3.1 Ozone Chemistry
3.1 Ozone Chemistry
3.1 Ozone Chemistry
OZONE
Ozone was first used for drinking water treatment in 1893 in the Netherlands. While being used
frequently in Europe for drinking water disinfection and oxidation, it was slow to transfer to the
United States. In 1987, the Los Angeles Aqueduct Filtration Plant was placed in service and now
treats up to 600 mgd of drinking water. In 1991, approximately 40 water treatment plants each
serving more than 10,000 people in the United States utilized ozone (Langlais et al., 1991). This
number has grown significantly, with Rice (in press) reporting that as of April 1998, 264 operating
plants in the United States use ozone. Most of these facilities are small: 149 plants are below 1 mgd.
Ozone is used in water treatment for disinfection and oxidation. Early application of ozone in the
United States was primarily for non-disinfection purposes such as color removal or taste and odor
control. However, since the implementation of the SWTR and proposal of the DBP rule, ozone
usage for primary disinfection has increased in the United States.
Ozone is a powerful oxidant, second only to the hydroxyl free radical, among chemicals typically
used in water treatment. Therefore, it is capable of oxidizing many organic and inorganic
compounds in water. These reactions with organic and inorganic compounds cause an ozone demand
in the water treated, which should be satisfied during water ozonation prior to developing a
measurable residual.
Ozone is sparingly soluble in water. At 20oC, the solubility of 100 percent ozone is only 570 mg/L
(Kinman, 1975). While ozone is more soluble than oxygen, chlorine is 12 times more soluble than
ozone. Ozone concentrations used in water treatment are typically below 14 percent, which limits
the mass transfer driving force of gaseous ozone into the water. Consequently, typical concentrations
of ozone found during water treatment range from <0.1 to 1mg/L, although higher concentrations can
be attained under optimum conditions.
Basic chemistry research (Hoigné and Bader, 1983a and 1983b; Glaze et al., 1987) has shown that
ozone decomposes spontaneously during water treatment by a complex mechanism that involves the
generation of hydroxyl free radicals. The hydroxyl free radicals are among the most reactive
oxidizing agents in water, with reaction rates on the order of 1010 - 1013 M-1 s-1, approaching the
diffusion control rates for solutes such as aromatic hydrocarbons, unsaturated compounds, aliphatic
alcohols, and formic acid (Hoigné and Bader, 1976). On the other hand, the half-life of hydroxyl free
radicals is on the order of microseconds, therefore concentrations of hydroxyl free radicals can never
reach levels above 10 –12 M (Glaze and Kang, 1988).
i.exe
3. OZONE
As shown in Figure 3-1 ozone can react by either or both modes in aqueous solution (Hoigné and
Bader, 1977):
O3
Indirect Oxidation of Substrate
Byproducts
by Hydroxyl Radical
Ozone Decomposition
via *OH
Radical Consumption by
Byproducts
HCO3-, CO3-2, etc.
The two oxidation pathways compete for substrate (i.e., compounds to oxidize). The direct oxidation
with aqueous ozone is relatively slow (compared to hydroxyl free radical oxidation) but the
concentration of aqueous ozone is relatively high. On the other hand, the hydroxyl radical reaction is
fast, but the concentration of hydroxyl radicals under normal ozonation conditions is relatively small.
Hoigné and Bader (1977) found that:
• Under acidic conditions, the direct oxidation with molecular ozone is of primary importance;
and
• Under conditions favoring hydroxyl free radical production, such as high pH, exposure to
UV, or addition of hydrogen peroxide, the hydroxyl oxidation starts to dominate.
This latter mechanism is used in advanced oxidation processes such as discussed in Chapter 7,
Peroxone, to increase the oxidation rates of substrates.
The spontaneous decomposition of ozone occurs through a series of steps. The exact mechanism and
reactions associated have not been established, but mechanistic models have been proposed (Hoigné
and Bader, 1983a and 1983b; Glaze, 1987). It is believed that hydroxyl radicals forms as one of the
intermediate products, and can react directly with compounds in the water. The decomposition of
ozone in pure water proceeds with hydroxyl free radicals produced as an intermediate product of
ozone decomposition, resulting in the net production of 1.5 mole hydroxyl free radicals per mole
ozone.
In the presence of many compounds commonly encountered in water treatment, ozone decomposition
forms hydroxyl free radicals. Ozone demands are associated with the following:
• Reactions with natural organic matter (NOM) in the water. The oxidation of NOM leads to
the formation of aldehydes, organic acids, and aldo- and ketoacids (Singer, 1992).
• Organic oxidation byproducts. Organic oxidation byproducts are generally more amenable to
biological degradation and can be measured as assimilable organic carbon (AOC) or
biodegradable dissolved organic carbon (BDOC).
• Synthetic organic compounds (SOCs). Some SOCs can be oxidized and mineralized under
favorable conditions. To achieve total mineralization, hydroxyl radical oxidation should
usually be the dominant pathway, such as achieved in advanced oxidation processes.
• Oxidation of bromide ion. Oxidation of bromide ion leads to the formation of hypobromous
acid, hypobromite ion, bromate ion, brominated organics, and bromamines (see Figure 3-2).
• Bicarbonate or carbonate ions, commonly measured as alkalinity, will scavenge the hydroxyl
radicals and form carbonate radicals (Staehelin et al., 1984; Glaze and Kang, 1988). These
reactions are of importance for advanced oxidation processes where the radical oxidation
pathway is predominant.
Figure 3-2. Reaction of Ozone and Bromide Ion Can Produce Bromate Ion and
Brominated Organics
3O2 ⇔ 2O3
Schönbein (Langlais et < biblio >) first discovered synthetic ozone through the electrolysis of
sulfuric acid. Ozone can be produced several ways, although one method, corona discharge,
predominates in the ozone generation industry. Ozone can also be produced by irradiating an
oxygen-containing gas with ultraviolet light, electrolytic reaction and other emerging technologies as
described by Rice (1996).
Corona discharge, also known as silent electrical discharge, consists of passing an oxygen-containing
gas through two electrodes separated by a dielectric and a discharge gap. Voltage is applied to the
electrodes, causing an electron flowthrough across the discharge gap. These electrons provide the
energy to disassociate the oxygen molecules, leading to the formation of ozone. Figure 3-3 shows a
basic ozone generator.
Atmosphere
Influent
Effluent
Ozone
Quench
(Option)
Ozone Gas
Ozone feed systems are classified as using air, high purity oxygen or mixture of the two. High purity
oxygen can be purchased and stored as a liquid (LOX), or it can be generated on-site through either a
cryogenic process, with vacuum swing adsorption (VSA), or with pressure swing adsorption (PSA).
Cryogenic generation of oxygen is a complicated process and is feasible only in large systems.
Pressure swing adsorption is a process whereby a special molecular sieve is used under pressure to
selectively remove nitrogen, carbon dioxide, water vapor, and hydrocarbons from air, producing an
oxygen rich (80–95 percent O2) feed gas. The components used in pressure swing adsorption
systems are similar to high pressure air feed systems in that both use pressure swing molecular
absorption equipment. Low pressure air feed systems use a heat reactivated desiccant dryer.
Oxygen Feed Systems - Liquid oxygen feed systems are relatively simple, consisting of a storage
tank or tanks, evaporators to convert the liquid to a gas, filters to remove impurities, and pressure
regulators to limit the gas pressure to the ozone generators.
Air Feed Systems - Air feed systems for ozone generators are fairly complicated as the air should be
properly conditioned to prevent damage to the generator. Air should be clean and dry, with a
maximum dew point of -60º C (-80º F) and free of contaminants. Air preparation systems typically
consist of air compressors, filters, dryers, and pressure regulators. Figure 3-5 is a schematic of large
scale air preparation system.
Particles greater than 1 µm and oil droplets greater than 0.05 µm should be removed by filtration
(Langlais et al., 1991). If hydrocarbons are present in the feed gas, granular activated carbon filters
should follow the particulate and oil filters. Moisture removal can be achieved by either compression
or cooling (for large-scale system), which lowers the holding capacity of the air, and by desiccant
drying, which strips the moisture from the air with a special medium. Desiccant dryers are required
for all air preparation systems. Large or small particles and moisture cause arcing which damages
generator dielectrics.
Typically, desiccant dryers are supplied with dual towers to allow regeneration of the saturated tower
while the other is in service. Moisture is removed from the dryer by either an external heat source or
by passing a fraction (10 to 30 percent) of the dried air through the saturated tower at reduced
pressure. Formerly, small systems that require only intermittent use of ozone , a single desiccant
tower is sufficient, provided that it is sized for regeneration during ozone decomposition time.
Air preparation systems can be classified by the operating pressure: ambient, low (less than 30 psig),
medium, and high (greater than 60 psig) pressure. The distinguishing feature between low and high
pressure systems is that high pressure systems can use a heatless dryer. A heatless dryer operates
normally in the 100 psig range, rather than the 60 psig range. Rotary lobe, centrifugal, rotary screw,
liquid ring, vane, and reciprocating compressors can be used in air preparation systems. Table 3-1
lists the characteristics of many of these types of compressors.
Reciprocating and liquid ring compressors are the most common type used in the United States,
particularly in small systems, the former because the technology is so prevalent and the latter because
liquid ring compressors do not need aftercoolers. Air receivers are commonly used to provide
variable air flow from constant volume compressors. Oil-less compressors are used in modern
systems to avoid hydrocarbons in the feed gas (Dimitriou, 1990).
Air
Desiccant Receiver
Filter Compressor Aftercooler Separator Dryer
Air
Rotary Screw 50 psi (single stage) to Variable with unloading Slightly more efficient than rotary lobe, draws
100 psi (2 stage) approximately 40% of full load power in
unloaded state, available in non-lubricated
design for larger capacities.
Liquid Ring 10–80 psi Constant volume Does not require lubrication or aftercooler,
relatively inefficient, common in United
States.
Vane High - to 100 psi Constant or variable Relatively inefficient, not common in U.S.
Table 3-2 presents a comparison of the advantages and disadvantages of each gas feed system.
Table 3-2. Comparison of Air and High Purity Oxygen Feed Systems
The voltage required to produce ozone by corona discharge is proportional to the pressure of the
source gas in the generator and the width of the discharge gap. Theoretically, the highest yield
(ozone produced per unit area of dielectric) would result from a high voltage, a high frequency, a
large dielectric constant, and a thin dielectric. However, there are practical limitations to these
parameters. As the voltage increases, the electrodes and dielectric materials are more subject to
failure. Operating at higher frequencies produces higher concentrations of ozone and more heat
requiring increased cooling to prevent ozone decomposition. Thin dielectrics are more susceptible to
puncturing during maintenance. The design of any commercial generator requires a balance of ozone
yield with operational reliability and reduced maintenance.
