DESIGN CRITERIA

1. References:
Uniform Plumbing Code: (U.P.C)

Table # 11-1 (Metric)

Table # 11-2 (Metric)

2. Calculations are based on Rational Method to determine Run-


Off discharge intensity based on 75 mm/hr Rainfall Intensity
and Uniform Plumbing Code.

3. Formulations:
Storm Discharge: Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.

360 = Conversion Factor


Stack # 1:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 126.6 M²

A = 0.01266 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.01266) / 360


= 0.902 / 360
= 0.00250 M³/sec
= 2.5 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 126.6 M² with storm discharge of 2.5 L/S is Ø80mm.

For more safe we use Ø110mm pipe.


Stack # 2:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 66 M²

A = 0.0066 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.0066) / 360


= 0.470 / 360
= 0.00130 M³/sec
= 1.30 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 66 M² with storm discharge of 1.30 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 3:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 56.8 M²

A = 0.00568 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00568) / 360


= 0.4047 / 360
= 0.001124 M³/sec
= 1.12 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 56.8 M² with storm discharge of 1.12 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 4:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area ( 69.8 M² + 62.8 M²) = 125 M²

A = 0.0125 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.0125) / 360


= 0.8906 / 360
= 0.00247 M³/sec
= 2.47 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 125 M² with storm discharge of 2.47L/S is Ø80mm.

For more safe we use Ø110mm pipe.


Stack # 5:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 144.9 M²

A = 0.01449 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.01449) / 360


= 1.03 / 360
= 0.00286 M³/sec
= 2.86 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 144.9 M² with storm discharge of 2.86/S is Ø80mm.

For more safe we use Ø110mm pipe.


Stack # 6:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 44.7 M²

A = 0.00447 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00447) / 360


= 0.318 / 360
= 0.000883 M³/sec
= 0.883 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 44.7 M² with storm discharge of 0.883 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 7:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 44.7 M²

A = 0.00447 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00447) / 360


= 0.318 / 360
= 0.000884 M³/sec
= 0.8 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 44.7 M² with storm discharge of 0.8 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 8:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 186.2 M²

A = 0.01862 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.01862) / 360


= 1.32 / 360
= 0.00368 M³/sec
= 3.68 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 186.2 M² with storm discharge of 3.68 L/S is Ø80mm.

For more safe we use Ø110mm pipe.0


Stack # 9:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 53.8 M²

A = 0.00538 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00538) / 360


= 0.3833 / 360
= 0.001064 M³/sec
= 1.064 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 53.8 M² with storm discharge of 1.064 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 10:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 130 M²

A = 0.013 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.013) / 360


= 0.926 / 360
= 0.002572 M³/sec
= 2.57 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 130 M² with storm discharge of 2.57 L/S is Ø80mm.

For more safe we use Ø110mm pipe.


Stack # 11:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 69.12 M²

A = 0.006912 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.006912) / 360


= 0.4924 / 360
= 0.001368 M³/sec
= 1.36 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 69.12 M² with storm discharge of 1.36 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 12:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 68.2 M²

A = 0.00682 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00682) / 360


= 0.485 / 360
= 0.00134 M³/sec
= 1.34 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 68.2 M² with storm discharge of 1.34 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 13:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 44.9 M²

A = 0.00449 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00449) / 360


= 0.319 / 360
= 0.000888 M³/sec
= 0.888 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 44.9 M² with storm discharge of 0.888 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 14:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 145.1 M²

A = 0.01451 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.01451) / 360


= 1.0338 / 360
= 0.00287 M³/sec
= 2.871 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 145.1 M² with storm discharge of 2.87 L/S is Ø80mm.

For more safe we use Ø110mm pipe.


Stack # 15:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 125 M²

A = 0.0125 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00664) / 360


= 0.8906 / 360
= 0.002473 M³/sec
= 2.47 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 125 M² with storm discharge of 2.47 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 16:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area (95.6 M² + 77 M² + 33.1 M²) = 56.8 M²

A = 0.00568 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00568) / 360


= 0.4047 / 360
= 0.001241 M³/sec
= 1.12 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 56.8 M² with storm discharge of 1.12 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 17:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 126.8 M²

A = 0.01268 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.01268) / 360


= 0.9034 / 360
= 0.002509 M³/sec
= 2.50 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 126.8 M² with storm discharge of 2.50 L/S is Ø80mm.

For more safe we use Ø110mm pipe.


Stack # 18:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 66 M²

A = 0.0066 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.0066) / 360


= 0.4702 / 360
= 0.001306 M³/sec
= 1.30 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 66 M² with storm discharge of 1.30 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 19:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area (73.7 M² + 54.5 M²) = 41 M²

A = 0.0041 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.0041) / 360


= 0.292 / 360
= 0.000811 M³/sec
= 0.81 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 41 M² with storm discharge of 0.81L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Stack # 20:

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Area to be drained:

Area = 98.7 M²

A = 0.00987 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.00987) / 360


= 0.703 / 360
= 0.00195 M³/sec
= 1.95 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Vertical Rainwater piping at 10mm/m slope required to drain the area
of 98.7 M² with storm discharge of 1.95 L/S is Ø50mm.

