Mcseng Rev4
Mcseng Rev4
Mcseng Rev4
INCORPORATED – “ECONOMIST”
MCS Series
Instruction manual
MCSeng – rev. 4
September 09
MECAIR S.r.l.
Diaphragm valves and electronic controls for dust collector filters
Via per Cinisello 97 – 20054 Nova Milanese – Milano – Italy
Phone ++39 0362 3751, telefax ++39 0362 367279
1
ELECTRONIC CONTROLLER WITH DELTA P
MCS SERIES – INSTRUCTION MANUAL
1. MAIN FEATURES
The MCS Economist completely controls the MECAIR diaphragm valves, on the dust collector filters,
with pneumatic cleaning procedures (pulse-jet). The main features of the MCS Economist are:
– Automatic regulation of cleaning, according to the level of filter clogging (∆P).
– Manual Cycle Time selection.
– Operating mode selection (MANUAL Mode or AUTOMATIC Mode).
– Automatic identification of connected valves (disconnected outlets are automatically skipped).
– Shut Down Cleaning, with programmable number of cycles.
– PRECOATING function.
– STAND-BY function.
– REMOTE function.
– Remote commutation of position (MANUAL or AUTOMATIC).
– ∆P value playback (option).
2
2. TECHICAL FEATURES
WEEE
The device should be disposed of in accordance with current European
regulations
3
3. INSTALLATION GUIDELINES
• Do not expose the MCS to direct sunlight in order to avoid overheating of the circuit board.
• Protect MCS from rain, water infiltration and humidity. Incomplete closing of the cover may
cause infiltration which can seriously damage the circuit board.
• The initial length of conduit which holds the electric cables which run to the MCS, should be
turned upwards or interrupted before the appliance.
appliance. This will stop any water or condensate
entering the MCS.
• Use Only cable gland with protection grade IP65 and of proper size ( according to the cable
used )
• A disconnecting switch has to be installed on the power line before the MCS
• All wiring should be carried out by a qualified electrician to avoid risk of fire and electrical
shocks
• MCS wiring has to be performed in order to separate the different types of cables, ( power ,
relay’s contact, valve output , 4-20ma
4 output) and in order
er not to pass close to the PCB.
• Before opening the unit , be sure that ,MCS is switched off (switch on/off (1) on 0 and wires on
clamps (4) disconnected , including connection to alarm / signal relays .
• Voltage selectors jumpers have o be positioned only by skilled personnel and following the
instructions.
• A wrong Voltage selectors jumpers positioning may cause potential danger to the personnel
safety .
4
4. PRELIMINARY CHECKS
1) Check that the MCS has no power (switch on/off [1] on 0 and terminals [4] disconnected).
2) Check that the value of power supply, registered on the yellow label [22] at the heading INGRESSO-
IN, is the same as the one of the available power supply of grid.
3) Check that the value of the outlets voltage (valves), registered on the yellow label [22] at the heading
USCITA-OUT, is the same as the one of the voltage on the serigraphy of the solenoid valves.
5. ELECTRICAL CONNECTIONS
1) Check that the MCS has no power (switch on/off [1] on 0 and terminals [4] disconnected).
2) Unscrew and open the terminal cover [20].
3) Pull out the extractable terminals [2].
4) Check that the connections to the valves are correct and insulated respect to the ground. Therefore
testing the insulation between ground [3] and common (C) with outlets connector disconnected.
5) Connect the valves to the terminals [2], between common (C) and numbered terminals of the outlets
· The grounding [3] of the valves is necessary if the outlets voltage is greater or equal to 48V.
· Never connect the commons (C) or the outlets to ground [3].
· The commons (C) are connected between them on the printed circuitry. Carry out a common to
each valve or group together the commons in one wire.
· The outlets are of static type, with “zero-crossing” command, to prevent electrical noises.
6) Put back the extractable terminals [2].
7) Power the MCS [4]: a) with 230 V of grid (L = phase, N = neutral)
b) with 115 V from auxiliary transformer
. It is necessary to connect to the ground one of two terminals of
secondary and to connect it to the N [4].
c) – Special realization 24/48 V: it is necessary to connect to the ground
one of two terminals of secondary and to connect it to the N [4].