Two different geometric configurations for the electrodes are used in commercial ozone generators:
concentric cylinders and parallel plates. The parallel plate configuration is commonly used in small
generators and can be air cooled. Figure 3-6 shows the basic arrangement for the cylindrical
configuration. The glass dielectric/high voltage electrode in commercial generators resembles a
fluorescent light bulb and is commonly referred to as a “generator tube.”
Most of the electrical energy input to an ozone generator (about 85 percent) is lost as heat (Rice,
1996). Because of the adverse impact of temperature on the production of ozone, adequate cooling
should be provided to maintain generator efficiency. Excess heat is removed usually by water
flowing around the stainless steel ground electrodes. The tubes are arranged in either a horizontal or
vertical configuration in a stainless steel shell, with cooling water circulating through the shell.
Ozone generators are classified by the frequency of the power applied to the electrodes. Low
frequency (50 or 60 Hz) and medium frequency (60 to 1,000 Hz) generators are the most common
found in the water industry, however some high frequency generators are available. Table 3-3
presents a comparison of the three types of generators. Medium frequency generators are efficient
and can produce ozone economically at high concentrations, but they generate more heat than low
frequency generators and require a more complicated power supply to step up the frequency supplied
by utility power. New installations tend to use medium or high frequency generators.
Once ozone gas is transferred into water, the dissolved ozone reacts with the organic and inorganic
constituents, including any pathogens. Ozone not transferred into the process water during contacting
is released from the contactor as off-gas. Transfer efficiencies of greater than 80 percent typically are
required for efficient ozone disinfection (DeMers and Renner, 1992).
• Injectors; and
• Turbine mixers.
The bubble diffuser contactor is commonly used for ozone contacting in the United States and
throughout the world (Langlais et al., 1991). This method offers the advantages of no additional
energy requirements, high ozone transfer rates, process flexibility, operational simplicity, and no
moving parts. Figure 3-7 illustrates a typical three stage ozone bubble diffuser contactor. This
illustration shows a countercurrent flow configuration (ozone and water flowing in opposite
directions), an alternating cocurrent/countercurrent arrangement, and a cocurrent flow configuration
(ozone and water flowing in the same direction). Also, the number of stages can vary from two to six
for ozone disinfection, with the majority of plants using two or three chambers for contacting and
reaction (Langlais et al., 1991).
Bubble diffuser contactors are typically constructed with 18 to 22 ft water depths to achieve 85 to 95
percent ozone transfer efficiency. Since all the ozone is not transferred into the water, the contactor
chambers are covered to contain the off-gas. Off-gas is routed to an ozone destruct unit, usually
catalysts, thermal, or thermal/catalysts.
Influent
Ozone Gas
Influent
Ozone Gas
C. Cocurrent Contactor
Influent
Ozone Gas
Bubble diffuser contactors use ceramic or stainless steel diffusers that are either rod-type or disc-type
to generate bubbles. Design considerations for these diffusers (Renner et al., 1988) include:
The configuration of the bubble diffuser contactor structure should best be designed to provide plug
flow hydraulics. This configuration will minimize the overall volume of the contactor while still
meeting the CT requirements for the system. Contactor volume is determined in conjunction with the
applied ozone dosage and estimated residual ozone concentration to satisfy the disinfection CT
requirement.
Table 3-4 summarizes the advantages and disadvantages of the bubble diffuser contactor (Langlais et
al., 1991). Also, diffuser pore clogging can be a problem when ozone dosages are intermittent and/ or
when iron and manganese oxidation is required. Channeling of bubbles is dependent on the type of
diffusers used and the spacing between diffusers.
Injector Dissolution
The injector contacting method is commonly used in Europe, Canada, and the United States
(Langlais et al., 1991). Ozone is injected into a water stream under negative pressure, which is
generated in a venturi section, pulling the ozone into the water stream. In many cases, a sidestream of
the total flow is pumped to a higher pressure to increase the available vacuum for ozone injection.
After the ozone is injected into this sidestream, the sidestream containing all the added ozone is
combined with the remainder of the plant flow under high turbulence to enhance dispersion of ozone
into the water. Figure 3-8 illustrates typical in-line and sidestream ozone injection systems.
Ozone Gas
Off Gas
Influent
Contactor
Injector
Ozone Gas
Injector
Off Gas
The gas to liquid ratio is a key parameter used in the design of injector contacting systems. This ratio
should be less than 0.067 cfm/gpm to optimize ozone transfer efficiency (Langlais et al., 1991).
Meeting this criterion typically requires relatively low ozone dosages and ozone gas concentrations
greater than 6 percent by weight (DeMers and Renner, 1992). High concentration ozone gas can be
generated using a medium-frequency generator and/or liquid oxygen as the feed gas.
To meet the CT disinfection requirements, additional contact time is required after the injector,
typically in a plug flow reactor. The additional contact volume is determined in conjunction with the
applied ozone dosage and estimated residual ozone concentration to satisfy the disinfection CT
requirement.
Table 3-5 summarizes the advantages and disadvantages of injection contacting (Langlais et al.,
1991).
Turbine mixers are used to feed ozone gas into a contactor and mix the ozone with the water in the
contactor. Figure 3-9 illustrates a typical turbine contactor. The illustrated turbine mixer design
shows the motor located outside the basin, allowing for maintenance access. Other designs use a
submerged turbine.
Ozone transfer efficiency for turbine mixers can be in excess of 90 percent. However, the power
required to achieve this efficiency is 2.2 to 2.7 kW-hr of energy per lb of ozone transferred
(Dimitriou, 1990).
Turbine mixing basins vary in water depth from 6 to 15 ft, and dispersion areas vary from 5 to 15 ft
(Dimitriou, 1990). Again, as with injector contacting, sufficient contact time may not be available in
the turbine basin to meet disinfection CT requirements; consequently additional contact volume may
be required.
Table 3-6 summarizes advantages and disadvantages for the turbine mixer contactor (Langlais et al.,
1991).
Advantages Disadvantages
Ozone transfer is enhanced by high turbulence resulting in Require energy input
small bubble size
Contactor depth less than bubble diffusion Constant gas flow rate should be maintained, reducing ozone
transfer efficiency
Aspirating turbines can draw off-gas from other chambers for Maintenance requirements for turbine and motor
reuse
Eliminates diffuser clogging concerns
The concentration of ozone in the off-gas from a contactor is usually well above the fatal
concentration. For example, at 90 percent transfer efficiency, a 3 percent ozone feed stream will still
contain 3,000 ppm of ozone in the off-gas. Off-gas is collected and the ozone converted back to
oxygen prior to release to the atmosphere. Ozone is readily destroyed at high temperature (> 350° C
or by a catalyst operating above 100° C) to prevent moisture buildup. The off-gas destruct unit is
designed to reduce the concentration to 0.1 ppm of ozone by volume, the current limit set by OSHA
for worker exposure in an eight hour shift. A blower is used on the discharge side of the destruct unit
to pull the air from the contactor, placing the contactor under a slight vacuum to ensure that no ozone
escapes.
3.2.2.5 Instrumentation
Instrumentation should be provided for ozone systems to protect both personnel and the equipment.
Gas phase ozone detectors should be provided in spaces such as generator rooms where ozone gas
may be and personnel are routinely present. An ozone detector is also needed on the outlet from the
off-gas destruct unit to ensure the unit is working properly. These units should be interlocked with
the ozone generator controls to shut down the ozone generation system should excess ozone be
detected. A dew point detector on the feed gas supply just upstream of an ozone generator is
required to protect the generator from moisture in the feed gas (when air is the feed gas). Flow
switches on the cooling water supply are needed to protect the generator from overheating and a
pressure switch to prevent over pressurization.
Other instrumentation can be used to monitor and control the ozone process, although manual control
is adequate for small systems, but most small systems are designed to operate automatically,
particularly in remote areas. Ozone monitors can be used in conjunction with process flow meters to
match ozone dose to process demands and control ozone generation. Sophisticated control schemes
can be implemented to minimize the cost of dosing with ozone and reduce operator attention
requirements. Many systems include residual monitoring at various points in the contactor to
maintain a desired ozone residual and prevent energy-wasting overdosing.
Filters and desiccant in air preparation systems should be changed periodically, with the frequency
depending on the quality of the inlet air and the number of hours in operation. Compressors require
periodic service, depending on the type and operating time. LOX tanks should be periodically
pressure tested. Piping and contact chambers should be inspected periodically to check for leaks and
corrosion.
Dielectric tubes should be periodically cleaned. This operation should be performed when the
generator efficiency drops 10-15 percent. Cleaning the tubes is a delicate operation as the tubes are
fragile and expensive. Adequate space should be provided for the cleaning operation and for storage
of spare tubes.
• Disinfection;
• Organic micropollutant oxidation, including taste and odor compounds, phenolic pollutants, and
some pesticides; and
3.3.1.1 Disinfection
Ozone is a powerful oxidant able to achieve disinfection with less contact time and concentration
than all weaker disinfectants, such as chlorine, chlorine dioxide, and monochloramine (Demers and
Renner, 1992). However, ozone can only be used as a primary disinfectant since it cannot maintain a
residual in the distribution system. Thus, ozone disinfection should be coupled with a secondary
disinfectant, such as chlorine, chloramine, or chlorine dioxide for a complete disinfection system.
Ozone will oxidize iron and manganese, converting ferrous (2+) iron into the ferric (3+) state and 2+
manganese to the 4+ state. The oxidized forms will precipitate as ferric hydroxide and manganese
hydroxide (AWWA, 1990). The precise chemical composition of the precipitate will depend on the
nature of the water, temperature, and pH. The ozone dose required for oxidation is 0.43 mg/mg iron
and 0.88 mg/mg manganese (Langlais et al., 1991). Iron oxidizes at a pH of 6-9 but manganese is
more effective at a pH of around 8. Also, over-ozonation has no effect on iron, but will resolubilize
manganese, which then should be reduced to manganese dioxide downstream.
Ozone is used to oxidize/destroy taste and odor-causing compounds because many of these
compounds are very resistant to oxidation. Suffet et al. (1986) confirmed that ozone is an effective
oxidant for use in taste and odor treatment. They found ozone doses of 2.5 to 2.7 mg/L and 10
minutes of contact time (ozone residual of 0.2 mg/L) significantly reduced taste and odors in the
specific waters they tested. Most early U.S. water plants (i.e., 1940-1986) installed ozonation
specifically for taste and odor removal.
