Test Report
Test Report
Test Report
PRD-2019-SU82
TEST REPORT OF
Explosion-proof Power Distribution Equipment
EN 60079-0:2018,
EN 60079-1:2014,
EN60079-7:2015+A1:2018,
EN 60079-31:2014
ANNEX 01 OF
ASSESSMENT REPORT N°PRD-2019-SU82
REVISION 0
ExTR Reference No. PRD-2019-SU82
Address ........................................ : No. 285 Shenghua Road, Huaishang District, Bengbu City, Anhui Province
Address ........................................ : No. 285 Shenghua Road, Huaishang District, Handan City, Anhui Province
flameproof requirements), inner components are Power meter, tachometer, temperature controlled meter,
etc. kinds of meters, Disconnecting switch, DC power, Current transformer, Surge protector, MCCB, MCB,
AC contactor, thermorelay, Time relay, intermediate relay, fuse, control transformer, PLC, soft starter,
frequency converter, terminal, Light-operated switch, Time control machine, etc., see the instruction;
2.3. Thread specifications: NPT thread and Metric thread of ISO standard; please specify thread
specification when ordering. Both steel pipe wiring and cable wiring are suitable for this product.
3. The detailed information and original record related to this product and sample are recorded in the test
record, SN: PRD-2019-SU82
Note:(1) The sample types of temperature test: see clause 26.5.1 of IEC60079-0:2011.
(2) The sample types of other tests are: EGKP-T
In accordance with OD 024, testing not fully performed by ExTL staff at the above ExTL address:
N/A
National differences considered as part of this evaluation, if any: N/A
Ex TEST REPORT
EN 60079-0
Explosive atmospheres – Part 0:
Equipment – General requirements
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
1 Scope
2 Normative references
4 Equipment grouping
5 Temperatures
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Small component temperature Not a small component.
5.3.3 for Group I or Group II electrical N/A
equipment
Circulating currents in
6.4 enclosures (e.g. of large No circulating current. N/A
electrical machines)
7.1 General
7.1.1 Applicability Spraying layer. Pass
7.1.2 Specification of materials
Refer to the documents provided by the
7.1.2.1 General Pass
manufacturer.
7.1.2.2 Plastic materials No plastic materials. N/A
The type of protection does not depend on
7.1.2.3 Elastomers the sealing gasket between the glass and the N/A
clamping ring .
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
7.2.2 Material selection No plastic material N/A
Alternative qualification of Alternative qualification of elastomeric sealing
7.2.3 N/A
elastomeric sealing O-rings O-ring is not used.
7.5 Accessible metal parts No accessible metal parts on the enclosure. N/A
9 Fasteners
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Ten M6x25 hexagon socket screws are used to
fasten the shell body and the cover. These
hexagon socket screws can only be removed by
the Allen wrench.
Ten M6x25 hexagon socket screws are used to
9.1 General Pass
fasten the shell body and clamping ring. These
hexagon socket screws can only be removed by
the Allen wrench.
All fasteners are made of stainless steel
0Cr18Ni9
13 Ex Components
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
14.4 Creepage and clearance Type of protection “d” and “tb”. N/A
15.3 Size of conductor connection See part IEC 60079-0 clause 15.1. Pass
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
16 Entries into enclosures
17.1 Ventilation
17.1.1 Ventilation openings No rotating machines. N/A
17.1.2 Materials for external fans No rotating machines. N/A
17.1.3 Cooling fans of rotating machines
17.1.3.1 Fans and fan hoods No rotating machines. N/A
Construction and mounting of
17.1.3.2 No rotating machines. N/A
the ventilating systems
Clearances for the ventilating
17.1.3.3 No rotating machines. N/A
system
17.1.4 Auxiliary motor cooling fans No rotating machines. N/A
17.1.5 Ventilating fans
17.1.5.1 Applicability No rotating machines. N/A
17.1.5.2 General No rotating machines. N/A
17.1.5.3 Fan and fan hoods No rotating machines. N/A
17.1.5.4 Construction and mounting No rotating machines. N/A
17.1.5.5 Clearances for rotating parts No rotating machines. N/A
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
17.2 Bearings No rotating machines. N/A
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Replacement of cells or
23.11 No cells or batteries. N/A
batteries
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
Compliance of prototype or The samples which were provided by
25 Pass
sample with documents manufacturer complay with the documents.