– Special realization 24 V DC: the terminals[4] are this: + – o
8) Close and screw the terminal cover [20].
The ∆P into the filter is measured by an internal probe, connected to the filter by 2 filtered pressure taps.
The filtered pressure taps avoid that the process powders block the tubes connecting probe and filter.
For the depressurised filters install on the filter wall both the filtered pressure taps, one on the dusty air
plenum and one on the clean air plenum. For the pressurised filters, install only one filtered pressure tap
on the dusty air plenum. For each filtered pressure taps refer to the instructions below: (Drawing 6.3):
1) Drill , on the filter wall, the 4 fixing holes for the tap (∅ 3,75 mm., inter axial distance 39 mm.).
2) At the centre of the 4 fixing holes, make 3-5 pressure intake holes, all in a circle with radius of 10
mm. The ∅ of the holes must be 4 mm.
3) Position the rubber seal. If the support surface is irregular, you must fill with silicon
4) Position the filtered pressure tap, with the tube connection turned upside.
5) Fix the filtered pressure tap with the self-tapping screws (∅ 4,25 mm.).
5
6.2. FILTERED PRESSURE TAPS: CONNECTION
Connect the 2 tubes of the filtered pressure taps to nipples [13]. Connect the tube of the tap of the filtered
air to the “-” inlet. Connect the tube of the tap of the dusty air to “+” inlet.
Note: – Install the pressure taps so that neither condensate nor powder can precipitated.
– The 2 tubes (∅ 6/4) that connect the filtered taps to nipples [13], must be lead upwards in the
first part of the circuit. This avoids that into the tubes precipitated condensation. In damp
processes, where condensation is likely, for each tube there must be a drain pipe.
– If the pressure taps are correctly installed and connected to nipples [13], the display [7] shows
positive values of ∆P. If the display shows negative values of ∆P, the connections of 2
pressure taps are reversed.
– If the ∆P goes below –0,14 kPa, on the display [7] appears “– – –”. In this case, reverse the
tubes of 2 filtered taps. If the problem persists, use the regulation [15] to reset the indication
at 0 kPa.
Filter wall
Seal
Ø 20
25 45
39
39 Wad
50
4 fixing holes
Ø 3,75 Con superfici irregolari,
With irregular surfaces, silicon the
siliconare abbondantemente
seal well before joining the parts.
50 25 la guarnizione prima di
Self-tapping screws
Ø 4,25
–
Filtered air
Fan
+
Dusty air
inlet
Bag filter
MCS
– +
Check that the MCS is not powered (switch on/off [1] on 0 and terminals [4] disconnected).
Check: 1) that the value of the power supply voltage, registered on the yellow label [22] with the
heading INGRESSO-IN,
INGRESSO is the same as the one of the available power supply.
2) that the value of the outlets voltage (valves), registered on the yellow label [22] with the
heading USCITA-OUT,
USCITA is the same as that printed on the solenoid valves.
1) Unscrew to 45° anticlockwise the 2 screws [21]. Simultaneously push up and open the
transparent cover of the MCS.
2) Unscrew the 4 screws of the green panel. Lift the green panel (do not remove it as it is
connected to the base of the enclosure!).
3) Check that the power supply voltage, selectable with the jumpers [5], is the same as the power
available (example.: both 230 V).
4) If the two voltages are different, move the jumpers [5] on the position selecting the same voltage
as that available.
1) Check that the outlets voltage, selectable with the jumpers [6], is the same as that indicated on
the solenoid valves (example.: both 24 V).
2) If the two outlets voltage are different, move the jumpers [6] on the position selecting the same
outlets voltage as that on the solenoid valves.
(ATTENTION: on the jumpers [6] select the same value for outlets voltage!).
1) Check that the type of outlets voltage, selectable with the jumpers [8], is the same as that on the
solenoid valves (example.: both AC).
2) If the two type of outlets voltage are different, move the jumpers [8] on the position selecting the
voltage required .
3) Replace the front panel and tighten the 4 screws of the panel.
4) Close the transparent cover and tighten the 2 screws [21], rotating them to 45° in clockwise
direction.
CAUTION!
Never select the outlets 230 V in DC for the outlets!