Early work on oxidation of DBP precursors seemed to indicate that the effects of ozonation, prior to
chlorination, were quite site-specific and unpredictable (Umphries et al., 1979). The key variables
that seem to determine ozone’s effect are dose, pH, alkalinity, and, above all, the nature of the
organic material. At low pH levels, precursor destruction by ozone is quite effective; however, above
some critical pH, ozone actually is less effective and in fact sometimes increases the amount of
chlorination byproduct precursors. For most humic substances this critical pH is 7.5, which is the
approximate level at which decomposition of ozone to hydroxyl free radicals increases rapidly, thus
increasing organic oxidation rates. Therefore, the implications that at lower pH (approximately 6-7),
at which molecular ozone predominates over the hydroxyl free radical, the initial THM precursor by-
products are different in nature than those formed by the hydroxyl free radicals oxidized at higher pH
levels. This is logical in light of the greater oxidation potential of the hydroxyl free radical over that
of ozone.
As alkalinity increases, it has a beneficial effect on THM formation potential (THMFP) (Langlais et
al., 1991). This is because alkalinity scavenges any hydroxyl free radicals formed during ozonation,
leaving molecular ozone as the sole oxidant, which is only capable of oxidizing organic precursors to
a lower oxidation sequence than does the hydroxyl free radical. Given neutral pH and moderate
levels of bicarbonate alkalinity, THMFP level reductions of 3 to 20 percent have been shown at
ozone doses ranging from 0.2 to 1.6 mg ozone per mg carbon (Singer et al., 1989; Georgeson and
Karimi, 1988).
Ozone can be effective in partially oxidizing organics in the water to biodegradable compounds that
can be removed by biological filtration (Demers and Renner, 1992). This partial oxidation gives rise
to lower molecular weight organics that are more easily biodegradable. This increase in the
biodegradable fraction of organic carbon occurs as a result of moderate to high levels of ozonation.
These ozone levels are typical of the doses commonly applied for disinfection.
Ozone has been reported by some to improve coagulation and filtration efficiency (Gurol and
Pidatella, 1993; Farvardin and Collins, 1990; Reckhow et al., 1993; Stolarik and Christie, 1997).
However, others have found no improvement in filter effluent turbidity due to ozonation (Tobiason et
al., 1992; Hiltebrand et al., 1986). Prendiville (1986) collected data from a large water treatment
plant showing that pre-ozonation was more effective than pre-chlorination to reduce filter effluent
turbidities. The cause of the improved coagulation is not clear, but several possibilities have been
offered (Reckhow et al., 1986), including:
Table 3-7. Criteria for Selecting Ozone Feed Points for Small Systems
Raw Water Quality Ozone Feed Point(s) Special Considerations
Category I Low ozone demand.
Turbidity < 10 NTU Raw Water or After Sedimentation Low disinfection byproducts.
Ozone Demand < 1mg/L Low biodegradable organics.
Category II Low ozone demand.
Turbidity > 10 NTU After Sedimentation High inorganic particulate.
Ozone Demand < 1mg/L Low biodegradable organics.
For high quality water with direct filtration, the only practical ozone feed point is the raw water.
Category II (Table 3-7) water is characterized by low ozone demand and high turbidity. This water
quality indicates the presence of inorganic material, such as clay or silt particles. For ozone to be
most effective for Category II water disinfection, it should be added after either pre-sedimentation or
conventional sedimentation.
Raw water with low turbidity and high ozone demand (Category III, Table 3-7) contains dissolved
constituents, not suspended, that contribute to a high ozone demand. An example of this type of
water is a ground water containing bromide ion, iron, manganese, color, or organics. For this water
quality, ozone can be added to either the raw water or after sedimentation. If the water contains
organic constituents that become more biodegradable by ozonation, a biological treatment step (see
Section 3.3.4) may be required. The presence of oxidizable organic constituents or bromide ion will
generate disinfection byproducts upon ozonation.
Category IV (Table 3-7) water would be considered the most difficult water to treat with ozone due
to its high turbidity and high ozone demand. An example of this water quality is surface water
containing high concentrations of organic material and inorganic particles. The most effective use of
ozone for this water quality is after sedimentation and possibly after filtration. If the water has an
extremely high ozone demand, dual ozone feed points may be required to achieve disinfection goals,
because the presence of large amounts of organic material may require a biological treatment step
and may generate disinfection byproducts.
• The use of ozone generates biodegradable organic matter (BOM) that can result in biological
growth which may also increase corrosion rates in distribution systems if not removed by
biologically active filtration. When ozonation is placed before biological filters, it can impact the
filters by increasing biological growth and increasing backwash frequency.
• Ozone is a strong oxidant that reacts with other oxidants, such as chlorine, chlorine dioxide, and
monochloramine.
• Ozone oxidation of iron and manganese generates insoluble oxides that should be removed by
sedimentation or filtration. These insoluble oxides also impact the filters by increasing load on
the filters and increasing backwash frequency.
• Using pre- and/or internal ozone on most raw waters reduces the subsequent chlorine, chlorine
dioxide, or monochloramine demand of the finished water so as to allow a stable chlorine-
compound residual to be maintained at a much lower level.
The reader is referred to EPA’s Simultaneous Compliance Guidance Document (expected to be
available in 1999) for additional information regarding the interaction between oxidants and other
treatment processes.
When ozonation is placed upstream of filtration, and environmental conditions such as dissolved
oxygen, pH, and temperature are favorable, microbiological activity is increased in the filter and
BDOC/AOC removal is enhanced. Ozone addition not only increases the biodegradability of the
dissolved organics, but also introduces large amounts of oxygen to the water, thus, creating an
excellent environment for biological growth on the filter media. The advantages of biologically
active filtration (Price, 1994) include the following which are all being met in most U.S. plants using
ozone:
• Production of a biologically stable water that does not promote excessive bacterial growth and
regrowth in the distribution system.
• Removal of NOM that can serve as precursors to byproduct formation as a result of residual
disinfection with free or combined chlorine.
• Ozone oxidation as a primary disinfectant prior to biologically active filtration reduces the
BDOC concentration in finished water, thus reducing chances of regrowth.
• Reduction of the residual disinfectant demand of the product water so that proposed regulations
limiting the maximum disinfectant residual can be met.
Biological activity can be supported on slow sand, rapid rate, and GAC media because these media
provide a surface for bacteria to attach. Factors such as available surface area, hydraulic loading rate,
contact time, availability of nutrients, temperature, and others will determine the performance and
BDOC removal efficiency. Biomass develops to higher levels on GAC because of the rougher
surface characteristics than on anthracite and sand.
Ozone addition prior to slow sand filtration can increase the efficiency of TOC removal by about 35
percent (Rachwal et al., 1988; Zabel, 1985). Ozone addition can also increase the efficiency of
BDOC removal with slow sand filters (Eighmy et al., 1991; Malley et al., 1993).
Research in the area of biologically active rapid rate filters has focused on the reduction of
assimilable organic carbon (AOC) instead of BDOC. While studies have shown rapid rate filtration,
employing either sand or dual media lowers AOC levels following ozonation, AOC does not measure
all the BDOC. AOC measures only that portion of the BDOC that is more easily assimilable or more
easily biodegradable under specific laboratory conditions by two specific microorganisms. Research
data shows that biodegradation of AOC can occur in rapid rate filters. The data should be viewed
with caution, since the more slowly biodegradable DOC, not measured by AOC, may be passing
through rapid rate filters.
GAC is made biologically active by the deliberate introduction of sufficient dissolved oxygen to
water just before passing through GAC columns (Katz, 1980). The high surface area and long
retention time in GAC provide an ideal environment to enhance biological growth.
Although ozone actually increases the amount of BDOC, the efficiency of subsequent biodegradation
on GAC can be such that the BDOC in GAC effluent is lower than the BDOC in the ozone influent
(Langlais et al., 1991). The degree to which biodegradable DOC is removed by ozone/GAC depends
upon the process conditions of temperature, amount of BDOC, and the GAC column loading rate,
measured by empty bed contact time (EBCT). For example, with an influent BDOC of 0.65 mg C/L
and a 10 minute EBCT, one would expect an effluent BDOC of 0.25 mg C/L. The effluent BDOC
then could be lowered by either:
• Adding ozone, which would increase the GAC influent BDOC and, therefore, lower the
effluent BDOC; or
• Adding more GAC or decreasing the loading rate, which would extend the EBCT and lower
the effluent BDOC (Billen et al., 1985, as cited in Langlais et al., 1991).
Huck et al. (1991) reported results from AOC profiles measured in a pilot treatment plant. The plant
treated Saskatchewan River water and included coagulation, flocculation, and sedimentation prior to
ozonation. Following ozonation, the water was filtered through a dual media (anthracite-sand) filter
followed by GAC adsorption. The results demonstrate:
• Variable AOC removal through coagulation, flocculation, and sedimentation (80 percent to
zero);
• Increased AOC after ozonation;
• AOC removal through dual media filtration improving at lower hydraulic loading rates and
filtered effluent AOC often less than raw water AOC, but highly variable; and
• AOC levels after GAC were low, almost always below raw water AOC concentrations and
adsorption appears to contribute to some immediate AOC removal.
The first site of action for virus inactivation is the virion capsid, particularly its proteins (Cronholm et
al., 1976 and Riesser et al., 1976). Ozone appears to modify the viral capsid sites that the virion uses
to fix on the cell surfaces. High concentrations of ozone dissociate the capsid completely. One
researcher found that the mechanism of ozone inactivation of bacteriophage f2 ribonucleic acid
(RNA) included releasing RNA from the phage particles after the phage coat was broken into many
pieces (Kim et al., 1980). This finding suggests that ozone breaks the protein capsid, thereby
liberating RNA and disrupting adsorption to the host pili. Further, the naked RNA may be
secondarily inactivated by ozone at a rate less than that for RNA within the intact phage. The
mechanism for inactivation of deoxyribonucleic acid (DNA) bacteriophage T4 has been found to be
quite similar to RNA inactivation: ozone attacks the protein capsid, liberates the nucleic acid, and
inactivates the DNA (Sproul et al., 1982). In contrast, more recent work on the tobacco mosaic virus
(TMV) shows that ozone has a specific effect on RNA. Ozone was found to attack both the protein
coat and RNA. The damaged RNA cross-links with amino acids of the coat protein subunits. The
authors concluded that TMV loses its infectivity because of its loss of protein coating.
The ability to maintain a high aqueous ozone concentration is critical from a regulatory disinfection
compliance standpoint. This means that factors that accelerate ozone decomposition are undesirable
for inactivation because the ozone residual dissipates faster and therefore reduces the CT credit,
requiring a corresponding increase in the ozone applied, thus increasing cost.