26 Type tests
The tests were carried out on the samples
26.1 General according to the standards IEC 60079-0,IEC Pass
60079-1 and IEC60079-31.
Tests were carried out under the most
26.2 Test configuration Pass
unfavourable consideration.
Explosive test mixtures used in tests comply
26.3 Tests in explosive test mixtures with the requirements of standard in Pass
IEC60079-1.
26.4 Tests of enclosures
26.4.1 Order of tests
The shell body and cover of enclosure is made Pass
of aluminium alloy. Test sequence of metallic
enclosure were as follows:
1. impact test
Metallic enclosures, metallic
26.4.1.1 parts of enclosures and glass 2. pressure test
parts of enclosures 3. IP test
4. tests of ability of the enclosure to withstand
pressure
5. test for non-transmission of an internal ignition
1.Encapsulation in the leading sheath. Pass
Non-metallic enclosures or non-
26.4.1.2 2.Cementing material between glass plate and
metallic parts of enclosures
shell body.
26.4.1.2.1 Group I electrical equipment Group II and group III equipment. N/A
Tests were performed in the following order:
1. thermal endurance to heat
2. thermal endurance to cold
3. impact test
Group II and Group III electrical 4. pressure test
26.4.1.2.2 Pass
equipment 5. IP test
6. tests of ability of the enclosure to withstand
pressure
7. test for non-transmission of an internal ignition
1. Place of impact: cover and shell body
Impact energy: 7J
Temperature: 23℃
Number of samples: 2
Times of impact: 1 for each place Pass
26.4.2 Resistance to impact
2. Place of impact: glass plate
Impact energy: 4J
Temperature:-45℃
Number of samples: 2
Times of impact: 1 for each sample
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
26.4.3 N /A
Drop test The equipment is stationary installed.
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
1. Power: 60W; test voltage: AC330V;
direction: upward 60° .
Position Temperature rise
(K)
Light-transmitting part 23
Branching point 11
Entry point 4
Surface on the LED 16
power body
bushing 15
Cementing material on 10
light-transmitting part
When the ambient temperature is 55℃, the
maximum surface temperature is 78℃,comply
with class T6.
When the ambient temperature is 40℃, the
maximum surface temperature is 63℃,comply
with class T6.
The temperature 55℃ at branching point is
66℃.
26.5.1.3 Maximum surface temperature The temperature 55℃ at entry point is 59℃. Pass
2. Power: 60W; test voltage: AC330V;
direction: downward 60°.
Position Temperature rise
(K)
Light-transmitting part 27
Branching point 12
Surface on the LED 20
power body
Bushing 17
Cementing material on 11
light-transmitting part
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
3 Power: 90W ; test voltage: AC330V;
direction: upward 60° .
Position Temperature rise
(K)
Light-transmitting part 31
Branching point 22
Surface on the LED 34
power body
Bushing 26
Cementing material on 24
light-transmitting part
When the ambient temperature is 55℃, the
maximum surface temperature is 86℃,comply
with class T5.
When the ambient temperature is 40℃, the
maximum surface temperature is 71℃,comply
with class T6.
The temperature 55℃ at branching point is
77℃.
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
26.6 Torque test for bushings
The wires go through the bushing and
26.6.1 Test procedure encapsulated by the epoxy resin. So the bushing N / A
can’t to subject to a torque test.
26.6.2 Acceptance criteria No torque applies on the bushing. N/A
Surface resistance test of parts The materials of enclosure are metallic and
26.13 of parts of enclosures of non- glass. N/A
metallic materials
Verification of ratings of
26.15 Ventilating fans are not included. N/A
ventilating fans
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
1. The over pressure test was carried on the
enclosure of light source compartment.
Test pressure: 0.83MPa.
Duration: 10s~12s.
27 Routine tests Pass
2. The over pressure test was carried on the
enclosure of power.
Test pressure: 1.3MPa.
Duration: 10s~12s.
28 Manufacturer's responsibility
29 Marking
29.3 General For the nameplate, see the cover of this report. Pass
Ex marking for explosive dust Ex tb IIIC T□ Db IP65, for the □, see general
29.5 Pass
atmospheres product information in the report cover.
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
The enclosure of EGKP-T- series is protected
29.7 Multiple types of protection Pass
by “d” and “tb” .
29.14 Cells and batteries Cells or batteries are not included. N/A
Converter-fed electrical
29.15 No converter-fed electrical machines. N/A
machines
30 Instructions
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
30.3 Electrical machines No electrical machines. N/A
Annex A
Supplementary requirements for cable glands N/A
(Normative)
A.1 General The Power Distribution Equipment do not N/A
contain cable glands.
