E6010 Catalog v21

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

DWG NO.

: 06203001
VER : 2.1_19/11/08
POWER METER HC 6010
sequentially view the more than 30 electrical
Introduction parameters.
About Power Meter HC 6010 To meet future metering environments, the power
HC 6010 power meters are conceptualized and meter is equipped with a serial port (RS-485 or RS-
intelligent to revolutionize the approach to 232), to allow connection to an open architecture
traditional power metering. computerized network. Running on PC or data
acquisition system and complying with Modbus®
Each power meter is a compact, electronically protocol. The software provides a simple yet
advanced and programmable multi-display metering practical solution to energy management in factories
device (MDMD). It is the answer to future generation and plant, small industries, building services, etc.
of electrical metering needs and methodology.
Parameters Conversion
Environmental Impact & Cost Saving The microprocessor-based power meter now provides
A power meter can replace many units of compatibility with the modicon Modbus® system as a
conventional analog or digital instruments and standard featured. From the VFD multi-display
change over switches (e.g. Amp, Volt, KVA, KW, PF, reading V, A, VA, W, Var, WH, etc. more than 30 power
KWH, KVarH, FQ etc.). and energy parameters. Via the RS-485 Modbus®
This saves on the wiring material usage and reduces communications, including the instant maximum and
the cost on metering needs. minimum of all parameters, maximum demand
With the power meter modern and practical MDMD, control, time stamping, etc. more than 90 parameters
the front layout of switch boards and control panels can be achieved by remote monitoring system.
are aesthetically refined.

Increase Productivity & Efficiency Features


The power meters are specifically designed to be ● Over 90 power and energy parameters
compatible with the world’s 2 most widely used DIN ● For factory and building automation
standard panel instruments (It fits the DIN 92 x 92 ● Modbus® RTU protocol
mm panel cutout holes). ● Maximum 600V
The power meter as a MDMD greatly reduced cabling ● True RMS conversion
complexity and time. It is also a standardize ● Instant maximum and minimum
hardware suitable for either 1 phase 2 wires, 1 phase ● VFD display clear and long-life
3 wires, 3 phase 3 wire or 3 phase 4 wires networks. ● Build in RTC (real time clock)
● Field programmable PT / CT ratio
Improved Technical Superiority and Reliability
The power meters are endowed with technical ● Accuracy up to 0.15%
specifications, (overload capabilities, accuracy levels, ● 4 isolated analog outputs to transducer function
long term stability, readout dependability etc.) far ● 4 pulse outputs based on KWH, KVarH, KVAH or AH
exceeding those of conventional instruments. To ● Maximum demand control applicable
overcome the critiques of digital metering, the power ● Memory for all setup and energy data
meter MDMD supports a VFD (Vacuum Fluorescent ● Comprehensive self test diagnostics
Display) screen with green (naturally comfortable) ● Low input burden 0.1VA (5A / 120V)
alphanumeric readouts. This allows visual clarity at ● Wide power supply range for AC / DC
long distance yet avoids parallax errors for close ● Compact physical configuration
range viewing. The multi-display readings can be ● Compatible for DIN & ANSI cut out
“damped” through it readout resolution besides the ● 2KV RMS input / output / power isolation
option to manually or automatically prioritize and

HSIANG CHENG ELECTRIC CORP.


4F., No.11, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231, Taiwan (R.O.C.)
TEL : 886-2-29175865~9 FAX : 886-2-29173946 E-mail : expo.sales@hc.com.tw
POWER METER HC 6010

Factory & Building Automation (FA & BA) Accuracy up to 0.15%


The power meter was developed for factory and With a well developed conversion, sampling and
building automation (FA & BA) applications, more all software compensation technology that make HC
of power and energy parameters can easily apply to 6010 power meter successfully meet the accuracy
wide range of AC switch-gear or industrial power requirement of modern metering, that voltage and
distribution system for metering. current up to 0.15% and other power up to 0.25%.

