Ufgs 21 13 17.00 10
Ufgs 21 13 17.00 10
Ufgs 21 13 17.00 10
SECTION 21 13 17.00 10
05/09
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.2.1 Hydraulic Design
1.2.1.1 Hose Demand
1.2.1.2 Basis for Calculations
1.2.2 Sprinkler Coverage
1.2.3 System Volume Limitations
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Fire Protection Specialist
1.4.2 Installer Qualifications
1.4.3 Shop Drawings
1.5 DELIVERY, STORAGE, AND HANDLING
1.6 EXTRA MATERIALS
PART 2 PRODUCTS
PART 3 EXECUTION
3.1 EXAMINATION
3.2 EARTHWORK
3.3 INSTALLATION REQUIREMENTS
3.4 INSPECTION BY FIRE PROTECTION SPECIALIST
3.5 ABOVEGROUND PIPING INSTALLATION
3.5.1 Protection of Piping Against Earthquake Damage
3.5.2 Piping in Exposed Areas
3.5.3 Piping in Finished Areas
3.5.4 Pendent Sprinklers Locations
3.5.5 Upright Sprinklers
3.5.6 Pipe Joints
3.5.7 Reducers
3.5.8 Pipe Penetrations
3.5.9 Escutcheons
3.5.10 Inspector's Test Connection
3.5.11 Drains
3.5.12 Installation of Fire Department Connection
3.5.13 Identification Signs
3.6 UNDERGROUND PIPING INSTALLATION
3.7 ELECTRICAL WORK
3.8 DISINFECTION
3.9 PIPE COLOR CODE MARKING
3.10 PRELIMINARY TESTS
3.10.1 Underground Piping
3.10.1.1 Flushing
3.10.1.2 Hydrostatic Testing
3.10.2 Aboveground Piping
3.10.2.1 Hydrostatic Testing
SECTION 21 13 17.00 10
**************************************************************************
NOTE: This guide specification covers the
requirements for dry pipe fire protection sprinkler
systems.
PART 1 GENERAL
**************************************************************************
NOTE: Because dry systems are slower in operation,
are less reliable, and require considerable and
critical maintenance, they should be limited in
application and used only in areas subject to
freezing. Areas that are not subject to freezing
should be protected with wet pipe sprinkler systems.
b. Sprinklers may be omitted from small rooms which are exempted for
specific occupancies in accordance with NFPA 101.
**************************************************************************
NOTE: Designer must ensure by calculation that a
sufficient number of systems is provided to limit
piping volume to less than 2800 liters (750 gallons).
**************************************************************************
Where the volume of any individual system piping volume exceeds 1890 L 500
gallons, provide the dry pipe valve with a quick-opening device. The
maximum system capacity controlled by one dry pipe valve shall not exceed
2800 L 750 gallons. Indicate the calculated volume of each system on the
Sprinkler System Shop Drawings.
1.3 SUBMITTALS
**************************************************************************
NOTE: Review submittal description (SD) definitions
in Section 01 33 00 SUBMITTAL PROCEDURES and edit
the following list to reflect only the submittals
required for the project. Submittals should be kept
to the minimum required for adequate quality control.
FM GLOBAL (FM)
NFPA 101 (2009; TIA 09-1; TIA 09-2) Life Safety Code
c. Design any portions of the sprinkler system that are not indicated
on the drawings or are not specified herein, including locating
sprinklers, piping, and equipment, and size piping and equipment. Base
the design of the sprinkler system on hydraulic calculations, and the
other provisions specified herein.
**************************************************************************
NOTE: Applications requiring multiple
densities/design areas must be referred to and shown
on the drawings.
Each dry pipe valve trim shall be provided with a local alarm device
consisting of a metal enclosure containing an alarm horn or bell, silence
switch, green power-on light, red low-air alarm light and amber trouble
light. Activate the alarm device by the low air pressure switch. Upon
reduction of sprinkler system pressure to approximately 70 kPa 10 psig
above the dry valve trip point pressure, the low air pressure switch shall
actuate the audible alarm device and a red low-air alarm light.
Restoration of system pressure shall cause the low-air alarm light to be
extinguished and the audible alarm to be silenced. An alarm silence switch
shall be provided to silence the audible alarm. An amber trouble light
shall be provided which will illuminate upon operation of the silence
switch and shall be extinguished upon return to its normal position.