A.2 Constructional requirements
A.2.1 Cable sealing The Power Distribution Equipment do not N/A
contain cable glands.
A.2.2 Filling compounds The Power Distribution Equipment do not N/A
contain cable glands.
A.2.3 Clamping
A.2.3.1 General The Power Distribution Equipment do not N/A
contain cable glands.
A.2.3.2 Group II or III cable glands The Power Distribution Equipment do not N/A
contain cable glands.
A.2.4 Lead-in of cable
A.2.4.1 Sharp edges The Power Distribution Equipment do not N/A
contain cable glands.
A.2.4.2 Point of entry The Power Distribution Equipment do not N/A
contain cable glands.
A.2.5 Released by a tool The Power Distribution Equipment do not N/A
contain cable glands.
A.2.6 Fixing The Power Distribution Equipment do not N/A
contain cable glands.
A.2.7 Degree of protection The Power Distribution Equipment do not N/A
contain cable glands.
A.3 Type tests
A.3.1 Tests of clamping of non-armoured and braided cables
A.3.1 Cable glands with
. clamping by the The Power Distribution Equipment do not N/A
1 sealing ring contain cable glands.
Cable glands with clamping by
A.3.1.2 The Power Distribution Equipment do not N/A
filling compound
contain cable glands.
Cable glands with clamping by
A.3.1.3 The Power Distribution Equipment do not N/A
means of a clamping device
contain cable glands.
A.3.1.4 Tensile test The Power Distribution Equipment do not N/A
contain cable glands.
A.3.1.5 Mechanical strength The Power Distribution Equipment do not N/A
contain cable glands.
A.3.2 Tests of clamping of armoured cables N/A
Tests of clamping where the
A.3.2.1 armourings are clamped by a The Power Distribution Equipment do not N/A
device within the gland contain cable glands.
A.3.2.1.1 Tensile test The Power Distribution Equipment do not N/A
contain cable glands.
A.3.2.1.2 Mechanical strength The Power Distribution Equipment do not N/A
contain cable glands.
IEC 60079-0
Clause Requirement – Test Result – Remark Verdict
A.4.1 Marking of cable glands The Power Distribution Equipment do not N/A
contain cable glands.
Marking of cable-sealing
A.4.2 The Power Distribution Equipment do not N/A
rings
contain cable glands.
Annex B
Requirements for Ex Components N/A
(Normative)
Annex C
Example of rig for resistance to impact test
(Informative)
Annex D
Motors supplied by converters
(Informative)
Annex E
Temperature rise testing of electric machines
(Informative)
Annex F
Guideline flowchart for tests of non-metallic enclosures or non-metallic parts of enclosures (26.4)
(Informative)
Page 1 of 19
ExTR Reference No.: PRD-2019-SU82.
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
1 Scope
2 Normative references
5 Flameproof joints
5.1 General requirements The joints of The Power Distribution Equipment Pass
comply with requirements of Clause
5 and are smeared with T039(A)wide –
temperature aircraft grease. Refer to technical
document provided by the manufacturer.
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
5.3 Threaded joints Position: two thread entries for cable gland(no Pass
plug)
Thread specification: M25
Thread pitbh: 1.5mm
Length of thread: 25mm
Number of full thread: 16
Metric thread complies with the requirements of
6g/6H fit tolerance and fulfils the requirements
of medium tolerance in ISO965-1 and ISO965-
3.
6 Sea joint
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
8.2 Bearings
8.2.1 Sleeve Bearings No shafts or bearings. N/A
8.2.2 Rolling-element bearings No shafts or bearings. N/A
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
11.1 Type of fastener See part IEC 60079-0 clauses 9.1 and 9.2. Pass
11.2 Plastic material or light alloys Plastic material or light alloys fasteners are not N/A
included.
11.3 Yield stress The property class of the M6 screws is A*-70. Pass
The warning words “CAUTION-USE
FASTENER W ITH YIELD STRESS≥
2
450N/mm ” are located in the nameplate.
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
11.8 Closing of through holes Through holes in the wall are not included. N/A
12 Materials
13.1 General There are two entries in the enclosure. The Pass
thread specification of entry is M25×1.5-6H,
which complies with the requirements of
tolerance. The thread specification of entry is
marked in the manual.