For more safe we use Ø110mm pipe.


Sizing of Storm Main Line # 1

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Stacks connected to Storm Main Line # 1

(Stack # 1 + Stack # 2 + Stack # 3 + Stack # 4 )

Area to be drained:

Area (126.6 M² + 66 M² + 56.8 M² + = 374.4 M²

+ 125 M²)

A = 0.03744 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.03744) / 360


= 2.66 / 360
= 0.00741 M³/sec
= 7.41 L/S
As per the uniform plumbing code – Table # 11-2 (Metric) the nearest size
of Horizontal Rainwater piping at 10mm/m slope required to drain the
area of 374.4 M² with storm discharge of 7.41 L/S is Ø125mm.
For more safe we use Ø150mm pipe.
Sizing of Storm Main Line # 2

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Stacks connected to Storm Main Line # 2

(Stack # 5 + Stack # 6 + Stack # 7 + Stack # 8 + Stack # 9)

Area to be drained:

Area (144.9 M² + 44.7 M² + 44.7 M²


+ 186.2 M² + 53.8 M²) = 474.3 M²

A = 0.04743 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.04743) / 360


= 3.379 / 360
= 0.00938 M³/sec
= 9.38 L/S

As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Horizontal Rainwater piping at 10mm/m slope required to drain the
area of 474.3 M² with storm discharge of 9.38 L/S is Ø125mm.
For more safe we use Ø150mm pipe.
Sizing of Storm Main Line # 3(Free Discharge)

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Stacks connected to Storm Main Line # 3 (Storm Main Line # 1 + Storm


Main Line # 2 )

(Stack # 1 + Stack # 2 + Stack # 3 + Stack # 4 + Stack # 5 + Stack # 6 + Stack


# 7 + Stack # 8 + Stack # 9)

Area to be drained:

Area (126.6 M² + 66 M² + 56.8 M² + = 848.5 M²


125 M² + 144.9 M² + 44.7 M² +
44.7 M² + 186 M² + 53.8 M²)

A = 0.08485 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.08485) / 360


= 6.0455 / 360
= 0.016 M³/sec
= 16.7 L/S
As per the uniform plumbing code – Table # 11-2 (Metric) the nearest size
of Horizontal Rainwater piping at 10mm/m slope required to drain the
area of 848.5 M² with storm discharge of 16.7 L/S is Ø150mm.
Sizing of Storm Main Line # 4

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Stacks connected to Storm Main Line # 4

(Stack # 10 + Stack # 11 + Stack # 12 + Stack # 13 + Stack # 14)

Area to be drained:

Area (130 M² + 69.12 M² + 68.2 M² + = 457.32 M²

44.9 M² + 145.1 M²)

A = 0.045732 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.045732) / 360


= 3.258 / 360
= 0.0090511 M³/sec
= 9.05 L/S
As per the uniform plumbing code – Table # 11-2 (Metric) the nearest size
of Horizontal Rainwater piping at 10mm/m slope required to drain the
area of 457.32 M² with storm discharge of 9.05 L/S is Ø125mm.
For more safe we use Ø150mm pipe.
Sizing of Storm Main Line # 5

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Stacks connected to Storm Main Line # 5

(Stack # 15 + Stack # 16 + Stack # 17 + Stack # 18)

Area to be drained:

Area (125 M² + 56.8 M² + 126.8 M² + 66 M²) = 374.6 M²

A = 0.03746 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.03746) / 360


= 2.669 / 360
= 0.007413 M³/sec
= 7.41 L/S
As per the uniform plumbing code – Table # 11-1 (Metric) the nearest size
of Horizontal Rainwater piping at 10mm/m slope required to drain the
area of 374.6 M² with storm discharge of 7.41 L/S is Ø125mm.
For more safe we use Ø150mm pipe.

Sizing of Storm Main Line # 6(Free Discharge)

Storm Discharge (M³/sec):


Rational Formula
Q = CIA * 1/360

Q = Runoff discharge, M³/sec


C = Runoff coefficient
I = Rainfall Intensity, mm/hr
A = Drainage area in Hectares.
360 = Conversion Factor

Stacks connected to Storm Main Line # 6 (Storm Main Line # 4 + Storm


Main Line # 5 )

(Stack # 10 + Stack # 11 + Stack # 12 + Stack # 13 + Stack # 14 + Stack # 15 +


Stack # 16 + Stack # 17 + Stack # 18)

Area to be drained:

Area (130 M² + 69.12 M² + 68.2 M² + = 831.92 M²


44.9 M² + 145.1 M²+ 125 M² +
56.8 M² + 126.8 M² + 66 M²)

A = 0.083192 hectare

C = 0.95 for Roofs.

I = 75mm/hr

Q = (0.95 x 75 x 0.083192) / 360


= 5.9274 / 360
= 0.0164 M³/sec
= 16.46 L/S

As per the uniform plumbing code – Table # 11-2 (Metric) the nearest size
of Horizontal Rainwater piping at 10mm/m slope required to drain the
area of 831.92 M² with storm discharge of 16.46 L/S is Ø150mm.

You might also like