3.3.7.1 pH
Studies have indicated that pH has little effect on the ability of dissolved ozone residuals to inactivate
acid-fast bacteria, such as Mycobacteria and Actinomycetes (Farooq, 1976). A slight decrease has
been found in the virucidal efficacy of ozone residuals as pH decreased (Roy, 1979). However, the
opposite effect was observed by Vaughn et al. (1987) (cited in Hoff, 1986). Changes in disinfection
efficacy with variations in pH appear to be caused by the ozone decomposition rate. Ozone
decomposition occurs faster in higher-pH aqueous solutions and forms various types of oxidants with
differing reactivities (Langlais et al., 1991). Tests carried out at constant ozone residual
concentration and different pH values showed that the degree of microorganism inactivation
remained virtually unchanged (Farooq et al., 1977). More recent studies have indicated decreased
virus inactivation by ozone at alkaline pH (pH 8 to 9) for poliovirus 1 (Harakeh and Butler, 1984)
and rotaviruses SA-11 and Wa (Vaughn et al., 1987).
Inactivation of Giardia muris cysts was found to improve when the pH increased from 7 to 9
(Wickramanayake, 1984a). This phenomenon was attributed to the possible changes in cyst
chemistry making it easier for ozone to react with the cyst constituents at the higher pH levels.
However, the same study found that inactivation of Naegleria gruberi cysts was slower at a pH 9
than at lower pH levels, thereby indicating that pH effects are organism-specific.
3.3.7.2 Temperature
As temperature increases, ozone becomes less soluble and less stable in water (Katzenelson et al.,
1974); however, the disinfection and chemical oxidation rates remain relatively stable. Studies have
shown that although increasing the temperature from 0 to 30oC can significantly reduce the solubility
of ozone and increases its decomposition rate, temperature has virtually no effect on the disinfection
rate of bacteria (Kinman, 1975). In other words, the disinfection rate was found to be relatively
independent of temperature at typical water treatment plant operating temperatures despite the
reduction in solubility and stability at higher temperatures.
Ozone inactivation of viruses and bacteria contained in aluminum floc (in the size range comparable
to those that could typically escape filtration) was not reduced at floc turbidity levels of 1 and 5 NTU
(Walsh et al., 1980). This study demonstrated that the microorganisms received no protection from
the aluminum floc. Similar results have been obtained for poliovirus 1, coxsackie virus A9, and E.
coli associated with bentonite clay (Boyce et al., 1981). However, adsorption of the f2 bacteriophage
at 1 and 5 NTU of bentonite clay was found to retard the rate of inactivation of ozone (Boyce et al.,
1981).
In some instances, river waters heavily polluted with organic matter were ozonated, and the results
indicated a degradation of large organic molecules into fragments more easily metabolized by
microorganisms. This fragmentation coupled with the inability of ozone to maintain an active
concentration in the distribution system, has led to increased slime growth and, consequently, water
quality deterioration during distribution (Troyan and Hanson, 1989).
Ozone is very effective against bacteria. Studies have shown the effect of small concentrations of
dissolved ozone (i.e., 0.6 µg/L) on E. coli. (Wuhrmann and Meyrath, 1955) and Legionella
pneumophila (Domingue, et al., 1988). E. coli. levels were reduced by 4 logs (99.99 percent
removal) in less than 1 minute with a ozone residual of 9 µg/L at a temperature of 12oC. Legionella
pneumophila levels were reduced by greater than 2 logs (99 percent removal) within a minimum
contact time of 5 minutes at a ozone concentration of 0.21 mg/L. Results similar to those obtained
for E. coli. have been found for Staphyloccus sp. and Pseudomonas fluorescens inactivation.
Streptococcus faecalis required a contact time twice as long with the same dissolved ozone
concentration, and Mycobacterium tuberculosis required a contact time six times as long for the same
reduction level as E. coli.
In regard to vegetative bacteria, E. coli is one of the most sensitive types of bacteria. Furthermore,
significant difference has been found among all the Gram-negative bacillae, including E. coli and
other pathogens such as Salmonella, which are all sensitive to ozone inactivation. whereas the Gram-
positive cocci (Staphyloccus and Streptococcus), the Gram-positive bacillae (Bacillus), and the
Mycobacteria are the most resistant forms of bacteria. Sporular bacteria forms are always far more
resistant to ozone disinfection than vegetative forms (Bablon, et al., 1991), but all are easily
destroyed by relatively low levels of ozone.
Protozoan cysts are much more resistant to ozone and other disinfectants than vegetative forms of
bacteria and viruses. Giardia lamblia has a sensitivity to ozone that is similar to the sporular forms
of Mycobacteria. Both Naegleria and Acanthamoeba cysts are much more resistant to ozone (and all
other disinfectants) than Giardia cysts. (Bablon et al., 1991). CT products for 99 percent inactivation
of Giardia lamblia and N. gruberi at 5oC were 0.53 and 4.23 mg • min/L, respectively
(Wickramanayake et al., 1984a and 1984b). Data available for inactivation of Cryptosporidium
oocysts, suggest that among protozoans, this microorganism is more resistant to ozone (Peeters et al.,
1989; Langlais et al., 1990). One study found that Cryptosporidium oocysts are approximately 10
times more resistant to ozone than Giardia (Owens et al., 1994).
Typically, viruses are more resistant to ozone than vegetative bacteria but less resistant than sporular
forms of Mycobacteria (Bablon, et al., 1991). The most sensitive forms of viruses are phages, and
there seems to be little difference between the polio- and coxsackie viruses. The sensitivity of human
rotavirus to ozone was determined to be comparable to that of Mycobacteria and polio- and
coxsackie viruses (Vaughn et al., 1987).
Keller et al. (1974) studied ozone inactivation of viruses by using both batch tests and pilot plant
data. Inactivation of poliovirus 2 and coxsackie virus B3 was more than 3 logs (99.9 percent) in the
batch tests with an ozone residual of 0.8 mg/L and 1.7 mg/L and a contact time of 5 minutes. Greater
than 5 log (99.999 percent) removal of coxsackie virus was achieved in the pilot plant with an ozone
dosage of 1.45 mg/L, which provided an ozone residual of 0.28 mg/L in lake water.
CT values shown in Figure 3-9 are based on disinfection studies using in vitro excystation of Giardia
lamblia. CT values obtained at 5oC and pH 7 were used as the basis for deriving the CT values at
other temperatures. A safety factor of 2 has been applied to the values shown in Figure 3-9.
2.0
0.5-log Inactivation
1.8
1-log Inactivation
1.5-log Inactivation
1.6
2-log Inactivation
3-log Inactivation
1.2
1.0
0.8
0.6
0.4
0.2
0.0
5 10 15 20 25
Temperature (°C)
CT values shown in Figure 3-10 for achieving 2-log inactivation of viruses were determined by
applying a safety factor of 3 to data obtained from a previous study on poliovirus 1 (Roy et al.,
1982). CT values for 3 and 4-log removal were derived by applying first order kinetics and assuming
the same safety factor of 3. Data obtained at a pH of 7.2 was assumed to apply for the pH range of 6
to 9.
Several research groups have investigated the efficiency of ozone for Cryptosporidium oocyst
inactivation. Table 3-8 summarizes CT values obtained for 99 percent inactivation of
Cryptosporidium oocysts. Results indicate that ozone is one of the most effective disinfectants for
controlling Cryptosporidium (Finch, et al., 1994) and that Cryptosporidium muris may be slightly
more resistant to ozonation than Cryptosporidium parvum (Owens et al., 1994). A wide range of CT
values has been reported for the same inactivation level, primarily because of the different methods
of Cryptosporidium measurements employed and pH, temperature, and above all, ozonation
conditions.
1.2
2-log Inactivation
3-log Inactiviation
4-log Inactivation
1
0.8
CT Product (mg min/L)
0.6
0.4
0.2
0
5 10 15 20 25
Temperature (°C)
Ozone dose and contact time (CT) requirements for the inactivation of Cryptosporidium oocysts in
drinking water when using ozone has not been established similar to the CT values for viruses and
Giardia cyst inactivation. Inactivation requirements (log removals) for Cryptosporidium oocysts
have not been established. In addition, as shown in Table 3-8, the CT requirements reported in the
literature vary from study to study which adds uncertainty to design CT requirements for specific
applications or regulatory needs.
Although ozone is an effective oxidant and disinfectant, it should not be relied upon as a secondary
disinfectant to maintain a residual in the distribution system. Monochloramine is attractive for this
purpose because it produces little to no halogenated DBPs. Chlorine is a candidate for secondary
disinfectant but the ozonated water may actually produce either more or less DBPs following the
addition of free chlorine depending on the nature of the organic material following ozonation unless
biologically active filtration precedes the addition of chlorine. The principal benefit of using ozone
for controlling DBP formation is that it allows free chlorine to be applied later in the treatment
process after precursors have been removed and at lower doses, thereby reducing DBPFP.
NH3
NH2Br, NHBr2
Organic
Br- HOBr H+ + OBr
-
Brominated
O3 Precursors
pKa = 8.7 @ 25 C
o Organic DBPs
O3 + OBr-
BrO3-
Figure 3-11. Principal Reactions Producing Ozone Byproducts
observed when using chlorine as a secondary disinfectant with ozone (McKnight and Reckhow,
1992; Logsdon et al., 1992). The ozonation byproduct of acetaldehyde is a known precursor for
chloral hydrate, a byproduct of chlorination. Enhancement of chloral hydrate has not been observed
when monochloramine is applied as the secondary disinfectant, or if biologically active filtration is
used following ozonation and prior to chlorination (Singer, 1992). Chloropicrin formation from free
chlorine appears to be enhanced by pre-ozonation (Hoigné and Bader, 1988) in the absence of
biologically active filtration prior to addition of chlorine.
Byproducts such as aldehydes, ketones, acids, and others will be formed upon ozonation of water.
