.
a) 90% b) 98 %
c) 80 % d) 12 %
138. The rating of SL 21 signal lamp is-----------------------.
a) 12 volts 24 watts & 12 volts 16 watts
b) 12 volts 33 watts & 12 volts 16 watts
c) 12 volts 24 watts & 12 volts 24 watts
d) 12 volts 16 watts & 12 volts 16 watts
139. The effective focal length of combination of inner colour lens and clear outer lens
is -----
a) 17 to 21mm b) 140mm
c) 100mm d) 5mm
140. Lamp to be used in ON aspect of signal is/are
a) SL21 b) SL35A
c) SL35B d) a&c
141. The rating of SL 18 signal lamp is-----------------------.
a) 12 volts 24 watts & 12 volts 16 watts
b) 12 volts 33 watts & 12 volts 33 watts
c) 12 volts 24 watts & 12 volts 24 watts
Page 71 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
d) 12 volts 24 watts
142. When Distant in single distant territory displays proceed aspect then indicates
-----------------
a) Run through on main line
b) run through on loop line
c) Train going to be received on main line band.
d) a&c
143. Red lamp protection provided to-----------------------
a) Protect blank signal
b) prevent blanking of signal
c) Replacement of signal to ON
d) a & b both
144. -----------------------------------ECR can be used for LED AC signal
a) Conventional ECR
b) LED AC ECR
c) LED DC ECR
d) a , b &
145. Normal working voltage of LED signal unit is / are -----------------
a) 110 volt AC b) 110 volt DC
c) 230 AC d) a&b
146. The insulation resistance of signalling cable shall not less than-------------------
147. The proceed aspect is displayed in four aspect automatic section when
________ automatic sections ahead and overlap are clear.
a) 4 b) 3 c) 5 d) 2
148. The rating of SL 35 A signal lamp is-----------------------.
a) 12 volts 24 watts & 12 volts 16 watts
b) 12 volts 33 watts & 12 volts 16 watts
c) 12 volts 24 watts & 12 volts 24 watts
d) 12 volts 16 watts & 12 volts 16 watts
149. The signal lamps are triple pin lamp to avoid----------------
a) Lamp theft
b) out of focus after replacement of lamp
c) use for domestic purpose
d) loose grip
150. The no load current of signal transformer shall not be more than -------------------
a) 5 mAmp b) 15 Amp
c) 40 mAmp d) 15 mAmp
151. The rating of SL 35 B signal lamp is-----------------------.
a) 12 volts 24 watts & 12 volts 16 watts
Page 72 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
b) 12 volts 33 watts & 12 volts 33 watts
c) 12 volts 24 watts & 12 volts 24 watts
d) 12 volts 16 watts & 12 volts 16 watts
152. The power ratting of signal transformer is -------------------
a) 400VA b) 40VA
c) 4KVA d) 40KVA
153. The tapping on secondary side of signal transformer is/are -------------------
a) 13 volt b) 14.5volt
c) 16 volt d) a,b &c
154. When MECR & Signal transformer are placed in side two aspect unit then
number of cable conductors required in tail cable (with double cutting) are----------
------------
a) 10 b) 8 c) 12 d) 6
155. When Distant in double distant territory displays proceed aspect then indicates -
----------------
a) Run through on main line
b) run through on loop line
c) Train going to be received on main line b.
d) a&c
156. When inner Distant in double distant territory displays proceed aspect then
indicates ----------------
a) Run through on main line
b) run through on loop line
c) Train going to be received on main line band.
d) a&b
157. When Distant in double distant territory displays proceed aspect then indicates -
----------------
a) Run through on main line
b) run through on loop line
c) Train going to be received on main line b.
d) a&c
158. When inner Distant in double distant territory displays proceed aspect then
indicates ----------------
a) Run through on main line
b) run through on loop line
c) Train going to be received on main line band.
