Design of Built-Up Column: Section Used
Design of Built-Up Column: Section Used
1 Design parameters
Factored Load 220 KN/m2
Axial Load 161.3333 KN/m2
Grade of Steel 250 N/mm2
OK
DESIGN OF PURLIN
1 Details
height for slope 1.5 m Grade of steel 250 Mpa
Span of truss 10 m Ymo 1.1
spacing of column(L) 5m
spacing of purlin 1m
tanӨ 0.15
Ө 8.53
3 SECTION USED:
Depth 72 mm
Breadth 72 mm
Thickness 4 mm
2 Load Calculation
Dead load of CGI sheet 0.75 KN/m2
Self weight of purlin KN/m2
Total dead load 0.75 KN/m2
Live Load 0.75 KN/m2
Factored total load 2.25 KN/m2
2.25 KN/m
Load normal to sheeting 2.225111 KN/m2
Load parallel to sheeting 0.333736 KN/m2
Section modulus
Zpz = Mz Ymo + 2.5 d.My Ymo
fy b. fy
= 42067.46 mm
DESIGN OF COLUMN BASE PLATE
1 DETAILS
a Grade of Steel
fy= 250 MPa
COLUMN
fu= 410 MPa
b SECTION USED:
COLUMN ISMC150
Depth 150 mm
Width 75 mm
Thickness of flange 5.7 mm
Thickness of web 9 mm
Area 213000 mm2
c FORCES ACTING
Factored Load 20 KN Mx 100
Axial Load Fz 14.66667 KN Moment My 100
Transverse Force Fx 57 KN Mz 0
Transverse Force Fy 24 KN
= 2222.222 mm2