The primary aldehydes that have been measured are: formaldehyde, acetaldehyde, glyoxal, and
methyl glyoxal (Glaze et al., 1991). Total aldehyde concentration in drinking water disinfected with
ozone range from less than 5 µg/L to 300 µg/L, depending on the TOC concentration and the applied
ozone to organic carbon ratio (Van Hoof et al., 1985; Yamada and Somiya, 1989; Glaze et al., 1989a;
Krasner et al., 1989; Glaze et al., 1991; LeLacheur et al., 1991). Aldehydes with higher molecular
weights have also been reported (Glaze et al., 1989b). Other organic byproducts of ozonation are
indicated in Table 3-9
Ozonation of a source water containing bromide ion can produce brominated byproducts, the
brominated analogues of the chlorinated DBPs. Song et al. (1997) found that bromate ion formation
is an important consideration for waters containing more than 0.10 mg/L bromide ion. These
brominated byproducts include bromate ion, bromoform, the brominated acetic acids and
acetonitriles, bromopicrin, and cyanogen bromide (if ammonia is present). An ozone dose of 2 mg/L
produced 53 µg/L of bromoform and 17 µg/L of dibromoacetic acid in a water containing 2 mg/L of
bromide ion (McGuire et al., 1990). Ozonation of the same water spiked with 2 mg/L bromide ion
showed cyanogen bromide formation of 10 µg/L (McGuire et al., 1990). Furthermore, ozone may
react with the hypobromite ion to form bromate ion (Amy and Siddiqui, 1991; Krasner et al., 1993), a
probable human carcinogen (Regli et al., 1992). Bromate ion concentrations in ozonated water up to
60 µg/L have been reported (Amy and Siddiqui, 1991; Krasner et al., 1993). Note that the amount of
bromide ion incorporated into the measured DBPs accounts for only one-third of the total raw water
bromide ion concentration. This indicates that other brominated DBPs exist that are not yet
identified (Krasner et al., 1989; MWDSC and JMM, 1992). Figure 3-12 shows the major pathways
for bromate ion formation.
O3 O3
HOBr / BrO - Br - BrO -
HO• HO • O3
BrO • Br B rO 2−
Disproportionation O3 O3
B rO 2− BrO • BrO −
3
O3 Disproportionation
B rO 3− B rO 2−
O3
B rO 3−
Figure 3-12. Main Pathways of Bromate Ion Formation when Ozone Reacts
with Bromide Ion
The organic acid and aldehyde byproducts of ozonation discussed above appear to be readily
biodegradable and are a component of the assimilable organic carbon (AOC) or biodegradable
organic carbon (BDOC). Ozonation increases the BOM by oxidation. Therefore, if water disinfected
with ozone is coupled with a biologically active process (i.e., biological active carbon), removal of
these biodegradable byproducts can be reduced. The use of biologically active filters, maintained by
discontinuing the application of a disinfectant to the filters, has been shown to successfully remove
aldehydes and other compounds representing a portion of the BDOC in a water (Bablon et al., 1988;
Rittman, 1990; Reckhow et al., 1992). See Section 3.3.4 for a detailed discussion on biological
active filters.
A recent study has shown that bromate ion and brominated organics can be controlled during
ozonation by the following techniques (Song et al., 1997):
• Low pH decreases bromate ion formation while increasing brominated organic formation;
• Ammonia addition with short ozone contact time decreases both bromate ion and brominated
organic formation;
• Hydrogen peroxide decreases brominated organic formation and may increase or decrease
bromate ion formation, depending on other water quality parameters; and
• Low ozone DOC ratio leads to low bromate ion and brominated organic formation.
In addition, the ambient air in any ozone generating or handling room and ozone destruct off-gas are
monitored for ozone concentration to protect workers in the event of leakages or destruct system
failure.
The range of ozone concentrations to be measured in the gas phase varies from less than 0.1 ppm by
volume (0.2 mg/m3 NTP) in ambient air and ozone destruct off-gas, to 1 to 2 percent (10 g/m3 NTP)
in contactor off-gas, to as high as 15 percent by weight (200 g/m3 NTP) in the ozone generator
output.
• UV absorption;
• Iodometric methods;
• Chemiluminescence; and
• Gas-Phase titration.
Table 3-10 presents the working range, expected accuracy and precision, operator skill level
required, interferences, and current status for gas phase ozone analysis.
3.5.1.1 UV Absorption
Gaseous ozone absorbs light in the short UV wavelength region with a maximum absorbance at
253.7 nm (Gordon et al., 1992). Instruments for measuring ozone by the absorption of UV radiation
are supplied by several manufacturers for gas concentrations below 0.5 ppm by volume (1 g/m3
NTP). In general, these instruments measure the amount of light absorptions when no ozone is
present and the amount of light absorptions when ozone is present. The meter output is the difference
of the two readings, which is directly related to the actual amount of ozone present. The International
Ozone Association (IOA) has accepted this procedure (IOA, 1989).
Iodometric procedures have been used for all of the ozone concentration ranges encountered in water
treatment plants (Gordon et al., 1992). This includes measurement of ozone directly from the
generator and of ozone as stripped from aqueous solution. For the iodometric method, the ozone-
containing gas is passed into an aqueous solution containing excess potassium iodide.
All other oxidizing materials act as interferences with iodometry (Gordon et al., 1992). Nitrogen
oxides (that may be present when ozone is generated in air) also act as interferences to iodometric
methods. The effects of nitrogen oxides may be eliminated by passing the ozone-containing gas
through absorbents such as potassium permanganate that are specific for nitrogen oxide gases.
However, no iodometric method is recommended for the determination of ozone in solution because
of the unreliability of the method (Gordon et al., 1989).
3.5.1.3 Chemiluminescence
Chemiluminescence methods can be used for the determination of low concentrations of ozone in the
gas phase (Gordon et al., 1992). One of the most commonly used methods is ethylene
chemiluminescence. Gas-phase ozone can be measured using the chemiluminescent reaction between
ethylene and ozone. This method is specific to ozone and is suitable for measurement of ozone in the
ambient air. The ethylene chemiluminescence procedure was adopted in 1985 by the EPA as its
reference method for determining ozone in the ambient atmosphere (McKee et al., 1975).
Chemiluminescent instruments are approved by the EPA for monitoring ambient ozone
concentrations of 0 to 0.5 or 0 to 1.0 ppm by volume. With regular calibration, this type of
instrument is capable of providing reliable analysis of any ozone in the ambient air from an
ozonation plant.
Two gas-phase titration methods have been studied as possible calibration methods for ambient
ozone analyzers and monitors (Gordon et al., 1992). These procedures are based on titration with
nitric oxide and back titration of excess nitric oxide (Rehme et al., 1980). These gas phase titration
procedures, evaluated by EPA, were compared with UV absorption and iodometry as calibration
methods for ethylene chemiluminescent ambient air ozone analyzers. As a result of these
comparisons, UV absorption has been specified as the method of calibration for ambient ozone
analyzers. Therefore, gas-phase titration methods are not recommended for use at ozonation facilities
(Gordon et al., 1992).
Table 3-11 shows the working range, expected accuracy and precision, operator skill level required,
interferences and current status for liquid phase residual ozone analytical methods.
The indigo colorimetric method is the only method for monitoring residual ozone in Standard
Methods, 1995. The indigo colorimetric method is sensitive, precise, fast, and more selective for
ozone than other methods. There are two indigo colorimetric methods: spectrophotometric and
visual. For the spectrophotometric procedure the lower limit of detection is 2 µg/L, while for the
visual procedure the detection limit is 10 µg/L.
Hydrogen peroxide, chlorine, manganese ions, ozone decomposition products, and the products of
organic ozonation exhibit less interference with the indigo colorimetric method than any of the other
methods (Langlais et al., 1991). However, the masking of chlorine in the presence of ozone can make
the indigo method problematic. In the presence of hypobromous acid, which forms during ozonation
of bromide-ion containing methods, an accurate measurement cannot be made with this method
(Standard Methods, 1995).
ACVK is readily bleached by ozone, which serves as the basis for this spectrophotometric procedure
first reported by Masschelein (1977). The procedure has been developed further for the measurement
of ozone in the presence of chlorine (Ward and Larder, 1973).
Bis-(Terpyridine)Iron(II) in dilute hydrochloric acid solution reacts with ozone to change the
absorbance spectra measured at 552 nm (Tomiyasu and Gordon, 1984). The only known interferent
is chlorine. However, chlorine interferences can be masked by the addition of malonic acid.
Alternatively, since the reaction between chlorine and the reagent is slower than the reaction with
ozone, the spectrophotometric measurements can be carried out immediately after reagent mixing to
reduce the chlorine interference. Chlorine dioxide does not interfere (Gordon et al, 1992).
The primary advantages of the Bis-(Terpyridine)Iron(II) Method are its lack of interferences, low
limits of detection (4 µg/L), broad working range (up to 20 mg/L), excellent reproducibility, and
agreement with the indigo colorimetric method.
In this indirect procedure, residual ozone is stripped from the solution using an inert gas. The amount
of ozone present in the gas phase is then analyzed by gas-phase analytical methods such as UV
absorption or chemiluminescence described previously. This stripping technique was developed to
minimize the complications caused by the presence of other oxidants in solution.
The success of this procedure initially depends upon the ability to strip ozone from the treated water
without any decomposition. Since stripping conditions such as temperature, pH, and salinity can
vary, the reliability of this method is suspect (Langlais et al., 1991).
The DBPR provides reduced monitoring opportunities (i.e., quarterly rather than monthly samples) if the
system demonstrates that the average source water bromide concentration is less than 0.05 mg/L based
upon representative monthly bromide measurements for one year. Systems can remain on the reduced
monitoring schedule until the running annual average source water bromide concentration, computed
quarterly, is equal to or greater than 0.05 mg/L based upon representative monthly measurements.
For compliance monitoring for bromate, systems must use the ion chromatography analytical method as
specified in USEPA Method 300.1, Determination of Inorganic Anions in Drinking Water by Ion
Chromatography, Revision 1.0 (USEPA, 1997).
If the average of samples covering any consecutive four-quarter period exceeds the MCL, the system is in
violation of the MCL and must notify the public pursuant to 40 CFR §141.32. The system must also
report to the State pursuant to 40 CFR §141.134. If the system fails to complete 12 consecutive months'
monitoring, compliance with the MCL for the last four-quarter compliance period must be based on an
average of the available data.
Stolarik and Christie (1997) present the results of 10 years of operation at the 600 mgd Los Angeles
Aqueduct Filtration and Ozone Facility. Operational experiences at this facility showed lower
particle counts (greater than one micron) with ozone use. The optimum ozone concentration in the
gas phase applied was found to be 6 percent when using the cryogenic oxygen production facilities,
and 4 to 5 percent when using liquid oxygen (LOX).
Ozone-resistant materials include the austenitic (300 series) stainless steels, glass and other ceramics,
Teflon and Hypalon, and concrete. The 304 series stainless steels can be used for “dry” ozone gas
(also for oxygen), 316 series should be used for “wet” service. Wet service includes piping in the
contactors and all off-gas piping and the off-gas destruct unit. Teflon or Hypalon should be used for
gasket materials. Concrete should be manufactured from Type II or Type IV cement. Typical
practice in the United States is to provide 3 inches of cover for reinforcing to prevent corrosion by
either ozone gas or ozone in solution, although Fonlupt (1979) reports that 4 cm (1.13 inches) is
adequate for protection. Hatches for access into contactors should be fabricated from 316 series
stainless steels and provided with ozone-resistant seals.