d) a&b
159. Which is not a function of UCR
(a) Locking of Point
(b) Verification of Points in Route
(c) Proving of Signal Knob in Reverse
Page 73 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
(d) Crank Handles IN
160. In Pt. WLR Ckt , Track Ckts are by passed by ____contact
161. WLR Does not pick Up if Point Detection (to desired position) is already
available
162. ---- Relays of Point Ckt Picks up only if Normal / Reverse Detection is broken
(a) WLR
(b) RCR/NCR
(c) NWR/RWR
163. ------ Relay`s ---- contact is used for Cross Protection across NWR / RWR relay
164. Siemens relays other name is -------------
A) k-50 B) k-60 C) k-59 D) k-69 E) none
165. Siemens relays specification is
A) IRS S46-76 B) IRS S47-76 C) IRS S46-77 D) IRS S76-
46 E) None
166. Siemens relays are ------------------------- type
A) Dependant B) independent C) separate
D) twin E) none
167. Siemens relays are --------------------- typ A) double
make double break B)spring C)contact
D) welding E)none
168. In Siemens relays there is no---------------------------contact
A) Front B) back C) arm D) metal E) none
169. in Siemens relays -----------pins are provided to prevent invert plugging
A) wide B)side C)hide D) guide E)none
170. --------------- action in Siemens relays is self cleaning.
A) Ripping B) fast C) slow D) wiping E) none
171. Pick up time in Siemens relays is -------------------
A) 5ms B) 75-80ms C) 15-20ms D) 25-60ms
E) none
172. Drop away time in Siemens relays is ------------------
A) 2-5ms B) 5-6ms C) 7-15ms D) 25-60ms E)
none
173. In Siemens neutral type relays -------------combination is available
A) 12f/4b B) 6f/2b C) 8f/8b D) 2f/6b
E) none
174. 6f/2b,4f/4b combinations are available in Siemens -------------------
A) ACI type B) ECR type C) clock type D) D type
E)none
175. In Siemens ACI type only -------- type is available
Page 74 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
A) 6f/2b B)5f/3b C) 4f/4b D)8f/8b E)none
176. In interlocked Siemens relays -------------combinations art available
A) 6f/2b B) 4f/4b C) 5f/3b
D) all given in A, B, C option E) none
177. In interlocked relay –---no contact is used as economizer contact
A) 11 B) 12 C) 13 D) 14 E) none
178. In interlocked type ------------- arrangement is provided to keep relay in pick up
condition
A) Mechanical B) electrical C) electronic
D) dynamic E) none
179. Interlocked relay is used for -------------------- circuit.
A) Conflicting B) series C) parallel
D) indication E) none
180. in interlocked type relays ------------coil is energized condition normally
A) top B) side C) up D) bottom E) none
181. In interlocked type relays ------------coil is de energized condition normally
A) Normal B) side C) reverse D) bottom E) none
182. ON ECR is used for --------------aspect
A) yellow B) green C) red D)white E)none
183. OFF ECR is used for ----------------aspect.
A) Yellow B) red C) blue D) on E) none
184. ON ECR contact combination is ------------- A) 6f/2b
B)4f/4b C)5f/3b D)3f/3b E) none
185. OFF ECR contact combination is -----
A) 6f/2b B) 4f/4b C) 5f/3b D) 3f/3b E) none
186. UECR contact combination is ----- A) 6f/2b
B) 4f/4b C) 5f/1b D) 3f/3b E) none
187. UECR is used for --------------aspect
A) Yellow B) green C) red D) route E) none
188. -----------pin combination is provided in Siemens relays to prevent
plugging of wrong relays A) guide
B) non magnetic C) residual D)coding E) none
189. in 5f/3b contact combination ---is back contact A) 11
B) 12 C) 13 D)14 E)15
190. in 5f/3b contact combination ---is back contact
A) 1 B) 2 C) 3 D) 4 E)11
191. in 5f/3b contact combination ---is back contact
A) 11 B) 12 C) 3 D)14 E)none
192. in 6f/2b contact combination ---is back contact
A) 11 B) 12 C) 13 D)14 E)15
193. In 6f/2b contact combination ---is back contact
Page 75 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
A) 1 B) 2 C) 3 D) 4 E) 5
194. Size of domino available in Siemens concept are
A)63mmx38mm B)83mmx68mm C) 45mmx34mm
D) 54mmx38mm E) none
195. Compartments given in domino are ---------
A) 11 B) 12 C) 13 D)14 E)15
196. Terminals provided in domino are -------
A) 12 B)14 C)16 D)18 E) none
197. -------- terminal carries neg of indication ckt
A) 3&8 B)8&13 C)16 D)15 E) none
198. Common aluminum plate is connected to terminal-------
A) 3&8 B)8&13 C)16 D)15 E) none
(A)Attention aspect control relay of signal No.5 (B) caution aspect controlling
relay of sig.No.5 (c) clear aspect control relay of sig.No.5 (D) None
359. 5 HGE Symbol indicates in signalling.
