LV Switchboard Dimensioning Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

C:\Users\r_sarkis\Desktop\Main 

LV Switchboards Dimensioning Guidline ‐ revB.xlsx Page 1
MAIN LV SWITCHBOARDS ‐ DIMENSIONING GUIDLINE

Dimensions: Schneider ‐ BLOKSET Siemens ‐ SIVACON S8 ABB ‐ MNS‐R


Incomers & Bus Couplers

. 600 mm (W) full length for 3P ACB of rating ≤ 3200A (Except in Dubai)
. 800 mm (W) & 1200 mm (D) full length for rating ≤ 2500A
. 700 mm (W) full length for rating ≤ 3200A (Except in Dubai) . 800 mm (W) full length for rating ≤ 3200A (DEWA & 3P+N & 4P ACBs))
. 1200 mm (W) & 1400 mm (D) full length for rating = 3200A
ACB Feeders (Withdrawable) . 800 mm (W) full length for rating ≤ 3200A (DEWA & DAEP) . 800 mm (W) full length for 3P ACB of rating = 4000A
. 1200 mm (W) & 1400 mm (D) full length for rating = 4000A
. 1200 mm (W) full length & 1200 mm (D) for  rating ≥ 4000A (DEWA & DAEP) . 1000 mm (W) full length for 3P+N & 4P ACBs of rating = 4000A
. 1200 mm (W) & 1400 mm (D) full length for rating = 5000A (IP42 MAX)
. 1000 mm (W) full length for rating = 5000A & 6000A

. 600+200 mm (W) full length for 3P ACB of rating ≤ 3200A (Except in Dubai)
. 700+200 mm (W) full length for rating ≤ 3200A (Except in Dubai)
. 800+200 mm (W) full length for rating ≤ 3200A (DEWA & 3P+N & 4P ACBs))
. 800+200 mm (W) full length for rating ≤ 3200A (DEWA & DAEP)
. 800+200 mm (W) full length for 3P ACB of rating = 4000A . 800 mm (W) & 1200 mm (D) full length for rating ≤ 2500A
. 1200+400 mm (W) full length & 1200 mm (D) for  rating ≥ 4000A (DEWA & DAEP)
. 1000+200 mm (W) full length for 3P+N & 4P ACBs of rating = 4000A . 1200 mm (W) & 1400 mm (D) full length for rating = 3200A
ACB Buscouplers (Withdrawable)
. 1000+200 mm (W) full length for rating = 5000A & 6000A . 1200 mm (W) & 1400 mm (D) full length for rating = 4000A
PS: 
. 1200 mm (W) & 1400 mm (D) full length for rating = 5000A (IP42 MAX)
. The 200 mm added is for internal vertical busbars (for info)
PS: 
. Add 400 mm cable ways if only front access
. Add 400 mm cable ways if only front access

