Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)

Configurable temperature transducer for the connection of 2, 3, and 4-conductor resistance thermometers
and resistance-type sensors. Can be configured via DIP switches or, with extended functionality, using the
software. Screw connection, standard configuration.

Product Description
The configurable temperature transducer with 3-way isolation is suitable for the connection of resistance thermometers and remote resistance-type
sensors with 2, 3, and 4-conductor connection technology.
The measured values are converted into a linear current or voltage signal.
You can configure the device using one of the free software solutions. Default settings can also be made directly on the device by simply using the
DIP switches (see configuration table). The measuring transducer supports fault monitoring.

Key Commercial Data


Packing unit 1 pc

GTIN

GTIN 4046356689205

Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area

Dimensions
Width 6.2 mm
Height 93.1 mm
Depth 101.2 mm

Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
08/05/2021   Page 1 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Technical data
Ambient conditions
Degree of protection IP20
EN 61000-6-2 When being exposed to interference, there may be
Noise immunity
minimal deviations.

Input data
Configurable/programmable Yes
Sensor types (RTD) that can be used Pt, Ni, Cu sensors
0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected
Linear resistance measuring range
measuring range)
Sensor input current approx. 200 µA
-200 °C ... 850 °C (Range depends on sensor type, range can be set
Temperature measuring range freely via software or in increments from -150°C to 850°C via DIP
switches)
Connection technology 2-, 3-, 4-conductor

Output data
Number of outputs 1
Configurable/programmable Yes
Voltage output signal 0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. output voltage approx. 12.3 V
Max. output current 24.6 mA
Load/output load voltage output 10 kΩ
Load/output load current output 500 Ω (at 20 mA)
Ripple < 20 mVPP
< 20 mVPP (at 500 Ω)

Power supply
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
Supply voltage range
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Typical current consumption < 27 mA (at 24 V DC)
Power consumption ≤ 700 mW (at IOUT = 20 mA, 9.6 V DC, load 500 Ω)

Connection data
Connection method Screw connection
Stripping length 12 mm

08/05/2021   Page 2 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Technical data
Connection data
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12

General
Transmission error resistance thermometer 0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)
Transmission error resistance-type sensor 2Ω
Maximum temperature coefficient 0.01 %/K
Status display LED red
Protective circuit Transient protection
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
EN 61000-6-2 When being exposed to interference, there may be
Noise immunity
minimal deviations.
Color green
Housing material PBT
Mounting position any
The T connector can be used to bridge the supply voltage. It can be
Assembly instructions
snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2

EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 0.04 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 0.1 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 0.02 %

Standards and Regulations


08/05/2021   Page 3 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Technical data
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Standards/regulations EN 61000-4-2
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Electrical isolation Basic insulation according to EN 61010

Conformance/approvals
Designation CE
Certificate CE-compliant
Designation UL, USA/Canada
Identification UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Designation Shipbuilding approval
Certificate DNV GL TAA00002R0
Temperature B
Humidity B
Vibration B
EMC B
Required protection according to the Rules shall be provided upon
Enclosure
installation on board

Environmental Product Compliance


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”

Drawings

08/05/2021   Page 4 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Pictogram Block diagram

Sensor / Field IN OUT PLC / DCS

S-Port

OUT U,I
1 1 5 + 5
active passive
GND 1
2 2 6 – 6
ϑ ϑ ϑ
+24V
3 3 7 +

IN U,I OUT
4 4 GND 2
8 –
FM
FM GND 2 +24V
POWER

Classifications
eCl@ss

eCl@ss 10.0.1 27210129


eCl@ss 11.0 27210129
eCl@ss 4.0 27200200
eCl@ss 4.1 27200200
eCl@ss 5.0 27200200
eCl@ss 5.1 27200200
eCl@ss 6.0 27200200
eCl@ss 7.0 27200206
eCl@ss 9.0 27210129

ETIM

ETIM 2.0 EC001446


ETIM 3.0 EC001446
ETIM 4.0 EC001446
ETIM 6.0 EC002919
ETIM 7.0 EC002919

UNSPSC

UNSPSC 6.01 30211506


UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 41112105
UNSPSC 18.0 41112105
UNSPSC 19.0 41112105
UNSPSC 20.0 41112105

08/05/2021   Page 5 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Classifications
UNSPSC
UNSPSC 21.0 41112105

Approvals
Approvals

Approvals

UL Listed / cUL Listed / DNV GL / cULus Listed

Ex Approvals

UL Listed / cUL Listed / cULus Listed

Approval details

UL Listed 
  http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  FILE E 238705

cUL Listed 
  http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm  FILE E 238705

DNV GL 
  https://approvalfinder.dnvgl.com/  TAA00002R0

cULus Listed 
    

Accessories
Accessories
DIN rail connector

08/05/2021   Page 6 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Accessories

DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728

DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
 
 

Evaluation unit

Monitoring module - MINI MCR-SL-FM-RC-NC - 2902961

The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to
monitor the supply voltages. The error is reported via an N/O contact. Screw connection, standard configuration.
 
 

Marking material

Transparent cover - MINI MCR DKL - 2308111

Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
 
 

Marking label - MINI MCR-DKL-LABEL - 2810272

Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
 
 

Power module

Power terminal block - MINI MCR-SL-PTB-FM - 2902958

The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the DIN rail connector.
The FM power terminal block offers the additional function of monitoring in combination with the fault monitoring
module. Screw connection.
 
 

08/05/2021   Page 7 / 8
https://www.phoenixcontact.com/pi/products/2902849

Resistance thermometer measuring transducer - MINI MCR-RTD-UI-


NC - 2902849
Accessories

Power terminal block - MINI MCR-SL-PTB - 2864134

MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw
connection, maximum current consumption of up to 2 A
 
 

Power supply

Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983

Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
 
 

Programming adapter

Adapter - IFS-BT-PROG-ADAPTER - 2905872

Bluetooth adapter with micro USB and S-PORT interface for wireless communication with the MINI Analog,
MINI Analog Pro, MACX Analog, INTERFACE system gateways, and PLC logic device series.
 
 

Programming adapter - IFS-USB-PROG-ADAPTER - 2811271

Programming adapter with USB interface, for programming with software. The USB driver is included in the software
solutions for the products to be programmed, such as measuring transducers or motor managers.
 
 