Fuse failure and generator cleaning comprised the major maintenance chores on the ozone generators
during the first years. Fuse failure was caused by a malfunction when its glass dielectric tube failed.
Vessels are cleaned every three years or when exit gas temperatures rise due to Fe3O4 deposits on the
ground electrode/heat exchanger surfaces.
Rod shaped ceramic diffusers worked well as ozone diffusers for the initial two years. These were
replaced by sintered stainless steel and ultimately a modified ceramic diffuser.
Ozone generators should be housed indoors for protection from the environment and to protect
personnel from leaking ozone in the case of a malfunction. Ventilation should be provided to prevent
excess temperature rise in the generator room, and to exhaust the room in the case of a leak.
Adequate space should be provided to remove the tubes from the generator shell and to service the
generator power supplies. Air prep systems tend to be noisy; therefore, it is desirable to separate
them from the ozone generators. Off-gas destruct units can be located outside if the climate is not
too extreme. If placed inside, an ambient ozone detector should be provided in the enclosure. All
rooms should be properly ventilated, heated, and cooled to match the equipment-operating
environment.
Continuous monitoring instruments should be maintained to monitor levels of ozone in the rooms.
Self-contained breathing apparatuses should be located in hallways outside the rooms liable to ozone
hazards. Ambient ozone exposure levels, which have been proposed by appropriate U.S.
organizations, are summarized below. The maximum recommended ozone levels are as follows:
• American Industrial Hygiene Association. Maximum, concentration for eight hour exposure
of 0.1 mg/L (by volume).
There is a question of whether prolonged exposure to ozone may impair a worker’s ability to smell or
be aware of ozone levels at less than critical levels. Awareness of an odor of ozone should not be
relied upon. Instrumentation and equipment should be provided to measure ambient ozone levels and
perform the following safety functions:
• Initiate an alarm signal at an ambient ozone level of 0.1 mg/L (by volume). Alarms should
include warning lights in the main control panel and at entrances to the ozonation facilities as
well as audible alarms.
• Initiate a second alarm signal at ambient ozone levels of 0.3 mg/L (by volume). This signal
would immediately shut down ozone generation equipment and would initiate a second set of
visual and audible alarms at the control panel and at the ozone generation facility entrances. An
emergency ventilation system capable of exhausting the room within a period of 2 to 3 minutes
also would be interconnected to the 0.3 mg/L ozone level alarm.
Ozone gas is a hazardous gas and should be handled accordingly. Ambient ozone levels should be
monitored and equipment shut- down and alarmed when levels exceed 0.1 ppm. Emergency
ventilation is typically provided for enclosed areas. Building and fire codes will provide additional
guidance. The OSHA exposure limit for an 8-hour shift is 0.1 ppm by volume. The pungent odor of
ozone will provide warning to operators of any possible ozone leak.
3.7 Summary
3.7.1 Advantages and Disadvantages of Ozone Use
The following list highlights selected advantages and disadvantages of using ozone as a
disinfection method for drinking water (Masschelein, 1992). Because of the wide variation of
system size, water quality, and dosages applied, some of these advantages and disadvantages
may not apply to a particular system.
Advantages
• Ozone is more effective than chlorine, chloramines, and chlorine dioxide for inactivation of viruses,
Cryptosporidium, and Giardia.
• Ozone oxidizes iron, manganese, and sulfides.
• Ozone can sometimes enhance the clarification process and turbidity removal.
• Ozone controls color, taste, and odors.
• One of the most efficient chemical disinfectants, ozone requires a very short contact time.
• In the absence of bromide, halogen-substitutes DBPs are not formed.
• Upon decomposition, the only residual is dissolved oxygen.
• Biocidal activity is not influenced by pH.
Disadvantages
• DBPs are formed, particularly by bromate and bromine-substituted DBPs, in the presence of bromide,
aldehydes, ketones, etc.
• The initial cost of ozonation equipment is high.
• The generation of ozone requires high energy and should be generated on-site.
• Ozone is highly corrosive and toxic.
• Biologically activated filters are needed for removing assimilable organic carbon and biodegradable
DBPs.
• Ozone decays rapidly at high pH and warm temperatures.
• Ozone provides no residual.
Consideration Description
Generation Because of its instability, ozone should be generated at the point of
use. Ozone can be generated from oxygen present in air or high purity
oxygen. The feed gas source should be clean and dry, with a maximum
dewpoint of -60oC. Ozone generation consumes power at a rate of 8 to
17 kWhr/kg O3. Onsite generation saves a lot of storage space.
Primary uses Primary uses include primary disinfection and chemical oxidation. As an
oxidizing agent, ozone can be used to increase the biodegradability of
organic compounds destroys taste and odor control, and reduce levels
of chlorination DBP precursors. Ozone should not be used for
secondary disinfection because it is highly reactive and does not
maintain an appreciable residual level for the length of time desired in
the distribution system.
Inactivation efficiency Ozone is one of the most potent and effective germicide used in water
treatment. It is effective against bacteria, viruses, and protozoan cysts.
Inactivation efficiency for bacteria and viruses is not affected by pH; at
pH levels between 6 and 9. As water temperature increases, ozone
disinfection efficiency increases.
Byproduct formation Ozone itself does not form halogenated DBPs; however, if bromide ion
is present in the raw water or if chlorine is added as a secondary
disinfectant, halogenated DBPs, including bromate ion may be formed.
Other ozonation byproducts include organic acids and aldehydes.
Limitations Ozone generation is a relatively complex process. Storage of LOX (if
oxygen is to be the feed gas) is subject to building and fire codes.
Points of application For primary disinfection, ozone addition should be prior to
biofiltration/filtration and after sedimentation. For oxidation, ozone
addition can be prior to coagulation/sedimentation or filtration
depending on the constituents to be oxidized.
Safety considerations Ozone is a toxic gas and the ozone production and application facilities
should be designed to generate, apply, and control this gas, so as to
protect plant personnel. Ambient ozone levels in plant facilities should
be monitored continuously.
3.8 References
1. Alceon Corp. 1993. Overview of Available Information on the Toxicity of Drinking Water
Disinfectants and Their By-products. Cambridge, MA.
3. AWWA (American Water Works Association). 1990. Water Quality and Treatment. F.W.
Pontius (editor), McGraw-Hill, New York, NY.
4. Bablon, G.P., C. Ventresque, R.B. Aim. 1988. “Developing a Sand-GAC Filter to Achieve High
Rate Biological Filtration.” J. AWWA.80(12):47.
5. Bablon, G., et al. 1991. “Practical Application of Ozone: Principles and Case Studies.” Ozone in
Water Treatment Application and Engineering. AWWARF.
6. Billen, G., et al. 1985. Action des Populations Bactériennes Vis-á-Vis des Matiéres Organiques
dans les Filtres Biologiques. Report to Compagnie Genérale des Eaux, Paris.
7. Boyce, D.S., et al. 1981. “The Effect of Bentonite Clay on Ozone Disinfection of Bacteria and
Viruses in Water.” Water Res. 15:759-767.
8. Bringmann, G. 1954. “Determination of the Lethal Activity of Chlorine and Ozone on E. coli.”
Z. f., Hygiene. 139:130-139.
9. Chang, S.L. 1971. “Modern Concept of Disinfection.” J. Sanit. Engin. Division. 97:689-707.
10. Cronholm, L.S., et al.1976. “Enteric Virus Survival in Package Plants and the Upgrading of the
Small Treatment Plants Using Ozone.” Research Report No. 98, Water Resources Research
Institute, University of Kentucky, Lexington, KY.
11. DeMers, L.D. and R.C. Renner. 1992. Alternative Disinfection Technologies for Small Drinking
Water Systems. AWWARF and AWWA, Denver, CO.
12. Dimitriou, M.A. (editor). 1990. Design Guidance Manual for Ozone Systems. International
Ozone Association, Norwalk, CN.
13. Domingue, E. L., et al. 1988. “Effects of Three Oxidizing Biocides on Legionella pneumophila,
Serogroup 1.” Appl. Environ. Microbiol. 40:11-30.
14. Eighmy, T.T., S.K. Spanos, J. Royce, M.R. Collins, J.P. Malley. 1991. “Microbial Activity in
Slow Sand Filters.” Conference proceedings, Slow Sand Filtration Workshop, Timeless
Technology for Modern Applications, Durham, NH.
15. Farooq, S. et al.1977. “The Effect of Ozone Bubbles on Disinfection.” Progr. Water Ozone Sci.
Eng. 9(2):233.
16. Farooq, S. 1976. Kinetics of Inactivation of Yeasts and Acid-Fast Organisms with Ozone. Ph.D.
Thesis, University of Illinois at Urbana-Champaign, IL.
17. Farvardin, M.R. and A.G. Collins. 1990. “Mechanism(s) of Ozone Induced Coagulation of
Organic Colloids.” Conference proceedings, AWWA Annual Conference, Cincinnati, OH.
18. Finch, G. R., E.K. Black, and L.L. Gyürék. 1994. “Ozone and Chlorine Inactivation of
Cryptosporidium.” Conference proceedings, Water Quality Technology Conference, Part II, San
Francisco, CA.
19. Franson, M.H., Eaton, A.D., Clesceri, L.S., and Greenberg, A.E., (editors). 1995. Standard
Methods for the Examination of Water and Wastewater, Nineteenth Edition. American Public
Health Association, AWWA, and Water Environment Federation, Washington D.C.
20. Georgeson, D.L. and A.A. Karimi. 1988. “Water Quality Improvements with the Use of Ozone
at the Los Angeles Water Treatment Plant.” Ozone Sci. Engrg. 10(3):255-276.
21. Giese, A.C. and E. Christensen. 1954. “Effects of Ozone on Organisms.” Physiol. Zool. 27:101.
22. Glaze W.H., M. Koga, D. Cancilla. 1989a. “Ozonation Byproducts. 2. Improvement of an Aqueous-
Phase Derivatizition Method for the Detection of Formaldehyde and Other Carbonyl Compounds
Formed by the Ozonation of Drinking Water.” Environ. Sci. Technol. 23(7):838.
23. Glaze, W.H., M. Koga M., D. Cancilla, et al. 1989b. “Evaluation of Ozonation Byproducts from
Two California Surface Waters.” J. AWWA. 1(8):66.
24. Glaze, W.H., et al.1987. “The Chemistry of Water Treatment Processes Involving Ozone, Hydrogen
Peroxide, and Ultraviolet Radiation.” Ozone Sci. Engrg. 9(4):335.