PLC Modbus® Compatible Comprehensive System Integration


The Modbus® communications protocol allows The HC 6010 power meter now provides the
information and data to be efficiently transferred Modbus® (are compatible with the Modicon system
between HC 6010 and modicon programmable logic as a standard feature for comprehensive system
controller (PLC) or other third party Modbus® integration. The PLC compatible RS-485 / RS-232
compatible monitoring and control system. The HC Modbus® communication protocol allows information
6010 can also establish a monitoring system just and data to be efficiently transferred between bower
simply adopt an IPC-based centralized master display meter HC 6010 and Modicon programmable logic
software. The RTU mode Modbus® protocol with controller (PLC) existing RTU Power SCADA system
default baud rate 9600 bps, 8 data bit. and DCS system or other Modbus® protocol
compatible system. For more detail information or
Build-in Real Time Clock (RTC) software backup please contact Hsiang Cheng Electric
HC 6010 power meters are with a build-in RTC (real Corp. or representative sales department.
time clock) that provide the internal time standard
and time stamp for all records attached to each
maximum and minimum energy measurements. RTC
also provided the demand-control time period 15 /
30 minutes for maximum power demand control of
utility load shedding.

Memory for all setup and energy data


All of the meter status setting and energy data are
retaining in memory while was lost power. HC 6010
power meter records includes the watt-hour that
been measured, the record of maximum demand
value, date and time, PT and CT ratio, the measured
system configuration, displaying setting, and
communication related.

Field Programmability
The field programmable power meter is able to set
e.g. CT and PT ratio, Modbus® address,
communication baud rate, parity, meter’s display, etc.
either programming by push-bottom or by rear RS-
485 / RS-232 communication port from a PC.

HSIANG CHENG ELECTRIC CORP.


4F., No.11, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231, Taiwan (R.O.C.)
TEL : 886-2-29175865~9 FAX : 886-2-29173946 E-mail : expo.sales@hc.com.tw
POWER METER HC 6010

Model & Ordering Number


Model : HC 6010
Ordering : HC 6010 - B - 5.0A - H - 1 - N

Version Option
N : No option
Current Input
A : Pulse output x 4
1.0A
B : Analog output x 4
5.0A
C : Pulse output x 2 + Analog output x 2
7.5A
D : Pulse output x 1 + Analog output x 3
Power Y : Special ordering
H : AC 80-260V, DC 80-330V
Communication Part
L : DC 20-60V
1 : RS-485
2 : RS-232
3 : RS-485 + RS-232
4 : RS-485 x 2
Y : Special ordering

Specification
Programmable measurements / Accuracy / Display readouts
Parameter Digital Display (maximum) Accuracy Phase1 Phase2 Phase3 Total Average
Vx3 5 (or 4) 9.9.9.9.9. V / KV 0.15% fs V1 V2 V3 VE
Ax3 5 (or 4) 9.9.9.9.9. A / KA 0.15% fs A1 A2 A3 AE
Watts 5 (or 4) 9.9.9.9.9. W / KW / MW / GW 0.25% fs W1 W2 W3 W
Vars 5 (or 4) 9.9.9.9.9. Var / KVar / MVar / GVar 0.25% fs Var1 Var2 Var3 Var
VA 5 (or 4) 9.9.9.9.9. VA / KVA / MVA / GVA 0.25% fs VA1 VA2 VA3 VAE
PF 4 0.9999 0.25% fs PF1 PF2 PF3 PF
WH 8 9.9.9.9.9.9.9.9. WH / KWH / MWH 0.8% rd WH
VarH 8 9.9.9.9.9.9.9.9. VarH / KVarH / MVarH 1% rd VarH
A0 5 (or 4) 9.9.9.9.9. A / KA 0.5% fs
Hz 5 (or 4) 70.000 0.03% rd
● Accuracy : Corresponding to each auto-range scale ● Accuracy performance range for WH / VarH / PF
● VL1 / VL2 / VL3 : Line to line voltage Cosθ : 1-0.5 for WH / PF
VP1 / VP2 / VP3 : Line to neutral voltage Sinθ : 1-0.5 for VarH
● PF1 / PF2 / PF3 : Related conversion elements Voltage ≧ 75V, Current ≧ 10% of rate
● A0 (neutral current, only for 3 phase 4 wires) ● Phase rotation
SEQ POST : positive sequence
SEQ NEG : negative sequence

HSIANG CHENG ELECTRIC CORP.