7
7.2. MANUAL AND AUTOMATIC MODE OPERATION
Note: select the shortest PULSE TIME possible, between all those compatible with maximum
obtainable particle separation. This is valid both in MANUAL and AUTOMATIC Mode.
• Ideal time for “bag” filters: between 100 ms and 400 ms.
• Ideal time for “standard cartridge” filters: between 500 ms and 1 second.
• Ideal time for “rotating nozzle cartridge” filters: between 1sec and 4 seconds.
In MANUAL Mode, the MCS commands the valves with fixed PAUSE TIME. The cleaning is not
dependant on the level of the filter bags clogging. The MANUAL Mode must be only used during the
start-up phase.
When the MCS is in MANUAL Mode, the LED MANUAL [30] flashes.
In MANUAL Mode, the PAUSE TIME depends on selected TCM. The link is: PAUSE TIME = TCM :
no. of connected valves. E.g.: if you connect 8 valves and you select a TCM of 360 seconds, PAUSE
TIME = 360 : 8 = 45 seconds.
In AUTOMATIC Mode, the cleaning is automatically adapted to the level of the filter bag clogging. The
cleaning starts when the filter ∆P exceeds the value of selected SET DELTA-P (see 7.3). The SET
DELTA-P to select depends on the structural characteristics and wear and tear of the filter and on the
type of process.
When the MCS is in AUTOMATIC Mode, the LED MANUAL [30] is off.
In AUTOMATIC Mode, the PAUSE TIME depends on the selected TCM*. The link is: PAUSE TIME
IN AUTOMATIC MODE = (PAUSE TIME IN MANUAL MODE : No. of connected valves) : 3 =
TCM : 3. For example if you have set a TCM of 360 seconds with 8 valves connected, PAUSE TIME IN
AUTOMATIC MODE = (360 : 8) : 3 = 45 : 3 = 15 seconds.
* It is also possibile to modify the pause time so as not to rely on the TCM. Refer to Point 15 p 4.
It is possible to pass from AUTOMATIC Mode to MANUAL Mode (and vice versa) closing a remote
contact. See below:
8
7.3 SETTINGS: PARAMETERS SELECTION
Check that all electrical connections have been done as described in Point 5.
Switch on/off [1] on 1. On the display [7] appears, for a few seconds the MCS identification code.
Immediately after, on the display appears the value of the filter ∆P. If the LED OK [18] and PAUSE
[12] turn on and the LED MANUAL [30] flashes, the MCS is in MANUAL Mode. If only the LED
OK [18] turns on, the MCS is in AUTOMATIC Mode.
Attention! When the fan stops, the display [7] must indicate a filter ∆P value of 0 kPa.
Otherwise, use the regulation [15] to reset the indication at 0.
1) Press SELECT MENU [9]: on the display [7] flashes the no. 1:
with +/– buttons [10] select the PULSE TIME (0,01 ÷ 9,99 sec).
2) Press SELECT MENU [9]: on the display [7] flashes the no. 2:
with +/– buttons [10] select the MANUAL CYCLE TIME (1 ÷ 999
sec).
The TCM is the number of seconds, after which, the MCS returns to
activate the first valve. In other words, it is the duration, in seconds,
of a complete cycle of cleaning, from the first to the last connected
valve.
When you select the TCM, the MCS automatically calculates the
PAUSE TIME, in this way:
– In MANUAL Mode, the PAUSE TIME is given by the selected
TCM divided by the no. of connected valves. E.g.: TCM = 360 sec
and no. connected valves = 8. PAUSE TIME = 360 : 8 = 45 sec.
– In AUTOMATIC Mode, the PAUSE TIME is given by the
selected TCM divided by 3, divided by the no. of connected
valves.
E.g.: TCM = 360 sec and no. of connected valves = 8. PAUSE
TIME = 360 : 3 : 8 = 15 sec.
– If the MCS has more than 32 outlets, it is useful to select a
PAUSE TIME unrelated to the TCM (see Chap. 15).
3) Press SELECT MENU [9]: on the display [7] flashes the no. 3:
with +/– [10] buttons select the SET DELTA-P (0,01 ÷ 9,99 kPa).
The cleaning starts every time that the filter ∆P exceeds the SET
DELTA-P.(+0,05kpa) The cleaning stops every time that the filter
∆P goes below the SET DELTA-P.