**************************************************************************
NOTE: Electric waterflow alarms are preferred.
Coordinate type and location of waterflow alarm with
the electrical designer.
**************************************************************************
**************************************************************************
NOTE: Drawings must indicate and detail the
connection of the waterflow pressure switch, low air
and valve tamper switch to the building fire alarm
system or to the base-wide fire reporting system.
The pressure switch shall supervise the air pressure in system and shall be
set to activate at 70 kPa 10 psi above the dry pipe valve trip point
pressure. The switch shall have an adjustable range between 35 and 500 kPa
5 and 80 psi. The switch shall have screw terminal connection and shall be
capable of being wired for normally open or normally closed circuit.
**************************************************************************
NOTE: The designer will coordinate the desired
location of the fire department connection with and
verify the type of threads used by the fire
department serving the building where the sprinkler
system is being installed.
**************************************************************************
2.11 SPRINKLERS
**************************************************************************
NOTE: The designer will indicate on the contract
drawings the type of sprinkler heads for each area
if more than one type of sprinklers is to be
provided. Delete sprinkler types from this
paragraph that are not intended for use in the
system(s) used in the contract.
**************************************************************************
Pendent sprinkler heads shall be the dry pendent type, unless otherwise
indicated. Pendent sprinkler shall be of the fusible strut or glass bulb
type, [recessed] [quick-response] type with nominal [13 mm 1/2 inch] [13.5
mm 17/32 inch] orifice. Pendent sprinklers shall have a [polished chrome]
As-Built Drawings
Spare Parts
Sway Bracing
SD-07 Certificates
**************************************************************************
NOTE: Level IV may be selected where warranted by
system complexity.
**************************************************************************
Perform the work specified in this section under the supervision of and
certified by the Fire Protection Specialist who is a registered
professional engineer and a Full Member of the Society of Fire Protection
Engineers or who is certified as a Level [III] [IV] Technician by National
b. Floor plans drawn to a scale not less than 1:100 1/8" = 1'-0"
which clearly show locations of sprinklers, risers, pipe hangers,
seismic separation assemblies, sway bracing, inspector's test
connections, drains, and other applicable details necessary to
clearly describe the proposed arrangement. Indicate each type of
fitting used and the locations of bushings, reducing couplings,
and welded joints..
Submit spare parts data for each different item of material and equipment
specified. The data shall include a complete list of parts and supplies,
with current unit prices and source of supply, and a list of parts
recommended by the manufacturer to be replaced after 1 year and 3 years of
service. Include alist of special tools and test equipment required for
maintenance and testing of the products supplied.
PART 2 PRODUCTS
2.2 NAMEPLATES
**************************************************************************
NOTE: The drawings must show the service connection
details, the underground water mains for the
sprinkler system and details of the water service
point-of-entry into the building and through the
floor slab, and underground piping restraints,
including number and size of restraining rods and
thrust blocks.
**************************************************************************
2.4.1 Pipe
Piping from a point 150 mm 6 inches above the floor to [a point 1500 mm 5
feet outside the building wall] [the point of connection to the existing
water mains] shall be ductile iron with a rated working pressure of [1034]
[1207] [_____] kPa [150] [175] [_____] psi conforming to AWWA C151/A21.51,
with cement mortar lining conforming to AWWA C104/A21.4. Piping more than
1500 mm 5 feet outside the building walls shall comply with Section 33 11 00
WATER DISTRIBUTION.
**************************************************************************
NOTE: This paragraph will be deleted if underground
valves are either not required or are specified
elsewhere.
**************************************************************************
Gate valves for underground installation shall be of the inside screw type
with counter-clockwise rotation to open. Where indicating type valves are
shown or required, indicating valves shall be gate valves with an approved
indicator post of a length to permit the top of the post to be located 900
mm 3 feet above finished grade. Gate valves and indicator posts shall be
listed in UL Fire Prot Dir or FM APP GUIDE.
Joints and fittings shall be designed for not less than 1200 kPa 175 psi
service and shall be the product of the same manufacturer; segmented welded
fittings shall not be used. Fitting and coupling houses shall be malleable
iron conforming to ASTM A 47/A 47M, Grade 32510; ductile iron conforming to
ASTM A 536, Grade 65-45-12. Gaskets shall be of silicon compound and
approved for dry fire protection systems. Gasket shall be the flush type
that fills the entire cavity between the fitting and the pipe. Nuts and
bolts shall be heat-treated steel conforming to ASTM A 183 and shall be
cadmium plated or zinc electroplated.