Outgoings: Schneider ‐ BLOKSET Siemens ‐ SIVACON S8 ABB ‐ MNS‐R


Non Starter Feeders
DEWA Only:
. 500 mm (W) full length for rating ≤ 1600A if Icu ≠ Ics & Cables
. 700 mm (W) full length for rating ≤ 1600A if Icu ≠ Ics & Busriser
. 2 Nb. ACBs ≤ 1600A & Icu ≠ Ics can be stacked in the same cubicle of 700+200 mm  . 600 mm (W) & 1200 mm (D) full length for rating ≤ 1250A
(W) & 1000mm (D) (Applicable for cables exit only) . 800 mm (W) & 1200 mm (D) full length for rating ≤ 2000A
. 800 mm (W) & 1200 mm (D) full length for rating = 2500A
. 400 mm (W) full length for 3P ACBs for rating ≤ 2000A ( Icu = Ics) (No need for cable 
DAEP Only: . 1200 mm (W) & 1400 mm (D) full length for rating = 3200A
way for single ACB)
. 700 mm (W) full length for rating ≤ 1600A if Icu = Ics = Icw & Busriser . 1200 mm (W) & 1400 mm (D) full length for rating = 4000A
ACB (Withdrawable) . 600 mm (W) full length for 3P+N & 4P ACBs for rating ≤ 2000A ( Icu = Ics)
. 2 Nb. ACBs ≤ 1600A & Icu = Ics = Icw can be stacked in the same cubicle of 700+200  . 1200 mm (W) & 1400 mm (D) full length for rating = 5000A (IP42 MAX)
. 3 Nb. ACBs ≤ 1600A can be stacked in the same cubicle of 600 mm (W) & 800 mm 
mm (W) & 1200mm (D) (Applicable for cables exit only)
(D) if rear accessible & in cubicle of 600+400 mm (W) if only front accessible
. 2 Nb. ACBs ≤ 1250A can be stacked in the same cubicle of 600 + 200 mm (W)
PS:  . 2 Nb. ACBs ≤ 1600A can be stacked in the same cubicle of 800 + 300 mm (W)
. Add 400mm cable ways since on withdrawable function, busbars are installed on the  . 2 Nb. ACBs = 2000A can be stacked in the same cubicle of 800 + 400 mm (W)
rear
. NW ACBs ‐‐> Icu = Ics = Icw (Applicable to DA/DAEP specs)
. NT ACBs ‐‐> Icu = Ics ≠ Icw (Not Applicable to DA/DAEP specs)
. MCCB of rating ≤ 250A takes 4M (H) in cubicle of 500+200mm (W) if without CTs 
(Fixed/plug in) with LSI protection
. MCCB of rating ≤ 250A takes 4M (H) in cubicle of 700+200mm (W) if With CTs  . MCCB 3P of rating ≤ 250A takes 3M (H) in cubicle of 600mm (W)
(Fixed/plug in) with LSI protection . MCCB 3P+N & 4P of rating ≤ 250A takes 4M (H) in cubicle of 600mm (W)
. MCCB of rating = 400A takes 6M (H) in cubicle of 700+200mm (W) if With CTs . MCCB 3P of rating ≤ 500A takes 4M (H) in cubicle of 600mm (W) . MCCB of rating ≤ 200A takes 8E (H) in cubicle of 600mm (W)
. MCCB of rating = 630A takes 8M (H) in cubicle of 700+200mm (W) (Fixed/plug in ‐  . MCCB 3P+N & 4P of rating ≤ 500A takes 5M (H) in cubicle of 600mm (W) . MCCB of rating ≤ 320A takes 12E (H) in cubicle of 600mm (W)
Cat A) . MCCB 3P of rating = 630A takes 5M (H) in cubicle of 600mm (W) . MCCB of rating = 400A takes 16E (H) in cubicle of 600mm (W)
Fixed / Plug In MCCB 
. MCCB of rating = 630A takes 12M (H) in cubicle of 700+200mm (W) With or Without  . MCCB 3P+N & 4P of rating = 630A takes 7M (H) in cubicle of 600mm (W) or full  . MCCB of rating ≤ 630A takes 24E (H) in cubicle of 600mm (W)
(in Multifeeder Fixed Enclosure)
CTs (Fixed/drawout ‐ Cat B) length  400 mm (W) cubicle.
. MCCB 3P+N of rating = 800A and 1250A takes full length  400 mm (W) cubicle. Note:
Note:  . Above is Applicable for 3P and 4P MCCBs
. Add 400 mm cable way if only front access (depending on cable size) Note: 
. 200 mm Added is for vertical busbar if more than 1 functional unit is installed in one  . Add 400 mm cable way if only front access
cubicle
. Above is Applicable for 3P and 4P MCCBs

C:\Users\r_sarkis\Desktop\Main LV Switchboards Dimensioning Guidline ‐ revB.xlsx Page 2
MAIN LV SWITCHBOARDS ‐ DIMENSIONING GUIDLINE