4F., No.11, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231, Taiwan (R.O.C.)
TEL : 886-2-29175865~9 FAX : 886-2-29173946 E-mail : expo.sales@hc.com.tw
POWER METER HC 6010
Input Display
☉ Range VFD/0.28"/green color, 3 rows of 9 alphanumeric
Voltage : 10 - 600V
Pulse output (PO) ..... option
Current : suitable for CT secondary rating (option)
☉ 4 pulse outputs photo-isolated (max.)
Maximum 6A for 5A rating
☉ Configurable Parameter, WH / VarH / VAH / AH
Maximum 1.2A for 1A rating
Unit, +1WH / +1QH / 1VAH / 0.01AH
Frequency : 40-70 Hz
☉ Pulse width / 50% duty cycle
☉ Burden

Voltage < 0.4VA at 600V Analog output (AO) ..... option


< 0.04VA at 150V ☉ 0.5% fs accuracy

Current < 0.1VA at rating ☉ 4 isolated analog outputs (maximum)

☉ Overload rating ☉ Standard output 4-20mAdc / load < 500Ω

Current Voltage ☉ Configurable Measured parameters

2 x rated continuous 750V continuous Input range, unipolar / bipolar


10 x rated 30 seconds 1000V 10 seconds Event logger
25 x rated 2 seconds 1200V 3 seconds 200 events with time-stamped
50 x rated 1 second Status change of switch input
Measured system Activation of setpoints / alarms
☉ Suitable for 3 phase 4 wires / 3 phase 3 wires / Operation of controlled relay output
single phase 2 & 3 wires / 3 phase balance Failure in self-test
☉ Select by input wiring & software configuration Programming access
Trace memory triggered
Programmability
Power ON / OFF
☉ Software accessible / password lock

☉ System selection : 3 phase 4 wires / 3 phase 3 Maximum / minimum logger


wires /1 phase 2 & 3 wires and 3 phase balance 20 parameters with time-stamped VP1, VP2, VP3,
☉ PT : 1 - 5000.0 ; CT : 1 - 65535 VPe, VL1, VL2, VL3, VLe, A1, A2, A3, A0, Ae, W, Var,
☉ Readout display control VA, F, PF, Vubl, Aubl
5 or 4 digits / auto scan or manual selection / RTC
scanning time Maximum deviation 5 sec in 24 hours
☉ Maximum demand 1 - 60 min Time for year / month / date / hour / minute / sec
☉ Maximum and minimum of instant measurement
Dielectric strength
☉ Communication
IEC 255-5
Baud rate 1200 / 2400 / 4800 / 9600 / 19200
2KV AC rms 1 minute between input/output/power
Address setting 1 - 254
☉ Calibration : software with password lock Impulse and surge test
☉ Memory : all of energy date and status setting ANSI/IEEE C37.90.1-1989 (3KV) SWC test
IEC 255-22-1 classⅢ SWC test
Communication port
IEC 255-22-4 classⅣ (IEC 801-4) SWC test
RS485 ; RS232
IEC 255-5 1.2 x 50us (5KV) impulse test
MODBUS® RTU protocol (two port maximum)

HSIANG CHENG ELECTRIC CORP.


4F., No.11, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231, Taiwan (R.O.C.)
TEL : 886-2-29175865~9 FAX : 886-2-29173946 E-mail : expo.sales@hc.com.tw
POWER METER HC 6010
Stability Power supply
Temperature range -25 to +55℃, ☉ AC 80 - 260V, 40 - 70 Hz, DC 80 - 330V

maximum 100 ppm/ ℃ DC 20 - 60V


Long term stability 0.15% drift maximum per year ☉ Dissipation maximum 12VA for AC and 6W for DC

Operating condition Mounting / Dimension


Temperature range -25 to +60℃, RH 20 - 95% Panel type mounting
non-condensed Size : 120 x 120 x 130.5 mm
Cut out : 92 x 92 mm
Storage condition
Temperature range -25 to +70℃, RH 20 - 95%
non-condensed

Dimension
120 138
18,5 83 18,5 21 98 19 91
14,5
11,1
16,5

AS A L BS BL C S C L X
Y
Z
Comm.
120

91
91
87

1 2 3 4 5 6 7 8 9 10 D E F

!
PA PB PC PN Power
16,5

9,5

14,5

CUT OUT
92x92mm

HSIANG CHENG ELECTRIC CORP.