25. Glaze, W.H., and J.W. Kang. 1988. “Advanced Oxidation Processes for Treating Groundwater
Contaminated with TCE and PCE: Laboratory Studies.” J. AWWA. 88(5):57- 63.
26. Glaze, W.H., H.S. Weinberg, S.W. Krasner, M.J. Sclimenti. 1991. “Trends in Aldehyde Formation
and Removal Through Plants Using Ozonation and Biological Active Filters.” Conference
proceedings, AWWA, Philadelphia, PA.
27. Goldstein, B.D., and E.M. McDonagh. 1975. “Effect of Ozone on Cell Membrane Protein
Fluorescence I. in vitro Studies Utilizing the Red Cell Membrane.” Environ. Res. 9:179-186.
28. Gordon, G. K. Rankness, D. Vornehm, and D. Wood. 1989. “Limitations of the Iodometric
Determination of Ozone.” J. AWWA. 81(6):72-76.
29. Gordon, G., W.J. Cooper, R.G. Rice, and G.E. Pacey. 1992. Disinfectant Residual Measurement
Methods, second edition. AWWARF and AWWA, Denver, CO.
30. Gurol, M.D. and M. Pidatella. 1983. “A Study of Ozone-Induced Coagulation.” Conference
proceedings, ASCE Environmental Engineering Division Specialty Conference. Allen Medine
and Michael Anderson (editors), Boulder, CO.
31. Haag, W.R. and J. Hoigné. 1984. “Kinetics and Products of the Reactions of Ozone with
Various Forms of Chlorine and Bromine in Water.” Ozone Sci. Engrg. 6(2):103-14.
32. Hann, V.A. 1956. “Disinfection of Drinking Water with Ozone.” J. AWWA. 48(10):1316.
33. Harakeh, M.S. and M. Butler. 1984. “Factors Influencing the Ozone Inactivation of Enteric
Viruses in Effluent.” Ozone Sci. Engrg. 6:235-243.
34. Hiltebrand, D.J., A.F. Hess, P.B. Galant, and C.R. O’Melia. 1986. “Impact of Chlorine Dioxide
and Ozone Preoxidation on Conventional Treatment and Direct Filtration Treatment Processes.”
Conference proceedings, AWWA Seminar on Ozonation: Recent Advances and Research
Needs, Denver, CO.
36. Hoigné J. and H. Bader. 1976. Role of Hydroxyl Radical Reactions in Ozonation Processes in
Aqueous Solutions, Water Res. 10: 377.
37. Hoigné J., and H. Bader. 1988. “The Formation of Trichloronitromethane (chloropicrin) and
Chloroform in a Combined Ozonation/Chlorination Treatment of Drinking Water.” Water Res.
22(3):313.
38. Hoigné J., and H. Bader. 1983b. “Rate Constants of Reaction of Ozone with Organic and
Inorganic Compounds in Water - II. Dissociating Organic Compounds.” Water Res. 17:185-194.
39. Hoigné J., and H. Bader. 1977. “The Role of Hydroxyl Radical Reactions in Ozonation
Processes in Aqueous Solutions.” Water Res. 10:377-386.
40. Hoigné J., and H. Bader. 1983a. “Rate Constants of Reaction of Ozone with Organic and
Inorganic Compounds in Water - I. Non-dissociating Organic Compounds.” Water Res. 17:173-
183.
41. Hoigné, J. and Bader, H. 1975. Ozonation of Water: Role of Hydroxyl Radicals as Oxidizing
Intermediates. Science, Vol. 190, pp. 782.
42. Huck, P.M., P.M. Fedorak, and W.B. Anderson. 1991. “Formation and Removal of Assimilable
Organic Carbon During Biological Treatment.” J. AWWA. 83(12):69-80.
43. IOA (International Ozone Association). 1989. Photometric Measurement of Low Ozone
Concentrations in the Gas Phase. Standardisation Committee--Europe.
44. Katz, J. 1980. Ozone and Chlorine Dioxide Technology for Disinfection of Drinking Water.
Noyes Data Corporation, Park Ridge, New Jersey.
45. Katzenelson, E., et al. 1974. “Inactivation Kinetics of Viruses and Bacteria in Water by Use of
Ozone.” J. AWWA. 66:725-729.
46. Keller, J.W., R.A. Morin, and T.J. Schaffernoth. 1974. “Ozone Disinfection Pilot Plants Studies
at Laconia, New Hampshire.” J. AWWA. 66:730.
47. Kim, C.K., et al. 1980. “Mechanism of Ozone Inactivation of Bacteriophage f2.” Appl. Environ.
Microbiol. 39:210-218.
48. Kinman, R.N. 1975. “Water and Wastewater Disinfection with Ozone: A Critical Review.” Crit.
Rev. Environ. Contr. 5:141-152.
49. Krasner, S.W., W.H. Glaze, H.S. Weinberg, et al. 1993. “Formation of Control of Bromate
During Ozonation of Water Containing Bromide.” J. AWWA. 85(5):62..
50. Krasner, S.W., et al. 1989. “The Occurrence of Disinfection By-products in US Drinking
Water.” J. AWWA.81(8):41.
51. Langlais, B., et al. 1990. “New Developments: Ozone in Water and Wastewater Treatment. The
CT Value Concept for Evaluation of Disinfection Process Efficiency; Particular Case of
Ozonation for Inactivation of Some Protozoa, Free-Living Amoeba and Cryptosporidium.”
Presented at the Int. Ozone Assn. Pan-American Conference, Shreveport, Louisiana, March 27-
29.
52. Langlais, B., D.A. Reckhow, and D.R. Brink (editors). 1991. Ozone in Drinking Water
Treatment: Application and Engineering. AWWARF and Lewis Publishers, Boca Raton, FL.
53. Langlais B. and D. Perrine. 1986. “Action of Ozone on Trophozoites and Free Amoeba Cysts,
Whether Pathogenic of Not.” Ozone Sci. Engrg. 8(3):187-198.
54. LeChevallier, M.W., W.C. Becker, P. Schorr, and R.G. Lee. 1992. “Evaluating the Performance of
Biologically Active Rapid Filters.” J. AWWA. 84(4):136-146.
55. LeLacheur, R.M., P.C. Singer, and M.J. Charles. 1991. “Disinfection By-products in New Jersey
Drinking Waters.” Conference proceedings, AWWA Annual Conference, Philadelphia, PA.
56. Logsdon, G.S., S. Foellmi, and B. Long. 1992. “Filtration Pilot Plant Studies for Greater
Vancouver’s Water Supply.” Conference proceedings, AWWA Annual Conference, Vancouver,
British Columbia.
57. Malley, J.P., T.T. Eighmy, M.R. Collins, J.A. Royce, and D.F. Morgan. 1993. “The True
Performance and Microbiology of Ozone - Enhanced Biological Filtration.” J. AWWA.
85(12):47-57.
58. Masschelein, W.J. 1992. "Unit Processes in Drinking Water Treatment." Marcel Decker D.C.,
New York , Brussels, Hong Kong.
59. Masschelein, W.J. 1977. “Spectrophotometric Determination of Residual Ozone in Water with
ACVK.” J. AWWA. 69:461-462.
60. McGuire, M.J., S.W. Krasner, and J. Gramith. 1990. Comments on Bromide Levels in State
Project Water and Impacts on Control of Disinfection Byproducts Metropolitan Water District
of Southern California.
61. McKee, H.C., R.E. Childers, and V.B. Parr 1975. Collaborative Study of Reference Method for
Measurement of Photochemical Oxidants in the Atmosphere, EPA EPA-650/4-75-016,
Washington, D.C. February.
62. McKnight A., and D.A. Reckhow. 1992. “Reactions of Ozonation Byproducts with Chlorine and
Chloramines.” Conference proceedings, AWWA Annual Conference, Vancouver, British
Columbia.
63. MWDSC and JMM (Metropolitan Water District of Southern California and James M.
Montgomery Consulting Engineers). 1992. “Pilot Scale Evaluation of Ozone and peroxone.”
AWWARF and AWWA, Denver, CO.
64. Morris, J.C. 1975. “Aspects of the Quantitative Assessment of Germicidal Efficiency.”
Disinfection: Water and Wastewater. J.D. Johnson (editor). Ann Arbor Science Publishers, Inc.,
Ann Arbor, MI.
65. Owens, J. H., et al. 1994. “Pilot-Scale Ozone Inactivation of Cryptosporidium and Giardia.”
Conference proceedings, Water Quality Technology Conference, Part II, San Francisco, CA.
66. Peeters, J. E. et al. 1989. “Effect of Disinfection of Drinking Water with Ozone or Chlorine
Dioxide on Survival of Cryptosporidium parvum Oocysts.” Appl. Environ. Microbiol.
55(6):1519-1522.
67. Perrine, D., et al. 1984. “Action d l’Ozone sur les Trophozoites d’Amibes Libres Pathogens ou
Non.” Bull Soc.Frnac. Parasitol. 3:81.
68. Prendiville, D.A. 1986. “Ozonation at the 900 cfs Los Angeles Water Purification Plant.” Ozone
Sci. Engrg. 8:77.
69. Price, M.L. 1994. Ozone and Biological Treatment for DBP Control and Biological Stability.
AWWARF and AWWA, Denver, CO, pp. 252.
70. Rachwal, A.J., et al. 1988. “Advanced Techniques for Upgrading Large Scale Slow Sand
Filters.” Slow Sand Filtration- Recent Developments in Water Treatment Technology, Ellis
Horwood Ltd, Chichester, U.K.
71. Reckhow, D.A., J.K. Edzwald, and J.E. Tobiason. 1993. “Ozone as an Aid to Coagulation and
Filtration.” AWWARF and AWWA, Denver, CO.
72. Reckhow, D.A., P.C.Singer, and R.R. Trussell. 1986. Ozone as a coagulant aid. Seminar
proceedings, Ozonation, Recent Advances and Research Needs, AWWA Annual Conference,
Denver, CO.
73. Reckhow, D.A., J.E. Tobiason, M.S. Switzenbaum, R. McEnroe, Y. Xie, X. Zhou, P.
McLaughlin, and H.J. Dunn. 1992. “Control of Disinfection Byproducts and AOC by Pre-
Ozonation and Biologically Active In-Line Direct Filtration.” Conference proceedings, AWWA
Annual Conference, Vancouver, British Columbia.
74. Regli, S., J.E. Comwell, X. Zhang., et al. 1992. Framework for Decision Making: An EPA
Perspective. EPA 811-R-92-005, EPA, Washington, D.C.