2.5.4 Flanges
2.5.4.1 Bolts
Bolts shall be ASTM A 449, Type 1 and shall extend no less than three full
threads beyond the nut with bolts tightened to the required torque.
2.5.4.2 Nuts
Nuts shall be [hexagon type conforming to ASME B18.2.2] [ASTM A 193/A 193M,
Grade 5][ASTM A 563M ASTM A 563, Grade [C3] [DH3]].
2.5.4.3 Washers
Washers shall meet the requirements of ASTM F 436M ASTM F 436. Flat
circular washers shall be provided under all bolt heads and nuts.
Hangers shall be listed in UL Fire Prot Dir or FM APP GUIDE and of the type
suitable for the application, construction, and pipe type and size to be
supported.
2.5.6 Valves
**************************************************************************
NOTE: A control valve is required for control of
each individual sprinkler riser. The type of such
valves should be either the OS&Y or wall type
indicator post. Where multiple risers are supplied
from a single water service, riser control valves of
the OS&Y type should be located in a valve room with
exterior access. For more guidance on arrangement
of sprinkler control valves, refer to NFPA 13,
Appendix A.
**************************************************************************
Manually operated sprinkler control valve and gate valve shall be outside
stem and yoke (OS&Y) type and shall be listed in UL Bld Mat Dir or
FM APP GUIDE.
Check valve 50 mm 2 inches and larger shall be listed in UL Bld Mat Dir or
FM APP GUIDE. Check valves 100 mm 4 inches and larger shall be of the
swing type with flanged cast iron body and flanged inspection plate, shall
have a clear waterway and shall meet the requirements of MSS SP-71, for
Type 3 or 4.
**************************************************************************
NOTE: If sprinkler system air capacity does not
require the provision of a quick opening device,
delete the last sentence.
**************************************************************************
**************************************************************************
NOTE: Show the power supply to the air compressor
and to the low air pressure alarm device on the
drawings.
**************************************************************************
Provide an air supply system in accordance with NFPA 13. The connection
pipe from the air compressor shall not be less than 13 mm 1/2 inch in
diameter and shall enter the system above the priming water level of the
dry pipe valve. Install a check valve in the system supply air piping from
the compressor. A shutoff valve of the renewable disc type shall be
installed upstream of this check valve. The air supply system shall be
sized to pressurize the sprinkler system to [275] [_____] kPa [40] [_____]
psi within 20 minutes.
**************************************************************************
NOTE: Delete air compressor when not required.
**************************************************************************
System shall be configured so that each dry pipe system is equipped with a
separate pressure maintenance device, air compressor, shutoff valve, bypass
valve and pressure gauge. Piping shall be galvanized steel in accordance
with ASTM A 795/A 795M or ASTM A 53/A 53M.
Each dry pipe valve trim shall be provided with a local alarm device
consisting of a metal enclosure containing an alarm horn or bell, silence
switch, green power-on light, red low-air alarm light and amber trouble
light. Activate the alarm device by the low air pressure switch. Upon
reduction of sprinkler system pressure to approximately 70 kPa 10 psig
above the dry valve trip point pressure, the low air pressure switch shall
actuate the audible alarm device and a red low-air alarm light.
Restoration of system pressure shall cause the low-air alarm light to be
extinguished and the audible alarm to be silenced. An alarm silence switch
shall be provided to silence the audible alarm. An amber trouble light
shall be provided which will illuminate upon operation of the silence
switch and shall be extinguished upon return to its normal position.
**************************************************************************
NOTE: Electric waterflow alarms are preferred.
Coordinate type and location of waterflow alarm with
the electrical designer.
**************************************************************************
**************************************************************************
NOTE: Drawings must indicate and detail the
connection of the waterflow pressure switch, low air
and valve tamper switch to the building fire alarm
system or to the base-wide fire reporting system.
The pressure switch shall supervise the air pressure in system and shall be
set to activate at 70 kPa 10 psi above the dry pipe valve trip point
pressure. The switch shall have an adjustable range between 35 and 500 kPa
5 and 80 psi. The switch shall have screw terminal connection and shall be
capable of being wired for normally open or normally closed circuit.