Outgoings: Schneider ‐ BLOKSET Siemens ‐ SIVACON S8 ABB ‐ MNS‐R


. MCCB of rating ≤ 160A takes 4M (H) in cubicle of 600mm (W)
. MCCB of rating ≤ 250A takes 5M (H) in cubicle of 600mm (W) . MCCB of rating ≤ 200A takes 8E (H) in cubicle of 600mm (W)
. MCCB of rating ≤ 400A takes 6M (H) in cubicle of 600mm (W) . MCCB of rating ≤ 320A takes 12E (H) in cubicle of 600mm (W)
. MCCB of rating ≤ 630A takes 8M (H) in cubicle of 600mm (W) or full length 400 mm  . MCCB of rating = 400A takes 16E (H) in cubicle of 600mm (W)
Drawout MCCB 
(W) cubicle . MCCB of rating ≤ 630A takes 24E (H) in cubicle of 600mm (W)
(Drawout MCCB in Fixed Compartment)
. MCCB 3P+N of rating = 800A and 1250A takes full length  600 mm (W) cubicle.
Note:
Note:  . Above is Applicable for 3P and 4P MCCBs
. Add 400 mm cable way if only front access
Can be fitted in the Same Enclosure of ACB incomer or bus coupler (Applicable for 
small projects) but 
separate coloumn required as per DCA single or redunancy industrial type PLC 
complying to IEC‐101
900mm width ‐ 1200 depth if rear access
900+900 width ‐ 650 depth coloumn required if front access Can be fitted in the Same Enclosure of ACB incomer or bus coupler but better to have  Can be fitted in the Same Enclosure of ACB incomer or bus coupler but better to have 
PLC & battery chargers
For Battery Chargers: it in a separate enclosure it in a separate enclosure of 600 mm (W)
separate coloumn required for battery and battery charger 
700 or 900 mm rear access panel
if front required 700+700 coloum                                                              
Better to have battery and charger from orginal manufacturer ready made 
standalone to be considered for less dimension if required.  

. Up to 300 kVAR 700+200 mm (W) x 1050 mm (D)
Capacitor Banks Enclosure
. Up to 500 kVAR in 1450 mm (W) x 850 mm (D)

Active Harmonic Filters Each reactor/filter (200A/300A) is about 900mm (W) x 650mm (D) x 2100mm (H) 800 mm (W) x 600 mm (D) for 300A

C:\Users\r_sarkis\Desktop\Main LV Switchboards Dimensioning Guidline ‐ revB.xlsx Page 3
MAIN LV SWITCHBOARDS ‐ DIMENSIONING GUIDLINE