~
Symbol indicates the relay.
602. During IB Signal failure & Telephone failure, the driver of the first train after
waiting
a) At restricted speed b) Full speed
c) Intermediate speed d) None of the above
603. During IB Signal failure & Telephone failure, during Clear visibility the driver of
the first train after waiting proceeds at
a) 15 Kmph b) 8 Kmph
c) Normal speed d) None of the above
604. During IB Signal failure & Telephone failure, during Poor visibilitythe driver of the
first train after waiting proceeds at
a) 15 Kmph b) 8 Kmph
c) Normal speed d) None of the above
607. In IBS working when train passes IB Signal at ‘ON’, the ACZR relay
a) Picks up b) Drops
c) No change in its status d) None of the above
608. In UAC, input voltage to EJB and EV is ---------------
A) 12V & 24V DC respectively B) 110 V AC
C) 24V DC D) 12V DC
609. In UAC, DC-DC converter output voltages are ____, _____ & _______
+5 V, +12V, +12V(ISO) B) +5 V, -12V, +12V(ISO)
Page 106 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
C) +5 V, +10V, +10V(ISO) D) +5 V, -10V, +10V(ISO)
610. Preparatory reset can be used in case of the __________sections provided with
axle counters.
A) Main line
B) Section between Advance starter and IBS
C) Block Instrument and BPAC
D) all of these.
611. In Universal Axle counters, the minimum input channel voltage coming from EJB
required at Evaluator CTB is _____ mv AC.
A) 1000 B) 150 C) 175 D) 1500
612. In UAC, Oscillator card output voltage & frequency is _________
A) 60 VAC & 5KHz B) 30 VAC & 5KHz
C) 60VAC & 5Hz D) 30VAC & 5Hz
613. In UAC Receiver coil output voltage is __________
A) 0.7 to 1.0 V AC B) 60 VAC
C) 1.0 to 1.2 V DC D) 105 to 110mv AC
614. In UAC Transmitter coil current is ____________
A) 100 milli Amps B) 3 to 5 micro Amps
C) 420 milli Amps D) 420 micro Amps
615. In UAC Receiver card out put voltage is _______________
A) 1.2 to 1.5 V AC B) 60 VAC
C) 1.2 to 1.5 V DC D) 105 to 110mv AC
616. In UAC, Dip voltage measured at the Receiver output coil shall be not more than
------ of its normal value.
A ) 90% B) 10% C) 15% D) 85%
617. Minimum spacing between sleepers for fixing Tx / Rx is _______
A) 550 mm B) 200mm C) 800mm D) 400mm
618. Minimum length of Track circuit required for trolley protection on either side of a
detection point in single Line section is __________________ mtrs
A)5 Rail lengths B) 3 Rail lengths
C) 8 Rail lengths D) 9 Rail lengths
619. Relays used for EVR & SUPR are of ______________ neutral line relays
A) QS3 type & 12V DC B) QS3 type & 24V DC
C) QN1 type & 12V DC D) QNA1 type & 12V DC
620. For connecting the output of electronic junction box to evaluator, the following
cables are to be used depending upon the distance between the two and
whether to be used in R.E. or non R.E. Area.
A) 4 quad axle counter cable as per specification No. TC-30 for RE & TC-31 for
Non-RE
B) PET quad of main telecom cable as per specification No.TC-14/75
C)Polythene jelly filled telephone cable as per specification No.TC-41 /90.