**************************************************************************
NOTE: The designer will coordinate the desired
location of the fire department connection with and
verify the type of threads used by the fire
department serving the building where the sprinkler
system is being installed.
**************************************************************************
2.11 SPRINKLERS
**************************************************************************
NOTE: The designer will indicate on the contract
drawings the type of sprinkler heads for each area
if more than one type of sprinklers is to be
provided. Delete sprinkler types from this
paragraph that are not intended for use in the
system(s) used in the contract.
**************************************************************************
Pendent sprinkler heads shall be the dry pendent type, unless otherwise
indicated. Pendent sprinkler shall be of the fusible strut or glass bulb
type, [recessed] [quick-response] type with nominal [13 mm 1/2 inch] [13.5
mm 17/32 inch] orifice. Pendent sprinklers shall have a [polished chrome]
**************************************************************************
NOTE: The use of corrosion resistant sprinklers is
generally limited to industrial type occupancies
such as those involving electroplating, steam rooms,
salt storage, and piers and wharves.
**************************************************************************
2.12.2 Hypochlorites
2.13 ACCESSORIES
Guard shall be a steel wire cage designed to encase the sprinkler and
**************************************************************************
NOTE: Indicate piping, type of connection and
equipment, such as a test header with hose valves,
required for flow testing of the backflow preventer
at full system demand as required by NFPA 13.
Arrangement of test assembly should be coordinated
with the installation.
**************************************************************************
Double-check backflow prevention assembly shall comply with ASSE 1015. The
assembly shall have a bronze, cast-iron or stainless steel body with
flanged ends. The assembly shall include pressure gauge test ports and
OS&Y shutoff valves on the inlet and outlet, 2-positive-seating check valve
for continuous pressure application, and four test cocks. Assemblies shall
be rated for working pressure of [1034] [1207] [_____] kPa [150] [175]
[_____] psi. The maximum pressure loss shall be 40 kPa 6 psi at a flow
rate equal to the sprinkler water demand, at the location of the assembly.
A test port for a pressure gauge shall be provided both upstream and
downstream of the double check backflow prevention assembly valves.
PART 3 EXECUTION
3.1 EXAMINATION
After becoming familiar with all details of the work, verify all dimensions
in the field, and advise the Contracting Officer of any discrepancy before
performing the work.
3.2 EARTHWORK
Pipe joints shall conform to NFPA 13, except as modified herein. Not more
than four threads shall show after joint is made up. Welded joints will be
permitted, only if welding operations are performed as required by NFPA 13
3.5.7 Reducers
3.5.9 Escutcheons
**************************************************************************
NOTE: Designer will indicate location of the
inspector's test connections and all associated
valves on the contract drawings, and will provide
details of drain piping, if drain piping is needed.
**************************************************************************
3.5.11 Drains
Provide main drain piping to discharge [at a safe point outside the
building] [at the location indicated]. Auxiliary drains shall be provided
as indicated and as required by NFPA 13. When the capacity of trapped
sections of pipe is less than 11 L 3 gallons, the auxiliary drain shall
consist of a valve not smaller than 13 mm 1/2 inch and a plug or nipple and
cap. When the capacity of trapped sections of piping is more than 11 L 3
gallons, the auxiliary drain shall consist of two 25 mm 1 inch valves and
one 50 x 300 mm 2 x 12 inch condensate nipple or equivalent, located in an
accessible location. Tie-in drains shall be provided for multiple adjacent
trapped branch pipes and shall be a minimum of 25 mm 1 inch in diameter.
Tie-in drain lines shall be pitched a minimum of 13 mm per 3 m 1/2 inch per
10 feet.
Signs shall be affixed to each control valve, inspector test valve, main
drain, auxiliary drain, test valve, and similar valves as appropriate or as
required by NFPA 13. Hydraulic design data nameplates shall be permanently
affixed to each sprinkler riser as specified in NFPA 13.
**************************************************************************
NOTE: Restraint of the underground piping must be
detailed on the contract drawings.