Outgoings: Schneider ‐ BLOKSET Siemens ‐ SIVACON S8 ABB ‐ MNS‐R


Starter Feeders / Fixed Solutions
DEWA Only:
. Up to 5.5 kW; 4M (H) in 700+200 mm (W)
. 7.5/11 kW; 6M (H) in 700+200 mm (W)
D.O.L. (Fixed)
DAEP Only:
. Up to 7.5 kW; 6M (H) in 700+200 mm (W) without meter
. Up to 7.5 kW; 8M (H) in 700+200 mm (W) with meter 
DEWA Only:
. 7.5/11 kW; 6M (H) in 700+200 mm (W)
. 15/18.5 kW; 9M (H) in 700+200 mm (W)
. 22/30/37 kW; 9M (H) in 700+200 mm (W)
. 45 kW; 12M (H) in 700+200 mm (W)
. 55/75 kW; 16M (H) in 700+200 mm (W)
Star‐ Delta (Fixed) DAEP Only:
. 7.5/18.5 kW; 8M (H) in 700+200 mm (W) without meter
. 7.5/18.5 kW; 12M (H) in 700+200 mm (W) with meter . Up to 22 kW; 8E (H) in 600 mm (W)
. 22/30/37 kW; 12M (H) in 700+200 mm (W) without meter                                               . Up to 37 kW; 12E (H) in 600 mm (W)
.22/30/37 kW; 14M (H) in 700+200 mm (W) with meter . Up to 55 kW; 16E (H) in 600 mm (W)
. 45 kW; 16M (H) in 700+200 mm (W) without meter . Up to 132 kW; 24E (H) in 600 mm (W)
.45 kW/ 55/75 kW; in 500 mm (W) full height with or without meter . Up to 250 kW; full length in 400 mm (W)
. Up to 37 kW; 12M (H) in 700+200 mm (W)
. Up to 45 kW; 18M (H) in 700+200 mm (W)
. 55/75 kW; full height in 700 mm (W) . Up to 30 kW; 12E (H) in 600 mm (W)
. 90 kW; full height in 700 mm (W) . Up to 55 kW; 16E (H) in 600 mm (W)
Soft Starter (Fixed)
. 110/160 kW; full height in 900 mm (W) . Up to 90 kW; 24E (H) in 600 mm (W)
. 200/250 kW; full height in 1200 mm (W) . 160 kW to 250 kW; full length in 400 mm (W)
. 355 kW; full height in 900 (W) & 1200 mm (D)
. 400/500 kW; full height in 1200 (W) & 1200 mm (D)
. Up to 15 kW; 12M (H) in 700+200 mm (W)
. 18.5/22/30 kW; 18M (H) in 700+200 mm (W)
. Up to 15 kW; 24E (H) in 600 mm (W)
. 37/45/55 kW; full height in 500 mm (W)
. Up to 11kW; 12M (H) in 600 mm (W) . Up to 55 kW; full height in 400 mm (W)
. 75/110 kW; full height in 700 mm (W)
VFD (Fixed) . Up to 15kW; 16M (H) in 800 mm (W) . Up to 132 kW; full height in 600 mm (W)
. 132/160 kW; full height in 900 mm (W)
. Above 55kW; full height in 600 mm (W) . Up to 225 kW; full height in 800 mm (W)
. 200/220 kW; full height in 1200 mm (W)
. Up to 360 kW; full height in 1000 mm (W)
. 250/315 kW; full height in 900 (W) & 1200 mm (D)
. 355/400 kW; full height in 1200 (W) & 1200 mm (D)
Note:  Note: 
. Add 400 mm cable ways if only front access . Add 400 mm cable ways if only front access

C:\Users\r_sarkis\Desktop\Main LV Switchboards Dimensioning Guidline ‐ revB.xlsx Page 4
MAIN LV SWITCHBOARDS ‐ DIMENSIONING GUIDLINE