Page 107 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
D) All of these
621. SSDAC used with block working, type of reset used is ________
A) Direct Hard Reset B) Conditional Hard Reset
C) Preparatory Reset D) Any one these can be used
622. In SSDAC of CEL make, card no 5 is _________
A) Modem Card.
B) Event Logger Card.
C) Micro controller Logic Board
D) Relay Driver Card.
623. In SSDAC of CEL make, card no 6 is _________
A) Modem Card.
B) Event Logger Card.
C) Micro controller Logic Board
D) Relay Driver Card.
624. In SSDAC of CEL make, card no 7 is _________
A) Modem Card.
B) Event Logger Card.
C) Micro controller Logic Board
D) Relay Driver Card.
625. In SSDAC of CEL make, card no 8 is ________
A) Modem Card.
B) Event Logger Card.
C) DC-DC Converter Card
D) Relay Driver Card.
626. In SSDAC of CEL make, card no 1&2 are _________
A) Modem Card.
B) Signal Conditioning Cards.
C) Micro controller Logic Boards
D) Relay Driver Card.
627. In SSDAC of CEL make, card no 3&4 are _________
A) Modem Card.
B) Signal Conditioning Cards.
C) Micro controller Logic Boards
D) Relay Driver Card.
628. In SSDAC of CEL make, _______ no. of conductors required for connecting two
SSDAC units.
A) 2 B) 4 C) 8 D) 10
629. Baud rate of modem card in SSDAC of CEL is --------------------------
A) 56KBPS B) 3000BPS
C) 300 BPS D) 9600BPS
630. In SSDAC of CEL make, the function of the Micro-controller Logic Board card is
Page 108 of 123
QUESTION BANK East Coast Railway
Objective Type Question S&T Department
Sno Multiple Choice
A) Wheel detection
B) Train direction is checking and Wheel counting.
C) Receives the remote wheel count and computes the status of the section for
clear or occupied.
D) all of these
631. In SSDAC of CEL make, Input voltage of the DC-DC converter Card is
A) 12V DC B) 110V AC C) 24V DC D) 110V DC
632. In SSDAC of CEL make, output voltages of the DC-DC converter Card is
A) 5V DC & 12V DC B) 5V DC & 24V DC
C) Both A & B D) None of these
633. Baud rate in SSDAC of ELDYNE (AzLS) is ----------
A) 56KBPS B) 3000BPS
C) 300 BPS D) 9600BPS
634. In AzLS, EAK consists of ____________
A) Back plane B) Evaluator board
C) Analog board D) all of these
635. Multi-section Digital Axle Counter system consists of ______________
A) Detection Point
B) Central Evaluator Unit and Reset Unit
C) Relay Unit and Event logger and diagnostic terminal
D) All of these
636. In MSDAC, Central Evaluator unit drives _______ Vital Relay in order to give
Free and occupied indication of an axle counter track section.
A) 24VDC, 1000 ohms Plug-in type
B) 12VDC, 1000 ohms Shelf type
C) 110VAC, 1000 ohms Plug-in type
D) None of these.
637. In CEL MSDAC, each Digital Axle counter field unit _____________
A) is configured as one Detection point.
B) Detects wheels and store counts based on 2 out of 2 logic.
C)Transmits count and health information to Central Evaluator.
D) All of these
638. In EFFTRONICS Datalogger, capacity of each Digital input card is ____ inputs.
A) 16 B) 32 C) 64 D) 512
639. In EFFTRONICS Datalogger, capacity of each Analog input card is _________
no. of analog channels.
A) 16 B) 8 C) 4 D) 2
640. In EFFTRONICS Datalogger, all Digital inputs are scanned at the rate of ______
m. sec.
1. LCPR DLBI
2. TCF & TGT Coil Resistance 148 Ohms
3. PR Relay 77 Ohms
2. Name the sixteen Zonal Railways and mention their Zonal Head quarters.
5. Calculate the amount of Security deposit for a Works Contract of value Rs. 2.25
Crores. What are the acceptable forms of Security deposit?
THE END
Version: 1.0