**************************************************************************
The fire protection water main shall be laid, and joints anchored, in
accordance with NFPA 24. Minimum depth of cover shall be [900] [_____] mm
[3] [_____] feet. The supply line shall terminate inside the building with
a flanged piece, the bottom of which shall be set not less than 150 mm 6
inches above the finished floor. A blind flange shall be installed
temporarily on top of the flanged piece to prevent the entrance of foreign
matter into the supply line. A concrete thrust block shall be provided at
the elbow where the pipe turns up toward the floor. In addition, joints
shall be anchored in accordance with NFPA 24 using pipe clamps and steel
rods from the elbow to the flange above the floor and from the elbow to a
pipe clamp in the horizontal run of pipe. Buried steel components shall be
provided with a corrosion protective coating in accordance with AWWA C203.
Piping more than 1500 mm 5 feet outside the building walls shall meet the
requirements of Section 33 11 00 WATER DISTRIBUTION.
**************************************************************************
NOTE: Coordinate power and alarm requirements with
3.8 DISINFECTION
**************************************************************************
NOTE: If government laboratory facilities are
available to conduct the bacterial examination of
the test samples, revise this paragraph
accordingly. The option of having the Contracting
Officer perform the sampling and testing will be
selected only if Government laboratory facilities
are available and with concurrence from appropriate
laboratory personnel. At some locations, either
county or installation health officers inspect the
disinfection process. If this is required, add a
notification requirement and give it to the office
to be notified, including phone number. For
modification of existing systems, provide special
procedures for disinfection of new equipment.
**************************************************************************
After all system components are installed and hydrostatic test(s) are
completed, the entire sprinkler system shall be disinfected. Flush all
sprinkler system piping with potable water until any entrained dirt and
other foreign materials have been removed before introducing chlorinating
material. Remove the flushing fitting of each cross main and of each grid
branch line and then back-flush through the sprinkler main drain.
**************************************************************************
NOTE: Designer will coordinate color code marking
with Section 09 90 00 PAINTS AND COATINGS. Color
code marking for piping which are not listed in
Table I of Paragraph 3.5 Pipe Color Code Marking of
Section 09 90 00 will be added to the table.
**************************************************************************
The system, including the underground water mains and the aboveground
piping and system components, shall be tested to assure that equipment and
components function as intended. The underground and aboveground interior
piping systems and attached appurtenances subjected to system working
pressure shall be tested in accordance with NFPA 13 and NFPA 24. Upon
completion of specified tests, complete certificates as specified in
paragraph SUBMITTALS.
3.10.1.1 Flushing
As specified in NFPA 13, an air pressure leakage test at 350 kPa 50 psi
shall be conducted for 24 hours. There shall be no drop in gauge pressure
in excess of 10 kPa 1.5 psi for the 24 hours. This air pressure test is in
addition to the required hydrostatic test.
Each alarm initiating device, including pressure alarm switch, low air
pressure switch, valve supervisory switch, and electrically-operated switch
shall be tested for proper operation. Water motor alarm shall be tested.
The connecting circuit [to the building fire alarm system] [and] [to the
base-wide fire report system] shall be inspected and tested.
Each dry pipe valve shall be trip-tested by reducing normal system air
pressure through operation the inspector's test connection. Systems
equipped with quick opening devices shall be first tested without the
operation of the quick opening device and then with it in operation. Test
results will be witnessed and recorded. Test results shall include the
number of seconds elapsed between the time the test valve is opened and
tripping of the dry valve; trip-point air pressure of the dry pipe valve;
water pressure prior to valve tripping; and number of seconds elapsed
between time the inspector's test valve is opened and water reaches the
orifice.
Final Acceptance Test shall begin only when the Preliminary Test Report has
been approved. The Fire Protection Specialist shall conduct the Final
Acceptance Test and shall provide a complete demonstration of the operation
of the system. This shall include operation of control valves and flowing
of inspector's test connections to verify operation of associated waterflow
alarm switches. After operation of control valves has been completed, the
main drain test shall be repeated to assure that control valves are in the
open position. Each system shall be completely drained after each trip
test. The system air supply system shall be tested to verify that system
pressure is restored in the specified time. In addition, the Fire
Protection Specialist shall have available copies of as-built drawings and
certificates of tests previously conducted. The installation shall not be
considered accepted until identified discrepancies have been corrected and
test documentation is properly completed and received. After the system
has been tested and drained, the system shall be drained periodically for
at least 2 weeks until it can be assured that water from the system has
been removed.
**************************************************************************
NOTE: The number of hours of instruction should be
determined based of the number and complexity of the
systems specified.
**************************************************************************
-- End of Section --