E6010 Catalog v21
E6010 Catalog v21
E6010 Catalog v21
: 06203001
VER : 2.1_19/11/08
POWER METER HC 6010
sequentially view the more than 30 electrical
Introduction parameters.
About Power Meter HC 6010 To meet future metering environments, the power
HC 6010 power meters are conceptualized and meter is equipped with a serial port (RS-485 or RS-
intelligent to revolutionize the approach to 232), to allow connection to an open architecture
traditional power metering. computerized network. Running on PC or data
acquisition system and complying with Modbus®
Each power meter is a compact, electronically protocol. The software provides a simple yet
advanced and programmable multi-display metering practical solution to energy management in factories
device (MDMD). It is the answer to future generation and plant, small industries, building services, etc.
of electrical metering needs and methodology.
Parameters Conversion
Environmental Impact & Cost Saving The microprocessor-based power meter now provides
A power meter can replace many units of compatibility with the modicon Modbus® system as a
conventional analog or digital instruments and standard featured. From the VFD multi-display
change over switches (e.g. Amp, Volt, KVA, KW, PF, reading V, A, VA, W, Var, WH, etc. more than 30 power
KWH, KVarH, FQ etc.). and energy parameters. Via the RS-485 Modbus®
This saves on the wiring material usage and reduces communications, including the instant maximum and
the cost on metering needs. minimum of all parameters, maximum demand
With the power meter modern and practical MDMD, control, time stamping, etc. more than 90 parameters
the front layout of switch boards and control panels can be achieved by remote monitoring system.
are aesthetically refined.
Field Programmability
The field programmable power meter is able to set
e.g. CT and PT ratio, Modbus® address,
communication baud rate, parity, meter’s display, etc.
either programming by push-bottom or by rear RS-
485 / RS-232 communication port from a PC.
Version Option
N : No option
Current Input
A : Pulse output x 4
1.0A
B : Analog output x 4
5.0A
C : Pulse output x 2 + Analog output x 2
7.5A
D : Pulse output x 1 + Analog output x 3
Power Y : Special ordering
H : AC 80-260V, DC 80-330V
Communication Part
L : DC 20-60V
1 : RS-485
2 : RS-232
3 : RS-485 + RS-232
4 : RS-485 x 2
Y : Special ordering
Specification
Programmable measurements / Accuracy / Display readouts
Parameter Digital Display (maximum) Accuracy Phase1 Phase2 Phase3 Total Average
Vx3 5 (or 4) 9.9.9.9.9. V / KV 0.15% fs V1 V2 V3 VE
Ax3 5 (or 4) 9.9.9.9.9. A / KA 0.15% fs A1 A2 A3 AE
Watts 5 (or 4) 9.9.9.9.9. W / KW / MW / GW 0.25% fs W1 W2 W3 W
Vars 5 (or 4) 9.9.9.9.9. Var / KVar / MVar / GVar 0.25% fs Var1 Var2 Var3 Var
VA 5 (or 4) 9.9.9.9.9. VA / KVA / MVA / GVA 0.25% fs VA1 VA2 VA3 VAE
PF 4 0.9999 0.25% fs PF1 PF2 PF3 PF
WH 8 9.9.9.9.9.9.9.9. WH / KWH / MWH 0.8% rd WH
VarH 8 9.9.9.9.9.9.9.9. VarH / KVarH / MVarH 1% rd VarH
A0 5 (or 4) 9.9.9.9.9. A / KA 0.5% fs
Hz 5 (or 4) 70.000 0.03% rd
● Accuracy : Corresponding to each auto-range scale ● Accuracy performance range for WH / VarH / PF
● VL1 / VL2 / VL3 : Line to line voltage Cosθ : 1-0.5 for WH / PF
VP1 / VP2 / VP3 : Line to neutral voltage Sinθ : 1-0.5 for VarH
● PF1 / PF2 / PF3 : Related conversion elements Voltage ≧ 75V, Current ≧ 10% of rate
● A0 (neutral current, only for 3 phase 4 wires) ● Phase rotation
SEQ POST : positive sequence
SEQ NEG : negative sequence
Dimension
120 138
18,5 83 18,5 21 98 19 91
14,5
11,1
16,5
AS A L BS BL C S C L X
Y
Z
Comm.
120
91
91
87
1 2 3 4 5 6 7 8 9 10 D E F
!
PA PB PC PN Power
16,5
9,5
14,5
CUT OUT
92x92mm
Communication Port
Output Port
POx4 or AOx4 POx2 + AOx2 POx1 + AOx3
1+ 1- 2+ 2- Shield + - + - Shield + - + - Shield
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
PO1 PO2 PO1 AO1
3+ 3- 4+ 4- Shield + - + - Shield + - + - Shield
6 7 8 9 10 6 7 8 9 10 6 7 8 9 10
AO1 AO2 AO2 AO3
Applications
The HC 6010 PC tool a utility program that can help user to connect to “HC 6010 Power Transducer” rapidly.
The HC 6010 PC Tool is provided along with every HC 6010, which allows easy access to all meter setup
information and actual values via a personal computer running Windows 95/98 and one of the PC’s
communication ports (COM1 or COM2). The PC Tool is able to do the function as bellows:
☉ Program / Modify setup information
☉ Load / save setup information files from / to disk
☉ Read actual “Basic” value (current / voltage / power / frequency)
☉ Read actual “statistics” value (maximum/minimum/time of maximum/time of minimum
☉ Output control (Pulse output / Analog output)
The HC 6010 PC Tool can be used as stand-alone without a HC 6010 to create or edit HC 6010 setup
information file.
Test Set
Communication Wiring
Computer
RS-485
D+ D-
Zt (*) R
(*) Terminating Impedance
at each end (typically)
120 ohm and 1nF C
Twisted Pair
Shiled Cable
Zt (*)
R
D+ D- D+ D- D+ D-
RS-485 RS-485 RS-485
METER METER METER