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
15 Type tests
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
15.1 General Carry out test on sample which has been Pass
subjected to the tests of enclosures in
accordance with IEC 60079-0. Samples were
tested according to the following sequence:
1.reference pressure measurement,
2.overpressure test,
3.test for non-transmission of an internal
ignition.
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
15.2.2.5 Apparatus intended for use in IIB+H2, for the nameplate, see the cover of this N/A
a single gas report.
15.2.3 Overpressure test
15.2.3.1 General 1. Test pressure for light source compartment Pass
was 0.84MPa.
Duration: 12s.
2. Test pressure for the power
compartment was 1.33MPa.
Duration: 11s.
No damage to the enclosure affecting the
explosion-proof performance has been found
after the tests.
15.2.3.2 Overpressure test - First See clause 15.2.3.1. Pass
method (static)
15.2.3.3 Overpressure test - Second First method N/A
method (dynamic)
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
15.3.3.5 Number of tests for single Test five times for the power compartment and Pass
piece production other five for light source compartment. The
explosions were not transmitted.
15.4.3.2 Acceptance criterion Breathing and draining devices are not N/A
included.
15.4.4 Tests for non-transmission of an internal ignition
15.4.4.1 General Breathing and draining devices are not N/A
included.
15.4.4.2 Test procedure Breathing and draining devices are not N/A
included.
15.4.4.3 Non-transmission test for breathing and draining devices
15.4.4.3.1 General Breathing and draining devices are not N/A
included.
15.4.4.3.2 Method A – Testing by Breathing and draining devices are not N/A
increased pressure included.
15.4.4.3.3 Method B – Testing by Breathing and draining devices are not N/A
oxygen enrichment of test included.
gases
15.4.4.4 Acceptance criterion Breathing and draining devices are not N/A
included.
16 Routine tests
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
16.1 General
16.1.1 Overview The Power Distribution Equipment are Pass
submitted to static
16.1.2 Routine overpressure test – overpressure
The test.
enclosures of the Power Distribution Pass
first method Equipment are submitted
to static overpressure test. Test pressure for
light source compartment is 0.84MPa. Test
pressure for the power compartment is
1.3MPa.
Test duration: 10s to 12s.
The routine test is considered satisfactory if the
enclosure suffers no permanent deformation or
damage affecting the explosion-proof
performance and the joints in no place are
permanently
First method enlarged.
was used.
16.1.3 Routine test – second N/A
method
16.1.4 Routine test – empty Routine overpressure test is carried out on the Pass
enclosure & parts of enclosure empty.
enclosure
16.5 Acceptance criteria After water pressure test, there is no damage to Pass
enclosure or permanent deformation on joints
that affecting the flameproof performance or no
leakage through the enclosure wall.
16.6 Batbh testing Each part of enclosure has been tested of Pass
pressure test, see drawing 1HRW 020 062,
1HRW 050 063, 1HRW 050 033
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
18.1 General Lamp holders or lamp caps are not parts of N/A
enclosure.
18.2 Device preventing lamps Lamp holders or lamp caps are not parts of N/A
working loose enclosure.
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
19.2 Resistance to tracking and No non-metalic material supporting live bare N/A
creepage distances on parts.
internal surfaces of the
enclosure walls
19.3 Requirements for type tests The explosion-proof Power Distribution N/A
Equipment is made by metal.
20 MARKING
20.2 Caution and warning The nameplate has the warning “Warning-after Pass
markings energizing, delay 15 minutes before opening”
and “CAUTION-USE FASTENER W ITH YIELD
2
STRESS≥450N/mm ”.
Annex A Additional requirements for crimped ribbon elements and multiple screen elements of breathing
(Normative) and draining devices
A.1 Crimped ribbon and multiple No crimped ribbon elements or multiple screen N/A
screen elements elements.
A.2 Path dimensions No crimped ribbon elements or multiple screen N/A
elements.
A.3 Annex B requirements No crimped ribbon elements or multiple screen N/A
elements.
A.4 Type tests No crimped ribbon elements or multiple screen N/A
elements.