4) Press SELECT MENU [9]: on the display [7] flashes the no. 4:
with +/– buttons [10] select the SET DELTA-P ALARM (0,01 ÷
9,99 kPa).
When the filter ∆P exceeds the SET DELTA-P ALARM, you are in
the presence of alarm.
5) Press SELECT MENU [9]: on the display [7] flashes the no. 5:
with +/– [10] buttons select the NO. OF CYCLES for the SHUT
DOWN CLEANING (0 ÷ 99 times).
(Select 0 to exclude the SHUT DOWN CLEANING).
– The SHUT DOWN CLEANING automatically starts when the
filter ∆P goes below 0,10 kPa.
9
6) Press SELECT MENU [9]: on the display [7] flashes the no. 6:
with +/– [10] buttons select the ∆P PRECOATING (0 ÷ 9,99 kPa).
In both Modes, the cycle will start only when the filter ∆P will
exceed the ∆P PRECOATING, whatever was the DELTA-∆P
selected. This allows to the filters to overload with preparation
powders.
– Select 0 to disable the PRECOATING function.
– Overpassed the ∆P PRECOATING, the function will auto delete:
now the cycle will only depend from the SET DELTA-P. Insert a
new ∆P PRECOATING value to restore the function.
– For the ∆P PRECOATING, it is possible to select only values
greater (at least of 0,10 kPa) than the SET DELTA-P.
– The SHUT DOWN CLEANING only starts when the ∆P
PRECOATING is overpassed. Otherwise, even if you stop the fan,
the SHUT DOWN CLEANING does not start.
7) Press SELECT MENU [9]: On the display [7] appears the code 7L. Immediately after it appears
the letter L and the 3 last numbers (from 0 to 999) of the 5 which
indicate the amount of hours for functioning of the MCS.
E.g.: MCS operating for 12.270 hours, on the display appears L270.
Press SELECT MENU [9]: On the display [7] appears the code 7H. Immediately after it appears
the letter H and the first 2 numbers (from 0 to 65) of the 5 which
indicate the amount of hours for functioning of the MCS.
E.g.: MCS operating for 12.270 hours, on the display appears H12.
8) Press SELECT MENU [9]: on the display [7] flashes the code 8PAS.
From here it is possible to enter the submenu.
9) Press SELECT MENU [9]: on the display [7] appears P000 : the cycle starts.
The functioning of the valve is indicated by the lighting up of the LED PULSE [11].
The pause between 2 valves firing is indicated by the lighting up of the LED PAUSE [12].
10
8. SHUT DOWN CLEANING
After every utilization, it is useful to carry out one or more cycles of SHUT DOWN CLEANING, to free
the filtering elements of residual dust. The SHUT DOWN CLEANING starts when the ∆P goes below
0,10 kPa..
ATTENTION: • The SHUT DOWN CLEANING only starts if the MCS is in AUTOMATIC Mode!
• The SHUT DOWN CLEANING only starts if the ∆P PRECOATING is exceeded.
Otherwise, even if you stop the fan, the SHUT DOWN CLEANING does not start.
* It is possible to get the Shut Down Cleaning Pause Time independent of TCM. Refer Point 15 point 5.
** It is possible to change this value. Refer Point 15 point 8.
9.1 LEDS
1) LED MANUAL [30]: flashes if the MCS is in MANUAL mode. It’s off if the MCS is in
AUTOMATIC mode.
2) LED PULSE [11]: It’s on when a valve is firing.
3) LED PAUSE [12]: it’s on between the firing of one valve and another
4) LED PRECOATING [32]: it flashes until the filter ∆P exceeds the ∆P PRECOATING; then it
switches off.
5) LED STAND-BY [31]: it flashes when the MCS is in stand-by.
9.2 LED OK
Incidental damages of the microprocessor are shown by the turning off of the LED OK [18]. This
problem is not able to be resolved by the customer: Refer problem directly to MECAIR.
To have remote signal LED OK connect the relay’s terminals WD on contacs C. N.O.
On the display [7] appears “P– – –” if the filter ∆P goes below –0,14 kPa. In this is the case:
1) Check that the filtered pressure taps are connected to the pressure nipples [13] see chapter 6.2.