4F., No.11, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231, Taiwan (R.O.C.)
TEL : 886-2-29175865~9 FAX : 886-2-29173946 E-mail : expo.sales@hc.com.tw
POWER METER HC 6010
Wiring
* 3P3W (2CT) * 3P4W2T
3 Phase 3 Wires Unbalance Load (2CT) 3 Phase 4 Wires Balance Load (2VT)
A S A L B S B L C S C L PA P B P C PN FG POWER A S A L B S B L C S C L PA P B P C PN FG POWER
+ - + -
L1 L1
L2 L2
L3 L3
Source Load
N
Source Load
* 3P3W (3CT) * 3P4W3T
3 Phase 3 Wires Unbalance Load (3CT) 3 Phase 4 Wires Unbalance Load (3VT)
A S A L B S B L C S C L PA P B P C PN FG POWER A S A L B S B L C S C L PA P B P C PN FG POWER
+ - + -
L1 L1
L2 L2
L3 L3
Source Load
** Setting system : 3 phase 4 wires 3VT N
Source Load
* 1P2W * 1P3W
1 Phase 2 Wires Unbalance Load 1 Phase 3 Wires Unbalance Load
A S A L B S B L C S C L PA P B P C PN FG POWER A S A L B S B L C S C L PA P B P C PN FG POWER
+ - + -
L1 L1
N N
Source Load
L2
Source Load
Note : * for power system setting display code.

Communication Port

RS-485 + RS-232 RS-485 x 2 RS-485 only RS-232 only


RS485 D+ D- NC RS485 D+ D- NC RS485 D+ D- NC RS232 RxD TxD SG
Comm1 X Y Z Comm1 X Y Z Comm1 X Y Z Comm1 X Y Z

RS232 RxD TxD SG RS485 D+ D- NC


Comm2 D E F Comm2 D E F

Output Port
POx4 or AOx4 POx2 + AOx2 POx1 + AOx3
1+ 1- 2+ 2- Shield + - + - Shield + - + - Shield
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
PO1 PO2 PO1 AO1
3+ 3- 4+ 4- Shield + - + - Shield + - + - Shield
6 7 8 9 10 6 7 8 9 10 6 7 8 9 10
AO1 AO2 AO2 AO3

HSIANG CHENG ELECTRIC CORP.


4F., No.11, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231, Taiwan (R.O.C.)
TEL : 886-2-29175865~9 FAX : 886-2-29173946 E-mail : expo.sales@hc.com.tw
POWER METER HC 6010

Applications
The HC 6010 PC tool a utility program that can help user to connect to “HC 6010 Power Transducer” rapidly.
The HC 6010 PC Tool is provided along with every HC 6010, which allows easy access to all meter setup
information and actual values via a personal computer running Windows 95/98 and one of the PC’s
communication ports (COM1 or COM2). The PC Tool is able to do the function as bellows:
☉ Program / Modify setup information
☉ Load / save setup information files from / to disk
☉ Read actual “Basic” value (current / voltage / power / frequency)
☉ Read actual “statistics” value (maximum/minimum/time of maximum/time of minimum
☉ Output control (Pulse output / Analog output)
The HC 6010 PC Tool can be used as stand-alone without a HC 6010 to create or edit HC 6010 setup
information file.

SCADA DCS PLC


System System
RTU

Test Set

RS-485 Modbus Communication Bus (RTU mode)

HC 6010 HC 6010 HC 6010 HC 6010 HC 6010

Communication Wiring
Computer
RS-485
D+ D-
Zt (*) R
(*) Terminating Impedance
at each end (typically)
120 ohm and 1nF C

Up to 32 devices Ground shield at SCADA /


maximum 4000 feet PLC / Computer only
(one end grounding) Shield

Twisted Pair
Shiled Cable

Zt (*)
R

D+ D- D+ D- D+ D-
RS-485 RS-485 RS-485
METER METER METER