Annex B Additional requirements for elements, with non-measurable paths, of breathing and draining
(Normative) devices
B.1 Sintered metal elements
B.1.1 Construction Non-measurable paths are not included. N/A
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
B.1.2 Bubble test pore size Non-measurable paths are not included. N/A
B.1.3 Density Non-measurable paths are not included. N/A
B.1.4 Open porosity and/or fluid Non-measurable paths are not included. N/A
permeability
B.1.5 Identification Non-measurable paths are not included. N/A
B.2 Pressed metal wire elements
B.2.1 Construction Non-measurable paths are not included. N/A
B.2.2 Specifications Non-measurable paths are not included. N/A
B.2.3 Bubble test pore size Non-measurable paths are not included. N/A
B.2.4 Density Non-measurable paths are not included. N/A
B.2.5 Open porosity and or fluid Non-measurable paths are not included. N/A
permeability
B.2.6 Identification Non-measurable paths are not included. N/A
B.3 Metal foam elements
B.3.1 Construction Non-measurable paths are not included. N/A
B.3.2 Chromium content Non-measurable paths are not included. N/A
B.3.3 Bubble test pore size Non-measurable paths are not included. N/A
B.3.4 Density Non-measurable paths are not included. N/A
B.3.5 Open porosity and/or fluid Non-measurable paths are not included. N/A
permeability
B.3.6 Identification Non-measurable paths are not included. N/A
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
IEC 60079-1
Clause Requirement – Test Result – Remark Verdict
Annex G Additional requirements for flameproof enclosures with an internal source of release
(Normative) (containment system)
G.1 General No internal source of release. N/A
G.2 Release conditions
G.2.1 No release No internal source of release. N/A
G.2.2 Limited release of a gas or No internal source of release. N/A
vapour
G.2.3 Limited release of a liquid No internal source of release. N/A
G.3 Design requirements for the containment system
G.3.1 General design requirements No internal source of release. N/A
G.3.2 Infallible containment system No internal source of release. N/A
G.3.3 Containment system with a No internal source of release. N/A
limited release
G.4 Type tests for the containment system
G.4.1 Overpressure test No internal source of release. N/A
G.4.2 Leakage test for an infallible No internal source of release. N/A
containment system
G.4.3 Leakage test for a No internal source of release. N/A
containment system with a
limited release
Annex H Requirements for machines with flameproof “d” enclosures fed from converters
(Normative)
H.1 General Not fed from converters. N/A
H.2 Construction requirements for Not fed from converters. N/A
bearings
H.3 Temperature requirements Not fed from converters. N/A
Standard.........................................: EN 60079-7:2015
Test procedure ...............................: EXTR
Test Report Form No. ....................: ExTR60079-7_4A
TRF Originator................................: EN60079-7:2015
Master TRF ....................................: dated2015- 08
Instructions for Intended Use of Ex Test Report:
This ExTR blank document is to be compiled and reviewed by the ExTL. The ExTR package in which this
ExTR is incorporated (comprised of a single ExTR document or multiple ExTR documents) is to be
accompanied by a single ExTR Cover Sheet, which is to be approved by the ExCB. ExTR Addendum(s)
and/or ExTR Report of National Differences may also supplement this ExTR.
Copyright © 2006 International Electrotechnical Commission Scheme for Certification to Standards
Relating to Equipment for use in Explosive Atmospheres (IECEx), Geneva, Switzerland. All rights
reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx is acknowledged as copyright owner and source of the material. IECEx takes no responsibility for
and will not assume liability for damages resulting from the reader's interpretation of the reproduced
material due to its placement and context.
Possible test case verdicts:
- test case does not apply to the test object ..................:N / A NA
- test object does meet the requirement ........................:Pass P
General remarks:
The tests results presented in this report relate only to the object tested.
This report shall not be reproduced except in full without the written approval of the testing laboratory.
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
1 SCOPE
2 NORMATIVE REFERENCES
4.1 General — P
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
4.2.2.1 General See drawing No. WM5HR 573 063.1~6(2P/3P P
assembly of plug core), WM5HR 573 066.1~
3(4P plug assembly), WM5HR 573 053.1~2(5P
assembly of plug core), WM5HR 906 005(screw
assembly);
WM5HR 552 231(2P/3P control switch),
WM5HR 573 065(4P assembly of socket core),
WM5HR 573 055(5P assembly of socket core),
WM5HR 906 005(screw assembly);
The connecting leads cross section are not
more than 2.5mm2.
The number and size of conductors that can be
safely connected have been specified in the
Operational Instruction.
4.2.2.2 Connections made using Terminals comply with IEC60947-7-1. P
terminals complying with IEC Test of terminals, see clause 6.9 of IEC60079-
60947-7-1, IEC 60947-7-2, IEC
7:2006 and clause 26.5.1 of IEC60079-0:2007.