2) If the problem persists: • disconnect the connection pipes between the pressure filtered taps and
pressure nipples [13]
• use the regulation [15] to reset the indication at 0 kPa.
• reconnect [13] the connection pipes between the pressure filtered taps
and pressure nipples [13].
11
9.4 LED ALARM
The LED ALARM [30] switch on if the ∆P inside the filter exceed the ∆P ALARM selected, or if
threre is a short circuit on one or more outlets.
a) If on the display [7] appears the code PPP1, the filter ∆P exceeded the selected ∆P ALARM.
Operate as follows:
1) Stabilise the filter ∆P.
2) Press “–” to return in run.
3) Press RESET [19]: the alarm disconnects.
b) If on the display [7] appears the letter A followed by a number, the valve countermarked with
that number is in short circuit. Operate as follows:
1) Continue to press the button “+” [10], to read on the display the number of the faulty
outlets. Attention: the alarm intervention excludes the faulty valve which is in short circuit.
2) Repair the damages .
2) Press “–” to return in run.
3) Press RESET [19]: the alarm disconnects. The command of defective valves restarts.
To have remote signal LED ALARM connect the relay’s terminals ALL on the
contacts C. N.C.
The PRECOATING function retards the cleaning cycle of the filter in order to allow that the filter bags
collect and absorb/permeate the preparation powders.
ATTENTION: selected the ∆P PRECOATING, the cycle begins only when the ∆P in the filter
exceeds the ∆P PRECOATING. This is the same in both modes (Manual/Auto), and
whatever the desired SET DELTA-∆P may be.
1) Select the ∆P PRECOATING at point 6) of 7.3. The LED PRECOATING [32] flashing.
· To exclude the PRECOATING function, select 0 at point 6) of 7.3.
· The ∆P PRECOATING selected must be between 0 and 9,99 kPa.
· The ∆P PRECOATING must be higher (almost of 0,10 kPa) than the selected SET DELTA-P.
2) When the filter ∆P exceeds the ∆P PRECOATING, the cycle starts and the PRECOATING function
auto deletes. The LED PRECOATING [32] turns off.
· To reactivate the function, select a new value of ∆P PRECOATING.
· The SHUT DOWN CLEANING only starts if the ∆P PRECOATING is already exceeded.
Otherwise, even if you stops the fan the SHUT DOWN CLEANING doesn’t starts.
On the LED display [7], the MCS shows the filter ∆P. Press DELTA-P/VALVES [14] to pass from
filter ∆P indication to active valve indication (and vice versa). When you turn on the MCS, on the
display automatically is visualised the filter ∆P.
12
12. STAND-BY FUNCTION
It is possible to put the MCS in STAND-BY from distance. When the MCS is in STAND-BY, all its
functions are blocked.
With the assembled board [4] is possible to broadcast to distance, on other unit, the ∆P value that is showed
on MCS display [7].Connect to the terminals 4÷ ÷20 mA POS [1] e 4÷ ÷20 mA NEG [2]. See drawing page 13.
13.1 4 ÷ 20 mA CONNECTION
13
1
4÷20 mA
POS S.B A.M RIGHT
DOWN
CORNER
OF MCS
remote 4÷20 mA
DISPLAY NEG p p
2
R
SHIELDED CABLE
POWER SUPPLY
5 ÷ 30 V DC 3
FRONT BACK
RIGHT TOP
PINS
CORNER
OF MCS
PLUGS
14
13.3 FULL-SCALE 4 ÷ 20 mA SETTING
1. Turn on the MCS (switch on/off [5] on 1) keeping pressed the RESET key until code “PPSS”
appears on the display. Release RESET key: on the display code “A 0” appears.
2. Press “– ” until compose on the display the number “A879”.
3. Press SELECT MENU: on the display appears the letter C and the number of outlets of the MCS.
(Example: in case of an MCS32, appears “C 32” on the display).
4. Press SELECT MENU: on the display appears “ P 0 “.
SELECT
5. Leave “P 0” if you want the full-scale value of 9,99 kPa
With “+” select “P 1” if you want the full-scale value of 1,00 kPa. PPSS
With “+” select “P 2” if you want the full-scale value of 2,00 kPa.