Outgoings: Schneider ‐ BLOKSET Siemens ‐ SIVACON S8 ABB ‐ MNS‐R


Starter Feeders / Withdrawable
Maximum Rated Power up to 250kW‐DOL per Functional Unit
Horizontal Busbar Up to 6000A
Vertical Busbar Up to 1300A installed at rear (No need for 200mm busway)
Rated short‐time current (Icw) Up to 85 kA 1s
Withdrawable Yes
. If single HBB on top or at bottom:
   a‐ 34M if 3P
   b‐ 32M if 3P+N
Available Space for Feeders
. If Double HBB on top:
   a‐ 30M if 3P
   b‐ 28M if 3P+N
. MCCB of rating ≤ 160A takes 4M (H) in cubicle of 600mm (W) (Withdrawable)
. MCCB of rating ≤ 250A takes 6M (H) in cubicle of 600mm (W) (Withdrawable) . MCCB of rating ≤ 50A takes 8E/2 (H) in cubicle of 600mm (W)
. MCCB of rating ≤ 300A takes 6M (H) in cubicle of 600mm (W) (Withdrawable) . MCCB of rating ≤ 200A takes 8E (H) in cubicle of 600mm (W)
. MCCB of rating ≤ 450A takes 8M (H) in cubicle of 600mm (W) (Withdrawable) . MCCB of rating ≤ 160A takes 4M (H) in cubicle of 600mm (W) . MCCB of rating ≤ 320A takes 12E (H) in cubicle of 600mm (W)
Withdrawable Compartment  . MCCB of rating ≤ 250A takes 5M (H) in cubicle of 600mm (W) . MCCB of rating = 400A takes 16E (H) in cubicle of 600mm (W)
(With fixed MCCB) Note:  . MCCB of rating ≤ 400A takes 6M (H) in cubicle of 600mm (W) . MCCB of rating ≤ 500A takes 24E (H) in cubicle of 600mm (W)
. Add 400 mm cable way if only front access . MCCB of rating ≤ 630A takes 8M (H) in cubicle of 600mm (W)
. 200 mm Added is for vertical busbar if more than 1 functional unit is installed in one  Note:
cubicle . Above is Applicable for 3P and 4P MCCBs
. Above is Applicable for 3P and 4P MCCBs
. Up to 11 kW; 4m in 600 mm (W) & 1050 mm (D) 
. Up to 37 kW; 8M in 600 mm (W) & 1050 mm (D)
. Up to 75 kW; 10M in 600 mm (W) & 1050 mm (D)
. Up to 110 kW; 10m in 600 mm (W) & 1050 mm (D)
. Up to 250 kW; 12M in 600 mm (W) & 1050 mm (D)

. Up to 18.5 kW; 8E/2 (H) in 600 mm (W)
DEWA:
. Up to 30 kW; 8E (H) in 600 mm (W)
D.O.L. (Withdrawable) . Up to 15 kW; 2M/2 in 600 mm (W) & 1000 mm (D) Up to 15kW; 2M (H) in 600mm (W)
. Up to 132 kW; 16E (H) in 600 mm (W)
. Up to 18.5 kW; 2M in 600 mm (W) & 1000 mm (D)
. Up to 250 kW; 24E (H) in 600 mm (W)
. Up to 30 kW; 4M/2 in 600 mm (W) & 1000 mm (D)
. Up to 45 kW; 4M in 600 mm (W) & 1000 mm (D)
. Up to 75 kW; 6M in 600 mm (W) & 1000 mm (D)
. Up to 110 kW; 8M in 600 mm (W) & 1000 mm (D)
. Up to 200 kW; 10M in 600 mm (W) & 1000 mm (D)
. Up to 250 kW; 12M in 600 mm (W) & 1000 mm (D)
. Up to 11 kW; 8E (H) in 600 mm (W)
. Up to 5.5 kW; 4m in 600 mm (W) & 1050 mm (D) . Up to 15kW; 3M (H) in 600mm (W)
. Up to 30 kW; 12E (H) in 600 mm (W)
Star‐Delta (Withdrawable) . Up to 7.5‐15 kW; 6M in 600 mm (W) & 1050 mm (D) . Up to 75kW; 5M (H) in 600mm (W)
. Up to 90 kW; 16E (H) in 600 mm (W)
. Up to 15‐45 kW; 8M in 600 mm (W) & 1050 mm (D) . Up to 250kW; 10M (H) in 600mm (W)
. Up to 160 kW; 24E (H) in 600 mm (W)
. Up to 18.5kW; 5M (H) in 600mm (W)
. Up to 55kW; 8M (H) in 600mm (W)
Soft Starter (Withdrawable) up to 45 kW; 24E (H) in 600 mm (W)
. Up to 110kW; 12M (H) in 600mm (W)
Not Applicable for DAEP . Up to 250kW; 16M (H) in 600mm (W)
Note:  Note: 
. Add 400 mm cable ways if only front access . Add 400 mm cable ways if only front access

C:\Users\r_sarkis\Desktop\Main LV Switchboards Dimensioning Guidline ‐ revB.xlsx Page 5