60999-1, or IEC 60999-2
4.2.2.3 Field wiring connection facilities See IEC60079-7:2006 clause 4.2.2.2. P
integral to “e” apparatus or
components
4.2.2.4 Connections designed to be — NA
used with cable lugs and similar
devices
4.2.2.5 Connections using permanent — NA
arrangements
4.2.3 Factory connections
4.2.3.1 General — P
4.2.3.2 Field wiring connection methods — P
used for factory connections
4.2.3.3 Permanent connections See drawing No. : WM5HR 573 062.1~ P
6(2P/3P assembly of socket core), WM5HR 513
022.1~3(2/3P assembly of conducting rod),
WM5HR 573 064.1~3(4P socket assembly),
WM5HR 513 015.1~2 (4/5P assembly of
conducting rod), WM5HR 573 054(5P socket
assembly).
The wiring and conducting rod are mechanically
pressed together inside the socket.
4.2.3.4 Pluggable connections No pluggable connections NA
4.2.3.5 Terminal bridging connections — NA
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
4.4.2 Creepage distances between (see appended table 4.4) P
bare conductive parts at different PA66: CTI=500, see annex 22
potentials
PBT: CTI= 500, see annex 20
DMC-2: CTI= 500, see annex 26
E44: CTI= 475, see annex 28
4.4.3 Effects of ribs and grooves (see appended table 4.4) P
PA66: CTI=500, see annex 22
PBT: CTI= 500, see annex 20
DMC-2: CTI= 500, see annex 26
E44: CTI= 475, see annex 28
4.6 Windings
4.6.1 Insulated conductors to comply — NA
with either 4.6.1.1 or 4.6.1.2
4.6.1.1 Two layers of insulation — NA
4.6.1.2 Enamelled round winding wires — NA
4.6.2 Windings following fastening and — NA
wrapping
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
4.6.3 Minimum nominal conductor — NA
dimension
4.6.4 Sensing elements of RTDs — NA
4.10 Fasteners — NA
5.1 General — NA
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
5.2.4.4.1 Starting current ratio IA/IN shall — NA
be determined and marked
5.2.4.4.2 Winding temperature sensors — NA
associated with protective
devices
5.2.4.5 Converter-fed motors — NA
5.2.4.6 Information on thermal — NA
protection
5.2.5 Winding requirements — NA
5.2.6 Stator winding terminals — NA
5.2.7 Stator winding insulation system — NA
5.2.8 Bearing seals and shaft seals
5.2.8.1 Non-rubbing seals and labyrinths — NA
5.2.8.2 Rubbing seals — NA
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
5.3.7.8 Where provided, isolation switch — NA
shall de-energize each
lampholder when the protective
cover is removed
5.7 Batteries
5.7.1 Secondary batteries with capacity greater than 25 Ah
5.7.1.1 General — NA
5.7.1.2 Battery containers — NA
5.7.1.3 Cells — NA
5.7.1.4 Connections — NA
5.7.2 Primary and secondary batteries — NA
with capacity up to 25 Ah
5.7.3 Release of flammable gas — NA
5.7.4 Charging of cells — NA
5.7.5 Discharge of cells — NA
5.7.6 Incorporation of other types of — NA
protection
5.7.7 Disconnection and transportation — NA
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
5.8 General purpose connection and — NA
junction boxes
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
6.2.2 Test conditions required for — NA
rotating electrical machines
6.2.3 Additional tests for machines
6.2.3.1 Stator winding insulation system
6.2.3.1.1 Test required for motor — NA
components
6.2.3.1.2 Arrangements for stator — NA
connection cables
6.2.3.1.3 Insulation systems and — NA
connection cables
6.2.3.1.4 Insulation systems and — NA
connecting cables - Impulse test
6.2.3.2 Cage rotor construction
6.2.3.2.1 Tests to be carried out using a — NA
machine representative of a
finished machine
6.2.3.2.2 Ageing process of rotor cage — NA
6.2.3.2.3 Motors to be subjected to 10 — NA
direct-on-line uncoupled starts or
10 locked rotor tests
6.2.3.2.4 Maintenance of terminal voltage — NA
and hydrogen concentration
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
6.6.2 Insulation resistance
6.6.2.1 Test conditions — NA
6.6.2.2 Insulation resistance — NA
6.6.3 Shock test
6.6.3.1 General — NA
6.6.3.2 Test conditions — NA
6.6.3.3 Test procedure — NA
6.6.3.4 Acceptance criteria — NA
6.6.4 Test for ventilation of battery container
6.6.4.1 Determination of the maximum — NA
hydrogen concentration within
the battery container
6.6.4.2 Determination of hydrogen flow — NA
rate
6.6.4.3 Test Method — NA
6.6.4.4 Test Procedure — NA
6.6.4.5 The test to be carried out at least — NA
twice
6.6.4.6 Hydrogen concentration not to — NA
exceed 2 %
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
6.9 Terminal insulating material tests After the thermal endurance test of the terminal, P
a pulling force test to the conductor which size
is 2.5mm2, the pull is 50N, the conductor shall
not separate from clamp device, the terminal
assembly shall not separate from the terminal
insulator.