MENU
With “+” select “P 3” if you want the full-scale value of 3,00 kPa. – +
With “+” select “P 4” if you want the full-scale value of 4,00 kPa.
With “+” select “P 5” if you want the full-scale value of 5,00 kPa. RESET
6. Press SELECT MENU: on the display appears the ∆P into the
filter.
7. Press SELECT MENU the cycle restarts.
14. HOURCOUNTER
The HOURCOUNTER counts the number of working hours of the MCS. The counting starts every time
that the filter ∆P exceeds 0,10 kPa. To visualise the HOURCOUNTER on the display [7]:
1) Press SELECT MENU [9] until on the display [7] appears the code 7L. Immediately after, it appears
on the display the letter L and the last 3 numbers (from 0 to 999) of 5 which indicate the total of
working hours of the MCS.
E.g.: if the MCS works from 12.270 hours, on the display appears L270.
2) Press SELECT MENU [9] until on the display [7] appears the code 7H. Immediately after, it appears
on the display the letter H and the first 2 numbers (from 0 to 65) of 5 which indicate the total of
working hours of the MCS.
E.g.: if the MCS works from 12.270 hours, on the display appears H12.
15. SUBMENU
The submenu allows to modify parameters and set functions which are not accessible from SELECT
MENU. You can access to submenu only if the MCS is in AUTOMATIC Mode. Follow this procedure:
1) Press SELECT MENU [9] until on the display [7] flashes the code 8PAS.
Press the button “+” [10] until compose the number 123.
2) Press SELECT MENU [9]: on display [7] flashes the letter 9: select with +/– [10] buttons the
function MANUAL PAUSE TIME. 0 = disable : MCS is normally working.
1 = enable : it is possible to set the pause time in step two of menu, the same time divided by 3 is the
AUTOMATIC PAUSE TIME.
15
4) Press SELECT MENU [9]: on the display [7] flashes the letter b:
modify with +/– [10] buttons the PAUSE TIME (in seconds) in AUTOMATIC Mode.
As seen in chapter 7.3, the PAUSE TIME in AUTOMATIC mode depends on TCM selected. Here
you can select a PAUSE TIME independently of TCM. If you select 0, the PAUSE TIME in
AUTOMATIC mode still depends by TCM.
5) Press SELECT MENU [9]: on the display [7] flashes the letter C:
modify with +/– [10] buttons the PAUSE TIME (in seconds) in SHUT DOWN CLEANING.
As see in chapter 8, the PAUSE TIME in SHUT DOWN CLEANING depends on TCM selected.
Here you can select a PAUSE TIME in SHUT DOWN CLEANING independents of TCM. If you
select 0, the PAUSE TIME in SHUT DOWN CLEANING still depends by TCM.
6) Press SELECT MENU [9]: on the display [7] flashes the letter d:
it is possible to select the value of MINIMUM FREQUENCY of CLEANING:
If in 3) you selected 0: leave 0.
If in 3) you selected 1: – leave 0 to have that the MINIMUM FREQUENCY of CLEANING is
15 times the TCM value/N° EV.
– Select with +/– [10] the value of MINIMUM FREQUENCY of
CLEANING, independent of TCM selected(max 99 sec).
7) Press SELECT MENU [9]: on the display [7] flashes the letter F:
select with +/– [10] buttons the function FINISHING of the CYCLE in AUTOMATIC Mode
UNTIL the LAST VALVE: 0 = disable, 1 = enable
8) Press SELECT MENU [9]: on the display [7] flashes the letter H:
modify with +/– [10] buttons the ∆P for the START of the SHUT DOWN CLEANING, zapping
the default value of 0,10 kPa.
Leave 0 to have the ∆P for the START of the SHUT DOWN CLEANING of 0,10 kPa.
Attention! The ∆P for the START of the S.D.C. determines the start of the HOURCOUNTER: the
counting starts when the filter ∆P exceeds the ∆P for the START of the S.D.C (+0,05kpa)
9) Press SELECT MENU [9]: on the display [7] flashes the letter L:
modify with +/–[10] buttons the TIME of RETARD for INSERTION of the HIGH ∆P ALARM
(0 - 99 seconds).
Press SELECT MENU: on the display [7] appears P000 : the cycle starts.