75. Rehme, K.A., J.C. Puzak, M.E. Beard, C.F. Smith, and R.J. Paur. 1980. Evaluation of Ozone
Calibration Procedures, EPA-600/S4-80-050, EPA, Washington, D.C, February.
76. Renner, R.C., M.C. Robson, G.W. Miller, and A.G. Hill. 1988. “Ozone in Water Treatment -
The Designer’s Role.” Ozone Sci. Engrg. 10(1):55-87.
77. Rice, R.G. 1996. Ozone Reference Guide. Electric Power Research Institute, St. Louis, MO.
78. Rice, R.G., P.K. Overbeck, K. Larson. 1998. Ozone Treatment for Small Water Systems.
Presented at the First International Symposium on Safe Drinking water in Small Systems. NSF
International/PAHP/WHO, Arlington, VA, May 10-13, 1998.
79. Riesser, V.W., et al. 1976. “Possible Mechanisms of Poliovirus Inactivation by Ozone.” Forum
on Ozone Disinfection, E. G. Fochtman, R.G. Rice, and M.E. Browning (editors), pp. 186-192,
International Ozone Institute, Syracuse, NY.
80. Rittman, B.E. 1990. “Analyzing Biofilm Processes Used in Biological Filtration.” J. AWWA.
82(12):62.
81. Roy, D. 1979. Inactivation of Enteroviruses by Ozone. Ph.D. Thesis, University of Illinois at
Urbana-Champaign.
82. Roy, D., R.S. Engelbrecht, and E.S.K. Chian. 1982. “Comparative Inactivation of Six
Enteroviruses by Ozone.” J. AWWA. 74(12):660.
83. Scott, D.B.M. and E.C. Lesher. 1963. “Effect of Ozone on Survival and Permeability of
Escherichia coli.” J. Bacteriol. 85:567-576.
84. Singer P.C. 1992. “Formation and Characterization of Disinfection Byproducts.” Presented at
the First International Conference on the Safety of Water Disinfection: Balancing Chemical and
Microbial Risks.
85. Singer, P.C., et al. 1989. “Ozonation at Belle Glade, Florida: A Case History.” Conference
proceeding, IOA Ninth Ozone World Conference.
86. Song, R., et al. 1997. “Bromate Minimization During Ozonation.” J. AWWA. 89(6):69.
87. Sproul, O. J., et al. 1982. “The Mechanism of Ozone Inactivation of Waterborne Viruses.”
Water Sci. Technol. 14:303-314.
88. Staehelin, J., R.E. Bühler, and J. Hoigné. 1984. “Ozone Decomposition in Water Studies by
Pulse Radiolysis. 2 OH and HO4 as Chain Intermediates.” J. Phys. Chem. 88:5999-6004.
89. Stolarik, G. F., and J.D. Christie. 1997. “A Decade of Ozonation in Los Angeles.” Conference
proceedings, IOA Pan American Group Conference, Lake Tahoe, NV.
90. Suffet, I.H., C. Anselme, and J. Mallevialle. 1986. “Removal of Tastes and Odors by
Ozonation.” Conference proceedings, AWWA Seminar on Ozonation: Recent Advances and
Research Needs, Denver, CO.
91. Tobiason, J.E., J.K. Edzwald, O.D. Schneider, M.B. Fox, and H.J. Dunn. 1992. “Pilot Study of
the Effects of Ozone and Peroxone on In-Line Direct Filtration.” J. AWWA. 84(12):72-84.
92. Tomiyasu, H., and G. Gordon. 1984. “Colorimetric Determination of Ozone in Water Based on
Reaction with Bis-(terpyridine)iron(II).” Analytical Chem. 56:752-754.
93. Troyan, J.J. and S.P. Hansen. 1989. Treatment of Microbial Contaminants in Potable Water
Supplies Technologies and Costs. Noyes Data Corporation, Park Ridge, New Jersey.
94. Umphries, M.D., et al. 1979. “The Effects of Pre-ozonation on the Formation of
Trihalomethanes.” Ozonews. 6(3).
95. USEPA. 1997. USEPA Method 300.1, Determination of Inorganic Anions in Drinking Water
by Ion Chromatography, Revision 1.0. EPA A/600/r-98/118.
96. Van Dijk, J.F.M., and R.A. Falkenberg. 1977. “The Determination of Ozone Using the Reaction
with Rhodamine B/Gallic Acid.” Presented at Third Ozone World Congress sponsored by the
IOA, Paris, France, May.
97. Van Gunten, U. and J. Hoigné. 1996. “Ozonation of Bromide-Containing Waters: Bromate
Formation through Ozone and Hydroxyl Radicals.” Disinfection By-Products in Water
Treatment , Minear, R.A. and G.L. Amy (editors). CRC Press, Inc., Boca Raton, FL.
98. Van Hoof, F., J.G. Janssens, H. van Dijck. 1985. “Formation of Mutagenic Activity During
Surface Water Pre-ozonation and Its Removal in Drinking Water Treatment.” Chemosphere,
14(5):501.
99. Vaughn, J.M., et al. 1987. “Inactivation of Human and Simian Rotaviruses by Ozone.” Appl.
Env. Microbiol. 53:2218-2221.
100. Walsh, D.S., et al. 1980. “Ozone Inactivation of Floc Associated Viruses and Bacteria.” J.
Environ. Eng. Div. ASCE. 106:711-726.
101. Ward, S.B. and D.W. Larder. 1973. “The Determination of Ozone in the Presence of Chlorine.”
Water Treatment Examination. 22:222-229.
102. Wickramanayake, G.B., et al. 1984b. “Inactivation of Giardia lamblia Cysts with Ozone.” Appl.
Env. Microbiol. 48(3):671-672.
103. Wickramanayake, G.B., et al. 1984a. “Inactivation of Naegleria and Giardia cysts in Water by
Ozonation.” J. Water Pollution Control Fed. 56(8):983-988.
104. Wickramanayake, G.B. 1984c. Kinetics and Mechanism of Ozone Inactivation of Protozoan
Cysts. Ph.D. dissertation, Ohio State University, Columbus, OH.
105. Wuhrmann, K., and J. Meyrath. 1955. “The Bactericidal Action of Ozone Solution. Schweitz.”
J. Allgen. Pathol. Bakteriol., 18:1060.
106. Yamada, H. and I. Somiya. 1989. “The Determination of Carbonyl Compounds in Ozonated
Water By the PFBOA Method.” Ozone Sci. Engrg. 11(2):127.
107. Zabel, T.F. 1985. “The Application of Ozone for Water Treatment in the United Kingdom -
Current Practice and Recent Research.” Ozone Sci. Engrg. 7(1):11.
OZONE..................................................................................................................................................................... 3-1
3.1 OZONE CHEMISTRY .................................................................................................................................... 3-1
3.2 OZONE GENERATION .................................................................................................................................. 3-4
3.2.1 Ozone Production .............................................................................................................................. 3-4
3.2.2 System Components .......................................................................................................................... 3-5
3.2.3 Operation and Maintenance ............................................................................................................. 3-15
3.3 PRIMARY USES AND POINTS OF APPLICATION OF OZONE ......................................................................... 3-16
3.3.1 Primary Uses of Ozone .................................................................................................................... 3-16
3.3.2 Points of Application ....................................................................................................................... 3-18
3.3.3 Impact on Other Treatment Processes ............................................................................................. 3-19
3.3.4 Biologically Active Filtration .......................................................................................................... 3-19
3.3.5 Pathogen Inactivation and Disinfection Efficacy............................................................................. 3-21
3.3.6 Inactivation Mechanisms ................................................................................................................. 3-22
3.3.7 Disinfection Parameters ................................................................................................................... 3-22
3.3.8 Inactivation of Microorganisms ....................................................................................................... 3-24
3.4 OZONATION DISINFECTION BYPRODUCTS ................................................................................................ 3-27
3.4.1 Ozone Byproduct Control................................................................................................................ 3-30
3.5 STATUS OF ANALYTICAL METHODS ......................................................................................................... 3-31
3.5.1 Monitoring of Gas Phase Ozone ...................................................................................................... 3-31
3.5.2 Monitoring of Liquid Phase Residual Ozone................................................................................... 3-35
3.5.3 Bromate Monitoring for Systems Using Ozone............................................................................... 3-37
3.6 OPERATIONAL CONSIDERATIONS ............................................................................................................. 3-38
3.6.1 Process Considerations .................................................................................................................... 3-38
3.6.2 Space Requirements......................................................................................................................... 3-38
3.6.3 Material Selection ............................................................................................................................ 3-39
3.6.4 Ozone System Maintenance............................................................................................................. 3-39
3.6.5 Ozone Safety.................................................................................................................................... 3-39
3.7 SUMMARY ................................................................................................................................................ 3-41
3.7.1 Advantages and Disadvantages of Ozone Use................................................................................. 3-41
3.7.2 Summary Table................................................................................................................................ 3-42
3.8 REFERENCES ............................................................................................................................................. 3-43
Table 3-1. Types of Compressors Used in Air Preparation Systems ........................................................................ 3-7
Table 3-2. Comparison of Air and High Purity Oxygen Feed Systems.................................................................... 3-8
Table 3-3. Comparison of Primary Characteristics of Low, Medium, and High Frequency Ozone Generators .... 3-10
Table 3-4. Bubble Diffuser Contactor Advantages and Disadvantages.................................................................. 3-12
Table 3-5. Injection Contacting Advantages and Disadvantages............................................................................ 3-13
Table 3-6. Turbine Mixer Contactor Advantages and Disadvantages .................................................................... 3-14
Table 3-7. Criteria for Selecting Ozone Feed Points for Small Systems ................................................................ 3-18
Table 3-8. Summary of Reported Ozonation Requirements for 99 Percent Inactivation of Cryptosporidium Oocycts
......................................................................................................................................................................... 3-27
Table 3-9. Principal Known Byproducts of Ozonation........................................................................................... 3-28
Table 3-10. Characteristics and Comparisons of Gas-Phase Ozone Analytical Methods....................................... 3-33
Table 3-11. Characteristics and Comparisons of Residual Ozone Analytical Methods ......................................... 3-36
Table 3-12. Summary of Ozone Disinfection Considerations ................................................................................ 3-42
Figure 3-1. Oxidation Reactions of Compounds (Substrate) During Ozonation of Water ....................................... 3-2
Figure 3-2. Reaction of Ozone and Bromide Ion Can Produce Bromate Ion and Brominated Organics.................. 3-3
Figure 3-3. Basic Ozone Generator .......................................................................................................................... 3-4
Figure 3-5. Schematic of an Air Preparation System ............................................................................................... 3-7