8 EX COMPONENT CERTIFICATES
8.1 General — NA
8.2 Terminals — NA
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
Number of cells..........................: — NA
Nominal voltage of cells............. : — NA
Rated capacity of cells...............: — NA
Duration of cell discharge .......... : — NA
WARNING - DO NOT CHARGE — NA
IN HAZARDOUS AREA.............:
Conductor range ........................: — NA
Rated voltage............................. : — NA
Operating temperature...............: — NA
9.2 Instructions for use
9.2.1 Battery operated apparatus No such design construction NA
Name of manufacturer or — NA
supplier or registered trademark
Manufacturer's type identification — NA
Number of cells — NA
Nominal voltage of the battery — NA
Rated capacity — NA
Charging instructions — NA
Safe operating conditions — NA
WARNING - REFER TO THE — NA
INSTRUCTION MANUAL FOR
BATTERY CHARGING
9.2.2 Terminals
Assigned torque value(s) See operational instruction P
Indication of rearrangement or — NA
adjustment to adapt to various
sizes of conductors
Instructions for proper conductor See operational instruction P
installation
Conductor insulation stripping See operational instruction P
requirements
9.2.3 Luminaires No such design construction NA
Bi-pin luminaires — NA
Screw-cap lamps — NA
9.2.4 Motors No such design construction NA
Routine maintenance and — NA
lubrication of bearings
Routine testing of insulated rotor — NA
bar insulation
9.3 Warning markings Has a warning marking: DO NOT OPEN WHEN P
ENERGIZED.
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
ANNEX A CAGE MOTORS- METHODS OF TEST AND OF CALCULATION
A.1 Temperature rise of the stator — NA
A.2 Temperature rise of the stator — NA
and rotor windings at rated
service
A.3 Determination of temperature — NA
rise in stalled motors
A.3.1 Ambient temperature and — NA
application of rated voltage and
rated frequency
A.3.2 Measurement of stator current — NA
A.3.3 Temperature rises in the rotor — NA
cage
A.3.4 Average temperature rise in the — NA
stator
A.3.5 Stalled motor test — NA
A.4 Calculation of temperature rise — NA
in stalled motors
A.4.1 Calculating the temperature of — NA
the short-circuited rotor
A.4.2 The rate of temperature rise — NA
A.5 Determination of time tE — NA
A.6 Motors designed for arduous — NA
starting conditions
A.7 Motors forming units with — NA
converters and the associated
protective devices
EN 60079-7
Clause Requirement – Test Result – Remark Verdict
B.4.2.2 Safety device sensing the — NA
temperature and at least one
other protective parameter
B.4.2.3 Safety device sensing a — NA
parameter other than the
temperature
B.4.3 Resistance heating unit of — NA
stabilized design
B.4.4 Heating device with temperature — NA
self-limiting characteristic
Clearance (cl) between circuit parts: Ur.m.s. a.c. or d.c. Required cl Measured cl
(V) (mm) (mm)
Type BCZ8060–16/250/3P
Control switch terminal 200~250(rated value 250) 5.0 13.0
Plug 200~250(rated value 250) 5.0 14.0
Socket 200~250(rated value 250) 5.0 20.0
Type BCZ8060–16/500/4P
Control switch terminal 480~500(rated value 500) 8.0 19.0
Plug 480~500(rated value 500) 8.0 14.0
Socket 480~500(rated value 500) 8.0 13.0
Type BCZ8060–16/415/5P
Control switch terminal 380~415(rated value 415) 6.0 19.0
Plug 380~415(rated value 415) 6.0 14.0
Socket 380~415(rated value 415) 6.0 13.0
Creepage (dcr) distance between Ur.m.s. a.c. or d.c. Required dcr Measured dcr
circuit parts: (V) (mm) (mm)
Type BCZ8060–16/250/3P
Control switch terminal 200~250(rated value 250) 8.0 13.0
Plug 200~250(rated value 250) 8.0 14.0
Socket 200~250(rated value 250) 8.0 20.0
Type BCZ8060–16/500/4P