Note: during the parameters and functions selection, after approximately 5 minutes from the last button
pressed, the MCS return in run.
MECAIR presets the parameters of every MCS (to change the preselections see 7.3).
16
17. TROUBLESHOOTING
IMPORTANT NOTE: if you use the MCS with power supply at 24V DC, check that it isn’t lower of 24V
and the power is suitable at connected load.
17
19. LEGEND
1) on/off switch
2) Extractable terminals (outlets and commons)
3) Ground terminals for outlets
4) Power supply terminals
5) Jumper for inlet power supply selection.
6) Jumper for voltage selection to valves
7) Display
8) Jumper for the frequency of outlet power supplies selection (A.C./D.C.).
9) SELECT MENU button
10) +/– buttons
11) LED PULSE
12) LED PAUSE
13) Inlet pressure nozzle
14) DELTA-P/VALVES button
15) Zero adjusting
16) AUTOMATIC/MANUAL mode button
17) LED ALARM
18) LED OK
19) RESET button
20) Terminals cover
21) 2 screws of transparent cover
22) Yellow label voltage setting
23) Fuse main supply
24) Relay ALL and relay WD terminals
25) Product code and registration number
26) Terminals for remote changing of the Mode
27) STAND-BY terminals
28) 4 ÷ 20 mA positive terminal.
29) 4 ÷ 20 mA negative terminal.
30) LED MANUAL
31) LED STAND-BY
32) LED PRECOATING
33) External contacts supply fuse
34) Internal
nternal +5v supply.( micro, display) fuse
ATTENTION!
Before you open the MT and connect the terminals, check that the
on/off [1] switch is on 0 and that the terminals [4] are disconnected.
18
20. MCS FRONT PANEL
19
21. MCS 4-32: GENERAL ASSEMBLY
33 34 9 7 12 11 14
17
Pause Pulse
Delta−P = kPa / Valves = N°
SELECT
DELTA−P
VALVES
18
MENU
19
RESET
10
21 PRECOATING
MANUAL
30
AUTOMATIC
16
ZERO
ADJUST
15
32
DIFFERENTIAL
PRESSURE
INLET
3 MCS
MECAIR S.r.l. NOVA MILANESE − MILANO − ITALY
Phone ++39 0362 3751 Fax ++39 0362 367279
13
4 2 22 25
20
5 26
8
6
23
24
28
1 29
27
20
Pause Pulse
Menu Delta−P = kPa / Valves = N°
1: Pulse time ( 0.01 − 9.99 sec ) SELECT
DELTA−P
2: Manual cycle time ( 1 − 999 sec )
VALVES
3: Set Delta−P ( 0.01 − 9.99 kPa )
MENU
4: Set Delta−p alarm ( 0.01 − 9.99 kPa )
5: Shut down cleaning ( 0 − 99 cycles ) ADJUST ALARM OK STAND
BY
6: Precoating ( 0 − 9.99 kPa )
7: Hour counter
RESET
8: Password
E: Run
MANUAL
PRECOATING
21
AUTOMATIC
ZERO
ADJUST
DIFFERENTIAL
22. MCS 36-64: GENERAL ASSEMBLY
PRESSURE
INLET
MECAIR S.r.l. NOVA MILANESE − MILANO − ITALY
MCS Phone ++39 0362 3751 Fax ++39 0362 367279
L N L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20 L21 L22 L23 L24 L25 L26 L27 L28 L29 L30 L31 L32 WD C N.O N.C
LINE COMMON OUTPUT 1-8 COMMON OUTPUT 9-16 COMMON OUTPUT 17-24 COMMON OUTPUT 25-32 ALL C N.O N.C
(Refer Page 19 )
23. MCS 68-128: GENERAL ASSEMBLY
(Refer page 19)
AUTOMATIC
ZERO
ADJUST
DIFFERENTIAL
PRESSURE
INLET
L N L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20 L21 L22 L23 L24 L25 L26 L27 L28 L29 L30 L31 L32 WD C N.O N.C
LINE COMMON OUTPUT 1-8 COMMON OUTPUT 9-16 COMMON OUTPUT 17-24 COMMON OUTPUT 25-32 ALL C N.O N.C
22
23