Control switch terminal 480~500(rated value 500) 12.5 19.0
Plug 480~500(rated value 500) 12.5 14.0
Socket 480~500(rated value 500) 12.5 13.0
Type BCZ8060–16/415/5P
Control switch terminal 380~415(rated value 415) 10.0 19.0
Plug 380~415(rated value 415) 10.0 14.0
Socket 380~415(rated value 415) 10.0 13.0
supplementary information
Standard......................................... : EN 60079-31:2014
Test procedure ............................... : EXTR
Test Report Form Number ............. : ExTR60079-31_2A (released 2014-01)
Instructions for Intended Use of Ex Test Report:
An Ex Test Report provides a clause-by-clause documentation of the initial evaluation and testing that
verified compliance of an item or product with an IEC Ex standard. This Ex Test Report is part of an ExTR
package that may include other Ex Test Report, Addendum and National Differences documents, along with a
single ExTR Cover. An Ex Test Report is to be compi and reviewed by the ExTL. The Issuing ExCB
indicates final approval of the Ex Test Report as part of the overall ExTR package on the associated ExTR
Cover.
Copyright © 2014 International Electrotechnical Commission System for Certification to Standards
Relating to Equipment for use in Explosive Atmospheres (IECEx System), Geneva, Switzerland. All
rights reserved.
This blank publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEx System is acknow ged as copyright owner and source of the material. The IECEx system takes no
responsibility for, and will not assume liability for, damages resulting from the reader's interpretation of the
reproduced material due to its placement and context.
IEC 60079-31
Clause Requirement – Test Result – Remark Verdict
1 Scope
2 Normative references
4 General
4.1 Levels of protection tb Pass
Equipment groups and ingress
4.2 IP67 Pass
protection
4.3 Requirements for electrical equipment with level of protection “ta”
4.3.1 Fault current The level of protection of EGKP-T- is “tb”. N/A
4.3.2 Maximum surface temperature The level of protection of EGKP-T- is “tb”. N/A
4.3.3 Overpressure The level of protection of EGKP-T- is “tb”. N/A
4.3.4 Dust exclusion The level of protection of EGKP-T- is “tb”. N/A
4.3.5 Protective devices
4.3.5.1 General The level of protection of EGKP-T- is “tb”. N/A
4.3.5.2 Thermal protective devices The level of protection of EGKP-T- is “tb”. N/A
Protection for arcing and
4.3.6 The level of protection of EGKP-T- is “tb”. N/A
sparking parts
4.4 Requirements for electrical equipment with Level of Protection “tb” and “tb”
4.4.1 Maximum surface temperature See test report IEC60079-0 clause 5.3 Pass
4.4.2 Over pressure See clause 6.1.1.3. Pass
4.4.3 Dust exclusion See clause 6.1.1. Pass
5 CONSTRUCTION
5.1 Joints
5.1.1 General Refer to test report IEC60079-1 clause 5.3. Pass
Threaded entries comply with IEC 60079-31 Pass
5.1.2 Threaded joints
clause 5.3.2.
5.1.3 Gaskets and seals No gaskets. N/A
The width of cemented joint between the glass Pass
5.1.4 Cemented joints plate and shell body of Power Distribution
Equipment is 10mm.
Operating rods, spindles and
5.1.5 No operating rods, spindles and shafts. N/A
shafts
5.1.6 Windows
Windows employing a cemented The glass plate is cemented to the shell body. Pass
5.1.6.1
joint
IEC 60079-31
Clause Requirement – Test Result – Remark Verdict
Windows employing a gasket See part IEC 60079-31 clause 5.1.6.1. N/A
5.1.6.2
joint
5.2 Cable glands No cable glands. N/A
5.3 Entries
5.3.1 Plain entries See clause 5.3.2 N/A
Thread specification: M25 Pass
Thread pitbh: 1.5mm
5.3.2 Threaded entries Length of thread: 25mm
Number of full thread: 16
Tolerance class: 6H